H Robust Load Frequency Control for Multi-Area Interconnected Power System with Hybrid Energy Storage System

School of Internet of Things Engineering, Jiangnan University, Wuxi 214000, China
*
Author to whom correspondence should be addressed.
Appl. Sci. 2018, 8(10), 1748; https://doi.org/10.3390/app8101748
Submission received: 20 August 2018 / Revised: 17 September 2018 / Accepted: 19 September 2018 / Published: 27 September 2018
(This article belongs to the Special Issue Applied Sciences Based on and Related to Computer and Control)

Abstract

:
To enhance the quality of output power from regional interconnected power grid and strengthen the stability of overall system, a hybrid energy storage system (HESS) is applied to traditional multi-area interconnected power system to improve the performance of load frequency control. A novel topology structure of interconnected power system with the HESS is proposed. Considering the external disturbances of the system and the interconnected factors between each control area, the dynamic mathematical model of each area in the new topology is established in the form of state-space equation. Combining the state feedback robust control theory with linear matrix inequality (LMI) theory, the controller is designed to calculate how much power the HESS should provide to power grid in real time, according to the load change of system. Taking the four-area interconnected power system as study object, the simulation results obtained by MATLAB prove that the application of HESS can well improve the frequency stability of multi-area interconnected system and the H robust controller proposed in this paper is effective.

1. Introduction

With the rapid development of new energy generation technologies such as photovoltaic power generation, wind power generation, et cetera, as well as user’s growing requirement of power quality and power supply reliability, power system has changed from the traditional centralized large power grid to the multi-area interconnected power system [1]. The reliability, flexibility and economy of power grid can be greatly improved by the coordinated and optimal operation of regional interconnected power system. Moreover, it should not be ignored that the interconnection of regional power systems will increase the uncertainties and bring problems about the frequency stability in the power network [1,2,3].
A high-quality power system requires the power frequency rate and voltage of system to be kept within a certain range around the set value. This requirement can be reached by adjusting the active power and reactive power of the system. The load frequency control (LFC) is an important part of the automatic power generation control (AGC) in power system and the function of the LFC is to ensure the stability of power system load frequency [4,5]. In other words, the LFC is used to keep the balance between the generating power and user load. Specific assignments of the LFC are as follows: (1) Make sure that the deviation of load frequency can be maintained at zero. (2) The switching power between tie-lines can return to the set value quickly under any load variation disturbance [6]. The study of load frequency stability control in power system began around the 1970s [7,8]. In pace with the development of LFC, the control mode has developed from only considering the load frequency stability into combining the load frequency with the tie-line exchanged power together [8,9,10]. The control object has also changed from a single generator to the whole power plant area, and from a single-area system to the multi-area interconnected power system [10]. Many scholars have been looking for methods to improve the control effect of the LFC, such as applying neural network theory, adaptive control, fuzzy control, predictive control and other optimal control theories. The chaos optimization algorithm is used to adjust the multi-area load frequency control PID controller in [11]. In [12], it is proposed to combine the adaptive modified bat algorithm with the fuzzy logic (FL) to set the parameters of the proportional controller on line to improve the control effect of the LFC. The particle swarm optimization (PSO) algorithm is applied to adjust parameters of the proposed PI controller in [13]. The uncertainty caused by the variation of governor and turbine parameters is considered in [14], and an adaptive model predictive control (AMPC) method is applied to the LFC controller for multi-area power systems which can change the object model in MPC structure online. However, the research on LFC optimization is not only reflected in the improvement of controller and algorithm. In [15], multiple controllable thyristors or synchronous series compensators are installed in multi-area power systems, improving the dynamic control effect of the LFC by the coordinated control of phase shifter.
The main contributions of this paper are as follows: (1) We propose a new diagram of four-area interconnected power system and establish the dynamic mathematical model of power system in each control area. (2) The HESS is introduced to provide the power flow in purpose of regulating the frequency and tie-line exchanged power of system. (3) We apply the generic mode control method in [16] to realize the charging and discharging of the HESS. (4) We design the H robust controller based on the LMI and state-feedback method to calculate how much power the HESS should provide to the power system. Through the analysis and comparison of simulation results from PID control, it is identified that the H controller can improve the stability of power frequency under external load disturbance and the HESS can convert the output power demand signal from the H controller into the corresponding power flow effectively.
This paper is organized as follows: in Section 2, a new topology diagram of four-area interconnected power system with the HESS is presented and concepts of the LFC and the HESS are introduced. Section 3 presents a detailed mathematical model of ith control area within the four-area interconnected power system in the form of state space equation. H state feedback controller is designed for power system with the HESS in the ith control area in Section 4, based on the mathematical model established in Section 3. Further simulation verification and results analysis of the method proposed in this paper are presented in Section 5. Finally, the conclusion is given in Section 6.

2. Multi-Area Interconnected Power System with the HESS

Interconnected power system is usually composed of several control areas. Each area is connected to another by a tie-line for power exchange under normal operating conditions to overcome the mismatch between the generation and the demand [17]. Under any load change disturbance, there are two control aims in the operation of interconnected power system model:
  • One objective is to make sure that the deviation of load frequency is zero or fluctuate in a certain really small range near zero.
  • Another objective is to ensure that the switching power of the tie line returns to the set value.
Taking the four-area interconnected power system as an example, a new topology diagram of interconnected power system with the HESS is presented in this paper which is shown in Figure 1 [6]. The regional power system consists of three parts: generation system, user load and the HESS. In Figure 1, “G” represents the generation system, “L” indicates the user load and the “H” denotes the hybrid energy storage system (HESS).

2.1. Load Frequency Control

Power system is a complex nonlinear dynamic system, because the power system is always affected by the load disturbance which results in the load frequency fluctuation [18]. In general, we use the method of near linearization to deal with the power system model. We usually adopt the linearization method near a certain working point to deal with the power system model [19,20]. A linear model is established to represent the dynamic model of system. The linearized model structure of system of ith control area in the interconnected power system is shown in Figure 2, which mainly includes the generator, the reheating turbine and the governor.
The linearized model of the governor is as follows:
G g i = 1 T g i s + 1
The linearized model of the reheat steam turbine is shown as:
G t i = c T r i s + 1 ( T r i s + 1 ) ( T t i s + 1 )
The linearized model of the generator is as bellow:
G p i = K p i T p i s + 1
The physical implications of variables in the model of ith (i = 1,2,3,4) control area are as follows: T g i , T r i , T t i , and T p i , respectively, represent the time constant of governor, the reheating time constant, the time constant of steam turbine and the time constant of power system. Δ X e i indicates the incremental variation of governor valve position. Δ P r i is the increment of output thermal power from reheat unit. Δ P t i e i denotes the deviation of power exchange between tie-lines. Δ P d i represents the load disturbance. Δ f i is the load frequency deviation of system. c is the reheating coefficient and K p i is the gain of power system. T i j represents the power synchronization coefficient of tie-line between the ith control area and the jth control area ( i j ). K A F i is the proportional negative feedback coefficient of the frequency deviation. φ i denotes the frequency deviation constant that satisfies φ i = β i / R i , where β i is the set value of frequency deviation and R i is the speed regulation gain.
To improve the power system with better dynamic performance, we should not only make sure that the frequency deviation ( Δ f i ) of the system tends to zero, but also ensure that the deviation of power exchange between tie lines ( Δ P t i e i ) is close to zero under any load disturbance. Considering the two targets above, the concept of area control error (ACE) is proposed in the LFC. The expression of ACE in the ith control area is formulated as (4):
A C E i = Δ P t i e i + φ i Δ f i
In this paper, there is an internal PI controller in power system for frequency regulation which can be seen in Figure 2. The controlled variable u l f c i is as follows:
u l f c i = K i s A C E i
where K i represents the control coefficient of PI regulation in ith control area.
Many works have been done to improve the control effect of the LFC and several novel control methods have been applied to the internal controller design in LFC. For example, the application of parameter self-adjusting algorithm to the PID controller [11,12] and the design of adaptive model predictive controller. In this paper, a hybrid energy storage system is introduced into traditional power system and an H robust state feedback controller is designed. The controller calculates the power supply in real time according to the variation of user load in system, and then the power control signal is transmitted to the HESS. The regulation of power in the system is realized by the effective charge and discharge of the HESS, which can ensure the stability of the load frequency.

2.2. Hybrid Energy Storage System

To guarantee the balance between the user power requirement and the active power generated by power grid, it is necessary to install the energy storage equipment with a certain capacity to adjust the power fluctuation of the power system. In the power system, the energy storage system is mainly used to calm down the fluctuating power of the system, reduce the sharp oscillation of system and cut down the peak and valley difference of the load power rate curve in purpose of enhancing the power quality [21,22,23]. We introduce the HESS into the inter-connected power system. The HESS aims to stabilize the load frequency of the power grid and eliminate a series of negative effects caused by the fluctuating power.
HESS is a kind of energy storage equipment composed of super capacitor (SC) and battery (B). The HESS has been proved theoretically that the structure can give full play to the characteristics of these two kinds of energy storage equipment by Dougal et al. in 2002 [24,25]. The SC has the characteristics of high power density, short charge and discharge time, high reliability and long cycle life. It is suitable for situations require high power, frequent electric charge and discharge instead of the battery with low energy density [22,25]. Nevertheless, the combination of SCs and batteries can not only meet the qualification of high power density and high energy density, but also can reduce the rated capacity of batteries and prolong its service life. Currently, the HESS has been widely regarded as an effective way to calm down the grid power fluctuation due to its technical and economic advantages [26,27].
The hybrid energy storage system (HESS) can be mainly divided into two categories: the passive HESS and the active HESS. In this paper, we choose an active parallel HESS comprised of super capacitors and Lithium-ion batteries. The basic structure of HESS is shown in Figure 3.
In Figure 3, the battery is connected with a boost converter and the supercapacitor is connected with a bi-directional DC-DC converter (buck-boost) [28]. Two converters share the same DC link which is connected to the power system through a DC-AC converter. As shown in Figure 3, the Lithium-ion battery part is composed of a inductance with high frequency L B , an IGBT (Insulated-Gate Bipolar Transistor) K 1 , a diode D 1 and an output filter capacitor C B which plays a role in protecting the battery [29]. U B a t is the voltage of the Lithium-ion battery. i B c is the inductor input current. i B a t denotes the boost converter output current. U d c represents the voltage of DC bus. The super capacitor part consists of a high frequency inductance L S c and two IGBTs K 2 and K 3 ; R s and L s represent the equivalent resistance and equivalent capacitance value of the super capacitor. U S c is the voltage of the SC. i S c is the inductor input current and it can be positive or negative. i S c is positive when the SC is in discharging mode. IGBT K 1 , K 2 and K 3 respectively controlled by binary signal q 1 , q 2 and q 2 . The PWM signals for Lithium-ion battery and super capacitor are generated according to the energy-management strategy [16]. The power exchange between the HESS and power system can be seen in Figure 4.
P c i represents the power requirement from power system corresponding to the output power instruction from the H state feedback controller designed in this paper. P B a t and P S c are the power should be provided to power system by the battery and super-capacitor. Moreover, P S c is positive when the SC is in discharging mode and negative in charging mode. There are two working modes, namely, the voltage-reduction or charging mode and the boosting or discharge mode [30]. The power instruction P S c and P B a t converted the corresponding current instruction i S c and i B a t by calculation [16]. The HESS absorbs or emits corresponding power according to the difference value between the power generated by the power grid and the power required on the user side, thus the stabilization of frequency fluctuation power in power grid can be realized.

3. Mathematical Model of Power System with the HESS in the ith Control Area

State space description can effectively reveal and utilize the inner state information of the system. By this way, the complexity of mathematical representation will not be increased when the numbers of variables increase. In this paper, the mathematical model of ith control area within the four-area interconnected power system is established in the form of state space equation. To facilitate modeling, the linear expression of the reheat steam turbine (Equation (2)) is decomposed as shown in Figure 5. In Figure 5, Δ P g i denotes the output power increment of power generation, Δ P r i is the output thermal power increment of reheat unit and Δ X e i indicates the incremental variation of governor valve position.
Thinking about the ith control area in a multi-area interconnected power system, define the output y i = A C E i , the input u i = P c i , inner state-space vector x i R 6 × 1 and the disturbance vector w i R 2 × 1 . The detailed expressions are as follows and all variables in state-vector x i are explained in Section 2.1.
x i = [ x i 1 x i 2 x i 3 x i 4 x i 5 x i 6 ] T = [ Δ f i Δ P g i Δ P r i Δ X e i Δ P t i e i A C E i d t ] T
w i = [ Δ P c i 2 π i = 1 , i j n T i j ] T
The state space model of power system in ith control area can be established as follows:
{ x ˙ i = A i x i + B i u i + F i w i y i = C i x i
where A i R 6 × 6 , B i R 6 × 1 , F i R 6 × 2 and C i R 1 × 6 are parameter matrices of system. Their expressions are as below:
B i = [ K p i T p i 0 0 0 0 0 ] T
C i = [ β i R i 0 0 0 0 0 ] T
F i = [ K p i T p i 0 0 0 0 0 0 0 0 0 2 π 0 ] T
A i = [ 1 T p i K p i T p i 0 0 K p i T p i 0 0 1 T t i 1 T t i 0 0 0 c T g i ( 1 R i + K A F i ) 0 1 T r i 1 T r i c T g i 0 c T g i 1 T g i ( 1 R i + K A F i ) 0 0 1 T g i 0 K i T g i 2 π i = 1 , i j n T i j 0 0 0 0 0 β i R i 0 0 0 0 0 ]

4. H State Feedback Controller Design for Power System with the HESS in the ith Control Area

Take the four-area interconnected power system as study object. The control block diagram designed for the ith control area is shown in Figure 6. P c i * is a given power instruction calculated by the H controller to the HESS. P c i denotes the power flow provided to power system by the HESS. y i is the output of power system in the ith control area which denotes the area control error (ACE). x i 1 , … , x i 6 (i = 1, 2, 3, 4) present six inner state quantities of the ith control area. The specific description and meaning of each state which have been given in Section 2 and Section 3.
Combining the mathematical model (Equation (6)) of power system in ith control area with the control structure shown in Figure 6, the closed-loop system model of the ith control area can be expressed as follows:
{ x ˙ i = A i x + B i u i + F i w i z i = C 1 i x + D 12 i u i v i = C 2 i x i
where w i represents the disturbance signal consisting of Δ P c i and 2 π i = 1 , i j n T i j , which, respectively, represent the load disturbance and the interregional interaction. u i is an input signal of system which is generated by the HESS, z i is an evaluation signal and v i is the observed signal of system. In this paper, we choose x i as the observed quantity. C 2 i is an identity matrix. A i , B i and F i are coefficient matrices of the controlled object which are detailed described in Section 3. C 1 i and D 12 i are both weighted coefficient matrices. It should be noticed that, if the selection of C 1 i or D 12 i is not appropriate, there will be a bad influence on the control performance of the system. q i j (i, j = 1, …, 6) and ρ i are weighting coefficients greater than zero. The definition of evaluation signal z i is as follows:
z i = [ q i 1 0 0 0 0 0 0 q i 2 0 0 0 0 0 0 q i 3 0 0 0 0 0 0 q i 4 0 0 0 0 0 0 q i 5 0 0 0 0 0 0 q i 6 0 0 0 0 0 0 ] x i + [ 0 0 0 0 0 0 ρ i ] u i
The controller coefficient matrix K i is designed satisfying the stability condition of ( A i , B i , C 2 i ) . The matrix D 12 i in Equation (7) is required to be column full rank to make sure that the controller K i is a real rational function matrix. The state feedback controller of power system in ith control area is designed as follows:
u i = K i x i
Substituting Equation (9) into Equation (7), the corresponding expression can be obtained as follows:
{ x ˙ i = ( A i + B i K i ) x i + F i w i z i = ( C 1 i + D 12 i K i ) x i v i = x i
Aiming at the problem about robust stability and disturbance suppression performance of control system, the key of state feedback controller design by using H control theory lies in: solving appropriate state feedback controller promising the closed-loop system is stable and the H norm of the closed-loop transfer function matrix is minimum or less than a given value. Let T z w be the transfer function from input w to output z. The goal of H design is guaranteeing the H norm of T z w to be less than γ and it can be expressed as follows:
T z w = ( C 1 i + D 12 i K i ) [ s I ( A i + B 2 i K i ) 1 B 1 i ]
The following three kinds of H controller design problems can be differentiated according to the selection of γ . If the state feedback controller K(s) can guarantee the closed-loop transfer function of the control system to be internally stable and the value of T z w is minimum. That is, T z w = γ 0 and it is called H controller optimal design. If K i satisfies the equation T z w = γ > γ 0 based on satisfying the sufficient stability condition of ( A i , B i , C 2 i ) , then this kind of problem is H controller suboptimal design problem. If T z w = γ 1 exists, then the corresponding H controller standard design problem [31,32,33].
Then, the following linear matrix inequality is established considering Equation (11) and standard design problem of H controller design:
[ A i X i + B 2 i W i + ( A i X i + B 2 i W i ) T B 1 i ( C 1 i X i + D 12 i W i ) T B 1 i T I 0 C 1 i X i + D 12 i W i 0 γ i 2 I ] < 0
If there exists a set of feasible solutions X i * and W i * can ensure the above inequality holds true, then u i = W i * ( X i * ) 1 x i is an H state feedback controller of the system and the controller coefficient matrix is K i = W i * ( X i * ) 1 . The control coefficient matrix K i can be obtained by using the MATLAB LMI toolbox, feasp() or mincx() function to solve the linear matrix inequality in Equation (12).

5. Simulation and Result Analysis

Taking the four-area interconnected power system as research object in this paper and each control area can be distinguished by setting different values to various parameter variables. In the case of Control Area 1, the parameter settings are shown in Table 1.
The electrical simulations of interconnected power system for four control areas area carried out through Matlab 2012a/Simulink in following three different cases:
  • Case 1: Traditional LFC, i.e., power system without the HESS.
  • Case 2: Power system with the HESS and external PID controller [14,34].
  • Case 3: Power system with the HESS and external H robust state feedback controller.
Set the simulation time to 100 s. To test the robust stability and the suppression ability of the control system under load disturbance, load interference is added to the power system in Control Area 1, as shown in Figure 7, which consists of step signal, ramp signal and sinusoidal signal [35]. It is worth pointing out that, when Area 1 is disturbed by load interference, the load frequency of power systems in the other three control areas will be affected through the tie-lines between each area.
Take the Area 1 as an example. In the process of H robust state feedback controller design, the weighting coefficients and performance indices are given as Table 2. Combining Section 4, the state feedback control coefficient matrix of Area 1 can be obtained by Matlab as K 1 = [−10.8625, 25.5883 5.2364, −8.8031, −7.6875, −9.2341] and coefficient matrices for other three control areas can be easily obtained by using the method above.
For Case 3, Figure 8 shows the control signal u 1 , u 2 , u 3 , u 4 for each control area from the H state feedback controller designed in this paper. These control signals denote the power instruction transmitted to the HESS from H controller. More attention should be paid to the magnitude order of the axis because they are different in each figure. It can be noticed that the orders of magnitude in Figure 8b–d are really small, respectively, 10 5 , 10 5 and 10 6 .
Figure 9 shows the load frequency deviation Δ f i ( i = 1 , 2 , 3 , 4 ) of each power system under load disturbance in Case 3. When the load disturbance of Figure 8 arises in Control Area 1, load frequencies of each power system will be subjected to varying degrees of influence. Under the condition of LFC with the HESS and external H robust state feedback controller, in Figure 8 we can see that the load frequency f i ( i = 1 , 2 , 3 , 4 ) restores stability rapidly in seconds and Δ f i ( i = 1 , 2 , 3 , 4 ) was guaranteed to be within ±0.0006 Hz since the maximum interference is almost 10 Kw. The result comparison of PID controller and H state-feedback controller is shown in Figure 10 under the condition of LFC with the HESS.
Figure 10 shows the control effect comparison of four areas in three different situations. The control effect is evaluated according to whether the value of the reference performance index A C E i ( i = 1 , 2 , 3 , 4 ) is close to zero. The expression of A C E i ( i = 1 , 2 , 3 , 4 ) is composed of terms Δ P t i e i and Δ f i , A C E i = Δ P t i e i + φ i Δ f i . The closer A C E i is to zero, the better is the control effect. Figure 10a–d, respectively, shows the simulation results of the Control Areas 1–4 in three different cases.
Comparing and analyzing the output waveform of the system, when the load disturbance occurs in Case 1, the A C E i values of each region oscillate greatly and it takes more time to recover the stability near the zero value. Comparing PID control and H robust state feedback control, it can be clearly seen in Figure 10 that H robust state feedback controller can effectively enhance the robustness and stability of the system in the condition of disturbance, keep the system output A C E i fluctuating within the range of ±0.0006 Hz near zero and restore the system frequency stability within 10 s.
The design goal of this paper is to return the stability of the load frequency of the power system as quickly as possible in the event of external load disturbances, namely, make the value of area control error ( A C E i ) stable at zero or within a minimum range near zero. Therefore, through the analysis of simulation results, it can be shown that the stability of power system and the control performance of the LFC can be improved effectively by introducing the HESS.

6. Conclusions

This paper studies the problem of improving the frequency stability of multi-area interconnected power system and proposes that the HESS should be introduced to restrain the frequency fluctuation of the interconnected power network. The mathematical model of a single control system is established and H robust state feedback controller based on LMI is designed to further enhance the robustness and stability of the system for the LFC. Finally, the feasibility and effectiveness of the proposed scheme are proven by the simulation and results analysis. Moreover, the coupling problem in large power system is not considered and the study of coupling quantity in large area power system will be the next research direction.

Author Contributions

All authors contributed to designing and performing measurements, data analysis, scientific discussions, and writing the article.

Funding

This work was partially supported by the National Natural Science Foundation of China (61503156), National Key Research and Development Program (2016YFD0400301), Open Research Fund of Jiangsu Collaborative Innovation Center for Smart Distribution Network, Nanjing Institute of Technology (XTCX201806), National first-class discipline program of Food Science and Technology (JUFSTR20180205), and State Grid Zhejiang Province Technology Project (SGTYHT/17-JS-201)

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Mi, Y.; Yang, Y.; Zhang, H. Sliding mode based load frequency control for multi-area interconnected power system containing renewable energy. In Proceedings of the 2014 IEEE Conference and Expo Transportation Electrification Asia-Pacific (ITEC Asia-Pacific), Beijing, China, 31 August–3 September 2014; pp. 1–6. [Google Scholar]
  2. Fang, Z.; Zhao, H.G.; Liu, Z.H. The influence of large power grid interconnected on power system dynamic stability. Proc. CSEE 2007, 27, 1–7. [Google Scholar]
  3. Gurrala, G.; Sen, I. Power system stabilizers design for interconnected power systems. IEEE Trans. Power Syst. 2010, 25, 1042–1051. [Google Scholar] [CrossRef]
  4. Saikia, L.C.; Nanda, J.; Mishra, S. Performance comparison of several classical controllers in AGC for multi-area interconnected thermal system. Int. J. Electr. Power Energy Syst. 2011, 33, 394–401. [Google Scholar] [CrossRef]
  5. Zuo, J.; Xie, P.; Li, Y. Intelligent optimization algorithm based load frequency controller design and its control performance assessment in interconnected power grids. Trans. China Electrotech. Soc. 2018, 33, 478–489. [Google Scholar]
  6. Xu, D.Z.; Liu, J.; Yan, X.G. A novel adaptive neural network constrained control for multi-area interconnected power system with hybrid energy storage. IEEE Trans. Ind. Electron. 2018, 65, 6625–6634. [Google Scholar] [CrossRef]
  7. Moorthi, V.R.; Aggarwal, R.P. Suboptimal and near-optimal control of a load-frequency-control system. Proc. Inst. Electr. Eng. 1972, 119, 1653–1660. [Google Scholar] [CrossRef]
  8. Bengiamin, N.N.; Chan, W.C. 3-level load-frequency control of power systems interconnected by asynchronous tie lines. Electr. Eng. Proc. Inst. 1979, 126, 1198–1200. [Google Scholar] [CrossRef]
  9. Bengiamin, N.N.; Chan, W.C. Multilevel load-frequency control of interconnected power systems. Electr. Eng. Proc. Inst. 1978, 125, 521–526. [Google Scholar] [CrossRef]
  10. Talaq, J.; Al-Basri, F. Adaptive fuzzy gain scheduling for load frequency control. IEEE Trans. Power Syst. 1999, 14, 145–150. [Google Scholar] [CrossRef]
  11. Farahani, M.; Ganjefar, S.; Alizadeh, M. PID controller adjustment using chaotic optimisation algorithm for multi-area load frequency control. IET Control Theory Appl. 2012, 6, 1984–1992. [Google Scholar] [CrossRef]
  12. Khooban, M.H.; Niknam, T. A new intelligent online fuzzy tuning approach for multi-area load frequency control: Self-adaptive modified bat algorithm. Int. J. Electr. Power Energy Syst. 2015, 71, 254–261. [Google Scholar] [CrossRef]
  13. Boroujeni, S.M.S.; Boroujeni, B.K.; Abdollahi, M. Multi-area load frequency control using PI controller tuned by particle swarm optimization. Res. J. Appl. Sci. Eng. Technol. 2011, 3, 1396–1401. [Google Scholar]
  14. Zaki Diab, A.A.; EL-Satter, M.A. Adaptive model predictive based load frequency control in an interconnected power system. In Proceedings of the IEEE Conference of Russian Young Researchers in Electrical and Electronic Engineering (EIConRus), Moscow, Russia, 29 January–1 February 2018; pp. 604–610. [Google Scholar]
  15. Menniti, D.; Pinnarelli, A.; Sorrentino, N. Coordinated control of phase shifters in multi-area power system to improve load-frequency dynamic performance. In Proceedings of the 16th IEEE Mediterranean Electrotechnical Conference, Yasmine Hammamet, Tunisia, 25–28 March 2012; pp. 241–244. [Google Scholar]
  16. Song, X.; Deng, J.; Xu, D. Generic model control for hybrid energy storage system in electric vehicles. In Proceedings of the IECON 2017—43rd Annual Conference of the IEEE Industrial Electronics Society, Beijing, China, 29 October–1 November 2017; pp. 7151–7156. [Google Scholar]
  17. Ma, M.; Liu, X.; Zhang, C. LFC for multi-area interconnected power system concerning wind turbines based on DMPC. IET Gener. Transm. Distrib. 2017, 11, 2689–2696. [Google Scholar] [CrossRef]
  18. Singhparmar, K.P. LFC system of multi-area interconnected power systems using TVAC-PSO based controller. Int. J. Comput. Appl. 2014, 88, 13–19. [Google Scholar]
  19. Pourmousavi, S.A.; Behrangrad, M.; Nehrir, M.H. LFC model for multi-area power systems considering dynamic demand response. In Proceedings of the IEEE/PES Transmission and Distribution Conference and Exposition, Dallas, TX, USA, 3–5 May 2016; pp. 1–5. [Google Scholar]
  20. Ma, M.; Zhang, C.; Liu, X. Distributed model predictive load frequency control of the multi-area power system after deregulation. IEEE Trans. Ind. Electron. 2017, 64, 5129–5139. [Google Scholar] [CrossRef]
  21. Shukla, R.R.; Patel, N.K. Effect of capacitive energy storage unit on frequency of interconnected multi-area power systems. In Proceedings of the 2018 Conference on Signal Processing and Communication Engineering Systems (SPACES), Vijayawada, India, 4–5 January 2018. [Google Scholar]
  22. Mufti, M.U.D.; Lone, S.A.; Iqbal, S.J. Super-capacitor based energy storage system for improved load frequency control. Electr. Power Syst. Res. 2009, 79, 226–233. [Google Scholar] [CrossRef]
  23. Farahani, M.; Ganjefar, S. Solving LFC problem in an interconnected power system using superconducting magnetic energy storage. Phys. C Supercond. Its Appl. 2013, 487, 60–66. [Google Scholar] [CrossRef]
  24. Holland, C.E.; Weidner, J.W.; Dougal, R.A.; White, R.E. Experimental characterization of hybrid power systems under pulse current loads. J. Power Sources 2002, 109, 32–37. [Google Scholar] [CrossRef]
  25. Khaligh, A.; Li, Z. Battery, ultracapacitor, fuel Cell, and hybrid energy storage systems for electric, hybrid electric, fuel cell, and plug-in hybrid electric vehicles: State of the art. IEEE Trans. Veh. Technol. 2010, 59, 2806–2814. [Google Scholar] [CrossRef]
  26. Zhang, G.; Tang, X.; Zhiping, Q.I. Application of hybrid energy storage system of super-capacitors and batteries in a microgrid. Autom. Electr. Power Syst. 2010, 299, R1013–R1039. [Google Scholar]
  27. Jiang, Q.; Hong, H. Wavelet-Based capacity configuration and coordinated control of hybrid energy storage system for smoothing out wind power fluctuations. IEEE Trans. Power Syst. 2013, 28, 1363–1372. [Google Scholar] [CrossRef]
  28. Duong, M.Q.; Nguyen, V.T.; Sava, G.N.; Scripcariu, M.; Mussetta, M. Design and simulation of PI-type control for the buck boost converter. In Proceedings of the 2017 International Conference on ENERGY and ENVIRONMENT (CIEM), Bucharest, Romania, 19–20 October 2017; pp. 79–82. [Google Scholar]
  29. Lukic, S.M.; Wirasingha, S.G.; Rodriguez, F. Power management of an ultra-capacitor/battery hybrid energy storage system in an HEV. In Proceedings of the 2006 IEEE Vehicle Power and Propulsion Conference, Windsor, UK, 6–8 September 2006; pp. 1–6. [Google Scholar]
  30. Choi, M.E.; Kim, S.W.; Seo, S.W. Energy management optimization in a battery/supercapacitor hybrid energy storage system. IEEE Trans. Smart Grid 2012, 3, 463–472. [Google Scholar] [CrossRef]
  31. Lei, H. H-infinity robust control of the suspension system for a bearingless motor of permanent magnet type. Control Theory Appl. 2008, 25, 711–716. [Google Scholar]
  32. Wang, Z.Y.; Zhen, Z.; Zhou, K.M. Dynamic hysteresis modeling and H-infinity robust control of piezoelectric actuators. Control Theory Appl. 2014. [Google Scholar] [CrossRef]
  33. Yang, M.; Li, Y.; Du, H. Hierarchical multi-objective H-infinity robust control design for wireless power transfer system using genetic algorithm. IEEE Trans. Control Syst. Technol. 2018, 1–9. [Google Scholar] [CrossRef]
  34. Padhan, D.G.; Majhi, S. A new control scheme for PID load frequency controller of single-area and multi-area power systems. ISA Trans. 2013, 52, 242–251. [Google Scholar] [CrossRef] [PubMed]
  35. Dullerud, G.E.; Paganini, F. A Course in Robust Control Theory; Springer: Berlin, Germany, 2000; Volume 36, p. B33. [Google Scholar]
Figure 1. Topological structure diagram of four-area interconnected power system.
Figure 1. Topological structure diagram of four-area interconnected power system.
Applsci 08 01748 g001
Figure 2. Linearization model structure of the system in ith control area.
Figure 2. Linearization model structure of the system in ith control area.
Applsci 08 01748 g002
Figure 3. Basic structure of the hybrid energy storage system.
Figure 3. Basic structure of the hybrid energy storage system.
Applsci 08 01748 g003
Figure 4. Power exchange between the HESS and power system.
Figure 4. Power exchange between the HESS and power system.
Applsci 08 01748 g004
Figure 5. Transfer function of reheat steam turbine in the ith control area.
Figure 5. Transfer function of reheat steam turbine in the ith control area.
Applsci 08 01748 g005
Figure 6. H robust state feedback control for the ith control area.
Figure 6. H robust state feedback control for the ith control area.
Applsci 08 01748 g006
Figure 7. The external load disturbance added to Control Area 1.
Figure 7. The external load disturbance added to Control Area 1.
Applsci 08 01748 g007
Figure 8. Control signals from controller of four areas in Case 3: (a) control signal u 1 ; (b) control signal u 2 ; (c) control signal u 3 ; and (d) control signal u 4 .
Figure 8. Control signals from controller of four areas in Case 3: (a) control signal u 1 ; (b) control signal u 2 ; (c) control signal u 3 ; and (d) control signal u 4 .
Applsci 08 01748 g008
Figure 9. Δ f i ( i = 1 , 2 , 3 , 4 ) of each power system under load disturbance in Case 3.
Figure 9. Δ f i ( i = 1 , 2 , 3 , 4 ) of each power system under load disturbance in Case 3.
Applsci 08 01748 g009
Figure 10. A C E i ( i = 1 , 2 , 3 , 4 ) of each control area under load disturbance in three different cases: (a) A C E 1 of Control Area 1; (b) A C E 2 of Control Area 2; (c) A C E 3 of Control Area 3; and (d) A C E 4 of Control Area 4.
Figure 10. A C E i ( i = 1 , 2 , 3 , 4 ) of each control area under load disturbance in three different cases: (a) A C E 1 of Control Area 1; (b) A C E 2 of Control Area 2; (c) A C E 3 of Control Area 3; and (d) A C E 4 of Control Area 4.
Applsci 08 01748 g010aApplsci 08 01748 g010b
Table 1. Parameters in Control Area 1 of the interconnected power system.
Table 1. Parameters in Control Area 1 of the interconnected power system.
T g i (s) T r i (s) T t i (s) R i (Hz/p.u.Mw) T 1 j ( j = 1 , 2 , 3 , 4 ) (s)
0.084.20.32.40.0707
K p 1 (s) T p 1 (s) c 1 β 1 (Hz/p.u.Mw) K A F 1
120200.350.4251.1
Table 2. Parameters of controller design for Control Area 1.
Table 2. Parameters of controller design for Control Area 1.
( i = 1 ) q i 1 q i 2 q i 3 q i 4 q i 5 q i 6 ρ 1 γ 1 2
Area 10.01250.010.0010.0050.0010.0130.090.86

Share and Cite

MDPI and ACS Style

Yan, W.; Sheng, L.; Xu, D.; Yang, W.; Liu, Q. H Robust Load Frequency Control for Multi-Area Interconnected Power System with Hybrid Energy Storage System. Appl. Sci. 2018, 8, 1748. https://doi.org/10.3390/app8101748

AMA Style

Yan W, Sheng L, Xu D, Yang W, Liu Q. H Robust Load Frequency Control for Multi-Area Interconnected Power System with Hybrid Energy Storage System. Applied Sciences. 2018; 8(10):1748. https://doi.org/10.3390/app8101748

Chicago/Turabian Style

Yan, Wenxu, Lina Sheng, Dezhi Xu, Weilin Yang, and Qian Liu. 2018. "H Robust Load Frequency Control for Multi-Area Interconnected Power System with Hybrid Energy Storage System" Applied Sciences 8, no. 10: 1748. https://doi.org/10.3390/app8101748

APA Style

Yan, W., Sheng, L., Xu, D., Yang, W., & Liu, Q. (2018). H Robust Load Frequency Control for Multi-Area Interconnected Power System with Hybrid Energy Storage System. Applied Sciences, 8(10), 1748. https://doi.org/10.3390/app8101748

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop