Article

Monitoring PM2.5 at a Large Shopping Mall: A Case Study in Macao

by
Thomas M. T. Lei
1,*,
Yan W. I. Chan
1 and
Mohd Shahrul Mohd Nadzir
2
1
Institute of Science and Environment, University of Saint Joseph, Macau 999078, China
2
Department of Earth Sciences and Environment, Faculty of Science and Technology, Universiti Kebangsaan Malaysia, Bangi 43600, Selangor, Malaysia
*
Author to whom correspondence should be addressed.
Processes 2023, 11(3), 914; https://doi.org/10.3390/pr11030914
Submission received: 13 February 2023 / Revised: 4 March 2023 / Accepted: 10 March 2023 / Published: 17 March 2023
(This article belongs to the Special Issue Air Quality Monitoring for Smart Cities and Industrial Applications)

Abstract

:
Employees work long hours in an environment where the ambient air quality is poor, directly affecting their work efficiency. The concentration of particulate matters (PM) produced by the interior renovation of shopping malls has not received particular attention in Macao. Therefore, this study will investigate the indoor air quality (IAQ), in particular of PM2.5, in large-scale shopping mall renovation projects. This study collected on-site PM data with low-cost portable monitoring equipment placed temporarily at specific locations to examine whether the current control measures are appropriate and propose some improvements. Prior to this study, there were no measures being implemented, and on-site monitoring to assess the levels of PM2.5 concentrations was non-existent. The results show the highest level of PM2.5 recorded in this study was 559.00 μg/m3. Moreover, this study may provide a reference for decision-makers, management, construction teams, design consultant teams, and renovation teams of large-scale projects. In addition, the monitoring of IAQ can ensure a comfortable environment for employees and customers. This study concluded that the levels of PM2.5 concentration have no correlation with the number of on-site workers, but rather were largely influenced by the processes being performed on-site.

1. Introduction

According to the United Nation’s (UN) News, 55% of the world’s population lived in urban areas in 2018, estimated to rise to 68% by 2050 [1]. The high population density in urban areas is often associated with air pollution and carbon emission problems [2]. As urban populations and the number of motor vehicles simultaneously increase, and countries become more industrialized, air pollution becomes more and more of a serious problem. The urban population spends their time in the indoor environment every day. Indoor air pollution directly affects people’s health. Studies showed that more than 4.3 million deaths each year are caused by poor IAQ [3]. Poor indoor air can lead to human discomfort, health problems, and even disease. Poor IAQ also has a negative impact on work efficiency. Poor indoor air will make staff emotionally irritable and physically tired and can even cause disease epidemics. Macao is a highly urbanized region with a very high population density of 27,259 inhabitants/km2 [4], and the total population of Macao reached 683,200 inhabitants in 2021 [5]. Therefore, IAQ is a serious issue for a high-density environment such as Macao [6,7,8]. There have been many related technical studies as the impact of IAQ on health has attracted more and more attention. The current understanding of the synergistic and antagonistic effects of multiple pollutants at low concentrations for a long time is not comprehensive.
This work focuses on the IAQ of shopping malls in Macao with frequent renovation projects. These projects of different sizes are carried out in operating buildings. However, the emission of PM10 and PM2.5 in the indoor environment caused by interior decoration is not thoroughly evaluated. More importantly, people spend about 90% of their time in indoor buildings, such as in schools, offices, and shopping centers [9,10,11,12]. Therefore, having a comfortable living environment and good IAQ are important factors that affect human health and work efficiency. The outbreak of COVID-19 in recent years has led to adopting social distancing measures such as school closures and working from home [13]. This has led to an increase in indoor activities and the growing problem of indoor air pollution, which has different levels of impact on the human body, so providing a good IAQ environment can minimize health impacts and economic losses.
In recent years, many buildings in Macao have been undergoing renovation work which causes an increase in particulate matters (PM) in indoor building. For example, Sands China invested $470 million in Hong Kong Dollars (HKD) in renovation projects of their premises in 2021. The concessionaire has invested more than $100 billion HKD over the years [14]. Nevertheless, there was minimal attention to indoor PM2.5 emissions in numerous interior renovation projects. On-site operators are exposed to high concentrations of PM2.5 for extended periods of time. The health of operators may be affected by the polluted air in the buildings. The emission of indoor PM2.5 is a serious threat to human health.
The concept of IAQ was first proposed in the 1990s in Nordic Countries and North America, focusing on indoor air in non-production places, such as residences, offices, schools, hospitals, and hotels. Due to people who stayed indoors for a long time often feeling uncomfortable, new problems and concepts, such as SBS and Legionnaires’ disease, gradually emerged [15]. People also realized that indoor air pollution was closely related to different diseases, such as asthma and lung cancer. SBS is a condition in which people experience acute health or comfort-related effects within a poor indoor environment, and the complaint may be for a specific room, area, or entire building, and research found that symptoms subsided or disappeared when the environmental elements causing SBS were removed [16]. The symptoms of SBS include headaches, dizziness, nausea, eye, nose, or throat irritation, dry cough, dry or itchy skin, difficulty concentrating, fatigue, reduced sensitivity to smells, hoarseness, allergies, colds, flu-like symptoms, increased incidence of asthma attacks, and personality changes [17]. The cause of these symptoms is unclear, but most victims said their symptoms could be relieved by leaving the property [18].
Some possible main contributors to SBS include chemical pollutants, biological pollutants, insufficient ventilation, poor air circulation, psychological factors, insufficient and inappropriate lighting, and poor acoustics [19,20,21,22,23,24,25,26]. Symptoms of BRI include coughing, chest pains, shortness of breath with mild exertion, edemas, palpitations, nosebleeds, cancer, pregnancy problems, and miscarriages. In addition, extrinsic allergic alveolitis, Legionnaires’ disease, humidifier fever, pneumonia, and occupational asthma are also known to occur due to BRI [27]. A large amount of formaldehyde was released inside buildings during the renovation process, which led to many residents experiencing acute irritation and poisoning symptoms, and some even suffered toxic hepatitis or allergic purpura [28,29]. These studies discovered that volatile organic compounds (VOCs) have a high contribution to indoor pollution sources for human exposure.
Systematic studies around IAQ initially focused on the relationship between indoor and outdoor air quality and the impact of indoor air pollutants on human health. The world’s first systematic and large-scale study of the relationship between indoor and outdoor air quality was conducted in 1965 [30]. The study measured the relationship between indoor and outdoor SO2, smoke, and dust, determining the relatively safe levels of IAQ during air pollution episodes. The relationship between smoking and indoor aerosol generation, indoor SO2 attenuation, and building age was also explored. The results showed significant differences between indoor and outdoor air quality and that IAQ might have more of an impact on human health than outdoor air quality [31].
This work hopes to establish a comprehensive management system for pre-assessment and to discuss IAQ management from the aspects of building material management, architectural design management, and facility management and to manage and control the level of IAQ in public places and civic buildings. In addition, this work aims to explore the correlation between the number of workers and the levels of PM2.5 concentrations in the shopping mall. Prior to this study, there were no measures being implemented, and on-site monitoring to assess the levels of PM2.5 concentrations was non-existent on this specific premises, which is a very concerning situation for both the workers and visitors. This study is the first assessment of the relationships between the level of PM2.5 concentrations, number of workers, and the construction processes in a large shopping mall in Macau.

2. Materials and Methods

In recent years, the government has made great efforts to promote Macao as a “World Center of Tourism and Leisure.” Shopping malls of different sizes and themes, each with its own unique architectural style, were built, large complexes combining food, drink, and entertainment, providing one-stop diversified facilities and attracting many tourists and locals, especially during weekends and holidays. In this study, fixed-point measurement was carried out on-site using low-cost portable monitoring sensors. As of now, there are no specific indoor air quality (IAQ) guidelines established or being enforced in the indoor buildings of Macao. Therefore, the IAQ standard would be the same as the ambient air quality standard established by the Macao Meteorological and Geophysical Bureau (SMG), which adopted the WHO Interim Target 2 (IT-2) standard.
The collected data were obtained using TSI Sidepak AM510 Personal Aerosol Monitor calibrated to factory settings, temporarily set up in two monitored areas, consisting of 2 h of data collection during the peak periods of the day when most shopping mall employees worked in their respective areas. The duration of monitoring campaign lasted for 14 days in each area. The collected data showed that the levels of PM2.5 concentration were different between these three collection points in two monitored areas, including Construction Site A and B and Renovation Area. During the construction phase, the level of PM2.5 concentration reached its peak because many processes were being performed, and different operation processes produced different levels of PM2.5 concentration. The construction site had a suitable hoarding, forming a barrier between the construction and public areas. In comparison, the renovation site was adjacent to the public area, in which the area was small and also had a suitable hoarding to prevent customers from entering by mistake. The measurement points in each area were chosen for the following reasons:
The construction area was large, with collection points A and B being core areas with complicated processes and dense flows of people. For this study, the monitored construction site was located on the upper floor of a shopping mall, with an area of about 11,000 m2. Hence, it was important to monitor these locations for the IAQ of the mall. The demolition process caused the worst air pollution at the construction site, which generally emits a high concentration of PM2.5, followed by the grinding and the drilling installation tasks. Figure 1 shows the layout of the construction site.
The renovation area measurement point was chosen because the scope of the store renovation was relatively small, and the collection point was chosen in the center of the district. For this study, the monitored renovation area was about 200 m2 and located in the center of the shopping mall, near many shops and restaurants. Figure 2 shows the collection point of the public area next to the store renovation area, and the measurement point was where the public gathered. The collected data reflect the impact of IAQ on the public and study the impact of PM2.5 on the health of the operators. The peak levels of PM2.5 concentration during the refurbishment were recorded during the cement-sand task when the cement and sand were mixed. The second highest levels recorded were during the grinding process, with a large amount of PM2.5 emitted during the grinding of ceiling surface defects.
The public area of the shopping mall is where customers gather for a short period of time. Customers may go to the stores or restaurants through the high-traffic corridor, which is very congested during public holidays and festivals. As shown in Figure 3, the collection point was located in a densely populated area. This study monitored the public area near the renovation area and collected the PM levels.
As part of this study, a survey on dust prevention measures was conducted. All 29 surveys received were completed by working professionals who applied at least one dust control measure in their working environment. The survey was voluntary and designed to allow the participants multiple answers to each question.

3. Results and Discussion

This section will discuss the levels of PM2.5 concentrations during the 14-day monitoring campaign in the construction and renovation areas, with the public area being the control of this study. This section also explores the correlation between the number of workers and the observed values for PM2.5 concentration in different locations, and the correlation between the levels of PM2.5 concentrations and the meteorological parameters such as temperature and humidity. A previous study shows that each construction activity demonstrates different pattern and level of PM2.5 concentration, and exposure to high concentration of PM2.5 has caused impairment of lung function performance and led to respiratory health problems [32]. In addition, the construction site needs to control and monitor its emission of PM2.5 with a proper construction time management schedule on site [33].

3.1. Construction Area

Figure 4 shows that the level of PM2.5 concentration at the construction site of collection point A was significantly higher at 307.00 μg/m3 on day 8 due to the spray-painting work. The level of PM2.5 concentration at collection point B was significantly higher at 332.00 μg/m3 on day 11 due to the drilling work. Painting and drilling work produce high levels of PM2.5 concentration, so it is necessary to check whether the control measures on-site are sufficient. It is necessary to improve the personal protective equipment (PPE) of the on-site personnel, such as by wearing N95 filter masks.
As shown in Table 1, descriptive statistics were obtained for the mean, median mode, minimum, and maximum concentration of PM2.5. Point B has a higher mean value for PM2.5 compared to point A at the construction site due to the demolition and drilling work. Since there are many elderly people and children in the shopping malls, the use of a blower fan is recommended to manage PM2.5 inside the shopping malls.

3.2. Renovation Area

Figure 5 shows the extremely high level of PM2.5 concentration from days 7 to 9 because of the cement-sand mixing task, with day 7 reaching a peak of 559 μg/m3. After the mixing task was completed, the level of PM2.5 concentration slowly dropped to a more reasonable level.
The data collected on site showed no significant relationship between the number of workers and the level of PM2.5 concentration. The high level of PM2.5 concentration was recorded during special tasks, such as cement-sand mixing, drilling, and demolition work. The collected data showed the high levels of PM2.5 concentration produced during these special tasks. Thus, corresponding control measures should be developed to reduce the high levels of PM2.5 concentration.
Table 2 shows a descriptive analysis of the renovation area. The level of PM2.5 concentration at the renovation site has a high peak, exceeding the levels in the construction area. The high PM2.5 levels were caused by the cement-sand mixing task. Thus, the use of cement slurry mixers should be adopted by the shopping mall, and protective measures should be taken in advance. Hence, it is clear that the shopping mall staff should consider each renovation carefully to ensure a safe level of IAQ is guaranteed.

3.3. Public Area

Figure 6 shows the levels of PM2.5 concentration in the public area, which is also the control of this study. The results show the levels of PM2.5 concentration to be significantly lower than in the construction and renovation area, with the peak levels being measured at only 37 μg/m3 on day 1.
Table 3 shows a descriptive analysis of the public area. The level of PM2.5 concentration at the public area has a mean of 20.14 μg/m3, which is well below the levels measured in the construction and renovation area. This shows that the processes being performed in the construction and renovation area have led to a burst of PM2.5 in a short period of time, causing a health hazard to the on-site personnel.
Figure 7 shows a cement slurry mixer commonly found in the construction industry and is used to mix cement and water into a uniform slurry, which can lower the emission of PM2.5 in a construction environment.

3.4. Correlation between Workers and PM2.5 Concentrations

According to Table 4, the correlation coefficient (r) between point A and point B is very low (r = 0.10). Thus, there is no correlation between these two collection points. Nevertheless, the number of workers and PM2.5 concentration in point A has a low-to-medium correlation (r = 0.38), and the number of workers and PM2.5 concentration in point B has a medium-to-high correlation (r = 0.51). Overall, the correlation between the levels of PM2.5 and the number of workers in the construction area (r = 0.38 to 0.51) is too low to show any relationship between them.
As shown in Table 5, the number of workers and PM2.5 concentration in the renovation area shows a low correlation (r = 0.11), which show there is no relationship between the levels of PM2.5 and the number of workers in the renovation area.
As shown in Table 6, the average temperature and relative humidity during the 14 days of the monitoring campaign are 21.9 °C and 50.1%, respectively.
As shown in Table 7, the correlation coefficient between the levels of PM2.5 concentration in the construction area A and B and the temperature is low (r = 0.23 to 0.50) and the humidity is very low (r = −0.17 to 0.24). The correlation coefficient between the levels of PM2.5 concentration in the renovation area and the temperature is medium (r = 0.55) and the humidity is low (r = 0.17). The correlation coefficient between the levels of PM2.5 concentration in the public area and the temperature is medium (r = 0.52) and the humidity is medium (r = −0.55). Overall, there is a low-to-medium correlation between the meteorological parameters and the levels of PM2.5 concentrations in all areas.
Hence, the use of prefabricated cement parts and structures constructed in the factory and only brought on-site for installation is recommended. In addition, optimizing work team structures and introducing robots for certain tasks will help to minimize human exposure to PM2.5 generated by cement-sand mixing tasks. Additionally, it is recommended that there should be fewer workers for demolition work, which could reduce threats to workers’ health due to poor IAQ. The shopping mall may consider optimizing the work team structure and even introduce robots to replace some manual labor.

3.5. On-Site Survey

As shown in Figure 8, 75.9% of the respondents believed that watering and spraying were the best control measures due to the relatively low cost of the humidification and dust reduction equipment and the smaller portable machines needed for this. Over 72.4% of respondents believed blower fans to be effective measures, with the advantages of relatively low cost, lightness, and flexibility of use. Furthermore, only 62.1%, and 37.9% of respondents believed water curtains and water mist blowers to be effective due to their large size and inability to be moved freely. Other measures, such as dust filters and curtain separators, were the least popular, only selected by 17.2% of the respondents. According to the survey results, preventing dust at the source is the most effective mitigation method.

4. Conclusions

IAQ is very important to the health of operators and ensuring good IAQ in these environments will minimize human and economic losses. The highest level of PM2.5 concentration recorded in this study was 559.00 μg/m3 in the renovation area, which is extremely hazardous even for short-term exposure and poses great threats to the health of the on-site personnel. The correlation between the number of workers and the levels of PM2.5 concentrations in different areas is low-to-medium (r = 0.11 to 0.51). In addition, the correlation between the meteorological parameters and levels of PM2.5 in different areas is low to medium (r = −0.55 to 0.55). Thus, it can be concluded that the number of workers and meteorological parameters have no direct influence on the levels of PM2.5 concentrations, but rather the processes being performed on-site is the most important factor that influences the levels of PM2.5 concentrations in the shopping mall. After the conclusion of this study, it has become a requirement to install an IAQ monitoring system on-site to monitor the level of real-time PM2.5 concentration in the construction and renovation area of the shopping mall. Further studies may be conducted to monitor different pollutants presented in the indoor environment. In addition, it is recommended that the local authorities establish an occupational safety standard for the levels of PM2.5 concentration in an indoor construction environment to protect the well-being of the on-site personnel and to serve as a reference for the construction management team.

Author Contributions

Conceptualization, T.M.T.L. and Y.W.I.C.; methodology, T.M.T.L.; software, T.M.T.L. and Y.W.I.C.; validation, T.M.T.L. and M.S.M.N.; data curation, T.M.T.L. and Y.W.I.C.; writing—original draft preparation, T.M.T.L. and Y.W.I.C.; writing—review and editing, T.M.T.L. and M.S.M.N.; supervision, T.M.T.L.; funding acquisition, T.M.T.L. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

3rd Party Data. Restrictions apply to availability of these data.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. UN. 68% of the world population projected to live in urban areas by 2050. United Nations News, 16 May 2018; pp. 2–5. [Google Scholar]
  2. Liu, H.; Cui, W.; Zhang, M. Exploring the causal relationship between urbanization and air pollution: Evidence from China. Sustain. Cities Soc. 2022, 80, 103783. [Google Scholar] [CrossRef]
  3. Raju, S.; Siddharthan, T.; McCormack, M.C. Indoor Air Pollution and Respiratory Health. Clin. Chest Med. 2020, 41, 825–843. [Google Scholar] [CrossRef]
  4. Szmigiera, M. Cities with the Highest Population Density Globally. 2021. Available online: https://www.statista.com/statistics/1237290/cities-highest-population-density/: (accessed on 1 November 2022).
  5. DSEC. Demographic Statistics. 2021. Available online: https://www.dsec.gov.mo/en-US/Statistic?id=101: (accessed on 1 November 2022).
  6. DSPA. Guidelines for Indoor Air Quality of General Public Places in Macau. 2022. Available online: https://www.dspa.gov.mo/pdf/GuideIndoorAir_tc.pdf: (accessed on 1 November 2022).
  7. SMG. Definition of Air Quality Index. 2021. Available online: https://www.smg.gov.mo/en/subpage/784/page/347: (accessed on 1 November 2022).
  8. Air Quality Guidelines. 2021. Available online: https://apps.who.int/iris/bitstream/handle/10665/345329/9789240034228-eng.pdf?sequence=1&isAllowed=y: (accessed on 1 November 2022).
  9. EPA. Indoor Air Quality. 2021. Available online: https://www.epa.gov/report-environment/indoor-air-quality: (accessed on 1 November 2022).
  10. Boxer, P.A. Indoor Air Quality A Psychosocial Perspective. J. Occup. Med. Toxicol. 1990, 32, 425–428. [Google Scholar] [CrossRef] [PubMed]
  11. Gulgun, D.; Cemile, D. Determination of Indoor Air Quality in University Student Canteens. Sak. Univ. J. Sci. 2021, 25, 1322–1331. [Google Scholar]
  12. Payus, C.; Carmen, C. Indoor air quality at shopping malls in Kota Kinabalu, Sabah (particulate matter and ozone). Ann. Trop. Med. Public Health 2017, 10, 31–35. [Google Scholar] [CrossRef]
  13. Barbour, N.; Menon, N.; Mannering, F. A statistical assessment of work-from-home participation during different stages of the COVID-19 pandemic. Transp. Res. Interdiscip. Perspect. 2021, 11, 100441. [Google Scholar] [CrossRef]
  14. Sands China. 2021 Annual Report. 2021. Available online: https://investor.sandschina.com/system/files-encrypted/nasdaq_kms/assets/2022/03/24/17-13-14/20220324%281%29_Annual%20Report.pdf: (accessed on 1 November 2022).
  15. Saini, J.; Dutta, M.; Marques, G. A comprehensive review on indoor air quality monitoring systems for enhanced public health. Sustain. Environ. Res. 2020, 30, 6. [Google Scholar] [CrossRef] [Green Version]
  16. EPA. Indoor Air Facts No. 4 Sick Building Syndrome. EPA—Air Radiat. (6609J) Res. Dev. (MD-56) 1991, 1–4. Available online: https://www.epa.gov/sites/default/files/2014-08/documents/sick_building_factsheet.pdf (accessed on 9 March 2023).
  17. Sarkingobir, Y.; Muhammadzayyanu, M.; Sarkingobir, S. Sick Building Syndrome: A Review of Related Literatures. Int. J. Med. Biosci. 2017, 1, 1. [Google Scholar]
  18. Joshi, S.M. The sick building syndrome. Indian J. Occup. Environ. Med. 2008, 12, 61. [Google Scholar] [CrossRef]
  19. IARC. IARC Monographs on the Evaluation of Carcinogenic Risks to Humans; World Health Organization International Agency for Research on Cancer: Lyon, France, 2006; Volume 88. [Google Scholar]
  20. Zhang, Q.; Gangupomu, R.H.; Ramirez, D.; Zhu, Y. Measurement of ultrafine particles and other air pollutants emitted by cooking activities. Int. J. Environ. Res. Public Health 2010, 7, 1744–1759. [Google Scholar] [CrossRef]
  21. Marvel, J.; Tronville, P. Ultrafine particles: A review about their health effects, presence, generation, and measurement in indoor environments. Build. Environ. 2022, 216, 108992. [Google Scholar] [CrossRef]
  22. Hospodsky, D.; Qian, J.; Nazaroff, W.W.; Yamamoto, N.; Bibby, K.; Rismani-Yazdi, H.; Peccia, J. Human occupancy as a source of indoor airborne bacteria. PLoS ONE 2012, 7, 4. [Google Scholar] [CrossRef] [Green Version]
  23. Luongo, J.C.; Fennelly, K.P.; Keen, J.A.; Zhai, Z.J.; Jones, B.W.; Miller, S.L. Role of mechanical ventilation in the airborne transmission of infectious agents in buildings. Indoor Air 2016, 26, 666–678. [Google Scholar] [CrossRef]
  24. Piscitelli, P.; Miani, A.; Setti, L.; DeGennaro, G.; Rodo, X.; Artinano, B.; Vara, E.; Rancan, L.; Arias, J.; Passarini, F.; et al. The role of outdoor and indoor air quality in the spread of SARS-CoV-2: Overview and recommendations by the research group on COVID-19 and particulate matter (RESCOP commission). Environ. Res. 2022, 211, 113038. [Google Scholar] [CrossRef]
  25. Power, M.C.; Kioumourtzoglou, M.A.; Hart, J.E.; Okereke, O.I.; Laden, F.; Weisskopf, M.G. The relation between past exposure to fine particulate air pollution and prevalent anxiety: Observational cohort study. BMJ 2015, 350, h1111. [Google Scholar] [CrossRef] [Green Version]
  26. Alhorr, Y.; Arif, M.; Katafygiotou, M.; Mazroei, A.; Kaushik, A.; Elsarrag, E. Impact of indoor environmental quality on occupant well-being and comfort: A review of the literature. Int. J. Sustain. Built Environ. 2016, 5, 1–11. [Google Scholar] [CrossRef]
  27. Crook, B. Legionella risk in evaporative cooling systems and underlying causes of associated breaches in health and safety compliance. Int. J. Hyg. Environ. Health 2020, 224, 113425. [Google Scholar] [CrossRef]
  28. Gallego, E.; Roca, X.; Perales, J.F.; Guardino, X. Determining indoor air quality and identifying the origin of odour episodes in indoor environments. J. Environ. Sci. 2009, 21, 333–339. [Google Scholar] [CrossRef]
  29. Scott, P.; Dan, C.; Paul, F.; Beth, H.; Terry, B. Weatherization and Indoor Air Quality: Measured Impacts in Single-Family Homes under the Weatherization Assistance Program; Oak Ridge National Laboratory: Oak Ridge, TN, USA, 2014. [Google Scholar]
  30. Zahaba, M.; Sarah Fatihah Tamsi, N.; Engliman, S.; Faiz Kamaruddin, A.; Artika Hassan, N.; Ariffin, A. Indoor air quality (IAQ) in a naval ship after refit program: A time variation analysis. IOP Conf. Ser. Earth Environ. Sci. 2022, 1013, 012004. [Google Scholar] [CrossRef]
  31. Otuyo, M.K.; Nadzir, M.S.M.; Latif, M.T.; Saw, L.H. In-train particulate matter (PM10 and PM2.5) concentrations: Level, source, composition, mitigation measures and health risk effect—A systematic literature review. Indoor Built Environ. 2022, 32, 460–493. [Google Scholar] [CrossRef]
  32. Rahman, S.A.A.; Yatim, S.R.M.; Abdullah, A.H.; Zainuddin, N.A.; Samah, M.A.A. Exposure of Particulate Matter 2.5 (PM2.5) on Lung Function Performance of Construction Workers. AIP Conf. Proc. 2019, 2124, 020030. [Google Scholar]
  33. Rosman, P.S.; Samah, M.A.A.; Yunus, K.; Hussain, M.R.M. Particulate Matter (PM2.5) At Construction Site: A Review. Int. J. Recent Technol. Eng. (IJRTE) 2019, 8, 255–259. [Google Scholar]
Figure 1. Layout of the construction site.
Figure 1. Layout of the construction site.
Processes 11 00914 g001
Figure 2. Layout of the renovation area.
Figure 2. Layout of the renovation area.
Processes 11 00914 g002
Figure 3. Layout of public area.
Figure 3. Layout of public area.
Processes 11 00914 g003
Figure 4. The levels of PM2.5 concentration and the number of workers at a construction area throughout a 14-day monitoring campaign in a large shopping mall.
Figure 4. The levels of PM2.5 concentration and the number of workers at a construction area throughout a 14-day monitoring campaign in a large shopping mall.
Processes 11 00914 g004
Figure 5. The levels of PM2.5 concentration and the number of workers in the renovation area throughout a 14-day monitoring campaign in a large shopping mall.
Figure 5. The levels of PM2.5 concentration and the number of workers in the renovation area throughout a 14-day monitoring campaign in a large shopping mall.
Processes 11 00914 g005
Figure 6. The levels of PM2.5 concentration in the public area throughout a 14-day monitoring campaign in a large shopping mall.
Figure 6. The levels of PM2.5 concentration in the public area throughout a 14-day monitoring campaign in a large shopping mall.
Processes 11 00914 g006
Figure 7. Wet cement sand mixing for building a brick wall at a renovation site.
Figure 7. Wet cement sand mixing for building a brick wall at a renovation site.
Processes 11 00914 g007
Figure 8. Response from the survey on dust control measures (multiple answers).
Figure 8. Response from the survey on dust control measures (multiple answers).
Processes 11 00914 g008
Table 1. Descriptive statistics for PM2.5 concentration at the construction site (in μg/m3).
Table 1. Descriptive statistics for PM2.5 concentration at the construction site (in μg/m3).
PM2.5—Construction Point APM2.5—Construction Point B
Mean137.86Mean145.57
Median134.00Median133.00
Mode85.00Mode110.00
Minimum32.00Min85.00
Maximum307.00Maximum332.00
Table 2. Descriptive statistics for PM2.5 in the renovation area (in μg/m3).
Table 2. Descriptive statistics for PM2.5 in the renovation area (in μg/m3).
PM2.5—Renovation Area
Mean265.36
Median213.50
ModeN/A
Minimum63.00
Maximum559.00
Table 3. Descriptive statistics for PM2.5 in the public area (in μg/m3).
Table 3. Descriptive statistics for PM2.5 in the public area (in μg/m3).
PM2.5—Public Area
Mean20.14
Median19.50
Mode19.00
Min10.00
Maximum37.00
Table 4. Correlation coefficient (r) between PM2.5 and workers in Point A and B of the construction area.
Table 4. Correlation coefficient (r) between PM2.5 and workers in Point A and B of the construction area.
PM2.5Construction Point AConstruction Point BWorkers
Construction Point A1.00
Construction Point B0.101.00
Workers0.380.511.00
Table 5. Correlation coefficient (r) between PM2.5 and workers in the renovation area.
Table 5. Correlation coefficient (r) between PM2.5 and workers in the renovation area.
PM2.5Renovation AreaWorkers
Renovation area1.00
Workers0.111.00
Table 6. Temperature and humidity during the 14-day monitoring campaign.
Table 6. Temperature and humidity during the 14-day monitoring campaign.
DayTemperature (°C) Humidity (%)
121.747.1
221.347.5
322.051.3
422.554.4
521.950.9
621.848.8
722.548.5
822.453.5
922.552.0
1022.051.4
1121.048.0
1221.547.5
1321.047.0
1422.054.0
Table 7. Correlation coefficient (r) between meteorological parameters and PM2.5 concentrations in different areas.
Table 7. Correlation coefficient (r) between meteorological parameters and PM2.5 concentrations in different areas.
Temperature (°C)Humidity (%)Construction Area AConstruction Area BRenovation AreaPublic Area
Temperature (°C)1
Humidity (%)0.7227249451
Construction Area A0.2338828080.24118581
Construction Area B−0.504839483−0.1705422720.0951821851
Renovation Area0.5484305740.1714888690.62435975−0.0416936771
Public Area−0.518369199−0.545497874−0.4370816890.322059792−0.2939916771
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Lei, T.M.T.; Chan, Y.W.I.; Mohd Nadzir, M.S. Monitoring PM2.5 at a Large Shopping Mall: A Case Study in Macao. Processes 2023, 11, 914. https://doi.org/10.3390/pr11030914

AMA Style

Lei TMT, Chan YWI, Mohd Nadzir MS. Monitoring PM2.5 at a Large Shopping Mall: A Case Study in Macao. Processes. 2023; 11(3):914. https://doi.org/10.3390/pr11030914

Chicago/Turabian Style

Lei, Thomas M. T., Yan W. I. Chan, and Mohd Shahrul Mohd Nadzir. 2023. "Monitoring PM2.5 at a Large Shopping Mall: A Case Study in Macao" Processes 11, no. 3: 914. https://doi.org/10.3390/pr11030914

APA Style

Lei, T. M. T., Chan, Y. W. I., & Mohd Nadzir, M. S. (2023). Monitoring PM2.5 at a Large Shopping Mall: A Case Study in Macao. Processes, 11(3), 914. https://doi.org/10.3390/pr11030914