1. Introduction
Realizing the development and utilization of green and clean energy has become a major trend to solve problems such as traditional energy shortages and environmental degradation. To ensure the consumption and efficient use of the large scale new energy, effective transmission technology is needed as a support [
1]. As the multi-terminal high-voltage direct current (HVDC) transmission system has the advantages of long transmission distance capability, large capacity and a flexible operation mode, etc., it has therefore become one of the main means to facilitate grid connections of large-scale renewable energy [
2].
Unreasonable distribution of the transmission line currents can introduce unnecessary transmission line losses, or even an overload of the converter station. In order to facilitate the power flow management inside the DC transmission network, inspired by the idea of power flow control devices developed in the AC transmission system, such as a unified power-flow controller (UPFC) and thyristor controlled series compensator (TCSC), a DC power flow controller (DCPFC) can be introduced in the multi-terminal HVDC transmission system [
3]. However, since the DC system does not have reactive power, reactance and phase angle, its power flow control can only be realized by adjusting the resistance or DC voltage of the transmission line. Therefore, there are two general design approaches for the DCPFC, which are a resistance control type and a DC voltage control type.
- (1)
For the resistance control type DCPFC, different implementation schemes have been designed in reference [
4] and reference [
5]. This kind of control scheme is simple to implement, but it can only adjust the equivalent resistance of the line in one direction, which limits its power flow control ability.
- (2)
For the DC voltage control type DCPFC, according to the voltage regulation means, it can be further divided into three main types, which are ① a DC transformer type [
6,
7,
8,
9,
10], ② an auxiliary voltage source type [
11,
12,
13,
14,
15] and ③ a capacitor-based interline energy-exchanged type [
3,
16,
17,
18,
19,
20,
21,
22,
23,
24]. In comparison, the DCPFC of capacitor-based interline energy-exchanged type has more advantages and better application prospects. For instance, it has fewer power devices; does not require an external power supply device; and can avoid withstanding the system-level high voltage and power, which help reduce the stress requirements of the power devices and system losses. Therefore, it has become a kind of DCPFC which is currently more researched and heavily focused on [
3,
20].
The capacitor-based interline energy-exchanged type DCPFC is usually called the interline DCPFC (IDCPFC). As shown in
Figure 1, its main control idea is to exchange the power between different transmission lines by charging/discharging the capacitor of IDCPFC, thereby achieving the power flow control of the transmission lines. Based on the concept depicted in
Figure 1a, two current flow controller (CFC) topologies were first proposed in reference [
16], however, only the basic conceptualization is introduced, its working principles and control method are not investigated enough. Focus on one topology of the CFC, its control strategy and operation principles were discussed in reference [
17]. Focus on the control method of another method was designed in references [
18,
19]. In addition, its operation states were analyzed, and an average mode which can be used for perform steady-state analysis was derived in reference [
19]. Furthermore, in order to simplify the CFC circuit structure, an improved CFC topology was proposed in reference [
20], and its characteristics were detailed compared to the traditional CFC topology proposed in reference [
16]. Based on the concept depicted in
Figure 1b, by increasing the DC capacitor number and introducing coupled inductors, a novel type of IDCPFCs with independent connections of the capacitor in two lines were respectively investigated in references [
3,
21,
22,
23]. In reference [
24], the application modular multilevel converter (MMC) device was also considered, and an MMC-based IDCPFC was proposed. These schemes in reference [
3,
21,
22,
23,
24] avoided the capacitor switching in the line. However, it should be noted that all the above existing topologies are characterized by two-port characteristics, which can only assist in regulating the current on one line. If the power flow control of multiple lines is required at the same time, the corresponding multi-port topology should be developed, and this problem is also an area that this paper deals with.
Currently, the research on multi-port IDCPFC (MI-DCPFC) is still in its infancy. Based on the MMC-based IDCPFC proposed in reference [
24], a MI-DCPFC topology based on MMC was developed in reference [
25]. However, it requires multi-winding transformers and needs to connect MMC in each control line, which leads to higher system costs. In addition, with the controlled line number being increased, its circuit topology and control system become relatively complicated. In reference [
26], a MI-DCPFC topology based on identical insulated gate bipolar transistor (IGBT) half-bridge was proposed. Its system structure is simple, and the cost of the port expansion is low. However, as only a basic control method is introduced, it can not achieve independent tracking of the current regulation commands for each transmission line, where the power flow regulating has limited freedom.
Combining the precious work in reference [
26], this paper presents a switches reduced topology of MI-DCPFC. In addition, for solving the problem of coupling of the port-output voltage of the traditional MI-DCPFC, a novel control strategy based on carrier phase shifting pulse width modulation (CPS-PWM) is proposed. This strategy achieved the decoupling of the port-output voltage, which can ensure independent tracking of the power flow regulating commands for different controlled lines. Moreover, key relationships between the system state variables were also detailed in this study. Finally, two five-terminal HVDC transmission systems were developed, and the performance of the proposed controller and control strategy were confirmed with the simulation and experiment studies under different conditions. The remainder of this paper is organized as follows: the traditional MI-DCPFC including its topology and control strategy is analyzed in
Section 2. The topology and operation principles of the simplified MI-DCPFC are analyzed in
Section 3. The novel control strategy is designed and the relationships between the system state variables are discussed in
Section 4. The simulation and experiment verifications are respectively carried out in
Section 5 and 6. Finally, a conclusion is given in
Section 7.
5. Simulation Results
To confirm the proposed MI-DCPFC topology and control strategy, the related verification was carried out in MATLAB/SIMULINK. The five-terminal HVDC transmission system as shown in
Figure 1 (repainting it as
Figure 13a) and a more complicated five-terminal HVDC transmission system with four-port MI-DCPFC as shown in
Figure 13b were developed, respectively.
The converter node VSC4 controls the systems DC bus voltage at 200 kV. The converter nodes VSC1 to VSC3 and the converter node VSC5 respectively inject P1 = 80 MW, P2 = 100 MW, P3 = 60 MW and P5 = 80 MW active power into the system. The main parameters of each transmission line are shown in
Table 4.
5.1. Three-Port MI-DCPFC Verified Results
5.1.1. Case 1
The working-mode 1 (I14 is reduced; I24 and I34 are increased) was verified in this case. In addition, to make it easy to compare and analyze each one, the simplified MI-DCPFC with the traditional and novel control methods were both tested, respectively.
The performance of the MI-DCPFC with the traditional control method in this case is shown in
Figure 14a–c. The MI-DCPFC is accessed into the system at 0.2 s, and with the command controlling line.14 current reduces to
I14 = 0.1 kA. It can be seen that before adjusting the line currents, the system is operating at a stable rate, and the values of each line current are about
I14 = 0.35 kA;
I24 = 0.62 kA;
I34 = 0.23 kA;
I45 = 0.40 kA;
I12 = 0.06 kA;
I23 = −0.07 kA, respectively. When the MI-DCPFC is inserted to the system at 0.2 s, the controlled line current
I14 quickly respond to the command value and maintain stable operation, as shown in
Figure 14a. In addition, as shown in
Figure 14b,c, the voltage
VTP1 introduced in the line 14 is stably switched between 0 and
Uc; while the voltages introduced in line 24 and line 34 are synchronized to switch between 0 and −
Uc, so
I24 and
I34 automatically respond to
I24 = 0.82 kA and
I34 = 0.28 kA, respectively. We found that the specific increased amounts of the currents
I24 and
I34 cannot be controlled separately at this time, which is consistent with the theoretical analysis in the previous section.
The performance of the MI-DCPFC with the novel control method is shown in
Figure 14d–g. The MI-DCPFC is inserted to the system at 0.2 s, and with the command in control,
I14 reduces to
I14 = 0.1 kA and
I24 remains unchanged. When operating to 1.2 s, the regulation command is re-changed, where with controlling
I14 reduced to 0.1 kA, but control
I24 increases to 0.7 kA. It can be observed that when the MI-DCPFC is accessed in the system, the controlled line current
I14 can also quickly respond to
I14 = 0.1 kA and maintain stable operation, as shown in
Figure 14d. What is more, it can be found that unlike with the traditional control method, as the voltage
VTP2 introduced in the line24 can be controlled and stably switched between
Uc, 0 and −
Uc, so the increased amounts of the current
I24 can be controlled freely at the same time.
The above simulation results show that the simplified MI-DCPFC with the novel control strategy can achieve the power flow control quickly and stably under the working-mode 1. Furthermore, when compared to the traditional control strategy, on the basis of the reducing control of the line current, the increased value of other line currents can be also controlled freely at the same time. In addition, the capacitor voltage fluctuation is small, and the voltage state introduced in the connection line by the output port is consistent with the theoretical analysis.
5.1.2. Case 2
The working-mode 6 (I24 and I34 are reduced; I14 is increased) was verified in this case. Similarly, to make it easy to compare and analyze the simplified MI-DCPFC with the traditional and novel control methods were tested, respectively.
The performance of the MI-DCPFC with the traditional control method in this case is shown in
Figure 15a–c. The MI-DCPFC is accessed into the system at 0.2 s, and with the command controlling line 34, the current reduces to
I34 = 0.15 kA. It can be observed that the controlled line current
I34 quickly responds to the command value and maintains stable operation when the MI-DCPFC is accessed in the system at 0.2 s, as shown in
Figure 15a. However, as shown in
Figure 15b,c, since the voltage
VTP2 introduced in the line 24 and voltage
VTP3 introduced in line 34 are synchronized to switch between 0 and
Uc, although the
I34 is also reduced, its specific reduced amounts cannot be controlled separately at this time.
The performance of the MI-DCPFC with the novel control method is shown in
Figure 15d–g. The MI-DCPFC is accessed in the system at 0.2 s, and with the command in control,
I24 and
I34 are reduced to
I24 = 0.5 kA and
I34 = 0.15 kA, respectively. When operating to
t4, the power flow control command is re-changed, where with controlling occurring,
I34 was reduced to 0.15 kA, but control
I24 further reduces to 0.4 kA. It can be observed that when the MI-DCPFC is accessed in the system, the controlled line current
I34 quickly responded to
I34 = 0.15 kA and maintained stable operation, as shown in
Figure 15d. What is more, the reduced amounts of the current
I24 can simultaneously be controlled freely with the reducing control of
I34. Correspondingly, the voltage
VTP2 introduced in the line 24 is controlled and stably switched between
Uc, 0 and −
Uc, as shown in
Figure 15e–g.
The simulation results in this case show that the simplified MI-DCPFC with the novel control strategy can achieve the power flow regulation quickly and stably under the working-mode 6. Furthermore, compared to the traditional control strategy, independent reduction control of each line current can be achieved when multiple line currents are reduced. Meanwhile, the capacitor voltage fluctuation is small, and the voltage state introduced in the connection line by the output port is consistent with the theoretical analysis.
5.2. Four-Port MI-DCPFC Verified Results
In order to further test the performance of the MI-DCPFC, the verification of a four-port MI-DCPFC was carried out. When the system starts up normally, it is tested with the following three different conditions, and the performance of the MI-DCPFC is shown in
Figure 16; the measurement values of each line current under different test conditions are shown in
Table 5.
- (1)
At 0.2 s, control I14 reduces to 0.05 kA, and control I24 and I45 increase to 0.7 kA and 0.5 kA, respectively;
- (2)
At 0.2 s, control I14 and I45 reduce to 0.2 kA and 0.3 kA, respectively; and control I24 increases to 0.7 kA;
- (3)
At 0.2 s, control I14, I45 and I24 reduce to 0.2 kA, 0.3 kA and 0.4 kA, respectively.
It can be observed that under the different control conditions, the controlled lines can all quickly track the corresponding power flow control commands, and then maintain stable operation. In addition, we can note that in the test conditions 1 and 3, MI-DCPFC only operates in control-mode 1 and control-mode 2, respectively; in test condition 2, control-mode 1 and -mode 2 participate in the regulation work simultaneously.
Concluding all previous simulation studies in this section, it can be seen that with the CPS-PWM control strategy proposed in this paper, the simplified MI-DCPFC can achieve effective power flow control under different power flow regulation requirements and its response speed is faster.