Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings
Abstract
:1. Introduction
2. Materials and Methods
2.1. Description of the Test Facility and Experimental Process
2.1.1. Setting of Air Temperature of Fresh Air (Supply Air Inlet)
2.1.2. Setting of Air Humidity of Fresh Air (Supply Air Inlet Section)
2.1.3. Air Temperature and Humidity Settings on Exhaust Air Inlet Section
2.1.4. Experimental Data Recording and Evaluation
2.2. Description of the Test Plan
- The test plan was basically divided into two ambient air conditions (winter outdoor air conditions for heating performance tests and summer outdoor air conditions for cooling performance tests).
- Based on Table 2, the extract air inlet relative humidity was set as 38% for heating performance tests and 47% for cooling performance tests during the experiments.
- A further objective was to perform tests in much wider outdoor air conditions than the EN 13141-7 standard instructs, extending also the values of effectiveness given by the producer. In this way, a 5 °C outdoor air temperature step change was managed in the range between −15 and 10 °C, and the outdoor air relative humidity was step-changed by 10% in the range between 70% and 100% for heating performance tests. For cooling performance tests, the outdoor air conditions were set between 27 and 40 °C with a 5 °C step change and between 40% and 90% with a 10% step change.
- The achievable humidity was in a ratio applicable to all states of operation, with equal distribution of achievable relative humidity.
- All tests were conducted under four different air volume flow rates (100, 200, 300, and 350 m3/h).
- The pressure difference between supply and exhaust fan was zero during the tests.
- The order of setting the steady-state test variables was the following before data recording: air volume flow rate, supply air inlet temperature, and finally the supply air inlet relative humidity.
- All tests were conducted under continuous monitoring of the supply air inlet relative humidity variables using the data collector instrument.
- The duration of each experimental test for every sequence order was at least 3000 s with a measurement rate of one per second to get the steady-state values. The sequence of measurements for all input parameters was conducted until the system reached the steady-state conditions.
3. Results and Discussion
3.1. Effectiveness of Air-to-Air PEE Energy Exchanger
3.1.1. Sensible Effectiveness vs. Dry-Bulb Temperature of PEE
3.1.2. Latent Effectiveness vs. Dry-Bulb Temperature of PEE
3.1.3. Total Effectiveness vs. Dry-Bulb Temperature of PEE
3.1.4. Latent Effectiveness vs. Relative Humidity of PEE
3.1.5. Total Effectiveness vs. Relative Humidity of PEE
3.1.6. Effectiveness vs. Outdoor Air Inlet Dry Temperature for EN Standards
3.2. Effectiveness of Air-to-Air PHE Heat Exchanger
3.2.1. Sensible Effectiveness vs. Dry-Bulb Temperature of PHE
3.2.2. Sensible Effectiveness vs. Outdoor Air Inlet Dry Temperature for EN Standards
3.2.3. Sensible Effectiveness Comparison between the PEE and PHE Exchangers
3.3. Uncertainty Calculations
- Random uncertainty: instrument accuracy;
- Systematic uncertainty: measurement calibration.
- 1
- Volumetric flow rate = 300 m3/h;
- 2
- Temperature of the supply air inlet = −7 °C;
- 3
- Relative humidity of the supply air inlet = 75%;
- 4
- Temperature of the exhaust air inlet = 20 °C;
- 5
- Relative humidity of the exhaust air inlet = 38%.
3.4. Energy Calculations
3.4.1. Utilization of Test Data for Energy Calculations
3.4.2. Results of the Energy Estimation
4. Conclusions
- The results showed that the values of the sensible effectiveness under different outdoor air temperature and relative humidity values are almost the same values for the PEE and PHE, and only the air volume flow rate, as an operation parameter, has an effect on the sensible effectiveness.
- The maximum value of sensible effectiveness was found at the lowest air volume flow rate (100 m3/h), which was 94.2% for the PHE and 94.1% for the PEE in summer conditions. The reason for this much lower sensible effectiveness at higher air volume flow rates for the PEE is due to the transfer of additional moisture to the supply air stream from the exhaust air stream.
- The PEE is likely to be used when there is a need to maintain the indoor air relative humidity level during the winter heating period or to reduce the moisture of the outdoor air (as supply inlet air) during the summer cooling period.
- The values of the latent and total effectiveness decrease when the relative humidity of the outdoor air increases.
- The maximum values of the latent and total effectiveness could be obtained for the lowest outdoor air dry-bulb temperature values.
Author Contributions
Funding
Acknowledgments
Conflicts of Interest
Abbreviations
EI | Exhaust air inlet |
EPBD | Energy Performance of Building Directive |
h | Enthalpy (kJ/kg) |
HVAC | Heating, ventilation, and air-conditioning |
Air mass flow rate (kg/h) | |
NZEB | Nearly zero-energy buildings |
O | Outdoor |
PEE | Polyethylene–polyether copolymer material-based counter-flow air-to-air energy exchanger |
PHE | Polystyrene material-based counter-flow air-to-air heat exchanger |
RH | Relative humidity (%) |
T | Temperature (°C) |
Air volume flow rate (m3/h) | |
x | Absolute humidity (gwater/kgdry air) |
Greek Letters | |
εs | Sensible effectiveness |
εL | Latent effectiveness |
εT | Total effectiveness |
ωR | Random uncertainty |
τ | time (h) |
Subscripts | |
EI | Exhaust air inlet |
O | Outdoor |
SI | Supply air inlet |
SO | Supply air outlet |
Appendix A
References
- Ferrara, M.; Monetti, V.; Fabrizio, E. Cost-optimal analysis for nearly zero energy buildings design and optimization: A critical review. Energies 2018, 11, 1478. [Google Scholar] [CrossRef]
- Tsirigoti, D.; Tsikaloudaki, K. The effect of climate conditions on the relation between energy efficiency and urban form. Energies 2018, 11, 582. [Google Scholar] [CrossRef]
- Wan, K.K.W.; Li, D.H.W.; Liu, D.; Lam, J.C. Future trends of building heating and cooling loads and energy consumption in different climates. Build. Environ. 2011, 46, 223–234. [Google Scholar] [CrossRef]
- Sailor, D.J.; Pavlova, A.A. Air conditioning market saturation and long-term response of residential cooling energy demand to climate change. Energy 2003, 28, 941–951. [Google Scholar] [CrossRef]
- Lam, J.C.; Tang, H.L.; Li, D.H.W. Seasonal variations in residential and commercial sector electricity consumption in Hong Kong. Energy 2008, 33, 513–523. [Google Scholar] [CrossRef]
- Giannakopoulos, C.; Hadjinicolaou, P.; Zerefos, C.; Demosthenous, G. Changing energy requirements in the Mediterranean under changing cimatic conditions. Energies 2009, 2, 805–815. [Google Scholar] [CrossRef]
- Karlsson, J.; Roos, A.; Karlsson, B. Building and climate influence on the balance temperature of buildings. Build. Environ. 2003, 38, 75–81. [Google Scholar] [CrossRef]
- Calise, F.; D’Accadia, D.M.; Barletta, C.; Battaglia, V.; Pfeifer, A.; Duic, N. Detailed modelling of the deep decarbonisation scenarios with demand response technologies in the heating and cooling sector: A case study for Italy. Energies 2017, 10, 1535. [Google Scholar] [CrossRef]
- Ahmed, K.; Carlier, M.; Feldmann, C.; Kurnitski, J. A new method for contrasting energy performance and near-zero energy building requirements in different climates and countries. Energies 2018, 11, 1334. [Google Scholar] [CrossRef]
- García, T.A.; Mora, D. Energy performance assessment of building systems with computer dynamic simulation and monitoring in a laboratory. WIT Trans. Ecol. Environ. 2011, 143, 449–460. [Google Scholar] [Green Version]
- Giuseppe, E.; Marco, M.; Angelo, Z.; Michele, D.C. The use of air handling units in residential near zero-energy buildings. WIT Trans. Ecol. Environ. 2017, 224, 147–158. [Google Scholar]
- Ahmed, Y.T.A.-Z.; Hong, G. Experimental investigation of counter flow heat exchangers for energy recovery ventilation in cooling mode. Int. J. Refrig. 2018, 93, 132–143. [Google Scholar]
- Engarnevis, A.; Huizing, R.; Green, S.; Rogak, S. Heat and mass transfer modeling in enthalpy exchangers using asymmetric composite membranes. J. Membr. Sci. 2018, 556, 248–262. [Google Scholar] [CrossRef]
- Silvia, G.-L.; Beatriz, R.-S.; José, M.M. Control strategies for energy recovery ventilators in the South of Europe for residential nZEB—Quantitative analysis of the air conditioning demand. Energy Build. 2017, 146, 271–282. [Google Scholar]
- D’Este, A.; Gastaldello, A.; Schibuola, L. Energy saving in building ventilation. WIT Trans. Ecol. Environ. 2005, 81, 335–344. [Google Scholar]
- Zhang, L.Z.; Zhu, D.S.; Deng, X.H.; Hua, B. Thermodynamic modeling of a novel air dehumidification system. Energy Build. 2005, 37, 279–286. [Google Scholar] [CrossRef]
- Mardiana, A.; Riffat, S.B. Review on physical and performance parameters of heat recovery systems for building applications. Renew. Sustain. Energy Rev. 2013, 28, 174–190. [Google Scholar] [CrossRef]
- Qiu, S.; Li, S.; Wang, F.; Wen, Y.; Li, Z.; Li, Z.; Guo, J. An energy exchange efficiency prediction approach based on multivariate polynomial regression for membrane-based air-to-air energy recovery ventilator core. Build. Environ. 2019, 149, 490–500. [Google Scholar] [CrossRef]
- Stefano, D.A.; Manuel, I.; Cesare, M.J.; Federico, P. Experimental analysis and practical effectiveness correlations of enthalpy wheels. Energy Build. 2014, 84, 316–323. [Google Scholar]
- EN 13141-7:2010, Ventilation for buildings—Performance testing of components/products for residential ventilation—Part 7: Performance testing of components/products of mechanical supply and exhaust ventilation units (including heat recovery) for mechanical ventilation systems intended for single family dwellings. In EN 13141-7:2010; European Commission: Brussels, Belgium, 2010.
- Understanding Heat Exchangers-Cross-Flow, Counter-Flow (Rotary/Wheel) and Cross-Counter-Flow Heat Exchangers. 2012 Zehnder Group AG report. Available online: www.zehnderamerica.com (accessed on 29 April 2019).
- American Society of Heating. Method of Testing Air-to-Air Heat Exchangers; American Society of Heating, ASHRAE Standard 84-1991; Refrigerating and Air Conditioning Engineers Inc.: Atlanta, GA, USA, 1991. [Google Scholar]
- González-Briones, A.; Chamoso, P.; Yoe, H.; Corchado, J.M. GreenVMAS: Virtual organization based platform for heating greenhouses using waste energy from power plants. Sensors 2018, 18, 861. [Google Scholar] [CrossRef]
- Stefano, D.A.; Cesare, M.J.; Paolo, L. Performance measurement of a cross-flow indirect evaporative cooler: Effect of water nozzles and airflows arrangement. Energy Build. 2019, 184, 114–121. [Google Scholar]
- Kline, S.; Mcclintock, F. Describing the uncertainties in single sample experiments. Mech. Eng. 1953, 75, 3–8. [Google Scholar]
- Zhang, L.Z. Heat and mass transfer in plate-fin enthalpy exchangers with different plate and fin materials, International. J. Heat Mass Transf. 2009, 52, 2704–2713. [Google Scholar] [CrossRef]
- Demis, P.; Aleksandra, C.; Anna, P.; Sergey, A.; Paweł, D. Performance comparison between counter- and cross-flow indirect evaporative coolers for heat recovery in air conditioning systems in the presence of condensation in the product air channels. Int. J. Heat Mass Transf. 2019, 130, 757–777. [Google Scholar]
Parameter | Value | Unit |
---|---|---|
Length of plates | 4 | mm |
Length of ducts | 8 | mm |
Heat/moisture exchange area | 30 | m2 |
Height of plate | 370 | mm |
Extract Air Inlet Dry-Bulb (Wet-Bulb) Temperature | Outdoor Air Inlet Dry-Bulb (Wet-Bulb) Temperature |
---|---|
Heating performance test | |
20 (12) °C | 7 (6) °C |
20 (12) °C | 2 (−1) °C |
20 (12) °C | −7 (−8) °C |
Cooling performance test | |
27 (19) °C (mandatory) | 35 (24) °C (mandatory) |
27 (19) °C (optional) | 27 (19) °C (optional) |
Nominal Value | Normal Value | Measured Value | Deviation | Uncertainly |
---|---|---|---|---|
40% RH | 39.9% RH | 40.5% RH | 0.6% RH | 0.5% RH |
0 °C | 0.09 °C | 0.3 °C | 0.21 °C | 0.08 °C |
1 m/s | 0.98 m/s | 1.00 m/s | 0.02 m/s | 0.05 m/s |
Average Seasonal Effectiveness | PEE | PHE | ||
---|---|---|---|---|
Winter | Summer | Winter | Summer | |
εs_av (%) | 86 | 86 | 90 | 91 |
εt_av (%) | 77 | 77 | - | - |
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Kassai, M.; Al-Hyari, L. Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings. Energies 2019, 12, 1727. https://doi.org/10.3390/en12091727
Kassai M, Al-Hyari L. Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings. Energies. 2019; 12(9):1727. https://doi.org/10.3390/en12091727
Chicago/Turabian StyleKassai, Miklos, and Laith Al-Hyari. 2019. "Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings" Energies 12, no. 9: 1727. https://doi.org/10.3390/en12091727
APA StyleKassai, M., & Al-Hyari, L. (2019). Investigation of Ventilation Energy Recovery with Polymer Membrane Material-Based Counter-Flow Energy Exchanger for Nearly Zero-Energy Buildings. Energies, 12(9), 1727. https://doi.org/10.3390/en12091727