Novel Reference Method for the Characterization of PD Measuring Systems Using HFCT Sensors
Abstract
:1. Introduction
- filter the background electrical noise present in the installations to perform the acquisitions with an adequate sensitivity,
- perform autonomous diagnosis and generate alarms when a critical defect is detected,
- determine the phase or phases affected by the defects,
- discriminate the presence of all the insulation defects present in the supervised installation,
- locate the emplacement of the defects,
- identify the type of defect associated with each PD source,
- and identify the defective elements of the installation.
- -
- Lack of reference or standardized procedures that allow their characterization in a complete and reproducible way.
- -
- Technical and economic difficulty to characterize them in a complete and reproducible way in on-site or laboratory installations. This is due to the lack of availability of these installations, high running costs, restricted use at a single site and the impossibility (in on-site installations) or great difficulty (in laboratory installations) to control the noise conditions.
- -
- With the use of the above installations, with the current state of the art, it is not possible to create the controlled measurement conditions necessary for the complete and reproducible characterization of the systems. Furthermore, with the same installation, it is not possible to make comparisons of results over time in various emplacements for various technologies.
2. Characterization Method and Associated Test Platform
- The methods do not consider their applicability in three-phase installations, thus some functionalities as those developed for the identification of the affected phase, or for defect detection analyzing the acquisitions obtained in the three phases, cannot be characterized. In industrial applications, the supervision is carried out simultaneously in the three phases, thus making it more effective.
- When the PD pulses used are measured, they are not representative of those acquired in real on-site measuring conditions. Furthermore, in [16] the PDs generated are very close to the measuring point.
- The on-site noise measuring conditions in the sensor environment, when measuring in one or various positions of an installation, are not considered or controlled. Thus, the system’s characterization considering the noise influence cannot be properly performed.
- When tests cells are used for the PD generation [16], HV application is required and the performance of repetitive tests over time is not possible due to the stochastic behavior of the pulses.
- The measuring conditions concerning the sensor coupling and the technical characteristics of the earth connections of the setups differ from those of a real installation [16].
- When the PDs generated with tests cells [16] or an analog generator [15] are measured by the sensors, as the physical characteristics of real on-site installations are not reproduced, the following technical aspects are not properly considered: the phase coupling and the polarity, attenuation, distortion and reflection of the pulses. Thus, the complete and adequate characterization of the systems cannot be performed.
- If the scale systems were not used and the characterizations were performed with an analog generator [15,17,19,20,21,22], injecting the signals that simulate defects and noise conditions directly into the acquisition unit would not be possible to perform the characterizations in a complete way with real sensors in a physical system and measuring in a non-limited number of points.
2.1. Scale Modular Test Platform
- Analog signal generator (ASG) subsystem (1). The signals generated by this element (high-frequency transient PD pulses and electrical noise) are of the same nature as those of real installations.
- Scale module subsystem, consisting of three-phase insulated cable elements (2), straight junction chambers (3), cable–GIS connection elements (4) and GIS modules (5).
- Defect injection subsystem (6) for the simulation of the PD sources. The defects can be simulated in the GIS compartments, cable terminals and cable joints.
- HFCT sensor subsystem (7). The measurements are performed in two positions, at the beginning and at the end of the distribution system.
- Noise injection subsystem (8) for the simulation of the background noise measuring conditions of a real installation in the sensor environment. Within this subsystem are the cable–GIS connection elements (4) and the HFCT sensors (7).
- Measuring subsystem (9), with a three-channel acquisition unit per measuring point.
2.2. Characterization Method
- -
- The background random noise is generated with the ASG and injected into the noise injection subsystem (step 6_b), where the same noise conditions of the real installations are simulated in the environment of the sensors [18].
- -
- The pulse-type noise, which propagates in a conducted way, is also generated with the ASG and injected in the same way as the analog signals that simulate the defects (step 6_b).
2.3. Characterization Tests
- Level 1 (low difficulty). The internal defect #1 is measured simultaneously with the on-site noise #1, which is generated in successive steps with increasing levels of amplitude.
- Level 2 (high difficulty). The internal defect #1 is measured simultaneously with a different on-site aleatory noise. This second noise, indicated in Table 2 as #2, is shown in Figure 6c,d. By generating the noise signal #2, the changing noise conditions of real installations are considered. With this level of difficulty, the noise signal is also generated with increasing levels of amplitude.
- Measurement of at least three insulation defects positioned in various elements and locations of the installation and in more than one phase, along with at least one pulse-type noise and one aleatory noise. Subsequent processing and analysis of the registered data in automatic mode. The defects #2, #3 and #4 and the noises #2 and #3 indicated in Table 2 are proposed for this test. The three defects and noise #3 are generated with the ASG subsystem and injected into the defect subsystem modules indicated in Figure 7, see the red lines and dots. The noise #2 is also generated with the ASG but injected into the two modules of the noise subsystem, see in Figure 7 the blue lines. The measurements are performed with the six HFCT sensors and two acquisition units shown in Figure 2 and Figure 7. The voltage reference signal required for the measurements is generated with the ASG, see the green lines in Figure 7. With the results obtained, Table 6 is completed. In this table it is indicated if the measuring system, in automatic mode, is able to report the presence of PD activity and to trigger any alarm. In addition, if it is able to report about: the number of defects, the phase or phases affected, the identification and location of the defects and the identification of the affected element.
- Realization of a second measurement for the evaluation of the capability to automatically analyze the evolution of defects over time. In this second test the capability to generate an alarm when critical levels of charge QIEC or PD rate are reached is also evaluated. In this test, a 30 min measurement is performed generating at least the three defects of the previous test (#2, #3, #4) with the two noises (#2 and #3), plus the additional aleatory noise #1 shown in Figure 6a,b. In this case, the aging of defect #2 is simulated, varying in 5 intervals of 6 min its QIEC and PD rate values. The values shown for each time interval in Table 3 are equivalent to the average of those measured in 200 h of aging of a real internal defect. To simulate on-site measuring conditions, the noise signals generation vary over time. The variation of these signals is performed by the generation of the successive combinations shown in the last row of Table 3.
Type of Defect or Noise | Position | Affected Phase | Defective Element | QIEC (pC) or 3σ | PD Rate (ppp) | Test Where It Is Used |
---|---|---|---|---|---|---|
Defect #1 internal cavity | At the end of the line | - | Cable terminal | 500–550 | 50–60 | 2 |
Defect #2 internal cavity | At the beginning of the line | R | GIS | 500 (**) | 50 (**) | 3, 4, 5, 6, 7, 8 and 9 |
Defect #3 internal surface | At the beginning of the line | R | Cable terminal | 500 | 50 | 3, 4, 5, 6, 7, 8 and 9 |
Defect #4 internal cavity | At the second joint | S | Second joint | 500 | 50 | 3, 4, 5, 6, 7, 8 and 9 |
Noise #1 aleatory | In the noise subsystem | R-S-T | - | 3.8 mV (*) | - | 2, 3, 4, 5, 6, 7, 8 and 9 |
Noise #2 aleatory | In the noise subsystems | R-S-T | - | 3.8 mV (*) | - | 2,3, 4, 5, 6, 7, 8 and 9 |
Noise #3 pulse-type | At the beginning of the line | R-S-T | - | 3.8 mV | - | 3, 4, 5, 6, 7, 8 and 9 |
Injected Signals (*) | Time (min) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
0–6 | 6–12 | 12–18 | 18–24 | 24–30 | ||||||
QIEC (pC) | PD Rate (ppp) | QIEC (pC) | PD Rate (ppp) | QIEC (pC) | PD Rate (ppp) | QIEC (pC) | PD Rate (ppp) | QIEC (pC) | PD Rate (ppp) | |
Defect #2 | 520–550 | 55–60 | 490–520 | 50–55 | 450–490 | 45–50 | 410–450 | 40–45 | 380–410 | 35–40 |
Noises #1, #2 and #3 | #2 (2 min) | #2 (2 min) | #2 (2 min) | #2 (2 min) | #2 (2 min) | |||||
#2 + #3 (2 min) | #2 + #3 (2 min) | #2 + #3 (2 min) | #2 + #3 (2 min) | #2 + #3 (2 min) | ||||||
#1 + #2 + #3 (2 min) | #1 + #2 + #3 (2 min) | #1 + #2 + #3 (2 min) | #1 + #2 + #3 (2 min) | #1 + #2 + #3 (2 min) |
- -
- It is an invasive technique, except when the measurements are performed in the capacitive tap of power transformer bushings.
- -
- The measurements are performed in frequency ranges where noise rejection is often challenging.
- -
- For the bandwidths specified, although the resulting charge value is obtained conveniently and matches the integral of the current pulse in the time domain, the waveform of the pulses is lost. Thus, if the original signals are not accessible, some diagnostic tools such as those used for PD source separation by the pulse waveform analysis cannot be applied.
3. PD Measuring System Characterization
3.1. Measuring System Characteristics and Functionalities
3.2. Method Application to Perform the Characterizations
4. Conclusions
5. Patent
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Acknowledgments
Conflicts of Interest
References
- IEC TS 62478:2016; High Voltage Test Techniques—Measurement of Partial Discharges by Electromagnetic and Acoustic Methods. TC 42 High-Voltage and High-Current Test Techniques. International Electrotechnical Commission (IEC) Standards: Geneva, Switzerland, 2016.
- Wang, X.; Li, B.; Roman, H.; Russo, O.L.; Chin, K.; Farner, K.R. Acousto-optical PD detection for transformers. IEEE Trans. Power Deliv. 2006, 21, 1068–1073. [Google Scholar] [CrossRef]
- Sikorski, W.; Wielewski, A. Low-Cost Online Partial Discharge Monitoring System for Power Transformers. Sensors 2023, 23, 3405. [Google Scholar] [CrossRef] [PubMed]
- Haddad, A.; Warne, D.F. Advances in High Voltage Engineering, 2nd ed.; IET Power and Energy Series; IET: London, UK, 2007; pp. 52–59. ISBN 978-0-85296-158-2. [Google Scholar]
- Montanari, G.C.; Cavallini, A.; Pasini, G. A Method for Detecting, Identifying and Locating Partial Discharges Occurring in a Discharge Site along an Electric Apparatus. Patent WO2009013639A1, 29 January 2009. [Google Scholar]
- Stone, G. Partial discharge-part VII. Practical techniques for measuring PD in operating equipment. IEEE Electr. Insul. Mag. 1991, 7, 9–19. [Google Scholar] [CrossRef]
- Ardila-Rey, J.A.; Rojas-Moreno, M.V.; Martínez-Tarifa, J.M.; Robles, G. Inductive sensor performance in partial discharges and noise separation by means of spectral power ratios. Sensors 2014, 14, 3408–3427. [Google Scholar] [CrossRef] [PubMed]
- Cavallini, A.; Montanari, G.C.; Puletti, F.; Contin, A. A new methodology for the identification of PD in electrical apparatus: Properties and applications. IEEE Trans. Dielectr. Electr. Insul. 2005, 12, 203–215. [Google Scholar] [CrossRef]
- Álvarez, F.; Garnacho, F.; Ortego, J.; Sánchez-Urán, M.A. Application of HFCT and UHF sensors in on-line partial discharge measurements for insulation diagnosis of high voltage equipment. Sensors 2015, 15, 7360–7387. [Google Scholar] [CrossRef] [PubMed]
- Koltunowicz, W.; Plath, R. Synchronous multi-channel PD measurements. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1715–1723. [Google Scholar] [CrossRef]
- Tian, Y.; Lewin, P.; Davies, A. Comparison of On-line Partial Discharge Detection Methods for HV Cable Joints. IEEE Trans. Dielectr. Electr. Insul. 2002, 9, 604–615. [Google Scholar] [CrossRef]
- Steennis, F.; Wagenaars, P.; van der Wielen, P.; Wouters, P.; Li, Y.; Broersma, T.; Harmsen, D.; Bleeker, P. Guarding MV cables on-line: With travelling wave based temperature monitoring, fault location, PD location and PD related remaining life aspects. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 1562–1569. [Google Scholar] [CrossRef]
- Wang, Y.; Chen, P.; Zhao, Y.; Sun, Y. A Denoising Method for Mining Cable PD Signal Based on Genetic Algorithm Optimization of VMD and Wavelet Threshold. Sensors 2022, 22, 9386. [Google Scholar] [CrossRef]
- Michau, G.; Hsu, C.; Fink, O. Interpretable Detection of Partial Discharge in Power Lines with Deep Learning. Sensors 2021, 21, 2154. [Google Scholar] [CrossRef] [PubMed]
- Vera, C.; Garnacho, F.; Klüss, J.; Mier, C.; Álvarez, F.; Lahti, K.; Khamlichi, A.; Elg, A.-P.; Rodrigo Mor, A.; Arcones, E.; et al. Validation of a Qualification Procedure Applied to the Verification of Partial Discharge Analysers Used for HVDC or HVAC Networks. Appl. Sci. 2023, 13, 8214. [Google Scholar] [CrossRef]
- Garnacho, F.; Ramírez, Á.; Álvarez, F.; Arcones, E.; Vera, C.A. Characterization of partial discharge measuring instruments by the generation of reference insulation defects in an experimental setup. In Proceedings of the 2018 IEEE 2nd International Conference on Dielectrics (ICD), Budapest, Hungary, 1–5 July 2018. [Google Scholar]
- Garnacho, F.; Álvarez, F.; Elg, A.-P.; Mier, C.; Lahti, K.; Khamlichi, A.; Arcones, E.; Klüss, J.; Rodrigo Mor, A.; Pakonen, P.; et al. Metrological Qualification of PD Analyzers for Insulation Diagnosis of HVDC and HVAC Grids. Sensors 2023, 23, 6317. [Google Scholar] [CrossRef] [PubMed]
- Arcones, E.; Álvarez, F.; Khamlichi, A.; Garnacho, F. Scale modular test platform for the characterization of PD measuring systems using HFCT sensors. Sensors 2024, 24, 1363. [Google Scholar] [CrossRef] [PubMed]
- Garnacho, F.; Ramírez, Á.; Álvarez, F.; Vera, C.A.; Arcones, E. Development of a programmable partial discharge generator for the evaluation of partial discharge measuring devices. In Proceedings of the 2018 IEEE 2nd International Conference on Dielectrics (ICD), Budapest, Hungary, 1–5 July 2018. [Google Scholar]
- Hu, Y.; Chiampi, M.; Crotti, G.; Sardi, A. Setting-up of a characterization system for digital PD measuring instruments. In Proceedings of the 2010 Conference on Precision Electromagnetic Measurements (CPEM), Daejeon, Republic of Korea, 13–18 June 2010. [Google Scholar]
- Hu, Y.; Chiampi, M.; Crotti, G. Characterisation system for the evaluation of digital partial discharge measuring instruments. IET Sci. Meas. Technol. 2015, 9, 817–825. [Google Scholar] [CrossRef]
- Khamlichi, A.; Garnacho, F.; Simón, P. New Synthetic Partial Discharge Calibrator for Qualification of Partial Discharge Analyzers for Insulation Diagnosis of HVDC and HVAC Grids. Sensors 2023, 23, 5955. [Google Scholar] [CrossRef] [PubMed]
- Renforth, L.A.; Giussani, R.; Mendiola, M.T.; Dodd, L. Online Partial Discharge Insulation Condition Monitoring of Complete High-Voltage Networks. IEEE Trans. Ind. Appl. 2019, 55, 1021–1029. [Google Scholar] [CrossRef]
- Kreuger, F. Partial Discharge Detection in High-Voltage Equipment; Butterworths: London, UK, 1989. [Google Scholar]
- Gulski, E.; Kreuger, F. Computer-aided recognition of discharge sources. IEEE Trans. Electr. Insul. 1992, 27, 82–92. [Google Scholar] [CrossRef]
- Kreuger, F.; Gulski, E.; Krivda, A. Classification of partial discharges. IEEE Trans. Electr. Insul. 1993, 28, 917–931. [Google Scholar] [CrossRef]
- Yan, X.; Bai, Y.; Zhang, W.; Cheng, C.; Liu, J. Partial Discharge Pattern-Recognition Method Based on Embedded Artificial Intelligence. Appl. Sci. 2023, 13, 10370. [Google Scholar] [CrossRef]
- Salama, M.M.A.; Bartnikas, R. Determination of neural-network topology for partial discharge pulse pattern recognition. IEEE Trans. Neural Netw. 2002, 13, 446–456. [Google Scholar] [CrossRef] [PubMed]
- IEC 60270:2000+AMD1:2015; High-Voltage Test Techniques—Partial Discharge Measurements. TC 42 High-Voltage and High-Current Test Techniques. International Electrotechnical Commission (IEC) Standards: Geneva, Switzerland, 2015.
- Guidelines for Partial Discharge Detection Using Conventional (IEC 60270) and Unconventional Methods; CIGRE WG D1.37 Technical Brochure 662, Electra; GIGRE: Paris, France, 2016; Volume 288.
Test | Name | Test | Name |
---|---|---|---|
1 | Sensitivity in the detection. | 6 | Localization of defects. |
2 | Noise rejection. | 7 | Identification of the type of defect. |
3 | Autonomous diagnosis and alarm management. | 8 | Identification of the defective element. |
4 | Identification of the phase affected. | 9 | Determination of the QIEC and PD repetition rate values. |
5 | Number of defects determination. |
Injected Pulse Charge (pC) | Sensitivity (Pulses Detected?) | Measured Values and Errors | |
---|---|---|---|
Pulse Charge (pC) | Error (%) | ||
1000 | Yes | 1000 (scale factor = 542.6) | - |
500 | Yes | 502 | 0.4 |
200 | Yes | 203 | 1.5 |
100 | Yes | 103 | 3 |
50 | Yes | 52 | 4 |
20 | Yes | 21 | 5 |
15 | Yes | 16 | 6.7 |
10 | Yes | 11 | 10 |
9 | Yes | 11 | 22.2 |
8 | No | - | - |
Injected Noise Signal | Background Base Noise + Noise #2 (3σ = 3.8 mV) | Background Base Noise + Noise #2 (3σ = 7.6 mV) | Background Base Noise + Noise #2 (3σ = 11.4 mV) | Background Base Noise + Noise #2 (3σ = 15.2 mV) | |
---|---|---|---|---|---|
QIEC value | Injected (*) 500–550 (pC) | 545 | 527 | 506 | 550 |
Measured (pC) | 539 | 172 | 54 | 5 | |
Error (%) | 1.1 | 67.4 | 89.3 | 99.1 | |
PD rate | Injected (*) 50–60 (ppp) | 58 | 52 | 56 | 55 |
Measured (ppp) | 56 | 24 | 10 | 1 | |
Error (%) | 3.4 | 53.8 | 82.1 | 98.2 | |
PRPD pattern |
Presence of PD Activity? | Alarms Triggered? | Number of Defects Detected | Affected Phases | Type of Defects Identified | Defect Location | Affected Elements |
---|---|---|---|---|---|---|
Yes | 3 | 3 | R and S | Internal cavity | 0 m | - |
Internal surface | 0 m | Cable terminal | ||||
Internal cavity | 1164 m | Cable joint |
Time Interval (min) | 0–6 | 6–12 | 12–18 | 18–24 | 24–30 |
---|---|---|---|---|---|
Alarm detected? | No | No | No | Yes | Yes |
Alarm triggered time | - | - | - | 19′06″ | - |
QIEC trend | |||||
PD rate trend |
Raw PRPD patterns obtained in one position and phase | Measurement in phase R at the beginning of the line | Measurement in phase S at the beginning of the line |
3D clustering diagram | 3D diagram obtained for phase R | 3D diagram obtained for phase S |
Individual PRPD patterns per cluster | ||
PD source mapping diagram | Phase R | Phase S |
3D clustering diagram per location | ||
Individual PRPD patterns for clusters #1, #2 and #3 | ||
Pattern #1 (Defect #2) | Pattern #2 (Defect #3) |
Pattern #4 (Defect #4) | Patterns #3 & #5 |
Defect | #2 | #3 | #4 |
---|---|---|---|
Pulse polarity | |||
PRPD patterns | |||
Type of defect | Internal cavity | Internal surface | Internal cavity |
Emplacement | At the beginning of the line in phase R | At the beginning of the line in phase R | In the second joint in phase S |
Defective element | GIS | Cable terminal | Cable joint |
Defect | Type | QIEC Value | PD Rate | ||||
---|---|---|---|---|---|---|---|
Injected | Measured | Error (%) | Injected | Measured | Error (%) | ||
#2 | Internal cavity | 500 | 479 | 4.2 | 50 | 47 | 6 |
#3 | Internal surface | 500 | 491 | 1.8 | 50 | 49 | 2 |
#4 | Internal cavity | 500 | 487 | 2.6 | 50 | 45 | 10 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Arcones, E.; Álvarez, F.; Ortego, J.; Garnacho, F. Novel Reference Method for the Characterization of PD Measuring Systems Using HFCT Sensors. Sensors 2024, 24, 3788. https://doi.org/10.3390/s24123788
Arcones E, Álvarez F, Ortego J, Garnacho F. Novel Reference Method for the Characterization of PD Measuring Systems Using HFCT Sensors. Sensors. 2024; 24(12):3788. https://doi.org/10.3390/s24123788
Chicago/Turabian StyleArcones, Eduardo, Fernando Álvarez, Javier Ortego, and Fernando Garnacho. 2024. "Novel Reference Method for the Characterization of PD Measuring Systems Using HFCT Sensors" Sensors 24, no. 12: 3788. https://doi.org/10.3390/s24123788
APA StyleArcones, E., Álvarez, F., Ortego, J., & Garnacho, F. (2024). Novel Reference Method for the Characterization of PD Measuring Systems Using HFCT Sensors. Sensors, 24(12), 3788. https://doi.org/10.3390/s24123788