Next Article in Journal
Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings
Previous Article in Journal
Novel Protection Scheme considering Tie Switch Operation in an Open-Loop Distribution System using Wavelet Transform
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Fault-Tolerant Control Strategies and Capability without Redundant Sub-Modules in Modular Multilevel Converters

1
China Energy Engineering Group Jiangsu Power Design Institute Co., LTD, Nanjing 211102, China
2
Institute of Electrical Engineering, Chinese Academy of Sciences, Beijing 100044, China
*
Author to whom correspondence should be addressed.
Energies 2019, 12(9), 1726; https://doi.org/10.3390/en12091726
Submission received: 18 April 2019 / Revised: 1 May 2019 / Accepted: 2 May 2019 / Published: 7 May 2019

Abstract

:
Sub-module (SM) faults in modular multilevel converters (MMCs) without redundancies result in unbalanced converter output voltages and improper control of modulation due to an unequal number of SMs inserted between the different phase-legs. The derived mathematics model of the MMC demonstrates the impact of the SM fault in the circulating currents and capacitor voltages. For achieving the SM fault-tolerance, detailed analysis of the MMC’s electrical quantities under SM fault-tolerant algorithms is provided together with two modulation reconfiguration techniques for maintaining voltage balance. Fault-tolerant abilities of the two modulation algorithms are also discussed and defined. Simulation results from a 21-level converter and experimental work in a three-phase five-level converter demonstrate the feasibility and performance of the proposed fault-tolerant control strategies.

1. Introduction

Modular multilevel converters (MMCs) have been widely used in high-voltage direct current (HVDC) transmission systems [1,2,3] and multi-terminal networks [4,5] due to its modularity, flexibility and scalability. The large number of output voltage levels and transformer-less operation makes it useful for some other applications [6,7,8,9].
In order to be applied better in HVDC transmission systems, MMCs need to handle a great diversity of fault conditions including i) AC-side faults [10], ii) unbalanced grid conditions [11,12], iii) DC-link short circuit faults [13,14] and iv) sub-module (SM) faults [15,16,17]. A SM fault represents a typical fault condition [17] and it is better to keep the operation of the MMC until the next scheduled maintenance. Therefore, the key to dealing with the SM failure is to quickly locate and bypass the failed sub-modules while reconfiguring the operation and control of the converter to account for the faulty SMs and avoid further issues [14].
The power semiconductor devices have two fault types: open-circuit fault and short-circuit fault [15]. Although faulty SMs need to be bypassed in both cases, the speed of fault detection differs for the two types of faults. Thus, uninterrupted operation of the converter and the overall system should be ensured for the duration of the fault. Open-circuit faults of an insulated gate bipolar translator (IGBT) for traditional voltage source converters (VSCs) have been extensively studied in the literature [18,19,20]. Fault detection in the MMC using a sliding mode observer was first discussed in [21]. For detecting SM failure, a Kalman filter was utilized in [22]. Reference [17] proposed a strategy for detecting the SM fault by means of state observers. Based on calculated capacitance, a clustering algorithm was applied in [23].
In order to maintain the normal operation of an MMC under SM failure conditions, the methods of redundant SMs are proposed by providing fault-tolerance [24,25,26,27]. The redundant SMs have two modes: 1) Cold-reserve and 2) hot-reserve. Compared to cold-reserve, the hot-reserve methods can shorten the charging time of redundant SMs and recover the normal operation rapidly. However, the two modes increase the cost of the converter and add to the operational complexity. Based on the system without redundant SMs or when the redundant SMs are used up, these methods [24,25,26,27] are invalid. Thus, the SM fault-tolerant methods without redundant SMs are widely discussed in recent papers.
A fault-tolerant control method based on arm energy calculation is proposed in [28]. Its modulation strategy is not regulated under this method, and the SM capacitor voltages of remaining SMs in the faulty arm will increase. For solving the problem of SM capacitor overvoltage produced in [28], a neutral-shift method for maintaining the balanced line voltages of the MMC was discussed in [29]. However, the modulation index and phase angle of modulation reference should be recalculated based on a table look-up. For a simplified calculation, modulation reconfiguration techniques based on zero-sequence voltage injection are proposed [30,31,32]. They provide fault tolerant operation without the requirement for additional hardware and are easily implemented. The outputs are balanced and the SM voltage in the faulty arm are controlled to a rated value by a modified modulation algorithm [30,31], the switching operations are different in unsymmetrical arms. However, the SMs failure only produced in one arm is considered in [29,30,31]. The universality of these methods should be further discussed. If the modulation technique [30,31] cannot be applied effectively, the unsymmetrical arm currents will cause unequal conduction and switching losses between the arms. Thus, the fault-tolerant ability under modulation reconfiguration techniques [30,31] should be calculated and discussed.
Aiming at these problems, the more effective modulation reconfiguration techniques regardless of fault detection and localization techniques that may be used will be proposed and discussed in this paper. An analysis of electrical quantities under a module fault condition is provided together with two reconfigurations of the modulation technique for maintaining voltage balance. Fault-tolerant ability of the algorithms is also discussed and the fault-tolerant ability is defined.
The paper is organized as follows. Section 2 and Section 3 introduces the MMC’s operating principles in order to derive an analytical mathematical model that is used for calculating the SM capacitor voltage ripples and the circulating currents. Section 4 adopts two modulation reconfiguration algorithms for fault-tolerant operation without a redundant SM and analyzes the capacitor voltage fluctuations and circulating current components under SM failures. In Section 5 and Section 6, validity of the proposed methods is demonstrated by experimental and simulation results. Section 7 summarizes the conclusions of this paper.

2. Basic Structure and Principle of MMC

In this paper, this basic structure of the MMC is shown in Figure 1. The structure of SM is half-bridge. There are N SMs in one arm.
Table 1 shows the switching states of the HB-SM (half bridge sub-module) under different operation conditions. When faults occur, the bypass switch will keep the faulty SM in state 2. The upper and lower arms average switching functions of phase j (j = a, b and c), Sju and Sjl can be expressed as [33]
{ s ju = 1 2 ( 1 m cos ω t ) s jl = 1 2 ( 1 + m cos ω t )
where ω represents the fundamental frequency, m represents the modulation index ( m [ 0 , , 1 ] ).
Figure 2 shows the equivalent circuit of an MMC, which ju and jl represent the upper and lower arms of phase j. ij represents the AC-side current; ijdiff is the circulating current; udc and idc are the DC voltage and current, respectively. uj is the output voltage of phase j. uju and ujl are the upper and lower arms output voltages, respectively. They can be expressed as Equation (2).
{ u ju = u dc 2 u j R i ju L d i ju d t u jl = u dc 2 + u j R i jl L d i jl d t
The iju and ijl are given by Equation (3), respectively
{ i j u = + 1 2 i j + i jdiff i jl = 1 2 i j + i jdiff .
Circulating currents can be suppressed under balanced [3] and unbalanced AC conditions [11]. Circulating current controller is also designed for the submodule fault condition [22]. Thus, the arm currents can be only the fundamental component and DC component by the appropriate control method.

3. System Analysis Under Faulty Conditions

The following section will derive the analytical model for the MMC under faulty conditions and derive the closed-form equations for the capacitor voltage ripple and circulating current.
Without any loss in the general analysis, we assume that there are x faulty SMs in the upper arm of phase j, and that they have been bypassed. The main component of circulating current is a double-line frequency component [34] during steady state. From Equation (3), the arm currents iju and ijl before the fault can be rewritten as
{ i ju = + 1 2 I j cos ( ω t + φ ) + i jdiff _ dc + I 2 cos ( 2 ω t + φ 2 ) i jl = 1 2 I j cos ( ω t + φ ) + i jdiff _ dc + I 2 cos ( 2 ω t + φ 2 )
where ijdiff_dc is the DC component in the circulating current, and I2 represents the amplitude of second order harmonic. φ2 and φ are the angles of second harmonic component in circulating current and the AC output current, respectively.
Based Equations (1) and (4), the average current through the SM capacitors of the upper and lower arms ijuc and ijlc can be given as
{ i juc = i ju s ju = 1 2 ( A 0 + A 1 + A 2 + A 3 ) i jlc = i jl s jl = 1 2 ( A 0 A 1 + A 2 A 3 )
where A0 is the DC component and Ah (h = 1,2,3) are the h-th order harmonics of the average currents which are given by
{ A 0 = i jdiff _ dc 1 4 I j m cos φ A 1 = 1 2 I j cos ( ω t + φ ) 1 2 I 2 m cos ( ω t + φ 2 ) i jdiff _ dc m cos ω t A 2 = I 2 cos ( 2 ω t + φ 2 ) 1 4 I j m cos ( 2 ω t + φ ) A 3 = 1 2 I 2 m sin ( 3 ω t + φ 2 ) .
The h-th frequency component of the arm current (h = 0, 1, 2, …, n) will cause a fluctuation of the same frequency in the SM capacitor voltages. The upper and lower arms’ capacitor fluctuations Δujuc and Δujlc are
{ Δ u juc = 1 2 ( A 1 ω C + A 2 2 ω C + A 3 3 ω C ) Δ u jlc = 1 2 ( A 1 ω C + A 2 2 ω C + A 3 3 ω C )
where C represents the capacitor value.
Due to the switching actions within the arms, the fluctuations of SM capacitor voltages and the output voltage uju(l) are coupled. Then, the output voltage fluctuations of SMs Δusmju and Δusmjl can be expressed as follows
{ Δ u smju =   s ju Δ u juc = ( 1 2 ) 2 1 ω C ( B 0 + B 1 + B 2 + B 3 + B 4 ) Δ u smjl = s jl Δ u jlc = ( 1 2 ) 2 1 ω C ( B 0 B 1 + B 2 B 3 + B 4 )
where B0 is the DC component and Bh is the h-th order harmonics on the voltages ripple.
{ B 0 = 1 2 i jdiff _ dc m 2 + 1 4 I j m cos φ + 1 4 I 2 m 2 cos ( φ 2 ) B 1 = 1 4 I 2 m cos ( ω t + φ 2 ) 1 16 I j m 2 cos ( ω t + φ ) B 2 = 1 4 I j m cos ( 2 ω t + φ ) 1 3 I 2 m 2 cos ( 2 ω t + φ 2 ) + 1 2 i jdiff _ dc m 2 cos ( 2 ω t ) B 3 = 1 16 I j m 2 cos ( 3 ω t + φ ) 1 4 I 2 m cos ( 3 ω t + φ 2 ) B 4 = 1 12 I 2 m 2 cos ( 4 ω t + φ 2 ) .
Due to the x bypass SMs, the voltage fluctuation of the phase j Δuj can be given as:
Δ u j = x = 1 N x Δ u smju + x = 1 N Δ u smjl = ( N x ) Δ u smju + N Δ u smjl = N 4 ω C ( B 0 + B 2 + B 4 ) f i r s t t e r m + x 4 ω C ( B 0 + B 1 + B 2 + B 3 + B 4 ) sec o n d t e r m
The voltage fluctuation Δuj exists within the whole arm, the circulating current ijdiff will include the same harmonic components can be expressed as follows
i jdiff = h = 1 n Δ u j ( ω h ) h ω 2 L
where Δuj (ωh) represents the h-line frequency component in the voltage fluctuation, ωh represents the h-line frequency.
Under conventional operation conditions, x is equal to zero, in which case the coefficients of the second term in Equation (8) are equal to zero. Thus, there are no fundamental or triple-line frequency components in the circulating current ijdiff. However, the odd frequency components (first term in Equation (8)) will exist in Δuj and, hence, in ijdiff when a SM fault occurs. Meanwhile, when the harmonic components in the second term among three phases are asymmetrical, the harmonic components will also flow in the DC side. The unbalanced arm voltages will cause imbalances in output voltages under conventional modulation methods. Thus, fault-tolerant modulation strategy should be utilized for fault-tolerant operation in MMCs.

4. Proposed Fault-Tolerant Strategies

In order to handle SM faults, two modulation techniques based on zero-sequence voltage injection are discussed in this section. The principle and operation conditions are also discussed under the faulted SM operation.

4.1. Generalized Discontinuous Pulse Width Modulation (GDPWM)

Zero-sequence voltage injection techniques can reduce the switching losses and deal with the unbalanced cases for VSCs. In this paper, the injected zero-sequence component Vz based on the generalized discontinuous pulse width modulation (GDPWM) [35] is written as:
V z = k V j max + ( k 1 ) × V j min + ( 2 k 1 ) V dc 2
where k (0 ≤ k ≤ 1) is the coefficient of the zero-sequence component. Vjmax and Vjmin are the maximum and minimum of the three-phase modulation waves Vj, respectively.
The reconfigured modulation waves Vj* by utilizing Equation (10) are shown in Figure 3.
Based on a 21-level simulation system which parameters are shown in Table 2, the modulation waves by GDPWM algorithm under different k is shown in Figure 4 during the modulation index m = 1.
From the Figure 4 one can see that the modulation waveforms are obviously affected by k. They are consistent with space vector pulse width modulation (SVPWM) when k is 0.5. When k is close to 0 or 1, the appearance of neutral-shift is outstanding. Based on this point, different modulation waveforms can be achieved by changing k when modulation index m is certain. By detecting the position and number of the faulty SMs, k is chosen to be close to 0 or 1. With the neutral-shift, the amplitude of the modulation waveforms can be adjusted to a certain value. Therefore, we can only activate healthy SMs to finish the modulation calculation based on this characteristic.

4.2. Amplitude-Limited Modulation (ALM)

To maintain the line voltages balance, another modulation algorithm is proposed and discussed in this section. The reconfigured modulation waves Vj* can be written as (11)
{ V a * = V a + V zu + V zl V b * = V b + V zu + V zl V c * = V c + V zu + V zl
where Vj* represent the reconfigured modulation waves; Vj are the original modulation waves; and Vzu, Vzl represent the zero-sequence voltages injected to upper and lower arm, respectively.
Assuming that xu is the maximum of faulty SMs among three upper arms, xl is the maximum of faulty SMs among three lower arms. k1 (k1 > 0) is the limiting factor of upper arm and k2 (k2 < 0) is the limiting factor of lower arm. They are decided by faulty SM numbers of upper and lower arms, and expressed as:
{ x u = 1 k 1 2 N x l = 1 + k 2 2 N .
When faulty SMs are detected and bypassed, the Vzu, Vzl can be expressed based (13 and 14):
{ V z u = k 1 V a , V a k 1 V z u = 0 , V a < k 1
{ V zl = k 2 V b , V b < k 2 V zl = 0 , V b k 2 .
The rule of reconfiguration depends on the faulty SM number and the operating point of an MMC as follows:
Case 1: Faulty SMs only appear in upper (lower) arms.
We assume that xu ≠ 0, xl = 0. If the faulty SM number is xuN(1−m)/2, then the faulty SMs are not required in the regular operation of the MMC. Thus, the modulation functions of the arms do not need to be reconfigured (k1 = 0, k2 = 0). If, however, the number xu > N(1−m)/2, the failed SMs are being bypassed. In order to avoid the number of remaining SMs not being adequate to generate the arm voltage, the amplitude of the faulty arm modulation cannot beyond a fixed value 2xu/N. For maintaining line voltages, the same for pre- and post- fault, the non-fault phase modulations should be reconfigured during the fixed value period in fault phase. Thus, the three phase modulation waves Vj* are given in Table 3 when only xu failure SMs appears in the upper arm of phase a. Figure 5 shows the modulation functions under m = 0.9, when 25% to 10% faulty SMs in the upper arm of phase a are considered. From Figure 5 we can observe that the larger faulty SMs number, the wider the reconfiguration range is. The peak values of the remaining two phases are decided by x.
Figure 6 describes the different faulty SMs numbers in upper arms of phase a and b. The results show that the effects of amplitude-limited by zero-sequence voltage injection are not influenced by the position and number of faulty SMs.
Case 2: Faulty SMs only appear in the same leg.
Figure 7 describes the zero-sequence voltage injection of 25% SMs fault in the upper arm of phase a and 10% SMs fault in the lower arm of phase b. The results also show that the effectiveness of amplitude-limited by zero-sequence voltage injection.
Case 3: xu and xl in different legs.
We assume that there are xu faulty SMs in the upper arm of phase a and xl faulty SMs in the lower arm of phase b. From Figure 8 one can observe that the faulty SMs number affects the form of zero-sequence voltage injection. Two faulty conditions xu = 15%N, xl = 10%N (k1 = 0.7, k2 = −0.8) and xu = 12.5%N, xl = 12.5%N (k1 = 0.7, k2 = −0.75) are considered in Figure 8b,c, and the reconfiguration based on ALM is failed under these two conditions.
From Figure 5, Figure 6 and Figure 7 one can see that over-modulation exists in the modulation waveforms under some conditions. Thus, the fault-tolerant strategy ability based on ALM should be discussed.

4.3. Operation conditions of GDPWM and ALM

Compared to GDPWM, ALM achieves greater customization. Both of them have limitations in fault-tolerance under some conditions.
a) Fault-Tolerant Capability of GDPWM
Due to the balanced state of the three-phase modulation references, k = 0.5 can be chosen preferentially under normal operation conditions. The system can ensure normal operation when (1 − 3 m/2)N failure SMs are bypassed (peak modulation wave is 3 m/2 when k = 0.5) under a conventional modulation technique. When extreme conditions appear, fault-tolerant strategies proposed in this paper can be applied for SM fault ride-through with no redundancy SMs. Without redundancy SMs, the system can keep running normally with the GDPWM algorithm under some SMs fault conditions. The maximum of faulty SMs in one arm is (2 − 3 m)N when GDPWM is applied.
The zero-sequence voltage vector coefficient k of GDPWM can be written as Equation (15). The k should approximate to 0 when xu is larger than xl. However, the k needs to approximate to 1 when xl is larger than xu. The MMC should stop operating when the faulty SM number reaches the threshold
{ k = 1 2 ( N x l N 1 2 ) ( 3 m 1 ) 2 3 m ,   x u < x l k = 2 ( N x u N 1 2 ) ( 3 m 1 ) 2 3 m ,   x u x l .
b) Fault-Tolerant Capability of ALM
The over-modulation will affect the outputs balanced, and the effectiveness is affected by the modulation index m and number of faulty SMs directly. The limiting condition is expressed as Equation (16). Figure 5, Figure 6 and Figure 7 show that not every situation can be accommodated by the modulation algorithm. The range of modulation reconfiguration should be defined so that there are no overlap regions as in Equation (17).
| 1 2 x N 3 m   sin ( ω t + 1 6 π ) | max 1
( arcsin 1 2 x u N m ω t π arcsin 1 2 x u N m ) ( π + arcsin 1 2 x l N m ω t 2 π arcsin 1 2 x l N m ) = 0
This fault-tolerant scheme only needs to bypass the faulty sub-modules, and the remaining SMs rated voltages stay stable. The line voltages and currents will be balanced by the proposed approach. However, due to the difference between the upper arm and lower arm SM numbers of the faulty phase, the switching models in arms are asymmetric. The Fourier analysis results of the modulation waves of Figure 5a are given in Figure 9. The fundamental frequency of phase a makes a considerable difference from phase b and c, although the other components are nearly the same. Therefore, the three modulation waves are also asymmetric. Thus, the charging and discharging processes of SMs in different phases are different. Based on the analysis of Section 3 we can estimate that the coupling effects between the voltage fluctuation and differential current will generate the odd-line frequency components in the circulating current when this modulation scheme used.

4.4. Capacitor Voltage Fluctuations and Circulating Current Analysis under GDPWM and ALM

Based on the results of Figure 4 and Figure 8 we can see that the DC component (z ≠ 0.5) and third harmonic exist in the GDPWM and various orders of harmonics appear in ALM.
The average switching function sju and sjl in phase j can be rewritten as:
{ s ju = 1 2 ( 1 m 0 m cos ω t m h cos ( h ω t + φ h ) ) s jl = 1 2 ( 1 + m 0 + m cos ω t + m h cos ( h ω t + φ h ) )
where m0 is the DC component in the modulation reference, and mh and φh represent the modulation index and angle of h-th order harmonic.
Assuming that second order harmonic of circulating current is suppressed before SM failure occurs, the arm currents can be rewritten as:
{ i ju = + 1 2 I j cos ( ω t + φ ) + i jdiff _ dc i jl = 1 2 I j cos ( ω t + φ ) + i jdiff _ dc .
Following the calculation of Section 3, the upper and lower arm voltages of phase j are derived as:
{ u ju = 1 2 C [ ( 1 m 0 ) i diff _ dc t m I j 4 cos φ t dc   component + m i diff _ dc 2 ω sin ω t + ( 1 m 0 ) I j 2 ω sin ( ω t + φ ) fundamental   component + m I j 8 ω sin ( 2 ω t + φ ) 2 nd   component + m h i diff _ dc h ω sin ( h ω t + φ h ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) uncertain   component ] u jl = 1 2 C [ ( 1 + m 0 ) i diff _ dc t m I j 4 cos φ t dc   component + m i diff _ dc 2 ω sin ω t + ( 1 m 0 ) I j 2 ω sin ( ω t + φ ) fundamental   component + m I j 8 ω sin ( 2 ω t + φ ) 2 nd   component + m h i diff _ dc h ω sin ( h ω t + φ h ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) uncertain   component ] .
From Equation (20) we can observe that the existence of m0 will produce the term midiff_dc, which causes the unequal DC component in the upper and lower arms under GDPWM. Meanwhile, the m0 also causes the non-complementation among the two arms in one phase. Thus, the progress of the charging and discharging of capacitor in the two arms are different. It will cause different capacitor voltage fluctuations in the two arms. Due to the h-th order harmonic in the modulation references, h-th, h − 1 and h + 1 order harmonics will appear in the arms under GDPWM and ALM, and capacitor voltage fluctuations are different between the arms in one phase.
Based on Equations (18) and (20), the outputs of upper and lower arm voltages uju, ujl are given in Equations (A1) and (A2) in the Appendix A. From the equations we can see that h, h ± 1, h ± 2, 2h and 2h ± 1 appear in the arm output voltages in addition to the fundamental component, second and third order harmonics. Assuming that x faulty SMs occur in the upper arm of phase j, the sum of the upper and lower arm output voltage is expressed in Equation (A3). The main components of Equation (A3) can be given as:
Δ u j 2 N 4 C [ m 0 I j 2 ω sin ( ω t + φ ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) m I j 8 ω sin ( 2 ω t + φ ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) ] x 1 m 0 4 C [ ( 1 m 0 ) I j 2 ω sin ( ω t + φ ) m i diff _ dc ω sin ω t m I j 8 ω sin ( 2 ω t + φ ) m h i diff _ dc h ω sin ( h ω t + φ h ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) ]
The harmonic components among the phase voltage are complex. Fundamental, second order, h and h + 1 order harmonics exist in the voltage. The fundamental component will provide the fundamental component in the circulating current, and it will cause energy imbalance between the arms. Fundamental, second- and third-order harmonics are the main components of the circulating currents. Thus, the circulating current controller should be designed aimed at these components under GDPWM and ALM.

5. Simulation Studies

This section provides two sets of results in order to demonstrate and evaluate the proposed methods and analysis results. A 21-level simulation system was used to verify the fault-tolerant strategies of the GDPWM and ALM.

a) GDPWM under Balanced Conditions

For verifying the effect of GDPWM in capacitor voltages and circulating current, simulation results with k changing from 0 to 1 are shown in Figure 10.
From the results we can see that the AC current ia, ib and ic (shown in Figure 10e) were balanced when k changed from 0 to 1. The performance of AC system control was not affected by the GDPWM under this condition. The upper and lower capacitors voltages (usma1-usma20) in Figure 10c and capacitors voltages (usma21-usma40) in Figure 10d were deviated from the rated value when k kept away from 0.5. Based on the characteristic of GDPWM, the activated SM in the lower arm was larger than that in upper arm when k was close to 0. Therefore, the fundamental component of the lower arm current was larger than that in the upper arm. Meanwhile, the lower arm SMs activated time was longer than that of the upper arm, and SMs capacitor voltages of the lower arm were higher. The consequence was opposite between k = 1 and k = 0. The fundamental and other harmonic components exist in the circulating current iadiff when k ≠ 0.5. When k was close to 0 or 1, the oscillation was larger in the circulating current.

b) Fault-Tolerance under GDPWM

Results of GDPWM are shown in Figure 11. At time 0.05 s, five faulty SMs appear in the upper arm of phase a (xu = 5). GDPWM was activated at 0.09 s. From the Figure 11b,c we can see that the SM faulty may have caused the over current in the arm. In Figure 11d, faulty SMs usma1-usma5 were bypassed. The healthy SMs capacitor voltages (usma6-usma20) increased to 580 V. The lower arm capacitor voltages (usma21-usma40) also increased. From these one can see that the performance of SM fault-tolerance was good when GDPWM was activated. The average capacitor voltages decreased and arm currents were balanced. The capacitor voltage fluctuations were consistent with theoretical analysis.

c) Fault-Tolerance under ALM

The simulation results with ALM are illustrated in Figure 12. Open-circuit SM failure occurred in the upper arm in phase a (ua1-ua4) at time 0.2 s. At time 0.4 s, the ALM method is activated.
It was observed that iau, ial and iadiff were sinusoidal and the capacitor voltages were stable under healthy operating conditions. Assuming that a SM fault occurs at t = 0.2 s, three phase currents iau, ial and iadiff became higher than normal which led to overcurrent within the arms. As (usma1-usma4) were faulty and bypassed, the remaining SMs voltages of the upper arm (usma5-usma20) increased, and their ripples also increased. The voltage increments were less than 10% of the rated voltage, it was relatively safe for SM voltages. At time 0.4 s, the ALM method was used and the values of (usma5-usma20) return to the reference value. From the FFT analysis of the circulating current, shown in Figure 12f, we observed that a decrease of 60% in the fundamental frequency component and a decrease of 85% in the third harmonic. These results meet the theoretical analysis of the previous section, which demonstrated that the ALM will not cause over current in the arms or overvoltage in SM capacitors.
From Equations (16) and (17), the maximum proportion of faulty SMs should be less than 30.72%N for an m = 0.8. When utilizing the simulation system by N = 20, the permitted greatest integer of faulty SMs is six. Figure 13 shows the results of the fault-tolerant ability when 30%N (xu = 6, k1 = 0.4) and x4 = 40%N (xu = 8, k1 = 0.2). When x4 = 30%N, the line voltages were balanced, however, the voltages were unbalanced when x4 = 40%N. Thus, the simulation results illustrate the validity of the theoretical calculation for Case 1.
For verifying the fault-tolerant capability of Case 3, Figure 14a provides the results of the fault-tolerant ability when 15%N faulty sub-modules in upper arm of phase a (xu = 3, k1 = 0.7) and 15%N faulty sub-modules in lower arm of phase b (xl = 3, k2 = −0.7). Figure 14b shows the results of xu = 4 and xl = 3. The line voltages were balanced in Figure 13a, however the voltages were unbalanced due to the distortion in the modulation wave of phase b in Figure 14b. The overlap regions affect the results of the ALM. Thus, these results illustrate that the validity of the theoretical calculation for Case 3.

6. Experimental Studies

For evaluating the feasibility and effectiveness of the proposed fault-tolerant strategies, a downscaled three-phase MMC prototype (N = 4) was utilized in this section. Figure 15 shows the experiment platform. The proposed methods were implemented in a digital signal processor. Meanwhile, a field programmable gate array was used to finish the PWM function. Every sub-module is controlled by a local complex programmable logic device. The parameters of this platform are listed in Table 4.

a) GDPWM

Figure 16 shows the results of GDPWM under one faulty and bypassed sub-module (usma1) in the upper arm of phase a. From the results one can see that the healthy capacitor usma2 increased 2 V during this fault period before the fault-tolerant strategy. When GDPWM was activated, the lower arm capacitor voltage usma5 was lower than its rated value and the upper arm capacitor voltage usma2 stopped increasing. The upper arm output voltage uau was changed by k = 0 during the fault. From Figure 16b one can see that the DC-bus current and arm currents iau, ial are distorted. When GDPWM was used, AC output currents (ia, ib) were not affected pre- and post-fault.

b) ALM

In the following simulations and experiments, the ALM was enabled at time t0. Sub-module usma1 was assumed to exhibit a fault at time t1. At time t2, the ALM method was enabled.
Illustrative experimental results are given in Figure 17, with the circulating current control enabled at all times. The unbalanced line voltages were balanced due to the ALM scheme used. The fundamental frequency component could be measured in the DC-link current idc (Figure 17a). By using the ALM scheme, the fluctuation in idc decreased by 60%. In Figure 17b, the remaining sub-module voltages in the upper arm increased, but the fluctuations of capacitor voltages were also stable. When the modulation was reconfigured, the SM voltages returned to their reference values. The arm currents iau,ial, circulating current iadiff are also shown in Figure 17c. Although a small fundamental frequency component was still present in the circulating current, there was no overcurrent in arm currents when the SM fault occurs.

c) Comparison

Simulation and experiment results of GDPWM and ALM indicated that the two strategies can achieve the fault-tolerant ability. The healthy SM capacitor voltages in the leg under ALM could reach to the rated value. Due to the obvious DC component, the fluctuations and average value of healthy SM capacitor voltages in the arms were different under GDPWM. It is consistent to the analysis of Equation (20). Thus, ALM achieved a better performance compared to GDPWM.

7. Conclusions

In this paper, a mathematical model for the fundamental and triple frequency components under SM fault and modulation reconfiguration conditions are derived. The proposed modulation reconfiguration methods to account for the faulty SMs in the arms of the MMC suppresses the overcurrent when fault detection, localization and modulation reconfiguration occurs while providing control of the circulating current under faulty SM conditions. The feasibility and effectiveness of proposed methods have been demonstrated by simulations and experiments results on three-phase 21-level and five-level MMC topologies.

Author Contributions

Conceptualization, J.L and J.Y.; formal analysis, J.L and J.Y.; writing – original draft, J.Y.; writing – review and editing, J.L and J.Y.

Funding

This research work was supported by the National Key Research and Development Program of China (2016YFB0900900).

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A

u ju = 1 m 0 4 C [ ( 1 m 0 ) I j 2 ω sin ( ω t + φ ) m i diff _ dc ω sin ω t m I j 8 ω sin ( 2 ω t + φ ) m h i diff _ dc h ω sin ( h ω t + φ h ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) ] m 4 C { ( 1 m 0 ) I j 4 ω [ sin ( 2 ω t + φ ) + sin φ ] m I j 16 ω [ sin ( 3 ω t + φ ) + sin ( ω t + φ ) ] m h I j 8 ( h + 1 ) ω [ sin ( ( h + 2 ) ω t + φ h + φ ) + sin ( h ω t + φ h + φ ) ] m h I j 8 ( h 1 ) ω [ sin ( h ω t + φ h φ ) + sin ( ( h 2 ) ω t + φ h φ ) ] m 2 i diff _ dc 2 ω sin 2 ω t m m h i diff _ dc 2 h ω [ sin ( ( h + 1 ) ω t + φ h ) + sin ( ( h 1 ) ω t + φ h ) ] m h 4 C { ( 1 m 0 ) I j 4 ω [ sin ( ( h + 1 ) ω t + φ h + φ ) sin ( ( h 1 ) ω t + φ h φ ) ] m I j 16 ω [ sin ( ( h + 2 ) ω t + φ h + φ ) + sin ( ( h 2 ) ω t + φ h φ ) ] m h I j 8 ( h + 1 ) ω [ sin ( ( 2 h + 1 ) ω t + 2 φ h + φ ) + sin ( ω t + φ ) ] m h I j 8 ( h 1 ) ω [ sin ( ( 2 h 1 ) ω t + 2 φ h φ ) sin ( ω t + φ ) ] m m h i diff _ dc 2 h ω [ sin ( ( h + 1 ) ω t + φ h ) + sin ( ( h 1 ) ω t + φ h ) ] m h 2 i diff _ dc 2 h ω sin ( 2 h ω t + 2 φ h ) }
u jl = 1 + m 0 4 C [ ( 1 m 0 ) I j 2 ω sin ( ω t + φ ) + m i diff _ dc ω sin ω t m I j 8 ω sin ( 2 ω t + φ ) + m h i diff _ dc h ω sin ( h ω t + φ h ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) ] m 4 C { ( 1 m 0 ) I j 4 ω [ sin ( 2 ω t + φ ) + sin φ ] m I j 16 ω [ sin ( 3 ω t + φ ) + sin ( ω t + φ ) ] m h I j 8 ( h + 1 ) ω [ sin ( ( h + 2 ) ω t + φ h + φ ) + sin ( h ω t + φ h + φ ) ] m h I j 8 ( h 1 ) ω [ sin ( h ω t + φ h φ ) + sin ( ( h 2 ) ω t + φ h φ ) ] + m 2 i diff _ dc 2 ω sin 2 ω t + m m h i diff _ dc 2 h ω [ sin ( ( h + 1 ) ω t + φ h ) + sin ( ( h 1 ) ω t + φ h ) ] m h 4 C { ( 1 m 0 ) I j 4 ω [ sin ( ( h + 1 ) ω t + φ h + φ ) sin ( ( h 1 ) ω t + φ h φ ) ] m I j 16 ω [ sin ( ( h + 2 ) ω t + φ h + φ ) + sin ( ( h 2 ) ω t + φ h φ ) ] m h I j 8 ( h + 1 ) ω [ sin ( ( 2 h + 1 ) ω t + 2 φ h + φ ) + sin ( ω t + φ ) ] m h I j 8 ( h 1 ) ω [ sin ( ( 2 h 1 ) ω t + 2 φ h φ ) sin ( ω t + φ ) ] + m m h i diff _ dc 2 h ω [ sin ( ( h + 1 ) ω t + φ h ) + sin ( ( h 1 ) ω t + φ h ) ] + m h 2 i diff _ dc 2 h ω sin ( 2 h ω t + 2 φ h ) }
Δ u j = ( N x ) u ju + N u jl = N ( u ju + u jl ) x u ju = 2 N 4 C [ m 0 I j 2 ω sin ( ω t + φ ) m I j 8 ω sin ( 2 ω t + φ ) m h I j ( h 1 ) ω sin ( ( h 1 ) ω t + φ h φ ) m h I j ( h + 1 ) ω sin ( ( h + 1 ) ω t + φ h + φ ) ] + 2 N m 0 4 C [ I j 2 ω sin ( ω t + φ ) + m i diff _ dc ω sin ω t + m h i diff _ dc h ω sin ( h ω t + φ h ) ] 2 N m 4 C { m 0 I j 4 ω [ sin ( 2 ω t + φ ) + sin φ ] m I j 16 ω [ sin ( 3 ω t + φ ) + sin ( ω t + φ ) ] m h I j 8 ( h + 1 ) ω [ sin ( ( h + 2 ) ω t + φ h + φ ) + sin ( h ω t + φ h + φ ) ] m h I j 8 ( h 1 ) ω [ sin ( h ω t + φ h φ ) + sin ( ( h 2 ) ω t + φ h φ ) ] } 2 N m h 4 C { m 0 I j 4 ω [ sin ( ( h + 1 ) ω t + φ h + φ ) sin ( ( h 1 ) ω t + φ h φ ) ] m I j 16 ω [ sin ( ( h + 2 ) ω t + φ h + φ ) + sin ( ( h 2 ) ω t + φ h φ ) ] m h I j 8 ( h + 1 ) ω [ sin ( ( 2 h + 1 ) ω t + 2 φ h + φ ) + sin ( ω t + φ ) ] m h I j 8 ( h 1 ) ω [ sin ( ( 2 h 1 ) ω t + 2 φ h φ ) sin ( ω t + φ ) ] } x u ju

References

  1. Marquardt, R.; Lesnicar, A. New concept for high voltage-modular multilevel converter. In Proceedings of the IEEE Power Electronics Specialists Conference, Aachen, Germany, 20–26 June 2004; pp. 1–5. [Google Scholar]
  2. Gemmell, B.; Dorn, J.; Retzmann, D.; Soerangr, D. Prospects of multilevel VSC technologies for power transmission. In Proceedings of the 2008 IEEE/PES Transmission and Distribution Conference and Exposition, Chicago, IL, USA, 21–24 April 2008; pp. 1–16. [Google Scholar]
  3. Saeedifard, M.; Iravani, R. Dynamic performance of a modular multilevel back-to-back HVDC system. IEEE Trans. Power Deliv. 2010, 25, 2903–2912. [Google Scholar] [CrossRef]
  4. Yin, J.; Wu, W.; Wei, T.; Wu, X.; Huo, Q. A Novel Fault-Tolerant Control of Modular Multilevel Converter under Sub-Module Faults Based on Phase Disposition PWM. Energies 2019, 12, 1–19. [Google Scholar]
  5. Beijing HVDC Engineering Co. Ltd. Zhoushan Multiterminal Flexible HVDC Project System Design Report; Beijing HVDC Engineering Co. Ltd.: Beijing, China, 2012; pp. 77–83. [Google Scholar]
  6. Mohammadi, P.H.; TavakoliBina, M. A transformerless medium voltage STATCOM topology based on extended modular multilevel converters. IEEE Trans. Power Electron. 2011, 26, 1534–1545. [Google Scholar]
  7. Mei, J.; Xiao, B.; Shen, K.; Tolbert, L.; Zheng, J. Modular multilevel inverter with new modulation method and its application to photovoltaic grid-connected generator. IEEE Trans. Power Electron. 2013, 28, 5063–5073. [Google Scholar] [CrossRef]
  8. Popova, L.; Pyrhonen, J.; Blaabjerg, K. Device Loading of modular multilevel converter MMC in wind power application. In Proceedings of the 2014 International Power Electronics Conference (IPEC-Hiroshima 2014-ECCE ASIA), Hiroshima, Japan, 18–21 May 2014; pp. 548–554. [Google Scholar]
  9. Jung, J.; Lee, H.; Sul, S. Control strategy for improved dynamic performance of variable-speed drives with the modular multileve converter. IEEE J. Emerg. Sel. Top. Power Electron. 2013, 3, 371–380. [Google Scholar] [CrossRef]
  10. Jung, J.; Cui, S.; Lee, Y.; Sul, S. A cell capacitor energy balancing control of MMC-HVDC under the AC grid faults. In Proceedings of the 2015 9th International Conference on Power Electronics and ECCE Asia (ICPE-ECCE Asia), Seoul, Korea, 1–5 June 2015; pp. 1–8. [Google Scholar]
  11. Guan, M.; Xu, Z. Modeling and control of a modular multilevel converter-based HVDC system under unbalanced grid conditions. IEEE Trans. Power Electron. 2012, 27, 4858–4867. [Google Scholar] [CrossRef]
  12. Rodriguez, P.; Luna, A.; Ciobotaru, M.; Teodorescu, R.; Blaabjerg, F. Advanced grid synchronization system for power converters under unbalanced and distorted operating conditions. In Proceedings of the IEEE Industrial Electronics IECON Conference, Paris, France, 7–10 November 2006; pp. 5173–5178. [Google Scholar]
  13. Li, X.; Song, Q.; Liu, W. Protection of nonpermanent faults on DC overhead lines in MMC-based HVDC systems. IEEE Trans. Power Deliv. 2013, 28, 483–490. [Google Scholar] [CrossRef]
  14. Weihao, Z.; Jing, S.; Haoze, L. Detection and localization of submodule open-circuit failures for modular multilevel converters with single ring theorem. IEEE Trans. Power Electron. 2019, 34, 3729–3739. [Google Scholar]
  15. Shao, S.; Wheeler, P.; Clare, J.; Watson, A. Fault detection for modular multilevel converters based on sliding mode observer. IEEE Trans. Power Electron. 2013, 28, 4867–4872. [Google Scholar] [CrossRef]
  16. Deng, F.; Chen, Z.; Khan, M.; Zhu, R. Fault detection and localization method for modular multilevel converters. IEEE Trans. Power Electron. 2015, 30, 2721–2732. [Google Scholar] [CrossRef]
  17. Li, B.; Shi, S.; Wang, B.; Wang, G.; Wang, W.; Xu, D. Fault diagnosis tolerant control of single IGBT open-circuit failure in modular multilevel converters. IEEE Trans. Power Electron. 2016, 31, 3165–3176. [Google Scholar] [CrossRef]
  18. Lu, B.; Sharma, S. Literature review of IGBT fault diagnostic and protection methods for power inverters. IEEE Trans. Ind. Appl. 2009, 45, 1770–1777. [Google Scholar]
  19. Campos-Delgado, D.; Espinoza-Trejo, D. An observer-based diagnosis scheme for single and simultaneous open-switch faults in induction motor drives. IEEE Trans. Ind. Electron. 2011, 58, 671–679. [Google Scholar] [CrossRef]
  20. Estima, J.; Cardoso, A. A new approach for real-time multiple open-circuit fault diagnosis in voltage source inverters. IEEE Trans. Ind. Appl. 2011, 47, 2487–2494. [Google Scholar] [CrossRef]
  21. Shao, S.; Clare, J.; Watson, A.; Wheeler, P. Detection and isolation of multiple faults in a modular multilevel converter based on a sliding mode observer. In Proceedings of the 2014 IEEE Energy Conversion Congress and Exposition (ECCE), Pittsburgh, PA, USA, 14–18 September 2014; pp. 3491–3495. [Google Scholar]
  22. Wu, W.; Wu, X.; Yin, J.; Jing, L.; Wang, S.; Li, J. Characteristic Analysis and Fault-Tolerant Control of Circulating Current for Modular Multilevel Converters under Sub-Module Faults. Energies 2017, 10, 1827. [Google Scholar] [CrossRef]
  23. Yang, Q.; Qin, J.; Saeedifard, M. Analysis, detection, and location of open-switch submodule failures in a modular multilevel converter. IEEE Trans. Power Deliv. 2016, 31, 155–164. [Google Scholar] [CrossRef]
  24. Wang, J.; Ma, H.; Bai, Z. A submodule fault ride-through strategy for modular multilevel converters with nearest level modulation. IEEE Trans. Power Electron. 2018, 33, 1597–1608. [Google Scholar] [CrossRef]
  25. Konstantinou, G.; Pou, J.; Ceballos, S.; Agelidis, V. Active redundant submodule configuration in modular multilevel converters. IEEE Trans. Power Deliv. 2013, 28, 2333–2341. [Google Scholar] [CrossRef]
  26. Liu, G.; Xu, Z.; Xue, Y.; Tang, G. Optimized control strategy based on dynamic redundancy for the modular multilevel converter. IEEE Trans. Power Electron. 2015, 30, 339–348. [Google Scholar] [CrossRef]
  27. Li, B.; Xu, Z.; Ding, J. Fault-tolerant control of medium-voltage modular multilevel converters with minimum performance degradation under submodule failures. IEEE Access 2018, 6, 11772–11781. [Google Scholar] [CrossRef]
  28. Hu, P.; Jiang, D.; Zhou, Y. Energy-balancing control strategy for modular multilevel converters under submodule Fault Conditions. IEEE Trans. Power Electron. 2014, 29, 5021–5029. [Google Scholar] [CrossRef]
  29. Yang, Q.; Qin, J.; Saeedifard, M. A post-fault strategy to control the modular multilevel converter under submodule failure. IEEE Trans. Power Deliv. 2016, 31, 2453–2463. [Google Scholar] [CrossRef]
  30. Shen, K.; Xiao, B.; Mei, J.; Tolbert, L.; Wang, J.; Cai, X.; Ji, Y. A modulation reconfiguration based fault-tolerant control scheme for modular multilevel converters. In Proceedings of the 2013 Twenty-Eighth Annual IEEE Applied Power Electronics Conference and Exposition (APEC), Long Beach, CA, USA, 17–21 March 2013; pp. 3251–3255. [Google Scholar]
  31. Mei, J.; Li, Y.; Tian, J.; Huang, C.; Lu, X.; Du, X.; Xie, Y.; Hu, Q.; Ma, T. Balancing control scheme for modular multilevel converters using virtual loop mapping with fault-tolerance capabilities. IEEE Trans. Ind. Electron. 2016, 63, 38–48. [Google Scholar] [CrossRef]
  32. Ma, M.; Hu, L.; Chen, A.; He, X. Reconfiguration of carrier-based modulation strategy for fault tolerant multilevel inverters. IEEE Trans. Power Electron. 2007, 22, 2050–2060. [Google Scholar] [CrossRef]
  33. Antonopoulos, A.; Angquist, L.; Nee, H. On dynamics and voltage control of the modular multilevel converter. In Proceedings of the 2009 13th European Conference on Power Electronics and Applications, Barcelona, Spain, 8–10 September 2009; pp. 1–10. [Google Scholar]
  34. Yazdani, D.; Bakhshai, A.; Jain, P. Adaptive notch filtering based grid synchronization techniques for converter interfaced distributed generation systems. In Proceedings of the IEEE-IECON Conference, Barcelona, Spain, 8–10 September 2009; pp. 3963–3965. [Google Scholar]
  35. Li, J.; Wu, W.; Yao, X. A zero-sequence voltage injection control scheme for modular multilevel converter under submodule failure. In Proceedings of the 2016 IEEE Energy Conversion Congress and Exposition (ECCE), Milwaukee, WI, USA, 18–22 September 2016; pp. 1–6. [Google Scholar]
Figure 1. Basic structure of a modular multilevel converters (MMC) and sub-module (SM) model.
Figure 1. Basic structure of a modular multilevel converters (MMC) and sub-module (SM) model.
Energies 12 01726 g001
Figure 2. The three-phase equivalent circuit of MMC.
Figure 2. The three-phase equivalent circuit of MMC.
Energies 12 01726 g002
Figure 3. Block diagram of zero-sequence voltage injection.
Figure 3. Block diagram of zero-sequence voltage injection.
Energies 12 01726 g003
Figure 4. Modulation waveforms with different coefficient of the zero-sequence component (k) under modulation index (m) = 1.
Figure 4. Modulation waveforms with different coefficient of the zero-sequence component (k) under modulation index (m) = 1.
Energies 12 01726 g004
Figure 5. Modulation waveforms with faulty SMs in one upper arm.
Figure 5. Modulation waveforms with faulty SMs in one upper arm.
Energies 12 01726 g005
Figure 6. Modulation waveforms with faulty SMs in two upper arms.
Figure 6. Modulation waveforms with faulty SMs in two upper arms.
Energies 12 01726 g006
Figure 7. Modulation waveforms with faulty SMs in upper arm and lower arm of one phase.
Figure 7. Modulation waveforms with faulty SMs in upper arm and lower arm of one phase.
Energies 12 01726 g007
Figure 8. Modulation waveforms under SM fault in the upper arm of phase a and lower arm of phase b.
Figure 8. Modulation waveforms under SM fault in the upper arm of phase a and lower arm of phase b.
Energies 12 01726 g008
Figure 9. FFT (Fast Fourier Transform) analysis of amplitude-limited modulation method.
Figure 9. FFT (Fast Fourier Transform) analysis of amplitude-limited modulation method.
Energies 12 01726 g009
Figure 10. Simulation results under different k under GDPWM: (a) Upper arm voltage; (b) lower arm voltage; (c) SM capacitor voltages of the upper arm; (d) SM capacitor voltages of the lower arm; (e) AC currents; (f) phase a circulating current.
Figure 10. Simulation results under different k under GDPWM: (a) Upper arm voltage; (b) lower arm voltage; (c) SM capacitor voltages of the upper arm; (d) SM capacitor voltages of the lower arm; (e) AC currents; (f) phase a circulating current.
Energies 12 01726 g010
Figure 11. Simulation results by GDPWM under SMs failure condition: (a) AC currents; (b) three phases of upper arm currents; (c) three phases of lower arm currents; (d) upper arm SM capacitor voltages; (e) lower arm SM capacitor voltages.
Figure 11. Simulation results by GDPWM under SMs failure condition: (a) AC currents; (b) three phases of upper arm currents; (c) three phases of lower arm currents; (d) upper arm SM capacitor voltages; (e) lower arm SM capacitor voltages.
Energies 12 01726 g011
Figure 12. Results of with ALM strategy: (a) SM capacitor voltages of the upper arm (usma1-usma20); (b) SM capacitor voltages of the lower arm (usma21-usma40); (c) arm currents iau,ial; (d) circulating current iadiff in phase a; (e) FFT analysis result of circulating current.
Figure 12. Results of with ALM strategy: (a) SM capacitor voltages of the upper arm (usma1-usma20); (b) SM capacitor voltages of the lower arm (usma21-usma40); (c) arm currents iau,ial; (d) circulating current iadiff in phase a; (e) FFT analysis result of circulating current.
Energies 12 01726 g012
Figure 13. Fault-tolerant ability simulation results of Case 1 under m = 0.8, N = 20: (a) 30%N failure SM in the upper arm of phase a; (b) 40%N failure SMs in the upper arm of phase a.
Figure 13. Fault-tolerant ability simulation results of Case 1 under m = 0.8, N = 20: (a) 30%N failure SM in the upper arm of phase a; (b) 40%N failure SMs in the upper arm of phase a.
Energies 12 01726 g013
Figure 14. Fault-tolerant ability simulation results of Case 3 under m = 0.8, N = 20: (a) 15%N failure SMs in phase a upper arm and 15%N failure SMs in phase b lower arm; (b) 20%N failure SM in phase a upper arm and 15%N failure SMs in phase b lower arm.
Figure 14. Fault-tolerant ability simulation results of Case 3 under m = 0.8, N = 20: (a) 15%N failure SMs in phase a upper arm and 15%N failure SMs in phase b lower arm; (b) 20%N failure SM in phase a upper arm and 15%N failure SMs in phase b lower arm.
Energies 12 01726 g014
Figure 15. MMC experimental platform.
Figure 15. MMC experimental platform.
Energies 12 01726 g015
Figure 16. Experiment results by generalized discontinuous pulse width modulation (GDPWM) under SMs failure condition: (a) Voltage experiment waveform; (b) current experiment waveform.
Figure 16. Experiment results by generalized discontinuous pulse width modulation (GDPWM) under SMs failure condition: (a) Voltage experiment waveform; (b) current experiment waveform.
Energies 12 01726 g016aEnergies 12 01726 g016b
Figure 17. Experimental waveforms of ALM strategy: (a) Line-to-line voltages eab, ebc and eca, DC-link current idc; (b) the voltage values of capacitors in phase a usma1- usma4; (c) arm currents iau, ial circulating current iadiff.
Figure 17. Experimental waveforms of ALM strategy: (a) Line-to-line voltages eab, ebc and eca, DC-link current idc; (b) the voltage values of capacitors in phase a usma1- usma4; (c) arm currents iau, ial circulating current iadiff.
Energies 12 01726 g017aEnergies 12 01726 g017b
Table 1. SM unit operation state.
Table 1. SM unit operation state.
StateT1/T2usmCapacitorVoltage
1On/offEdischargedecreased
chargeincreased
2Off/on0bypassuncharged
Table 2. Simulation system parameters of N = 20.
Table 2. Simulation system parameters of N = 20.
ItemValue
Rated Power S10 MVA
DC voltage udc10 kV
Number of SMs per arm N20
SM capacitance C5000 μF
Arm inductance L5 mH
Fundamental frequency f50 Hz
Table 3. Amplitude-limited modulation algorithm.
Table 3. Amplitude-limited modulation algorithm.
Range of ωtVa(ωt)Vb(ωt)Vc(ωt)
arcsin 1 2 x / N m ω t π arcsin 1 2 x / N m 1 2 x N 1 2 x N 3 m sin ( ω t + 1 6 π ) 1 2 x / N + 3 m sin ( ω t + 5 6 π )
Other ranges m cos ω t m cos ( ω t 2 3 π ) m cos ( ω t + 2 3 π )
Table 4. Parameters of the laboratory prototype and controllers.
Table 4. Parameters of the laboratory prototype and controllers.
ItemValue
DC voltage120 V
SMs number4
SM capacitance2000 μF
Arm inductance5 mH
Fundamental frequency50 Hz
Digital control period150 μs

Share and Cite

MDPI and ACS Style

Li, J.; Yin, J. Fault-Tolerant Control Strategies and Capability without Redundant Sub-Modules in Modular Multilevel Converters. Energies 2019, 12, 1726. https://doi.org/10.3390/en12091726

AMA Style

Li J, Yin J. Fault-Tolerant Control Strategies and Capability without Redundant Sub-Modules in Modular Multilevel Converters. Energies. 2019; 12(9):1726. https://doi.org/10.3390/en12091726

Chicago/Turabian Style

Li, Jinke, and Jingyuan Yin. 2019. "Fault-Tolerant Control Strategies and Capability without Redundant Sub-Modules in Modular Multilevel Converters" Energies 12, no. 9: 1726. https://doi.org/10.3390/en12091726

APA Style

Li, J., & Yin, J. (2019). Fault-Tolerant Control Strategies and Capability without Redundant Sub-Modules in Modular Multilevel Converters. Energies, 12(9), 1726. https://doi.org/10.3390/en12091726

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop