In all cases, the ten cable types presented on
Table 1 were considered. Additionally, it was considered:
as the number of hours during the expected wind farm lifetime, assuming that it is 20 years;
EUR/Wh as the cost of active energy;
EUR/Wh as the cost of reactive energy;
as the load factor, which reflects the real operating conditions during the wind farm lifetime, and is the ratio between the generated current and the maximum current that can be generated;
rad/s as the angular frequency.
The optimization models were constructed using FICO Xpress Mosel (Xpress Mosel Version 4.8.0), and then they were solved with FICO Xpress Optimizer. Computations were performed on a computer Intel(R) Core(TM) i7-8550U CPU @ 1.80 GHz 1.99 GHz with 8GB RAM and 64 bits.
The results of each wind farm are analyzed in the following sections.
4.1. WF-102-S2 Wind Farm
The first case study is the WF-102-S2 wind farm with two substations and 102 wind turbines with
MW of rated power, interconnected by a
kV grid. With these parameters, the rated current drawn by each turbine is
A, and the maximum number of wind turbines per branch line is
. This value is due to the fact that the maximum current intensity that the available cables can support is
,
Table 1, and so
, Equation (
9).
The coordinates of the wind turbines and substations are in
Table A1.
Two scenarios are considered for this wind farm: the wind farm original, WF-102-S2, and the wind farm WF-102-S2W, which includes a limit in the sidewalk connection.
For the first scenario, WF-102-S2, the obtained cable connection layout is presented in
Figure 3, the costs in the optimal solution are presented in
Table 2, and information about optimal cable connections is presented in
Table 3.
The correspondent model WFLMS for this scenario has 207 constraints and 94,758 variables, and the processing time to obtain the optimal solution was 79 s.
The total cost obtained is EUR 10,475,772.3, where 60.5% is the infrastructure cost, corresponding to EUR 6,332,484.5, 23.0% is the active losses cost, corresponding to EUR 2,410,659.4, and 16.5% is the reactive losses cost, corresponding to EUR 1,732,628.4. The highest amount corresponds to the infrastructure cost, and the smallest part is the reactive losses cost during wind farm lifetime.
Table 3 shows information about the cable types being used in the optimal solution. In the optimal solution, only five different types of cables are used: type 3 in 41 connections, type 4 in 23 connections, type 7 in 18 connections, type 8 in 6 connections, and type 10 in 14 connections.
The second scenario, WF-102-S2W, is obtained by limiting to two the connections passing on the walkway, adding constraint (
22) with
in the model WFLMS.
The optimal connection layout for WF-102-S2W is presented in
Figure 4 and the costs in the optimal solution are presented in
Table 2.
The correspondent model has 207 constraints and 94,758 variables, and the processing time to obtain the optimal solution was 85.3 s.
In the optimal solution, only five different types of cables are used: type 3 in 39 connections, type 4 in 22 connections, type 7 in 17 connections, type 8 in 10 connections, and type 10 in 14 connections,
Table 3.
The total cost is EUR 10,667,045.8, where: 57.3% is the infrastructure cost, corresponding to EUR 6,112,964.7; 23.7% is the active losses cost, corresponding to EUR 2,527,016.9; and 19.0% is the reactive losses cost, corresponding to EUR 2,027,064.2.
There are two sectors in both optimal wind farm solutions, WF-102-S2 and WF-102-S2-w: one has an installed capacity of 100 MW, with 50 wind turbines connected to substation
and the other one has 104 MW of installed capacity, with 52 turbines connected to substation
. There are ten branch lines linked to each substation, and the number of wind turbines in each branch line ranges between four and eight turbines. In the optimal solutions, only five different types of cables are used 3, 4, 7, 8, and 10, as shown in
Table 3.
Comparing both scenarios’ optimal solutions, in
Table 2 and
Table 3, as expected, the total cost corresponding to the optimal solution when limiting the number of connections to a subset of turbines, study case WF-102-S2-W, is higher. This phenomenon is due to the increasing of active and reactive loss costs that are not compensated by the decreasing observed in the infrastructure cost. Note that these changes in costs result from the use of lower types of cables, which are cheaper but have higher energy losses.
4.2. WF-74-S3 Wind Farm
The second wind farm, WF-74-S3, is formed by 74 turbines with
MW of rated power, interconnected by a
kV grid. With these parameters, the rated current drawn by each turbine is
A, and the maximum number of wind turbines per branch line is
. Sixteen possible positions for substations, distributed in a grid of 4 × 4-type points over the wind farm, are considered:
,
, ...,
. The coordinates of the wind turbines and substations are presented in
Table A2.
The goal is to optimize the cable layout, choosing at most three of the available substations. To solve this problem, the model WFLMS including constraint (
23) with
is considered.
The optimal connection layout is presented in
Figure 5, the costs in the optimal solution are shown in
Table 4, and information about optimal cable connections is presented in
Table 5.
The model has 166 constraints and 60,474 variables, and the processing time to obtain the optimal solution was 158.4 s.
The optimal wind farm has three sectors: one has an installed capacity of 26 MW, with 18 wind turbines connected to the substation ; the other one has 50 MW of installed capacity, with 25 turbines connected to the substation ; and the last one has 31 wind turbines connected to the substation , having 62 MW.
There are seven branches connected to substation
, in which the number of turbines varies from one to five. Substation
is linked to eight branch lines; it also has a number of turbines ranging between one and five. There are nine branch lines linked to the substation
, in which the number of turbines varies between one and six. In the optimal solutions, only five different types of cables are used: type 3 in 30 connections, type 4 in 21 connections, type 7 in 13 connections, type 8 in 6 connections, and type 10 in 4 connections, as shown in
Table 5.
The total cost is EUR 2,908,787.57, where 64.9% is the infrastructure cost, corresponding to EUR 1,887,148.4, 22.7% is the active losses cost, corresponding to EUR 660,641.2, and 12.4% is the reactive losses cost, corresponding to EUR 360,997.9,
Table 4.
Once again, the highest amount corresponds to the infrastructure cost and the lowest amount is the reactive losses cost during wind farm lifetime.
Comparing this approach with approaches in the literature, Reference [
22], the presented model is much faster at finding the optimal solution.