Next Article in Journal
Near-Road Traffic-Related Air Pollution: Resuspended PM2.5 from Highways and Arterials
Previous Article in Journal
Analyzing the Job Demands-Control-Support Model in Work-Life Balance: A Study among Nurses in the European Context
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Case Study: Safety Assessment of Plant Layout between Ethylene Storage Tanks and Process Equipment According to Capacity and Weather Conditions

Department of Health & Safety Convergence Science, Korea University, Anam-ro 145, Seongbuk-gu, Seoul 02841, Korea
*
Author to whom correspondence should be addressed.
Int. J. Environ. Res. Public Health 2020, 17(8), 2849; https://doi.org/10.3390/ijerph17082849
Submission received: 7 March 2020 / Revised: 16 April 2020 / Accepted: 17 April 2020 / Published: 21 April 2020
(This article belongs to the Section Environmental Health)

Abstract

:
In a chemical plant, even if an explosion occurs in a storage tank that handles flammable materials, the minimum separation distance is applied in a way to prevent chain explosion. This is because when an explosion occurs in a storage tank, thermal radiation affects nearby process equipment and causes a chain explosion. The separation distance between storage tanks and process equipment in a chemical plant depends on the global engineering guidelines PIP (Process Industry Practice) PNE00003 and GAPS (Global Asset Protection Services) GAP.2.5.2. However, there is a limitation in the global engineering guidelines that provide only a consistent separation distance according to the item types without considering the storage capacity and climatic conditions around the storage tank. This study analyzed the distance of thermal radiation (up to 37.5 kW/m2) according to the capacity of ethylene storage tank and climatic conditions by utilizing the Phast (DNV GL), which is widely used as a tool for quantitative risk analysis. The accident scenario was applied using the U.S. EPA (Environment Protection Agency)’s worst leakage accident scenario, considering climate variables, air temperature, wind speed, and atmospheric stability. In the simulation, atmospheric stability did not affect the radius of thermal radiation. Moreover, the thermal radiation tended to increase with increase in wind speed in the ambient condition and winter, but not in summer. Because both PIP PNE00003 and GAP.2.5.2 yield consistent separation distances without considering storage capacity and weather conditions, quantitative risk analysis of the results of thermal radiation is necessary to ensure safety.

1. Introduction

Ethylene is a representative chemical raw material used in polyethylene, ethylene glycol, PVC, etc. and can be considered the most basic material in the petrochemical industry manufactured at an NCC (Naphtha Cracking Center) or ECC (Ethane Cracking Center) [1]. When constructing a chemical plant for ethylene-related processes, the location of the plant facility must be determined by conducting a safety-distance review via a plot plan. In particular, the location of the storage tank, which handles a large amount of ethylene should be the most important when conducting a safety-distance review [2].
The locations of facilities included in the plot plan of a chemical plant are set at an early stage of designing and must be carefully reviewed because they can significantly affect the economy (the quantity of pipes and land use) [3]. The review stage is the most important stage in terms of safety distance. Because chemical plants store and handle large amounts of flammable materials, there is a risk of explosion. Therefore, the separation distance must be set by considering the characteristics of each facility to minimize the damage in the event of an explosion [4]. The safety distance is considered, in collaboration with process safety engineers, piping engineers, and engineers from other disciplines [5]. The widely used engineering guidelines related to safety distances are ‘PIP PNE00003: Process Unit and Offsites Layout Guide’ and ‘GAP.2.5.2: Oil and Chemical Plant Layout and Spacing’ [6]. PIP PNE 00003 is a standard for separation distances issued by an association called Process Industry Practice (PIP). PIP is composed of about 98 major engineering companies and provides engineering guideline by their consultations. GAP.2.5.2 is a standard for separation distances issued by an association called Global Asset Protection Services (GAPS). GAPS provides engineering guidelines from the insurance company’s point of view to prevent property loss for the owners of a chemical plants. They suggest safety distances of 46 and 106.75 m, respectively, between the ethylene storage tank and process equipment. However, there is a limitation in that both guidelines suggest a consistent separation distance without considering the capacity of ethylene storage and atmospheric conditions.
Therefore, this study aims to suggest the assessment of safety distance between ethylene storage tanks and process equipment considering the storage capacity and atmospheric conditions. In the previous study, when applying the concept of separation distance, it was suggested that the effect of thermal radiation should be considered [7]. It was noted that the effect of the thermal radiation could be analyzed by the Quantitative Risk Analysis (QRA) technique. This study also considered the effect of thermal radiation on the separation distance. As a simulation tool for the QRA technique, Phast (DNV GL) was used. Phast is widely used as a QRA simulation tool [8]. This is because Phast is designed to comply with legal requirements from around the world, such as the Dutch’s yellow book, the U.S. EPA (Environment Protection Agency) regulation, and the UK’s HSE (Health and Safety Executive) regulation [9,10,11].

2. Background

Ethylene is a petrochemical product that is at the center of supply and demand in the global petrochemical market. Ethylene is used in the gas phase at ambient temperature but liquefied under the conditions of low temperature and high pressure during storage and transportation [12]. This study aims to analyze the safety distance between ethylene storage tanks and process equipment. Ethylene storage tanks form a liquid pool during leakage, and in the event of a fire, the vicinity is affected by thermal radiation [13]. Globally, the effect of 37.5 kW/m2 of thermal radiation on process-plant facilities is considered fatal, as summarized in Table 1 [14].
Many studies have been carried out that have selected 37.5 kW/m2 as the criterion for the influence of thermal radiation on process equipment. There was a study that found 37.5 kW/m2 is suitable as a thermal radiation criterion causing damage to facilities in an experiment that applied thermal radiation to a sample of an offshore platform, and propane was applied for the source material of thermal radiation [15]. Another study selected 37.5 kW/m2 as the criterion for causing chain explosion under the influence of thermal radiation of process equipment and Liquefied Petroleum Gas (LPG) was applied for the source material of thermal radiation [16]. There was also a study that the separation distance between the propylene process equipment and the other facilities of chemical plant should be 37.5 kW/m2 of thermal radiation, and propylene was applied for the source material of thermal radiation [17]. Another study applied 37.5 kW/m2, the criterion of thermal radiation, which has a fatal effect on structures when an explosion occurs due to a leak in an Liquefied Natural Gas (LNG) tank, and LNG was applied for the source material of thermal radiation [18]. Therefore, this study analyzed thermal radiation up to 37.5 kW/m2, considering the ethylene storage capacity and atmospheric conditions. QRA is widely used for such thermal radiations [19]. This study used Phast as a QRA simulation tool. The catastrophic rupture scenario provided by Phast was considered as the leakage scenario of the ethylene storage tank [20]. In addition, EPA’s worst-case leak scenario was applied for other conditions required for the leakage scenario [21] to conservatively approach the effects of thermal radiation due to the ethylene storage tank.

3. Methodology and Results

The radius of thermal radiation (up to 37.5 kW/m2) was considered. The methodology flow chart applied in this study is shown in Figure 1. In this study, thermal radiation was analyzed by Phast’s Gaussian model. The Gaussian model is a representative method that is considered for the release of materials that are lighter than air. Since the source material of this study, ethylene, is lighter than air, the Gaussian model was applied. Atmospheric stability was estimated by the temperature difference according to the height and classified into seven categories from A to G. This study was applied based on atmospheric stability D and F according to EPA’s worst-case scenario.
Ethylene was applied as the target material, and the process conditions of the tank (source item) for storing ethylene in the liquid phase are presented in Table 2. Nine storage tank capacities were set from 10 to 50 m3 with an interval of 5 m3.
The height of the source of leakage in the ethylene storage tank was based on the condition of leakage from the ground and 50% relative humidity in the air according to EPA’s worst-case scenario [21]. The following atmospheric temperatures were applied—ambient temperature (25 °C), summer (40 °C), and winter (0 °C). The applied wind speed and atmospheric stability are presented in Table 3.
The simulation results at ambient temperature (25 °C) are presented in Table 4 and Figure 2, and the results of regression analysis with polynomial fitting are presented in Table 5.
Regression equations for each case are expressed as Equations (1)–(3). The calculation of each equation provided results with high interpretation reliabilities.
Case   1   and   2 Y = 35.46308 + 2.2785 X 0.01528 X 2
Case   2   and   3 Y = 41.49652 + 2.44807 X 0.0166 X 2
Case   4   and   5 Y = 45.27472 + 2.55867 X 0.01752 X 2
The difference in atmospheric F also did not affect the radius of thermal radiation (up to 37.5 kW/m2). This was true not only at ambient temperature (25 °C) but also under summer (40 °C) and winter (0 °C) conditions when the atmospheric stability was fixed at D, and simulation was performed using the atmospheric conditions in Table 6.
The simulation results for summer (40 °C) and winter (0 °C) are shown in Table 7, Figure 3, and the regression analysis with polynomial fitting is shown in Table 8.
For each case, the regression equation is expressed as Equations (4)–(9). Each calculation provided high interpretation results.
Summer   Case   1 Y = 32.91524 + 2.1227 X 0.01428 X 2
Summer   Case   2 Y = 44.33229 + 2.6596 X 0.018 X 2
Summer   Case   3 Y = 43.45616 + 2.43186 X 0.01672 X 2
Winter   Case   1 Y = 39.44695 + 2.54553 X 0.01697 X 2
Winter   Case   2 Y = 44.90677 + 2.69489 X 0.01817 X 2
Winter   Case   3 Y = 47.98425 + 2.77211 X 0.01879 X 2
In the summer (40 °C) condition, a wind speed of 1.5 m/s showed a thermal radiation of 37.5 kW/m2, which is very different from other temperature conditions. Wind speeds of 5 and 3 m/s did not show large differences, but the thermal radiation was the largest at 3 m/s. However, in winter (0 °C) and ambient temperature (25 °C) conditions, the thermal radiation was confirmed to widen to 37.5 kW/m2 with increasing wind speed. Figure 4 presents the thermal radiation up to 37.5 kW/m2 for each wind speed case at ambient temperature (25 °C), summer (40 °C), and winter (0 °C) conditions.
PIP PNE00003, one of the most widely used engineering guidelines that does not consider weather conditions and ethylene storage capacity, suggests a safety distance of 46 m between the ethylene storage tank and process facility, which is underestimated irrespective of the storage and weather conditions. A safety distance of 106.75 m suggested by GAP.2.5.2 is valid only under certain capacity and weather conditions. Table 9 presents the analysis results for each weather condition through the polynomial fitting derived from this study.

4. Discussion

The separation distance in chemical plants is considered as inherent safety to prevent chain explosion [22]. In chemical plants, the storage tank handles a large amount of chemicals, so it should be considered first when designing the separation distance [23]. Since the separation distance is applied as a concept to prevent chain explosion, it is independent of toxic dispersion.
The design of chemical plant is divided into code-based design and performance-based design according to the approach. Following the consistent regulation along the global engineering guideline is called code-based design, and applying the actual performance considering various factors is called performance-based design [24]. Currently, the separation distance is dependent on the global engineering guidelines like other design fields of chemical plants. However, it is difficult to consider the global engineering guidelines as guaranteeing safety because no detailed factors are considered [25]. QRA is performed to complement the limitations of the global engineering guidelines [26,27]. PIP PNE00003 and GAP.2.5.2 are the global engineering guidelines in the separation distance field [6]. The storage tank capacity and atmospheric conditions are not considered in the separation distance between the storage tank and the process equipment presented in these guidelines. These guidelines just categorize only by item type, such as storage tank or pump and so on, and provide only consistent separation distance between categories. Therefore, this study used QRA to analyze the separation distance between storage tank and process equipment.
The influence range was analyzed for thermal radiation up to 37.5 kW/m2 in the case of a fire due to contact with an ignition source. At ambient temperature, atmospheric stability did not affect the radius of thermal radiation, and the same results were obtained for summer and winter conditions. The atmospheric stability was simulated by changing only the wind speed with fixed D.
Polynomial fitting of the radius of thermal radiation for each weather case, according to the capacities of ethylene storage under ambient temperature, summer, and winter conditions, provided results with an average reliability of 99.892%. In the summer, changes in the radius of thermal radiation according to wind speed were not observed, but in the case of ambient temperature and winter, the radius of thermal radiation increased with increase in wind speed.
In comparison with existing international engineering guidelines, a safety distance of 46 m (PIP PNE00003) is underestimated in all cases of capacities and atmospheric conditions, and a distance of 106.75 m (GAP.2.5.2) does not guarantee safety when the capacities presented in Table 9 are exceeded and the weather conditions are not met.
Therefore, when setting the distance between the ethylene storage tank and the process equipment in the future, it is possible to meet the safety distance that cannot be established by existing engineering practices using the result of the Phast simulation, considering weather conditions. This study limited only one substance to be stored (ethylene), climatic conditions to three categories (ambient temperature, summer, winter), and wind speed conditions to three categories (1.5, 3, 5 m/s). However, it is expected that the same approach to the storage of different materials and different atmospheric conditions through the methodology of this study would be able to supplement the limitations of the global engineering guidelines.

5. Conclusions

Ethylene is the base material of the chemical industry and can be obtained through the process of naphtha cracking or ethylene cracking. In addition, ethylene is one of the basic constituents of a chemical plant as the scale of ethylene production is considered a measure of the chemical-industry development of a country. Ethylene occurs in the gaseous phase at ambient temperature but may be converted to the liquid phase under conditions of high pressure and low temperature, which is convenient for storage and transportation. A large amount of ethylene is stored in ethylene storage tanks, making them a major item to be considered when determining the safety distance.
The separation distance according to thermal radiation was applied in the previous studies. For thermal radiation, the explosive characteristic of the material is the most important parameter. The main factors that determine the explosiveness of each material are the Lower Flammable Limit (LFL) and the molecular weight for the dispersion radius. The environmental factors may include toxic dispersion, but this was not considered in this study because it indicated that it limited thermal radiation.
Global guidelines suggest that 37.5 kW/m2 is the limit of thermal radiation that the process equipment can experience. When leakage occurs in the ethylene storage tank, a pool forms, and fire or explosion may occur on contact with an ignition source. This study investigated the safety distance between ethylene storage tanks and process equipment. The radius of thermal radiation (37.5 kw/m2) was simulated using Phast. The trends were also analyzed for different ethylene storage capacities and weather conditions.
In the results, atmospheric stability did not affect the radius of thermal radiation. Under ambient temperature, the radius of thermal radiation increased with increase in wind speed in winter but not in summer. In addition, a regression equation was derived through polynomial fitting for each case, and all regression-equation calculations exhibited a high interpretation reliability of 99.892% on average.
In the previous studies, there has been research of the separation distance by thermal radiation. However, there have been no studies comparing the separation distance suggested by the global engineering guidelines. In the process safety engineering field like separation distance, the academic part is important, but the practical part must also be considered. This is because if only the academic part is considered, the possibility of applicability in the work-site operation is likely to be excluded. This study introduced the contents of global engineering guidelines used in work-site operation and introduced methods to compensate for the limitations of these guidelines.
International engineering guidelines include PIP PNE00003 and GAP.2.5.2. The safety distance between the ethylene storage tank and process equipment presented in PIP PNE00003 is underestimated, irrespective of the ethylene storage capacity and atmospheric conditions. The safety distance suggested by GAP.2.5.2 is applicable only under certain weather conditions and storage capacity.
Fundamentally, both PIP PNE00003 and GAP.2.5.2 offer consistent separation distances that do not consider ethylene storage capacity or weather conditions. Therefore, it is necessary to include a simulation tool, such as QRA, for precise safety-distance determination.

Author Contributions

J.-Y.C. and S.-H.B. conceived and designed the experiment; J.-Y.C. performed the task of data processing and coding, analyzed the results, and wrote the manuscript; S.-H.B. edited the manuscript. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Lee, A.J. A Study on the Development of Petrochemical Industry in China and It’s Implications for Korea-China FTA. Master’s Thesis, Incheon National University, Incheon, Korea, 2015. [Google Scholar]
  2. Abbasi, M.H.; Benhelal, E.; Ahmad, A. Designing an Optimal Safe Layout for a Fuel Storage Tanks Farm: Case Study of Jaipur Oil Depot. Int. J. Chem. Mol. Nucl. Mater. Metall. Eng. 2014, 8, 147–155. [Google Scholar] [CrossRef]
  3. Yang, J.S.; Lee, C.J. The research of layout optimization for LNG liquefaction plant to save the capital expenditures. Korean Chem. Eng. Res. 2019, 57, 51–57. [Google Scholar] [CrossRef]
  4. Oil and Chemical Plant Layout and Spacing. Available online: https://docplayer.net/48710333-Oil-and-chemical-plant-layout-and-spacing.html (accessed on 17 April 2020).
  5. Mecklenburgh, J.C. Process Plant Layout; Wiley: New York, NY, USA, 1985; pp. 43–46. [Google Scholar]
  6. Center for Chemical Process Safety. Guidelines for Siting and Layout of Facilities, 2nd ed.; Wiley: New York, NY, USA, 2018; pp. 193–198. [Google Scholar]
  7. Casal, J. Evaluation of the Effects and Consequences of Major Accidents in Industrial Plants, 2nd ed.; Elsevier: Amsterdam, The Netherlands, 2018; pp. 439–481. [Google Scholar]
  8. Oh, S.K.; Jo, Y.D. A Study on Safety Distance for Small Scale LNG Storage facility. J. Korea Saf. Manag. Sci. 2014, 16, 185–191. [Google Scholar] [CrossRef]
  9. Kim, H.S.; Jeon, B.H. Analysis of Impact Zone of Quantitative Risk Assessment based on Accident Scenarios by Meteorological Factors. J. Korean Soc. Environ. Eng. 2017, 685–688. [Google Scholar] [CrossRef]
  10. Kim, J.H.; Jung, S.H. Offsite Consequence Modeling for Evacuation Distances against Accidental Hydrogen Fluoride (HF) Release Scenarios. Korean Chem. Eng. Res. 2016, 582–585. [Google Scholar] [CrossRef]
  11. Park, S.W.; Jung, S.H. Recommended Evacuation Distance for Offsite Risk Assessment of Ammonia Release Scenarios. J. Korean Soc. Saf. 2016, 55, 156–161. [Google Scholar] [CrossRef] [Green Version]
  12. Ha, S.Y.; Choi, J.H. Performance Improvement on the Re-Liquefaction System of Ethylene Carrier using Low-Global Warming Potential Refrigerants. J. Soc. Nav. Archit. Korea 2018, 55, 415–420. [Google Scholar] [CrossRef]
  13. Cleaver, P.; Johnson, M.; Ho, B. A summary of some experimental data on LNG safety. J. Hazard. Mater. 2007, 140, 429–438. [Google Scholar] [CrossRef] [PubMed]
  14. Lees, P. Lees’ Loss Prevention in the Process Industries, 3rd ed.; Elsevier: Amsterdam, The Netherlands, 2005; pp. 252–253. [Google Scholar]
  15. Gibson, A.G.; Humphrey, J.K.; Di-Modica, P.; Christke, S.; Kotsikos, G.; Holliday, R. Post-fire integrity of composite gratings for offshore platforms. J. Reinf. Plast. Comp. 2014, 33, 543–555. [Google Scholar] [CrossRef]
  16. So, W.; Kim, Y.H.; Shin, D.I.; Lee, G.B.; Yoon, E.S. Optimal Location of Additional Facilities for Minimization of Domino Effect. Korean J. Chem. Eng. 2011, 28, 656–666. [Google Scholar] [CrossRef]
  17. Han, S.H.; Lee, H.C.; Park, K.S.; Kim, T.O. Consequence Analysis for Fire and Explosion Accidents in Propylene Recovery Process. J. Korean. Inst. Gas. 2014, 18, 52–60. [Google Scholar] [CrossRef] [Green Version]
  18. Hightower, M.; Gritzo, L.; Luketa-Hanlin, A. Safety implications of a large LNG tanker spill over water. Process. Saf. Prog. 2005, 23, 168–174. [Google Scholar] [CrossRef]
  19. Yet-Pole, I.; Shu, C.M.; Chong, C.H. Applications of 3D QRA technique to the fire/explosion simulation and hazard mitigation within a naphtha-cracking plant. J. Loss Prev. Process Ind. 2009, 22, 506–515. [Google Scholar] [CrossRef]
  20. Witlox, H.W.M.; Fernandez, M.; Harper, M.; Oke, A.; Stene, J.; Xu, Y. Verification and validation of Phast consequence models for accidental releases of toxic or flammable chemicals to the atmosphere. J. Loss Prev. Process Ind. 2018, 55, 457–470. [Google Scholar] [CrossRef]
  21. Risk Management Program Guidance for Offsite Consequence Analysis. Available online: https://www.epa.gov/rmp/rmp-guidance-offsite-consequence-analysis (accessed on 6 March 2020).
  22. Cozzani, V.; Tugnoli, A.; Salzano, E. The development of an inherent safety approach to the prevention of domino accidents. Accid. Anal. Prev. 2009, 41, 1216–1227. [Google Scholar] [CrossRef] [PubMed]
  23. Lin, C.I.; Wang, H.F. Research on Safety and Security Distance of Flammable Liquid Storage Tank. Procedia Eng. 2011, 11, 51–60. [Google Scholar] [CrossRef] [Green Version]
  24. Han, D.H.; Lee, J.H. Performance Based Design of Passive Fire Protection Using Consequence Analysis. J. Korean Soc. Saf. 2004, 19, 102–107. [Google Scholar]
  25. Stickles, R.P.; Melhem, G.A.; Eckhardt, D.R. Improve the design of fire emergency relief systems. Chem. Eng. Prog. 1995, 91, 50–57. [Google Scholar]
  26. Brewerton, R.W.; Geddes, P.; Medonos, S.; Raman, R.; Wilkins, C.C.E. Experience in the Application of the Goal Setting Regime and Risk-Based Design of Safety Critical Elements in the Oil & Gas Industry. In Proceedings of the International Conference on Offshore Mechanics and Arctic Engineering (OMAE), Nantes, France, 9 June 2013. [Google Scholar]
  27. Schofield, S. Offshore QRA and the ALARP principle. Reliab. Eng. Syst. Safe 1998, 61, 31–37. [Google Scholar] [CrossRef]
Figure 1. Methodology flowchart in this study.
Figure 1. Methodology flowchart in this study.
Ijerph 17 02849 g001
Figure 2. Thermal radiation radius up to 37.5 kW/m2 according to ethylene storage capacity at ambient temperature (25 °C).
Figure 2. Thermal radiation radius up to 37.5 kW/m2 according to ethylene storage capacity at ambient temperature (25 °C).
Ijerph 17 02849 g002
Figure 3. Thermal radiation radius up to 37.5 kW/m2 according to ethylene storage capacity in summer (40 °C) and winter (0 °C) conditions.
Figure 3. Thermal radiation radius up to 37.5 kW/m2 according to ethylene storage capacity in summer (40 °C) and winter (0 °C) conditions.
Ijerph 17 02849 g003
Figure 4. Thermal radiation radius up to 37.5 kW/m2 according to ethylene storage capacity in ambient temperature (25 °C), summer (40 °C), and winter (0 °C) conditions.
Figure 4. Thermal radiation radius up to 37.5 kW/m2 according to ethylene storage capacity in ambient temperature (25 °C), summer (40 °C), and winter (0 °C) conditions.
Ijerph 17 02849 g004
Table 1. Thermal radiation rating adversely affecting chemical plant equipment.
Table 1. Thermal radiation rating adversely affecting chemical plant equipment.
SourceDescription
Assessment Guidance: Dinenno (1982)37.5 kW/m2: Equipment damage (Gelderblom, 1980)
Effects of Thermal Radiation—World Bank: 198537.5 kW/m2: Sufficient to cause damage to process equipment
Design and Assessment Guidance—BS 5980: 199037.5 kW/m2: Intensity at which damage is caused to process equipment
Table 2. Process condition of ethylene storage tank.
Table 2. Process condition of ethylene storage tank.
Operating ConditionVariable
Operating temperature−103.2 °C
Operating pressure0.055 kgf/cm2g
Storage capacity10, 15, 20, 25, 30, 35, 40, 45, 50 m3
Table 3. Wind speed and atmospheric stability applied to the simulation.
Table 3. Wind speed and atmospheric stability applied to the simulation.
Weather CaseWind Speed (m/s)Atmospheric Stability
Case 11.5D
Case 2F
Case 33D
Case 4F
Case 55D
Case 6F
Table 4. Simulation results at ambient temperature (25 °C).
Table 4. Simulation results at ambient temperature (25 °C).
Weather CaseEthylene Storage Volume (m3)Distance Downwind to Intensity Level 3 (37.5 kW/m2) (m)
Case 1 (1.5/D) and Case 2 (1.5/F)1055.9493
1566.7322
2075.5822
2583.1903
3089.9265
3596.0267
40101.657
45106.838
50111.732
Case 3 (3/D) and Case 4 (3/F)1063.4705
1575.0616
2084.5516
2592.666
3099.8702
35106.335
40112.298
45117.83
50123.013
Case 5 (5/D) and Case 6 (5/F)1068.2042
1580.3337
2090.2283
2598.6466
30106.096
35112.864
40119.004
45124.654
50130.074
Table 5. Regression analysis results according to polynomial fitting: Simulation under ambient temperature (25 °C) condition.
Table 5. Regression analysis results according to polynomial fitting: Simulation under ambient temperature (25 °C) condition.
Weather CaseInterceptB1B2Statistics
ValueStandard ErrorValueStandard ErrorValueStandard ErrorAdj. R-Square
Case 1 and 235.463081.14322.27850.08498−0.015280.001390.99894
Case 3 and 441.496521.260582.448070.09371−0.01660.001530.99887
Case 5 and 645.274721.34562.558670.10003−0.017520.001640.99881
Table 6. Wind speed and atmospheric stability applied to simulations in summer (40 °C) and winter (0 °C) conditions.
Table 6. Wind speed and atmospheric stability applied to simulations in summer (40 °C) and winter (0 °C) conditions.
Weather CaseWind Speed (m/s)Temperature (°C)
Summer Case 11.540
Summer Case 23
Summer Case 35
Winter Case 11.50
Winter Case 23
Winter Case 35
Ambient Case 11.525
Ambient Case 23
Ambient Case 35
Table 7. Simulation results in summer (40 °C) and winter (0 °C) conditions.
Table 7. Simulation results in summer (40 °C) and winter (0 °C) conditions.
Weather CaseEthylene Storage Volume (m3)Distance Downwind to Intensity Level 3 (37.5 kW/m2) (m)
Summer Case 11051.9886
1562.0542
2070.2753
2577.3549
3083.593
3589.2994
4094.5108
4599.3632
50103.851
Summer Case 21068.2257
1580.8162
2091.0897
2599.9327
30107.739
35114.842
40121.359
45127.348
50132.939
Summer Case 31065.2316
1576.791
2086.1365
2594.1513
30101.218
35107.59
40113.409
45118.836
50123.868
Winter Case 11062.3411
1574.4295
2084.2913
2592.8115
30100.386
35107.262
40113.569
45119.4
50124.91
Winter Case 21069.1151
1581.8961
2092.3217
25101.286
30109.233
35116.433
40123.039
45129.183
50134.869
Winter Case 31072.8759
1586.0084
2096.7068
25105.938
30114.078
35121.426
40128.206
45134.439
50140.301
Table 8. Regression analysis results according to polynomial fitting: Simulation under summer (40 °C) and winter (0 °C) conditions.
Table 8. Regression analysis results according to polynomial fitting: Simulation under summer (40 °C) and winter (0 °C) conditions.
Weather CaseInterceptB1B2Statistics
ValueStandard ErrorValueStandard ErrorValueStandard ErrorAdj. R-Square
Summer Case 132.915241.066292.12270.07927−0.014280.00130.99894
Summer Case 244.332291.323742.65960.0984−0.0180.001610.99895
Summer Case 343.456161.282132.431860.09531−0.016720.001560.9988
Winter Case 139.446951.267652.545530.09423−0.016970.001540.99897
Winter Case 244.906771.356022.694890.1008−0.018170.001650.99893
Winter Case 347.984251.403692.772110.10435−0.018790.001710.99891
Table 9. Storage capacity of ethylene to satisfy the safety distance of GAP.2.5.2 according to atmospheric conditions.
Table 9. Storage capacity of ethylene to satisfy the safety distance of GAP.2.5.2 according to atmospheric conditions.
Weather ConditionEthylene Capacity Where the Safety Distance of GAP.2.5.2 Can Be Conservative (m3)
Ambient25 °C and 1.5D44.6 or less
25 °C and 3D34.9 or less
25 °C and 5D30.3 or less
Summer40 °C and 1.5D55.5 or less
40 °C and 3D29.2 or less
40 °C and 5D33.9 or less
Winter0 °C and 1.5D34.2 or less
0 °C and 3D28.3 or less
0 °C and 5D25.6 or less

Share and Cite

MDPI and ACS Style

Choi, J.-Y.; Byeon, S.-H. Case Study: Safety Assessment of Plant Layout between Ethylene Storage Tanks and Process Equipment According to Capacity and Weather Conditions. Int. J. Environ. Res. Public Health 2020, 17, 2849. https://doi.org/10.3390/ijerph17082849

AMA Style

Choi J-Y, Byeon S-H. Case Study: Safety Assessment of Plant Layout between Ethylene Storage Tanks and Process Equipment According to Capacity and Weather Conditions. International Journal of Environmental Research and Public Health. 2020; 17(8):2849. https://doi.org/10.3390/ijerph17082849

Chicago/Turabian Style

Choi, Jae-Young, and Sang-Hoon Byeon. 2020. "Case Study: Safety Assessment of Plant Layout between Ethylene Storage Tanks and Process Equipment According to Capacity and Weather Conditions" International Journal of Environmental Research and Public Health 17, no. 8: 2849. https://doi.org/10.3390/ijerph17082849

APA Style

Choi, J. -Y., & Byeon, S. -H. (2020). Case Study: Safety Assessment of Plant Layout between Ethylene Storage Tanks and Process Equipment According to Capacity and Weather Conditions. International Journal of Environmental Research and Public Health, 17(8), 2849. https://doi.org/10.3390/ijerph17082849

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop