1. Introduction
The pressure tension testing method was originally developed by the Building Research Council as a new method of examining anisotropic loading conditions on materials [
1]. The pressure tension apparatus uses standard 100 mm × 200 mm concrete cylinders as samples. Concrete core samples can also be used. The size of the sample allows this test method to be adapted to common concrete testing procedures used in industry. The test uses a pressurized gas equally applied along the curved surface of the cylinder, with rubber O-rings at either end of the specimen to hold the gas between the testing chamber and the concrete cylindrical sample surface, as shown in
Figure 1. The two flat ends of the cylinder are left open to the atmosphere, which causes a net induced tension field to arise within the concrete sample parallel to the longitudinal axis of the cylinder. Komar [
2] devised and implemented a novel instrumentation system that allowed for fully automated control of the loading rate and variety of loading conditions, including ramped loading at different rates, cyclic loading, constant loading rate (such as creep), and controlled unloading. This study uses the method of cyclic loading.
In this test method, a tension field will be produced from a compressive load. It can be understood as a net effective stress which is consistent with principles first developed for soil mechanics [
3]. Concrete is a two-phase material with a solid phase consisting of the hydrated cementitious matrix and the aggregates, and a liquid phase consisting of the pore water. The different reactions of the two phases to a biaxial stress gives rise to the pressure tension effect: the liquid phase reacts in a hydrostatic manner, in contrast to the solid phase which reacts in the directions of the applied load. All the stresses in the plane of gas loading cancel each other out, with a net tension field arising along the axis of the cylinder [
4], which is shown in
Figure 2. The pressure tension apparatus uniformly increases the gas pressure applied to the concrete cylinder until the point where the solid phase of the specimen can no longer remain together, at which point the concrete cylinder breaks at the weakest plane along its length. The gas pressure at the moment of failure is taken as the ultimate tensile strength of the concrete.
Rashidi et al. [
5] conducted an experimental study to evaluate the strength of concrete subjected to Indirect Diametrical Tensile (IDT), Unconfined Compressive Strength (UCS) and submaximal modulus testing methods. Their experimental design involved the application of a specific strain rate of 1 mm/min on concrete specimens. IDT employs a controlled loading condition to split the cylinder into two half-cylinders. In contrast, the present experimental design uses gas pressure to achieve the same mode of failure.
Ultrasonic Pulse Velocity (UPV) provides information about the evolution of the pore space of concrete, for both hydration and changes due to durability issues. Komar [
2] used UPV to track the hydration process during curing; they found UPV could distinguish between different pore structures at early ages and could track the evolution of the pore structures over the curing period. UPV can be divided into three categories: Direct (sensors opposite to each other), indirect (adjacent sensors), and semi-direct (sensors at right angles) transmission. Ultrasonic waves have been used to predict and evaluate concrete strength and its properties in several studies [
6]. However, this method can also be used to detect the internal deficiencies of concrete such as cracks. In this experimental work, the UPV method is used to determine the presence of cracks in concrete after a low magnitude of tensile stress is applied. The UPV test is a measurement of the continuity of the solid part of the concrete through which the stress waves propagate, and it is well-suited for evaluating any changes to this solid structure due to ongoing deterioration. The test apparatus produces and applies a pulse into the concrete by means of a pulse transducer and receiver and encompasses the ability to accurately measure the amount of time the pulse takes to pass through the concrete.
2. Materials and Methods
A total of 22 standard concrete cylinders (100 mm × 200 mm) were cast and tested. The concrete used in the cylinders was made using the mix design shown in
Table 1. The specimens were molded and compacted based on ASTM C31 [
7]. After 24 h of curing in their molds, the cylinders were removed and stored in ambient laboratory conditions for over 2 years.
In a pressure-tension test, a destructive test method that specifically evaluates the tensile capacity of concrete, a cylindrical steel jacket is used to hold a concrete cylinder serving as the specimen. A rubber O-ring is used at each end to keep an airtight seal and prevent possible gas leakage. With the ends then left free, gas pressure is incrementally applied to the curved surface of the concrete cylinder until the specimen ultimately fractures across a single plane perpendicular to the axis of the concrete specimen. The value of gas pressure at fracture thus corresponds to the maximum tensile capacity of the concrete. Compressed air is used as the loading medium for all specimens in this experimental work. The air was pressurized using a portable air compressor with a maximum available pressure of about 17 MPa, which was stored in a pressurized gas vessel attached to the compressor and the testing machine. A variable check valve was used to keep the pressure head constant in order to minimize inconsistency in the test caused by pressure variance in the storage tank. A needle valve was used as the controller for the flow rate of the compressed gas into the testing chamber. The valve was operated by a mechanical actuator which was controlled using custom software and monitored using a digital acquisition device (DAQ). Measurement of pressure within the test chamber was obtained using a digital pressure transducer directly adjacent to the chamber, which was used as a control input in the software. The pressure transducer had a measured error of ±0.05 MPa. The DAQ had a sensing resolution of approximately 0.1 s [
2,
6]. All pressure-time plots were recorded and stored, and the data point immediately preceding failure was used as the failure load.
The implemented control algorithm is a modified proportional integral derivative function which automatically varies the valve position based on the detected error between the measured pressure and the set point. The set point is an arbitrary time-dependent function, and all tests carried out in this study used a uniformly increasing pressure-time signal with a rate of about 0.02 to 0.03 MPa/second, comparable to loading rates in both ASTM C 496 and ASTM C 33 [
6]. A higher rate of about 0.10 to 0.15 MPa/second was used during the cyclic loading of the specimens to expedite the process.
Rubber O-rings with a diameter of 10 mm were used to seal the interface between the test chamber and the concrete sample (
Figure 1). One or two layers of polyvinylchloride tape was applied on both ends of the cylinder to provide a better seal between the O-rings and the cylinder, which occasionally had voids or deterioration defects that could cause leakage around the O-rings. The O-rings were torqued with a series of six lug nuts bearing on a steel plate in a manner that applied equal pressure on them and ensured a tight seal for the loading gas.
Pressure tension testing is affected by the moisture content of the specimens; samples with a higher water content fail at a higher tensile resistance as compared to dry specimens [
2]. For dry samples, the failure mode in pressure tension testing changes from a single crack to a volumetric failure at a lower applied tensile stress [
2,
8].
Fatigue loading can be categorized into low-cycle and high-cycle loading. Low-cycle loading encompasses the introduction of a few high-stress load cycles such as the application of the earthquake loads on a structure. Conversely high-cyclic loading is categorized by the introduction of a large number of low-stress load cycles, such as the live load applications on the bridges and airport pavements.
The flexural test method is the most commonly used method for fatigue testing. Comparatively, compressive fatigue tests have been studied to a lesser extent. After the emergence of nonlinear fracture mechanics toward evaluating the performance of concrete, some researchers have shown interest in the fatigue characteristics of concrete in tension [
9,
10,
11]. Nevertheless, there are very limited studies available on the behavior of plain concrete under direct tension fatigue loading [
12,
13,
14,
15]. The challenges associated with direct tensile testing on concrete is also a primary reason for limited and often conflicting data availability.
Furthermore, non-destructive testing (NDT) was employed to evaluate the progressive damage inflicted by tensile loading on concrete cylinders using UPV apparatus. A Proceq TICO model of automatic UPV was used for this experimental study. Three measurements of transit times along the axis of the cylinder were recorded, and the average of these three values was noted. Length measurements from the cylinders (i.e., height of the concrete cylinder specimens) were used to convert the travel times into the UPV values reported. A commercially available water-based lubricant was used to ensure a good connection between the transmitter/receiver and the greatly variable surface of the concrete samples.
In this study, two piezoelectric sensors are placed at opposite ends of the test specimen (i.e., direct method). Electronic pulses are generated by one sensor, while the other sensor measures the time taken by the pulse to transmit through the concrete. Knowing the distance traveled (i.e., the height of the concrete cylinder specimen in this case), transmission velocity will be calculated based on the resultant value and the condition of the concrete may be determined.
4. Finite Element Modeling
ABAQUS FEA software, a commercially available finite-element analysis program, was used to model the concrete cylinder. The Concrete Damage Plasticity Model (CDPM) was used to define the parameters of the concrete—these parameters are computed using MATLAB toolbox [
16].
For concrete modeling, 3D 8-node Linear Isoparametric Elements with reduced integration (C3D8R) have been utilized. In order to model the gas pressure, two parts are defined; first a solid element with C3D8R features; and second the Eulerian type with EC3D8R (an 8-node linear Eulerian brick, reduced integration, hourglass control). It should be noted that the solid part covers both Eulerian and concrete cylinder.
Figure 8 displays the geometry of Finite Element Modeling (FEM).
The material properties for gas pressure (Eulerian Type) is considered to be Equation of State (EOS) with the type of Ideal Gas. The gas constant and ambient pressure are 278 × 10
8 mJ/(tonne K) and 0.101325 MPa, respectively. Also, Non-Linear Dynamic Explicit analysis is used for simulation. The contact behavior has both Tangential (frictionless) and Normal (hard contact) behaviors. The Discrete Field was converted to Volume Fraction Tools to make Eulerian part as pressure. The initial gas pressure is applied as Predefined Stress and gravity load. Also, the cyclic pressure is assigned based on the amplitude. The amplitude is displayed in
Figure 9 and the stress distribution in concrete cylinder is shown in
Figure 10.
When cyclic loading was applied at low pressure, the concrete sample did not fail in tension. Then, the maximum pressure in the cyclic loading was increased step-by-step in the FEM sample until the observation of fatigue failure after few cycles to simulate the low-cycle fatigue failure. Interestingly, the FEM sample failed after 13 cycles that is very similar to the experimental result of sample 17 (
Table 5). Also, the sample in FEM failed under a pressure that was lower than the maximum applied pressure in previous cycles. FEM and experimental results of specimen No. 17 are compared in
Figure 11.
5. Conclusions
A total of 22 standard concrete cylinders were tested under tension using a pressure-tension apparatus. Based on the limited number of test results reported in this paper, one can conclude that the tensile strength of the dry specimens was lower than that of the wet specimens with a lower coefficient of variation in the test results. Therefore, it will be safer and more reliable to test the specimens in dry conditions.
It was shown that failure in tension due to fatigue can happen as early as the second cycle of loading if the concrete specimen has been loaded up to a high percentage of its tensile capacity (most probably more than 62% of its tensile capacity).
ABAQUS FEA software was used to model the pressure-tension test. It was shown that the failure under low-cycle tensile force can be predicted using appropriate parameters in the software. It was also found that concrete specimens subjected to a low-cycle loading protocol always fail at a lower stress level compared to the maximum value applied in the previous cycles. This was the case for both the experimental results as well as the FEM. With respect to the quantification of the effects of fatigue on the performance of concrete, comparison of the experimental and FEM results illuminates the maximum stress before failure to be 7.7% higher in FEM. Additionally, the stress at failure was 23.0% higher in FEM compared to the experimental result.
NDT was also employed to evaluate the progressive damage inflicted by tensile load in concrete using the UPV apparatus. It was shown that the application of a tensile stress on a concrete affects its internal structure and causes an increase in travel times and a lower UPV measurement. The experimental results presented in this paper prove that the UPV method can be used effectively for the detection of cracks in hardened concrete subject to tensile stresses—as low as about 0.4 MPa.