1. Introduction
Commutation failures (CFs) are very common events in traditional line commutated converter (LCC)-based HVDC systems, which are usually caused by voltage reductions following AC-side faults [
1,
2,
3]. The occurrence of CF will inevitably cause many transients, such as temporary interruption of power transmission, voltage fluctuation, etc. [
4,
5]. After the fault is cleared, the HVDC system is expected to recover from CF as soon as possible. Otherwise, continuous CFs may cause converter block [
6], which threatens system security. It is important to improve the recovery performance to counter continuous CFs, and many previous works have been dedicated to this topic [
7,
8,
9].
For LCC-based HVDC systems, the valve-firing control system generates valve-firing pulses, based on the firing angle order and the reference voltage at the AC side. The control system plays the most important role during the transient of recovery from CF. Currently, the most widely implemented control strategies in the real world can be categorized into either an ABB-based or SIEMENS-based strategy. For the two types of control strategies, the calculations of the firing angle order are different, but the key idea of the control system during the transient is very similar, which is to enlarge the margin of extinction angle by triggering the thyristor gates in advance. Many auxiliary controls have been proposed to improve the performance under large disturbances [
10,
11], among which the commutation failure prevention (CFPREV) mechanism has been widely applied [
12]. In addition, many different types of dynamic var sources have been used to enhance the immunity against CFs, e.g., synchronous compensator (SC), static synchronous compensator (STATCOM) [
13,
14], etc.
In the previous literature, the main focus is centered on inducing the firing angle order, which will then be fed into the firing pulse generator to create trigger pulses. Usually, the firing pulses are generated by comparing the firing angle order and the measured commutating voltage phase angle. The dynamic behavior of the phase angle measurement will definitely influence the performance of recovery from CF, which has attracted many researchers. Authors in [
15] compared the dynamic performance of different HVDC systems under traditional phase-lock control and PLL-less control. In ref. [
16], a novel phase-locked strategy is proposed based on dynamic phasor modelling to provide more accurate phase angle information. The influence of phase-locked control on small single stability was analyzed in [
17], and the results showed that there are coupling effect between phase-locked controller and LCC controller. To overcome the disadvantage of traditional phase-lock control under the unbalanced and distorted grid conditions, a double decouple synchronous reference frame was proposed in [
18].
In LCC-based HVDC systems, the phase-locked oscillator (PLO) is usually applied to provide the phase information. During the transient process of recovery from CFs, the dynamic behavior of PLO will definitely influence the execution of firing thyristors. If the measured phase angle deviates from the real phase angle, the thyristors may not fire correctly, inducing unexpected CFs. In this paper, a novel adaptive PLO is proposed, where the control parameters can be adaptively changed following the system state. During the process of recovery from CF, the var consumption of converters will rise from 0 to about of the active power consumption in a very short period, which will induce the fluctuation of commutating voltage. Thus, if the PLO cannot capture the voltage phase information correctly under a large signal disturbance, the recovery may fail and continuous CFs will happen.
In this paper, an adaptive PLO structure is proposed to improve the performance of recovery process from CF, where the control parameters can be adjusted following the system state. During the process of fault recovery, the PLO is preferred to capture the fast change of commutating voltage, whereas the small signal stability is considered as the more important factor during normal operation. The main contributions can be summarised as follows: the proposed PLO can improve transient performance compared to the traditional method, which can provide more accurate phase information during the fault recovery process.
The rest of this paper is organized as follows.
Section 2 presents the parametric fault voltage equations and the main problems to be resolved, and then the detailed solution method is illustrated in
Section 4. In
Section 5, case studies are performed to demonstrate the effectiveness of the approach, followed by concluding remarks in the last section.
4. The Adaptive PLO Control Algorithm
From
Section 3, it is known that the parameters of PI-controller are very important to the performance of PLO. In our work, an adaptive scheme of control parameters is proposed, where the PI-controller applies different control parameters under different conditions.
For the LCC-based HVDC systems, the commutation process highly relies on the commutating voltage, so the variation of commutating voltage is selected to indicate the system operation condition. During the CF faults at the converter side induced by AC system faults, the commutating voltage is typically at a low level. After the AC system faults are cleared, the commutating voltage begins to rise along with the recovery from CF. If the variation of commutating voltage is greater than a threshold value, it is reasonable to regard the system is suffering a large disturbance. Assume that, the rms of commutating voltage is
. Then,
where
is the specified constant for determining the system state.
When the system is operated under steady-state conditions, the performance of PLO is preferred to be with higher small signal stability. Thus, the control parameter of PI-controller should have a smaller value. If CF occurs, it will be better to apply a larger to gain fast dynamic response.
As depicted in
Figure 6, the RMS of commutating voltage can be evaluated based on the measured three-phase voltage at the AC side. A first-order inertia link with time constant
is firstly applied to suppress the high-frequency harmonies, followed by the derivative block to determine the signal changing rate, i.e.,
. Here,
is the derivative time constant. Usually, the derivative can amplify noise, so the inertia link should be added to minimize noise interference. Then, a signal is generated by comparing
with a specified constant
, shown as (
9). Depending on this signal, selectors are employed to change the value of
and
.
where
,
,
and
are different predefined gains for selectors to take.
The main idea is that and can be changed adaptively depending on the state of commutating voltage. In general, the RMS of the commutating voltage has its specified value ranges in many grid codes, which could be used as reference for setting Cs values. However, it is still worth noting that the setting of Cs is also a compromise between the controller’s sensitivity and stability.
5. Case Studies
To investigate the effectiveness of the proposed method, the CIGRÉ benchmark model for LCC-based HVDC system is applied [
21] with a short-circuit ratio of 2.0 on the platform of PSCAD/EMTDC and RT-LAB, respectively.
5.1. Three-Phase Fault
At first, simulations are performed in PSCAD/EMTDC and three phase fault is applied. The original control parameters are and . In the proposed method, , , and . When s, a three-phase fault takes place at the inverter side, and the fault duration time is s.
Figure 7 show the comparison between firing angle order and actual firing angle under the original control algorithm. At the moment of
s, commutation failure happens due to the voltage dip. After the fault is cleared, the system recovers from commutation failure. It can be seen that, the actual firing angle is greater than the firing angle order during the period between
and
. That means, the measured phase angle has a time lag with the actual phase angle. From (
7), the voltage-time area for commutation will be reduced, which may cause continuous commutation failures. In this case, continuous commutation failure can be observed at about
s.
In
Figure 8, the actual firing angle and firing angle order are compared under the proposed method. It can be seen that, the actual firing angle is almost same with the order after the fault is cleared at
s. That means the output of PLO can reflect the phase angle during the process of recovery from CF. If the control order of the system controller can be effectively implemented, continuous CF can be avoided in this case. If the original control parameters are applied, the control order cannot be carried out correctly and the unexpected continuous CF will occur. To better demonstrate the commutation progress, the responses of extinguish angle and commutating voltage under different control algorithms are given in
Figure 9 and
Figure 10, respectively. It can be seen that, the proposed method can eliminate the continuous commutation failure, which will benefit the voltage recovery.
5.2. Single Phase Ground Fault
In the second case, the unbalanced fault is applied in PSCAD/EMTDC, where the control parameters are set as the same with the ones in
Section 5.1. When
s, a fault happens at phase-A and is cleared after
s.
Figure 11 show the comparison under the original control algorithm. It can be seen that, the actual firing angle is less than the firing angle order during the period between
and
. In this case, the voltage-time area for commutation is larger than the one expected, so no CF occurs. After that, the actual firing angle is greater than the order, which means the actual commutation area is smaller than the ordered. Thus, continuous CF takes place at the moment of
s. During the recovery process from second CF, the phase angle with time lags provided by the original PLO leads to the third CF. If the protection scheme of continuous CFs is implemented, this converter will be blocked. Compared to the case with balanced faults, the original control strategy may lead to a worse result in the case with unbalanced faults.
Compared to the original strategy,
Figure 12 shows the actual firing angle and firing angle order under the proposed method. It can be seen that the firing angle order can be carried out better, and no continuous CF is observed. That means, the proposed method can enhance the ability of recovery from CF with unbalanced faults, compared to the original strategy. The response of extinguish angle and commutating voltage under different control algorithms are given in
Figure 13 and
Figure 14, respectively. Similar with the case under 3PF, the proposed method performs better than the original algorithm does. When
s, the extinguish angle reduce dramatically to the critical extinguish angle under the original method, meaning that a continuous commutation failure happens. On the contrary, the proposed method can capture the phase information correctly and the fault recovery performs normally under the expected strategy.
5.3. Small Signal Stability
In this case, the small signal stability of the proposed method is investigated. From
Section 3.2, it is known that the parameter
with larger value can provide a faster response, but may make the small signal stability worse. So, if the system is operated under normal condition, the control parameters are adaptively changed to smaller ones in the proposed method. Here, we set
and
to 100 and 300 for the conventional constant control strategies, even in the normal operation while
,
,
and
for the proposed adaptive strategy which are the same as previous subsections. A single-line ground fault with a 400
fault resistance is applied at phase-A at
s and cleared after
s. The fault resistance applied here is relative high, and commutation failure will not happen, which can be interpreted as a small disturbance to the HVDC system. A comparison of commutating voltage between the proposed method and the one with larger parameters is shown as
Figure 15.
It can be seen that, the commutating voltage under the proposed method begins to stabilize at about s, and the control parameters for normal operation will be effective at this moment. On the contrary, the voltage with larger and does not shift toward the stable state but fluctuates, which means the control parameters applied in the transient process of recovery may cause stability problems under small disturbance.
5.4. Recovery Performance Comparison with Traditional Approaches
To counter the commutation failure, one of the most popular and effective solutions is to trigger the thyristor gates in advance, which may however slow down the recovery speed. Here, the benefit of the proposed method is investigated on the platform of RT-LAB, and a comparison with the dynamic phasor-based (DP-based) PLL proposed in [
16] is presented.
To investigate the performance of proposed method and its beneficial after application, a single-line ground fault with
is applied at
s and cleared after 0.1 s. In this case, an improved CFPREV control is compared [
12], where the recovery speed is limited by the commutation margin.
Figure 16 illustrates the performance of firing angle order by different methods. During the fault recovery process, the firing angle order recovers faster, if the proposed PLO is used. The reason for this is that an accurate voltage phase angle can largely improve the effectiveness of the control strategy. The error of phase angle may cause an incorrect execution, so that the controller must slow down the recovery process to ensure that the recovery is successful.
Aside from the recovery speed, the commutation margin is also compared, and
Figure 17 shows a comparison of the
. It can be seen that, the implementation of our method can provide a better result. During the recovery process, the extinguish angle of the proposed method is maintained at about 20 degrees, whereas the result by conventional approach reaches about 15 degrees. The proposed method enhances the effectiveness of the recovery control strategy by considering both the recovery speed and the risk of failure.
To further investigate the effectiveness compared with other similar techniques, a DP-based PLL is compared, which is based on the theory of Fourier expansion.
Figure 18 depicts the comparison between different approaches. During the recovery process, the original PLO provides a phase angle with time lag, shown as the blue dashed line. From
Section 2.2, it is known that this time lag may result in recovery failure. As for the comparison between the proposed method and DP-based approach, there is almost no difference between their results. It can be seen that the output of PLO of the proposed method and DP-based PLL are almost identical, which verifies the accuracy of our method. Although the DP-based method gains high accuracy during the large disturbance, the small signal stability should also be considered.
Figure 19 shows the small signal response comparison, where a single-line ground fault of 700
is applied at phase-A when
and cleared after 0.1 s. As seen, an oscillation occurs in the results by DP-based method, whereas the oscillation of the proposed method is much better. Moreover, it should be pointed out that the proposed PLO can be realized by modifying the original control, while the DP-based approach requires a completely new implementation.