An Economic Analysis of Load Leveling with Battery Energy Storage Systems (BESS) in an Electricity Market Environment: The Korean Case

1
Department of Electrical and Computer Engineering, Seoul National University, 1 Gwanak-ro, Gwanak-gu, Seoul 08826, Korea
2
Department of Electrical Engineering, Jeju National University, 102 Jejudaehak-ro, Jeju-si, Jeju 63243, Korea
*
Author to whom correspondence should be addressed.
Energies 2019, 12(9), 1608; https://doi.org/10.3390/en12091608
Submission received: 22 March 2019 / Revised: 20 April 2019 / Accepted: 23 April 2019 / Published: 27 April 2019
(This article belongs to the Special Issue Distributed Energy Storage Devices in Smart Grids)

Abstract

:
The capacity of battery energy storage systems (BESS) is expected to increase for power system applications. However, as the cost of BESS is high, economic feasibility must be considered when using BESS in grid applications. Load leveling with BESS is one such application for which the economic implications have been analyzed in the literature. However, these studies do not sufficiently consider the fact that the leveled loads will lead to a change in electricity prices, thereby modifying charging/discharging operations of BESS. Additionally, in a competitive electricity market, electricity prices are not determined by the generator cost functions. Market participants’ strategic decisions also affect prices. Therefore, we conducted an economic analysis of load leveling with BESS in an electricity market from the perspective of a utility company and/or a government agency. In our analysis of the Korean market, we examine whether the leveled loads necessarily lead to economic benefits. Load leveling performance and the associated economic benefit are quantitatively analyzed for varying sizes of BESS. Further, the policy implications related to using BESS are derived from the analysis results.

1. Introduction

The urgent environmental need to reduce greenhouse gas emissions has led to the integration of renewable energy sources (RESs) into the power grid. In 2018, the global cumulative installed capacity of RESs such as wind power and solar photovoltaic (PV) generation amounted to 539,123 MW [1] and 402.5 GW [2], respectively. However, RESs have disadvantages in terms of variability, intermittency, and uncertainty of electricity generation [3]. Therefore, energy storage systems (ESS), particularly battery ESS (BESS), have recently been attracting significant interest in the electricity industry as an effective means of mitigating the disadvantages of RESs [4,5].
The installed BESS capacity for power system applications is expected to increase consistently, not only for utility-scale applications but also for distributed small-scale applications, whereby a large number of BESS are expected to be connected to PV systems and behind the meter [6,7]. This trend of increasing BESS usage is likely to be accelerated by the widespread adoption of electric vehicles (EVs), supported by improvements in vehicle-to-grid and grid-to-vehicle technologies [8]. Furthermore, cost reductions in BESS technology are widely expected to become a key determinant of their increased installation. For instance, it is expected that the cost of lithium-ion BESS will decrease significantly, namely by 54–61%, between 2016 and 2030 [6], or by 52% between 2018 and 2040 [9]. For the latter period, it is estimated that USD 620 billion in investment in the vehicle and the electricity sectors will ensue [9].
Despite the positive forecasts regarding the cost of BESS, currently, costs are still so high that the economic feasibility of their installation is not always given [10]. For this reason, several studies have dealt with the economic aspects of BESS [11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30,31,32,33,34,35,36,37,38]. For instance, studies examine the BESS size and the associated charging/discharging strategy for optimal usage, either by minimizing total cost or maximizing the net present value (NPV) of grid-connected renewable energy systems [11,12,13,14,15]. Further, for a given BESS capacity, studies examine the operating strategy (i.e., the charging/discharging schedule) is determined to minimize the cost or maximize the net benefit under a dynamic pricing scheme [16,17,18]. Other researchers consider how a bidding strategy for BESS in an electricity market environment can also be developed to increase profit [19,20]. The economic aspects of BESS have also been considered for EV charging station planning [21,22,23]. Finally, economic considerations are important in the process of designing and operating a microgrid with ESS [24,25,26], where the methods based on particle swarm optimization have been used to determine an optimal size and/or an optimal operational strategy of ESS in a microgrid. Particular consideration is given to the integration of RESs into the microgrid in [24,25,26].
Economic feasibility is also an important factor to be considered for the various grid applications of BESS [5,27]. This study focuses on the application of load leveling and analyzes its economic benefits. Peak shaving using the discharging operation of BESS (when electricity demand is particularly high) is inevitably followed by the charging operation during off-peak periods. Therefore, the analysis of load leveling with BESS in this study includes peak shaving. Previous studies dealing with the economic aspects of load leveling with BESS obtained the following results: It was found that load leveling with BESS achieves an increase in the cost savings of thermal units [28,29,30]. Further, research suggests that BESS can be used to maximize the NPV of a renewable energy system and a substation [31,32]. Evidence also suggests that the leveled loads with BESS may provide economic benefits by reducing the required capacity of other equipment, such as generators and transformers, and by reducing the frequency with which investment in such network equipment is needed [33]. Finally, it has been shown that an economic benefit can also be obtained by peak shaving or peak reduction with BESS under a dynamic electricity pricing scheme [34,35,36]. Since the accurate forecasts of generation and load are essential to improving the performance of peak shaving, a method for peak shaving combined with a forecasting method based on the adaptive neuro-fuzzy inference system is presented in [37].
Customers of electricity providers, particularly the industrial customers, pay the electricity bill, which is comprised of the consumed energy cost and the peak demand surcharge. Thus, the economic benefit of load leveling or peak reduction with BESS is obvious to customers. Since the buying cost of electricity is a major cost component of a utility company, the provider’s economic benefit with BESS corresponds to the reduction in the purchasing cost. Further, this economic benefit is relevant for the government agencies which are responsible for the policies of the electricity industry because the government permits billing rates to customers considering the cost of a utility. It can induce a utility to lower the bill if the cost can be reduced by load leveling with BESS. This study considers the perspective of a utility company and/or government agency. Hence, the problem to address in this study can be simply expressed as the following questions: Does load leveling with BESS necessarily lead to the economic benefit of a utility company? If so, how does the economic benefit change as the BESS size increases? If not, what is the reason for the results contrary to the previous studies?
Answering these questions fills a research gap as the insightfulness of previous studies is limited by the fact that electricity prices are always regarded as given. However, if the number and/or size of BESS is large, then the leveled loads with BESS will result in a change in electricity prices, which, in turn, modifies the charging/discharging operation of BESS. Accounting for this reality induces an iterative process that is challenging to resolve. If the electricity price follows a typical parabolic cost function, the iterative process may be resolved by mathematically finding a converging point. However, in a competitive electricity market, the strategic decisions of participants may distort the electricity price pattern. Therefore, the change in electricity prices due to the leveled loads with BESS should be estimated as a basis for performing any economic analysis. Consequently, in this study, we derive the answers to the research questions by conducting an economic analysis of load leveling from the perspective of a utility company, while considering changes in electricity prices, particularly thus induced by large BESS in an electricity market environment. To illustrate the results, we consider the situation of Korea’s electricity market and use the corresponding data as a case study.
The contributions of this paper are (1) the change in electricity prices due to the leveled loads are explicitly considered in the economic analysis as the price function is defined with respect to loads; (2) in defining the price function, a data-driven regression model is used and estimation accuracy is achieved by data grouping; (3) it is shown as a main claim that it may be blind faith for load leveling with BESS whereby a large cumulative capacity of BESS is always economically beneficial.
The remainder of the paper is organized as follows. To provide important background information, Section 2 summarizes the structure of the Korean electricity market. Section 3 describes the optimization formulation to perform load leveling and a method to estimate electricity prices with respect to the load. Section 4 presents the necessary data for the analysis. Section 5 presents the results of the case study, followed by a discussion in Section 6. Finally, concluding remarks are provided in Section 7.

2. Korean Electricity Market

The electric industry in Korea was re-structured in 2001, whereby the vertically integrated utility company, the Korea Electric Power Corporation (KEPCO), was divided into an independent system operator, the Korea Power Exchange (KPX); some generation companies (GENCOs), subsidiaries of KEPCO; and the KEPCO itself playing correspondingly a reduced role. The Korean electricity market was also defined as a result of the restructuring and is now run by the KPX.
The Korean electricity market is a cost-based pool. The GENCOs submit the amount of electricity generation capacity and the cost function to the KPX. Then, the KPX determines the hourly generation of each GENCO based on forecasted demand. The methods applied to this end, such as economic dispatch or optimal power flow, must satisfy various conditions, such as balance of supply and demand, reserve requirements, and maximum power flows of transmission lines. The KPX also sets the hourly system marginal price (SMP). The SMP is usually set as the marginal generation cost of the most expensive generator, or the marginal generator, and is used in the settlement process. The KEPCO buys electricity through the market and pays the GENCOs according to the SMP. The KEPCO recovers the cost of purchasing electricity by invoicing customers based on the billing rates approved by the government agency.

3. Methodology

3.1. Load Leveling

The variation in original loads is mitigated or leveled by BESS charging/discharging operations. The load leveling performance can be evaluated based on how close the leveled loads are to a reference value. The mean-squared error (MSE) is selected in this study as a measure of closeness to the reference value. Thus, the objective function to determine the optimal BESS operation for load leveling is the MSE with respect to the reference value ( P ¯ r e f , h ):
1 H h = 1 H ( P L , h P ¯ r e f , h ) 2
where P L , h is the original load at hour h and H is the number of hours corresponding to the time horizon for load leveling. The reference, P ¯ r e f , h , is defined for all h as the constant average of the original loads during the entire time period:
P ¯ r e f , h = 1 H k = 1 H P L , k , h = 1 , 2 , H
Alternatively, BESS can be operated for load leveling on a daily basis. In this case, the reference value on a specific day d may be defined as:
P ¯ r e f , h = 1 24 k = 1 24 P L , k , k d
For convenience, the references in Equations (2) and (3) are denoted as the yearly reference (Yref) and the daily reference (Dref), respectively. After including BESS, P L , h in (1) is replaced with the leveled load, P ˜ L , h , defined as:
P ˜ L , h = P L , h + P B , h
where P B , h is the electricity used to charge the BESS (leading to a positive value) or discharged from the BESS (resulting in a negative value) at hour h . Therefore, load leveling involves determining the value of P B , h that minimizes Equation (1), subject to the BESS-related constraints described below.
The first constraint is related to the maximum hourly charging and discharging power, P B m a x , given as:
P B m a x P B , h P B m a x
In this study, the value of P B m a x is considered equal to BESS capacity. For normal operation, the state of charge (SOC) of the BESS should be bounded:
S O C B l o w S O C B , h S O C B u p p
where S O C B , h is the SOC at hour h and S O C B l o w and S O C B u p p are the lower and upper bounds of the SOC, respectively. The value of S O C B , h is updated every hour according to the following rule:
S O C B , h = { S O C B , h 1 + η B , c h P B , h / P B m a x , if   P B , h > 0   ( charging ) S O C B , h 1 , if   P B , h = 0   ( no   operation ) S O C B , h 1 + P B , h / ( η B , d c h P B m a x ) , if   P B , h < 0   ( discharging )
where η B , c h and η B , d c h are the charging and discharging efficiencies, respectively. From Equation (7), even if η B , c h and η B , d c h are equal, the update equation is asymmetric because the effects of these values are different for charging and discharging. However, the asymmetry for considering the loss of BESS makes the solution of the optimization problem using the mixed integer quadratic programming method extremely time-consuming. For example, when H is set to 168 h (one week), both η B , c h and η B , d c h are set to 95%, the BESS size is 50 GWh, the computation time to find the optimal solution is 110 s. By contrast, if the loss of BESS is neglected, that is, if η B , c h and η B , d c h in Equation (7) are equal to one, it can be reduced to a simpler equation:
S O C B , h = S O C B , h 1 + P B , h / P B m a x
As a result, for the same load leveling problem over 168 h, the computation time falls significantly to just 0.2 s, which is a 99.82% decrease in computation time. The leveled loads with and without the loss of BESS are shown in Figure 1 together with the original load. Figure 1 clarifies that the solutions for the two cases are very similar in shape, and their mean absolute percentage errors (MAPEs) are as small as 0.26%. This minor difference is not the primary concern of this study. Moreover, in our analysis, H is equal to 8760 h (one year). This means that if the formulas that consider the loss of BESS are applied, the computation time would be too large because the search space expands exponentially as H increases. Consequently, Equation (8) without loss is used instead of Equation (7) for the remainder of this study. This enhances computational efficiency without causing a noteworthy loss of informativeness of results.

3.2. Electricity Price as a Function of Load

Electricity prices should be represented as a function of load to estimate the change in price for the leveled loads. Among the methods for identifying the relationship between input and output values, we selected the polynomial regression method [38], in which the load corresponds to the input, and the electricity price is the output. Then, the price function, ρ h ( P L , h ) , can be represented as:
ρ h ( P L , h ) = β 0 + β 1 P L , h + β 2 P L , h 2 + + β m P L , h m + ε h
where β m ’s are the regression coefficients and ε h is the error term. It should be noted that the original loads, P L , h , are used in (9) because the price function is found using the original loads. Then, the change in price after load leveling is estimated by substituting the leveled load, P ˜ L , h , into the price function in (9).
The degree of the polynomial, m , is selected according to the adjusted R 2 index, which indicates the quality of the regression model. When a model fits the data well, the adjusted R 2 index becomes closer to 1 [38]. Therefore, the degree of the polynomial is chosen as the value where the adjusted R 2 saturates at a value closer to 1 or its rate of increase becomes moderately small.

4. Case Description

The data on loads and electricity prices are taken from the Korean power system for the year 2018 [39,40]. The case study consists of three steps. The first step is to find the leveled loads using BESS based on the formulation in Section 3.1. It is performed by varying the BESS size from 1 GWh to 150 GWh by increments of 1 GWh, where the maximum size is approximately 1.7 times the peak load of 87.03 GWh. The maximum and minimum SOC are set to 90% and 10%, respectively. The two references of Yref and Dref are applied separately. The second step is to represent the electricity prices as a function of loads using a polynomial regression. In order to determine a suitable degree of polynomial, the adjusted R-squared values are calculated by varying the degree of the polynomial (which entails varying the number of terms in the polynomial regression) from one to nine. Then, the fitted price function of loads is derived as a polynomial function of the selected degree. The final step is to perform the economic analysis by calculating the total cost of leveled loads based on the results from the first and second steps.
For a more detailed economic analysis, another simulation, which is essentially the opposite of the previous scenario, is performed to examine how the BESS operation for reducing the cost affects the load leveling performance. In other words, BESS are operated with the goal of minimizing the total cost, not optimizing load leveling. Then, it can be investigated to what extent the adjusted loads are spread with respect to the reference, Yref or Dref, by calculating the MSE. In this second scenario, the first step is to again vary the BESS size from 1 GWh to 150 GWh by increments of 1 GWh, thus determining the charging/discharging schedule of BESS, which reduces the total cost for the original electricity prices. Then, the adjusted loads and the corresponding total cost are calculated. The second step is to calculate the MSE for the adjusted loads with respect to Yref and Dref.
The monthly and hourly load patterns are represented as box plots using Matlab in Figure 2a,b, respectively. When generating Figure 2a, the hourly loads over the year are grouped by month. Thus, the number of data points in each month is equal to 24 h times the number of days in the corresponding month. Then, the monthly loads in each month are sorted in ascending order and represented as a box plot, where the upper and lower sides of the blue box indicate the 75th percentile (the third quartile, Q3) and 25th percentile (the first quartile, Q1), respectively. The red line in the middle of the blue box indicates the median (50th percentile) of the sorted loads and the highest and lowest black lines indicate the maximum and minimum values, respectively. When generating Figure 2b, the hourly loads over the year are grouped by hour, such that there are 365 data for each hour group. Then, the hourly loads for each hour are sorted in ascending order and represented as a box plot. Like Figure 2a, the upper side, the red line, and the lower side of the blue box indicate the 25th percentile, 50th percentile (median), and 75th percentile of the sorted loads. However, the hourly loads are distributed quite widely, such that there are some points that are greater than Q3 + 1.5 times (Q3 − Q1) or less than Q1 − 1.5 times (Q3 − Q1). These data points are referred to as whiskers. This type of points can be interpreted as outliers in data analysis and are represented as red crosses in Figure 2b. If there are red crosses outside the highest and lowest black lines, then the black line indicates Q3 + 1.5 times (Q3 − Q1) or Q1 − 1.5 times (Q3 − Q1); otherwise, it indicates the maximum or minimum value of the sorted hourly loads. The average hourly load of the analyzed year is equal to 61.25 GWh. Figure 2 shows that summer (July and August) and winter (January, February, and December) are the peak seasons of electricity consumption over the year. In addition, during a day, two peaks occur just before and just after noon.
The monthly and hourly patterns of original electricity prices are represented as the box plots using Matlab in Figure 3a,b, respectively. The methods of grouping the price data for the year and the meaning of the symbols of the box plot are the same as those for the loads in Figure 2a,b. Electricity prices need to be represented as a function of load in this study, which requires a relationship to exist between them. Figure 3b shows a similar pattern to Figure 2a, although peak and off-peak hours are not as apparent as the loads. Therefore, it can be inferred that there is a positive relationship between loads and electricity prices. However, the monthly variation of electricity prices in Figure 3a does not show a clear pattern which was observed seen in Figure 2a. Therefore, we checked the correlation coefficient between loads and electricity prices. The correlation coefficient for the entire dataset is 0.47, indicating a moderately positive correlation. By contrast, Table 1 shows that the monthly correlation coefficients are very high, indicating a highly positive relationship. Consequently, the polynomial regression is performed on monthly data, so that a total of 12 price functions are found to estimate the price change in response to the leveled loads. The specific results of the polynomial regression are presented in Section 4.

5. Simulation Results

5.1. Load Leveling

It is expected that the load will be leveled more and the MSE will decrease as the BESS size increases. Further, the important result to be examined is not the absolute value of the MSE, but how much the MSE is reduced when BESS size is increased. Therefore, the load leveling performance in terms of the MSE is represented in Figure 4a as the percentage ratio to the MSE of the original loads without BESS. Since two references of Yref and Dref are used in this study, two graphs of the MSE ratio are shown in Figure 4a. Additionally, the original loads and the leveled loads with the BESS sizes of 50 GWh and 150 GWh for the month of May are shown in Figure 5 to identify the changes from load leveling more clearly. Another measure to examine the load leveling performance is the maximum/minimum values of the leveled loads because they will be closer to a reference, that is, the maximum will decrease and the minimum will increase, as the BESS size increases. Thus, the maximum/minimum values of the leveled loads for Yref and Dref are given in Figure 4b.
Figure 4a shows that the marginal improvement in the load leveling performance by the unit increase in BESS size gradually decreases as BESS size increases. This is because the load duration of very high or very low loads is relatively short, so that a relatively small BESS can significantly improve load leveling. However, as BESS size increases, the duration for which loads need to be lowered or raised with respect to the reference value increases. Therefore, the degree of reduction in MSE decreases. More specifically, the decrease in the degree of reduction is severe, especially for Yref, because the load leveling is performed for the same constant reference over the entire time period. Figure 4a clarifies this relationship by showing the slow decrease in the MSE for Yref, which makes a significant difference for a large BESS. Specifically, the MSE for Dref is reduced to less than 10% for a BESS size greater than 70 GWh. By contrast, the MSE for Yref is still equal to approximately 48%, even for a BESS size of 150 GWh.
On the other hand, as Figure 4b shows, the maximum and minimum values of the leveled loads are almost the same for the two references. Specifically, the maximum values of the leveled loads for the two references are equal to each other in the beginning (hence why the lines in the graph almost exactly coincide), but a difference in the minimum values becomes evident from the BESS size of 30 GWh. The results can be clarified with Figure 5. Regardless of whether the load leveling is performed during a year or a day, the goal is to lower the high loads and raise the low loads. Thus, the overall shapes of Figure 5 for the two reference values are similar. However, the highs and lows improve more for Yref than for Dref. This is because the number of days with high loads, such as summer and winter weekdays, is greater than the number of days with low loads, such as holidays and spring/autumn weekends. Therefore, lowering the maximum total loads for Yref is equivalent to lowering the maximum of a day of high loads for Dref. However, after increasing the minimum of the holidays and weekends of low loads, the minimum of the leveled days of low loads remains unchanged. Consequently, as seen in Figure 4b, the minimum of the leveled load for Dref hardly changes after some point, which corresponds to a BESS size of 30 GWh in this case study.

5.2. Representation of Electricity Prices

In Figure 6, electricity prices are represented as a scatter plot with respect to the load. Although the electricity price appears to increase as the load increases, a relationship between them is difficult to identify. Therefore, considering the monthly correlation coefficients in Table 1, we divide the data by month and represent them as separate scatter plots in Figure 7. Contrary to Figure 6, the variation of data points is small, so a relationship between electricity prices and loads becomes evident.
The results of the adjusted R-squared values are shown in Figure 8. By checking whether the adjusted R-squared value is close enough to 1, the degrees of the polynomial of each month, from January to December, are selected as 6, 3, 4, 4, 4, 4, 5, 3, 4, 4, 4, and 4, respectively. The fitted functions are represented as the solid red lines on the original data points in Figure 7. The fitted graph of each month in Figure 7 represents the original electricity prices well. Specifically, the MAPE of the fitted electricity prices during a year is equal to 1.78%.

5.3. Economic Analysis

First, the accuracy of the fitted electricity price function is examined in terms of the total cost. The total cost for the original prices and loads is calculated as 50,776 billion KRW and the total cost for the fitted prices and original loads is also equal to 50,776 billion KRW. This is evidence of the suitability of the fitted price function. The estimated costs after load leveling with the BESS are shown in Figure 9 as a percentage of the total cost of 50,776 billion KRW for the original prices and loads without BESS. Figure 9 shows that, regardless of whether the load leveling is performed for Yref or Dref, the total cost monotonically increases as BESS size increases. Based on the expectation that an economic benefit should accrue from load leveling due to the reduction in peaks, this result seems counterintuitive at first. However, closer inspection of Figure 7 indicates that this should nevertheless be the natural result because electricity prices increase fast in the range of small loads, but they increase slowly in the range of high loads. As a result, the increased cost due to upward leveling of small loads is greater than the decreased cost from downward leveling of high loads. Consequently, the total cost increases after load leveling with BESS. In addition, Figure 7 shows that the total cost for Yref is greater than that for Dref. This implies that more effort is required to flatten the loads over a longer time period, resulting in a greater cost increase.
The results suggest that we need to rethink the purpose of load leveling. If the price function is a quadratic one based on the cost of the physical operation of generators [41], the total cost will monotonically decrease as BESS size increases, although the extent of the decrease will gradually become smaller. Then, it should be a natural decision to use BESS for load leveling, and the problem is essentially reduced to deciding on a suitable BESS size by comparing the cost decrease from the leveled loads against the cost increase from the BESS. However, as Figure 9 indicates, the costs which are physically incurred by generators is not the only factor to be considered in deciding on electricity prices or bidding prices in a market environment. For example, under some bidding strategies, bid prices for low loads could be set much higher than the actual generation costs and those for high loads could be set at a level comparable to the actual generation cost. In this case, the electricity prices shown in Figure 7 would result. Consequently, without other benefits, such as improved reliability and stability due to the leveled load, one cannot simply assume that load leveling is a worthwhile grid application of BESS from an economic standpoint, particularly in an electricity market environment.

5.4. BESS Operation for Reducing the Cost

The results of the second scenario, the cost minimization scenario, are shown in Figure 10. Like Figure 9, the total cost and the MSE are represented in Figure 10 as the percentage of the corresponding results for the original prices and loads without BESS. Figure 10 shows that the total cost decreases linearly as the BESS size increases because BESS are operated to minimize the total cost. However, the MSEs for Yref and Dref increase rapidly to tens of times the MSE without BESS, which is completely against the purpose of load leveling. This is because, in the process of minimizing the cost, the loads greater than the reference value are increased and the loads less than the reference value are decreased. This means that the loads can be changed to deviate further from the reference value to reduce the cost.

6. Discussion

The results of load leveling in Section 5.1 indicate that loads can be flattened more as BESS size increases. However, it should be noted that the extent of load leveling performance is gradually reduced, while the costs of BESS remain high. Therefore, if the total cost of electricity consumption decreases due to the leveled loads, it may be necessary to compare the marginal reduction in the total cost reduction with the marginal increase in the investment for the unit increase in BESS size. Then, the optimal BESS size can be determined. However, as presented in Section 5.3, the total cost rather monotonically increases as the BESS size increases and the load is correspondingly flattened more. This suggests that the load leveling with BESS may not necessarily lead to economic benefits for a utility company, particularly in a competitive electricity market environment. Subsequently, it becomes meaningless to discuss how much the economic benefit is as the BESS size increases and which BESS size is optimal for the load leveling application in terms of economic benefit. What is the reason for these counterintuitive results? It can be inferred from Figure 7 that the complex strategic decisions of the participants in an electricity market may result in a complex pattern of electricity prices, whereby prices increase quickly in the range of small loads but increase slowly in the range of high loads. In this case, it may be simply incorrect to state that the utility’s investment in BESS can be recovered after some years through the reduced purchasing cost of electricity.
This conflict between the economic benefit and the load leveling application with BESS can be verified more clearly by reviewing the results of the second scenario. In order to reduce the total cost, BESS are charged during the periods of low electricity price and discharged during high price periods. However, this means that operating BESS with the goal of reducing electricity costs actually widened the variation of the resulting loads. Consequently, in a certain electricity market environment, the economic operation of BESS to recover investment costs will increase the fluctuation of net loads. As a result, the side costs of maintaining the reliability and stability of electricity networks may undermine the utility company’s profit.
The results in this study lead to some guidelines for designing a policy related to the BESS for load leveling. First, it should not simply be assumed that BESS with a high cumulative capacity is always economically beneficial even if the investment cost in BESS is low enough. Second, load leveling with the BESS may rather increase the total cost of electricity provision, particularly in a competitive electricity market environment. In this case, the load leveling needs to be linked to other purposes than economic benefit to justify the validity of using the BESS. Third, when a large number of distributed BESS are integrated into the power system, the pricing mechanism of electricity should be elaborately designed to prevent the synchronized operation of the BESS. This is necessary to ensure systems remain sufficiently profitable and that the power system is reliable.

7. Conclusions

BESS, alongside renewable energy sources, are expected to become a major component of future power systems. However, an analysis of their economic feasibility is essential because, at present, the costs of investing in BESS are significant. Among the various grid applications of BESS, this study focused on load leveling and analyzed its economic benefits in an electricity market environment. For economic analysis, load leveling is formulated as a constrained optimization problem, which is then solved using mixed integer quadratic programming. Additionally, the electricity prices are represented as a function of the load using the polynomial regression method to estimate the adjusted prices for the leveled loads.
The results of the economic analysis using Korean data show that the degree of reduction in the MSEs of the leveled loads decreases as BESS size increases. The problem that MSE reduction decreases with the increase in BESS size is more severe for the yearly reference because load leveling is performed for the same constant reference over a longer time period. Further, the results show that, contrary to the simple expectation that load leveling will result in decreased cost of electricity generation, the total cost monotonically increases as the BESS size increases and accordingly, the loads are flattened more. By contrast, if BESS are operated to minimize the cost, the variation of net loads severely increases, which is the opposite to what load leveling is intended to achieve.
The results suggest some guidelines for designing policy related to BESS for load leveling. First, it should not be assumed that a large cumulative capacity of BESS is always economically beneficial if its price is low enough. Second, load leveling with BESS may actually increase the total cost of electricity provision, particularly in a competitive electricity market environment. In this case, the justification for pursuing load leveling needs to be based on some purpose other than economic benefit to ensure the validity of using BESS. Finally, when a large number of distributed BESS are integrated into the power system, the electricity pricing scheme should be elaborately designed to prevent the synchronized operation of BESS and thereby, ensure the power system remains reliable.
Meaningful further research could consider the following topics: First, it is assumed that GENCOs’ bids do not change for utilities’ application of load leveling with BESS. That is, the price function itself may change with leveled loads, which results in another iterative process. Thus, defining this iterative mechanism becomes a research issue, which will be very difficult to be addressed because it involves strategic, not just technical, decisions on behalf of GENCOs. Second, if the leveled loads improve reliability and stability of power systems, a different kind of economic analysis can be done by translating the improved reliability into monetary value. Third, it is assumed in this study that BESS are operated only for load leveling. Thus, it may be necessary to consider that BESS are utilized partly for load leveling and partly for another purpose, and to determine an optimal proportion between the applications of BESS.

Author Contributions

H.T.K. developed the optimization model, set up the simulation environment, and performed the simulations. Y.G.J. designed the study, performed the analysis, thoroughly revised the paper and checked the overall logic of the work. Y.T.Y. provided insightful comments on the modeling and analysis.

Funding

This research was supported by Korea Electric Power Corporation (Grant number: R18XA03) and the 2019 scientific promotion program funded by Jeju National University.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

Acronyms
RESRenewable energy source
PVPhotovoltaic
ESSEnergy storage systems
BESSBattery energy storage systems
EVElectric vehicle
NPVNet present value
KEPCOKorea Electric Power Corporation
KPXKorea Power Exchange
GENCOGeneration company
SMPSystem marginal price
MSEMean-squared error
SOCState of charge
MAPEMean absolute percentage error
Indices
h Index of hour
d Index of day
Parameters
x P ¯ r e f , h Reference for load leveling
P L , h Original load at hour h
P B m a x BESS size
S O C B l o w Lower bound of the SOC
S O C B u p p Upper bounds of the SOC
η B , c h Charging efficiency of BESS
η B , d c h Discharging efficiency of BESS
H Number of hours
m Degree of polynomial in regression
Variables
P ˜ L , h Leveled load at hour h
P B , h Electricity charged (positive) to or discharged (negative) from BESS at hour h
S O C B , h SOC of BESS at hour h
ρ h Electricity price at hour h
β m Regression coefficients
ε h Error term in regression

References

  1. Global Wind Energy Council. Global Wind Report-Annual Market Update 2017. Available online: http://gwec.net/publications/global-wind-report-2/ (accessed on 6 July 2018).
  2. International Energy Agency. A Snapshot of Global PV (1992–2017). Available online: http://www.iea-pvps.org/?id=266 (accessed on 6 July 2018).
  3. Xie, L.; Carvalho, P.M.S.; Ferreira, L.A.F.M.; Liu, J.; Krigh, B.H.; Popli, N.; Ilic, M.D. Wind Integration in Power Systems: Operational Challenges and Possible Solutions. Proc. IEEE 2011, 99, 214–232. [Google Scholar] [CrossRef]
  4. Castillo, A.; Gayme, D.F. Grid-Scale Energy Storage Applications in Renewable Energy Integration: A Survey. Energy Convers. Manag. 2014, 87, 885–894. [Google Scholar] [CrossRef]
  5. Luo, X.; Wang, J.; Dooner, M. Overview of Current Development in Electrical Energy Storage Technologies and the Application Potential in Power System Operation. Appl. Energy 2015, 137, 511–536. [Google Scholar] [CrossRef]
  6. IRENA. Electricity Storage and Renewables: Costs and Markets to 2030. International Renewable Energy Agency (IRENA), 2017. Available online: https://www.irena.org/publications/2017/Oct/Electricity-storage-and-renewables-costs-and-markets (accessed on 25 February 2019).
  7. U.S. Energy Information Administration. Battery Storage Market Trends. U.S. Energy Information Administration, 2018. Available online: https://www.eia.gov/analysis/studies/electricity/batterystorage/ (accessed on 25 February 2019).
  8. Coignard, J.; Saxena, S.; Greenblatt, J.; Wang, D. Clean Vehicles as an Enabler for a Clean Electricity Grid. Environ. Res. Lett. 2018, 13, 054031. [Google Scholar] [CrossRef]
  9. Bloomberg NEF. Energy Storage is a $620 Billion Investment Opportunity to 2040. 2018. Available online: https://about.bnef.com/blog/energy-storage-620-billion-investment-opportunity-2040/ (accessed on 19 February 2019).
  10. Xia, S.; Chan, K.W.; Luo, X.; Bu, S.; Ding, Z.; Zhou, B. Optimal Sizing of Energy Storage System and Its Cost-Benefit Analysis for Power Grid Planning with Intermittent Wind Generation. Renew. Energy 2018, 122, 472–486. [Google Scholar] [CrossRef]
  11. Korpaas, M.; Holen, A.T.; Hildrum, R. Operation and Sizing of Energy Storage for Wind Power Plants in a Market System. Int. J. Electr. Power Energy Syst. 2003, 25, 599–606. [Google Scholar] [CrossRef]
  12. Ru, Y.; Kleissl, J.; Martinez, S. Storage Size Determination for Grid-Connected Photovoltaic Systems. IEEE Trans. Sustain. Energy 2013, 4, 68–81. [Google Scholar] [CrossRef] [Green Version]
  13. Harsha, P.; Dahleh, M. Optimal Management and Sizing of Energy Storage Under Dynamic Pricing for the Efficient Integration of Renewable Energy. IEEE Trans. Power Syst. 2015, 30, 1164–1181. [Google Scholar] [CrossRef]
  14. Khalilpour, R.; Vassallo, A. Planning and Operation Scheduling of PV-Battery Systems: A Novel Methodology. Renew. Sustain. Energy Rev. 2016, 53, 194–208. [Google Scholar] [CrossRef]
  15. Talent, O.; Du, H. Optimal Sizing and Energy Scheduling of Photovoltaic-Battery Systems under Different Tariff Structures. Renew. Energy 2018, 129, 513–526. [Google Scholar] [CrossRef]
  16. Telaretti, E.; Ippolito, M.; Dusonchet, L. A Simple Operating Strategy of Small-Scale Battery Energy Storages for Energy Arbitrage under Dynamic Pricing Tariffs. Energies 2016, 9, 12. [Google Scholar] [CrossRef]
  17. Hemmati, R. Technical and Economic Analysis of Home Energy Management System Incorporating Small-Scale Wind Turbine and Battery Energy Storage System. J. Clean. Prod. 2017, 159, 106–118. [Google Scholar] [CrossRef]
  18. Lujano-Rojas, J.M.; Dufo-López, R.; Bernal-Agustín, J.L.; Catalão, J.P.S. Optimizing Daily Operation of Battery Energy Storage Systems Under Real-Time Pricing Schemes. IEEE Trans. Smart Grid 2017, 8, 316–330. [Google Scholar] [CrossRef]
  19. Faqiry, M.N.; Edmonds, L.; Zhang, H.; Khodaei, A.; Wu, H. Transactive-Market-Based Operation of Distributed Electrical Energy Storage with Grid Constraints. Energies 2017, 10, 1891. [Google Scholar] [CrossRef]
  20. Fleer, J.; Zurmühlen, S.; Meyer, J.; Badeda, J.; Stenzel, P.; Hake, J.-F.; Sauer, D.W. Price Development and Bidding Strategies for Battery Energy Storage Systems on the Primary Control Reserve Market. In Proceedings of the 11th International Renewable Energy Storage Conference, IRES 2017, Düsseldorf, Germany, 14–16 March 2017. [Google Scholar]
  21. Xiang, Y.; Liu, J.; Li, R.; Li, F.; Gu, C.; Tang, S. Economic Planning of Electric Vehicle Charging Stations Considering Traffic Constraints and Load Profile Templates. Appl. Energy 2016, 178, 647–659. [Google Scholar] [CrossRef]
  22. Baik, S.H.; Jin, Y.G.; Yoon, Y.T. Determining Equipment Capacity of Electric Vehicle Charging Station Operator for Profit Maximization. Energies 2018, 11, 2301. [Google Scholar] [CrossRef]
  23. Luo, L.; Gu, W.; Zhou, S.; Huang, H.; Gao, S.; Han, J.; Wu, Z.; Dou, X. Optimal Planning of Electric Vehicle Charging Stations Comprising Multi-Types of Charging Facilities. Appl. Energy 2018, 226, 1087–1099. [Google Scholar] [CrossRef]
  24. Nikolovski, S.; Baghaee, H.R.; Mlakic, D. ANFIS-Based Peak Power Shaving/Curtailment in Microgrids Including PV Units and BESSs. Energies 2018, 11, 2953. [Google Scholar] [CrossRef]
  25. Kaviani, A.K.; Baghaee, H.R.; Riahy, G.H. Optimal Sizing of a Stand-Alone Wind/Photovoltaic Generation Unit Using Particle Swarm Optimization. Simulation 2009, 85, 89–99. [Google Scholar] [CrossRef]
  26. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B.; Talebi, H.A. Reliability/Cost-Based Multi-Objective Pareto Optimal Design of Stand-Alone Wind/PV/FC Generation Microgrid System. Energy 2016, 115, 1022–1041. [Google Scholar] [CrossRef]
  27. Palizban, O.; Kauhaniemi, K. Energy Storage Systems in Modern Grids—Matrix of Technologies and Applications. J. Energy Storage 2016, 6, 248–259. [Google Scholar] [CrossRef]
  28. Lo, C.H.; Anderson, M.D. Economic Dispatch and Optimal Sizing of Battery Energy Storage Systems in Utility Load-Leveling Operations. IEEE Trans. Energy Convers. 1999, 12, 824–829. [Google Scholar] [CrossRef]
  29. Kerestes, R.J.; Reed, G.F.; Sparacino, A.R. Economic Analysis of Grid Level Energy Storage for the Application of Load Leveling. In Proceedings of the 2012 IEEE Power and Energy Society General Meeting, San Diego, CA, USA, 22–26 July 2012; pp. 1–9. [Google Scholar]
  30. Hemmati, R.; Saboori, H. Short-Term Bulk Energy Storage System Scheduling for Load Leveling in Unit Commitment: Modeling, Optimization, and Sensitivity Analysis. J. Adv. Res. 2016, 7, 360–372. [Google Scholar] [CrossRef] [PubMed]
  31. Dicorato, M.; Forte, G.; Pisani, M.; Trovato, M. Planning and Operating Combined Wind-Storage System in Electricity Market. IEEE Trans. Sustain. Energy 2012, 3, 209–217. [Google Scholar] [CrossRef]
  32. Cho, S.M.; Shin, H.S.; Kim, J.C. Modeling of Battery Energy Storage System at Substation for Load Leveling and Its Economic Evaluation. Trans. Korean Instit. Electric. Eng. 2012, 61, 950–956. [Google Scholar] [CrossRef] [Green Version]
  33. Dupont, G.; Baltus, P. Dimensioning and Grid Integration of Mega Battery Energy Storage System for System Load Leveling. In Proceedings of the 2009 IEEE Bucharest PowerTech, Bucharest, Romania, 28 June–2 July 2009. [Google Scholar]
  34. Zheng, M.; Meinrenken, C.; Lackner, K.S. Smart Households: Dispatch Strategies and Economic Analysis of Distributed Energy Storage for Residential Peak Shaving. Appl. Energy 2015, 147, 246–257. [Google Scholar] [CrossRef]
  35. Telaretti, E.; Dusonchet, L. Battery Storage Systems for Peak Load Shaving Applications: Part 1: Operating Strategy and Modification of the Power Diagram. In Proceedings of the 2016 IEEE 16th International Conference on Environment and Electrical Engineering (EEEIC), Florence, Italy, 7–10 June 2016. [Google Scholar]
  36. Graditi, G.; Ippolito, M.G.; Telaretti, E.; Zizzo, G. Technical and Economical Assessment of Distributed Electrochemical Storages for Load Shifting Applications: An Italian Case Study. Renew. Sustain. Energy Rev. 2016, 57, 515–523. [Google Scholar] [CrossRef]
  37. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B. Multi-Objective Optimal Power Management and Sizing of a Reliable Wind/PV Microgrid with Hydrogen Energy Storage Using MOPSO. J. Intell. Fuzzy Syst. 2017, 32, 1753–1773. [Google Scholar] [CrossRef]
  38. James, G.; Witten, D.; Hastie, T.; Tibshirani, R. An Introduction to Statistical Learning with Applications in R, 7th ed.; Springer: New York, NY, USA, 2013. [Google Scholar]
  39. Hourly Load Forecast of Korea Power eXchange. Available online: http://www.kpx.or.kr/www/contents.do?key=223 (accessed on 18 January 2019).
  40. System Marginal Price of Korea Power eXchange. Available online: http://www.kpx.or.kr/www/contents.do?key=225 (accessed on 18 January 2019).
  41. Bergen, A.R.; Vital, V. Power System Analysis, 2nd ed.; Prentice-Hall: Upper Saddle River, NJ, USA, 2000. [Google Scholar]
Figure 1. Leveled loads with and without the loss of battery energy storage systems (BESS) compared with original loads.
Figure 1. Leveled loads with and without the loss of battery energy storage systems (BESS) compared with original loads.
Energies 12 01608 g001
Figure 2. Box plots for original loads: (a) Monthly loads; (b) Hourly loads.
Figure 2. Box plots for original loads: (a) Monthly loads; (b) Hourly loads.
Energies 12 01608 g002
Figure 3. Box plots for original electricity prices: (a) Monthly prices; (b) Hourly prices.
Figure 3. Box plots for original electricity prices: (a) Monthly prices; (b) Hourly prices.
Energies 12 01608 g003
Figure 4. Mean-squared error (MSE) and maximum/minimum values of the leveled loads with respect to BESS size: (a) MSE for Yref and Dref; (b) Maximum and minimum values for Yref and Dref.
Figure 4. Mean-squared error (MSE) and maximum/minimum values of the leveled loads with respect to BESS size: (a) MSE for Yref and Dref; (b) Maximum and minimum values for Yref and Dref.
Energies 12 01608 g004
Figure 5. Original and leveled loads with BESS of 50 GWh and 150 GWh in May: (a) Leveled loads for Yref; (b) Leveled loads for Dref.
Figure 5. Original and leveled loads with BESS of 50 GWh and 150 GWh in May: (a) Leveled loads for Yref; (b) Leveled loads for Dref.
Energies 12 01608 g005
Figure 6. Electricity prices with respect to the loads over a year.
Figure 6. Electricity prices with respect to the loads over a year.
Energies 12 01608 g006
Figure 7. Electricity prices with respect to loads (blue dots) in each month and the fitted prices (solid red lines) using the polynomial regression.
Figure 7. Electricity prices with respect to loads (blue dots) in each month and the fitted prices (solid red lines) using the polynomial regression.
Energies 12 01608 g007
Figure 8. Adjusted R-squared values of the polynomial regression with a degree of polynomial from one to nine.
Figure 8. Adjusted R-squared values of the polynomial regression with a degree of polynomial from one to nine.
Energies 12 01608 g008
Figure 9. Estimated cost of leveled loads with respect to BESS size.
Figure 9. Estimated cost of leveled loads with respect to BESS size.
Energies 12 01608 g009
Figure 10. Total cost from optimized BESS operation to reduce the cost and MSEs for Yref and Dref of the resulting loads.
Figure 10. Total cost from optimized BESS operation to reduce the cost and MSEs for Yref and Dref of the resulting loads.
Energies 12 01608 g010
Table 1. Correlation coefficients between monthly loads and electricity prices.
Table 1. Correlation coefficients between monthly loads and electricity prices.
JanuaryFebruaryMarchAprilMayJune
0.840.790.810.920.720.85
JulyAugustSeptemberOctoberNovemberDecember
0.900.840.810.880.870.84

Share and Cite

MDPI and ACS Style

Kim, H.T.; Jin, Y.G.; Yoon, Y.T. An Economic Analysis of Load Leveling with Battery Energy Storage Systems (BESS) in an Electricity Market Environment: The Korean Case. Energies 2019, 12, 1608. https://doi.org/10.3390/en12091608

AMA Style

Kim HT, Jin YG, Yoon YT. An Economic Analysis of Load Leveling with Battery Energy Storage Systems (BESS) in an Electricity Market Environment: The Korean Case. Energies. 2019; 12(9):1608. https://doi.org/10.3390/en12091608

Chicago/Turabian Style

Kim, Hyung Tae, Young Gyu Jin, and Yong Tae Yoon. 2019. "An Economic Analysis of Load Leveling with Battery Energy Storage Systems (BESS) in an Electricity Market Environment: The Korean Case" Energies 12, no. 9: 1608. https://doi.org/10.3390/en12091608

APA Style

Kim, H. T., Jin, Y. G., & Yoon, Y. T. (2019). An Economic Analysis of Load Leveling with Battery Energy Storage Systems (BESS) in an Electricity Market Environment: The Korean Case. Energies, 12(9), 1608. https://doi.org/10.3390/en12091608

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop