Enhancing Coordination Efficiency with Fuzzy Monte Carlo Uncertainty Analysis for Dual-Setting Directional Overcurrent Relays Amid Distributed Generation

Department of Electrical Engineering, Yildiz Technical University, Istanbul 34220, Turkey
*
Author to whom correspondence should be addressed.
Sensors 2024, 24(13), 4109; https://doi.org/10.3390/s24134109
Submission received: 24 May 2024 / Revised: 18 June 2024 / Accepted: 21 June 2024 / Published: 25 June 2024
(This article belongs to the Topic Power System Protection)

Abstract

:
In the contemporary context of power network protection, acknowledging uncertainties in safeguarding recent power networks integrated with distributed generation (DG) is imperative to uphold the dependability, security, and efficiency of the grid amid the escalating integration of renewable energy sources and evolving operational conditions. This study delves into the optimization of relay settings within distribution networks, presenting a novel approach aimed at augmenting coordination while accounting for the dynamic presence of DG resources and the uncertainties inherent in their generation outputs and load consumption—factors previously overlooked in existing research. Departing from conventional methodologies, the study proposes a dual-setting characteristic for directional overcurrent relays (DOCRs). Initially, a meticulous modeling of a power network featuring distributed generation is undertaken, integrating Weibull probability functions for each resource to capture their probabilistic behavior. Subsequently, the second stage employs the fuzzy Monte Carlo method to address generation and consumption uncertainties. The optimization conundrum is addressed using the ant lion optimizer (ALO) algorithm in the MATLAB environment. This thorough analysis was conducted on IEEE 14-bus and IEEE 30-bus power distribution systems, showcasing a notable reduction in the total DOCR operating time compared to conventional characteristics. The proposed characteristic not only achieves resilient coordination across a spectrum of uncertainties in both distributed generation outputs and load consumption, but also strengthens the resilience of distribution networks overall.

1. Introduction

1.1. Importance

In the dynamic realm of power distribution systems, the integration of distributed generation resources presents a distinctive array of hurdles in ensuring the dependable and effective protection of power networks. Coordinating directional overcurrent relays (DOCRs) become increasingly intricate when faced with uncertainties arising from both distributed generation (DG) outputs and load consumption patterns. Conventionally, relay configurations have been established without considering the dynamic presence of DG sources or fluctuations in their performance, thereby constraining the adaptability of the distribution networks. Traditional DOCRs are typically set to trigger at a fixed current level and direction, predicated on predetermined settings that are primarily suited to standard operating conditions. Nevertheless, the increasing incorporation of DG into power systems has introduced new challenges for protection and coordination. DG sources such as solar and wind power, exhibit variability in their output due to factors such as weather conditions and fluctuations in demand. This variability can result in shifts in fault currents and locations within the power system, complicating the maintenance of effective coordination using conventional single-setting DOCRs. To address these challenges, recent research has concentrated on the development of dual-setting DOCRs, which provide greater flexibility and adaptability in coordinating protection schemes in the presence of DG. Dual-setting relays enable a single relay to function in both the forward/primary and reverse/backup directions, simultaneously. This innovative programming approach augments relay operation efficiency by reducing the total relay tripping time. In light of these advancements, the following section presents a literature review encompassing recent modern research in this area.

1.2. Literature Review

Traditional directional overcurrent relays (DOCRs) have long been the cornerstone of power system protection strategies, offering fixed parameters for pickup currents, time delays, and directional features. However, as power systems undergo transformations with the integration of distributed generation (DG) and encounter heightened uncertainties, the shortcomings of single-setting relays have become apparent. Early investigations into traditional DOCRs primarily focused on optimizing relay configurations for coordination and fault detection under stable operational conditions. Pioneering research [1,2,3,4,5] underscored the significance of precisely configuring relay parameters to ensure efficient coordination and mitigate the risk of erroneous operations. Similarly, other studies [6,7] shed light on the complexities of coordinating protection schemes in systems with extensive DG penetration, proposing heuristic-driven methodologies to bolster coordination reliability. However, these endeavors have yet to present a comprehensive framework for modeling uncertainties in distribution power networks. As power systems transition towards more decentralized and dynamic architectures, the necessity for adaptive protection schemes becomes paramount [8]. Dual-setting DOCRs have emerged as a promising solution for addressing the limitations of single-setting relays and enhancing protection coordination in modern power systems [9]. These dual-setting relays offer flexibility to independently adjust the pickup currents and time delays for each directional setting, thereby enabling improved fault detection and discrimination across various operating scenarios [10]. Recent advancements in dual-setting DOCRs have been spurred by the incorporation of advanced optimization techniques and uncertainty analysis. Several studies [11,12,13] introduced optimization algorithms tailored for dual-setting relays, leveraging methodologies such as genetic algorithms and particle swarm optimization to identify optimal relay settings while considering system constraints and coordination requisites. These methodologies demonstrate enhanced coordination capabilities. In addition, a scheme based on the overcurrent theory using a supervisory system with communication capabilities was developed to re-evaluate the coordination for every topological change in the power system [14]. Furthermore, the behavior of overcurrent relays was studied, concentrating on operating speed and relay selectivity to ensure proper coordination of the protection system [15]. Alternatively, the manta ray foraging optimization approach was utilized to enhance overcurrent relay (OCR) configurations and maintain coordination tolerances within relay pairs [16], while simulated annealing–linear programming was used to obtain optimal OCR coordination [1]. Moreover, a comprehensive analysis of the selectivity challenges in OCR design based on statistical data was carried out [17]. Furthermore, the tripping characteristics of OCR relays, both standard and non-standard, were investigated using the tug-of-war optimization algorithm and the charged system search algorithm [18]. Consequently, to address the increased short-circuit currents arising from DG integration, an online communication system with multi-setting relays developed from offline experiments was incorporated [19]. In addition, a protective system based on communication linkages between OCRs with ideal standard features placed on both sides of the distribution lines and protection zones was suggested [20]. Furthermore, modern numerical relays with multifunctional data storage, communication, and signal processing functions were used to optimize relay settings while considering the various operational scenarios related to DG resources. An advanced two-level algorithm intended to optimize protective relay parameters by integrating various operating scenarios within communication systems was also introduced [21]. In another study, relay working times were determined using only the local voltage magnitude [22]. In a further study, a novel OCR-based area protection scheme designed especially for distribution networks with significant DG source penetration was proposed [23]. Additionally, wind speed and direction predictions were employed to facilitate online relay settings, initially determined offline using optimization techniques [24]. Furthermore, a unique non-communication-based time–current–voltage dual-setting directional overcurrent prevention strategy designed specifically for distribution systems with DG integration was also introduced [25]. The sine–cosine technique was used to overcome optimal coordination issues associated with directional OCRs [26]. In a further work, network topology groups and ideal relay settings were discussed concurrently [27]. Furthermore, support vector machines were used as a classifier to establish predefined trip times for OCRs [28]. Moreover, a multi-agent system-based hierarchical protection approach was used to provide a comprehensive protection strategy, with higher levels of updated relay settings and lower ones concentrating on fault clearance and protection coordination [29]. Ultimately, to increase the versatility of protection methods, user-defined dual-setting OCRs with hybrid time current-voltage characteristics were designed [30]. Numerous studies have investigated the protection of optimized microgrids (MGs) and smart grids (SGs), such as those referenced in [31,32]. However, their focus was primarily on the foundational network configuration and selectivity constraints. This myopic approach risks selectivity constraints that breach alternate topologies. Moreover, the absence of a comprehensive modeling strategy for uncertainties poses significant challenges in real-world applications. In light of these limitations, some scholars, as exemplified in [33,34], have explored protection coordination across diverse grid configurations, while protecting MGs/SGs with a singular setting group sans additional communication infrastructure for various configurations. However, while this is convenient and practical, it may impede protection speed due to multifarious constraints and a restricted search space for DOCRs. Entering the concept of adaptive protection is a pragmatic avenue to address concerns in MG/SG protection across varying operating conditions and topologies. Nonetheless, the implementation of adaptive protection systems necessitates extensive telecommunication links and introduces uncertainty into their operations [34]. However, dependable communication-aided adaptive schemes have significant advantages. Numerous research endeavors have scrutinized adaptive protective schemes for SGs/MGs. For instance, the authors of [35] introduced an adaptive and robust protection mechanism that accounts for the power quality characteristics and voltage indicators. Similarly, the authors of [36] reported adaptive protection considering the stability constraints of distributed generations (DGs), whereas [37] focused on reducing coordination optimization constraints. However, it is crucial to optimize the current and time settings of OCRs while overlooking optimization of the characteristic curves. This oversight, coupled with the absence of a comprehensive method to address uncertainties, renders these methods practical, yet potentially less efficient in real-world scenarios. In active distribution networks (ADNs), SGs, and MGs, uncertainties stemming from load and generation units can lead to protection miscoordination. To address this challenge, a study [38] proposed clustering different network topologies into a limited set, facilitating the determination of optimal relay settings for each cluster. This approach, simultaneously tackles setting groups and optimal network topology clusters, while also investigating the impact of relay characteristics on reducing operating times. Despite these advancements, the number of available setting groups remains significantly lower than the number of potential configurations, limiting multiple-setting group-based protective schemes to a handful of topologies and operation modes. In [39], a pioneering setting-group-based scheme for protecting networked MGs employing DOCRs was introduced. This scheme ensures adequate protection across all MGs under various interconnections with the utility grid. However, while [39] offers a model for categorizing MG interconnections into distinct groups and determining optimal relay settings, it falls short in accommodating diverse states of uncertainties in the protection scheme. However, these studies have yet to present a practical and comprehensive scheme for modeling uncertainties in protection settings, which could potentially impact the performance and reliability compared to traditional methods. Reference [40] introduced a methodology aimed at addressing uncertainty in demands and DGs within distribution systems through Monte Carlo simulation, a statistical technique that generates multiple random samples of uncertain parameters to analyze system behavior and understand the impacts of uncertainties on system performance. However, the neglect of the fuzzification of relay inputs in this research raises concerns about the efficiency and accuracy of the proposed scheme. The incorporation of uncertainty analysis using fuzzy Monte Carlo techniques has further bolstered the capabilities of dual-setting DOCRs to mitigate uncertainties stemming from DG integration and load variations, aspects overlooked in previous state-of-the-art research. Although significant strides have been made in the development and application of dual-setting DOCRs, challenges persist, including the lack of standardized methodologies for relay parameter optimization and coordination algorithms. Future research endeavors should prioritize addressing these challenges to propel power system protection toward meet the evolving requirements of modern power systems.

1.3. Contribution

The integration of dual-Setting directional overcurrent relays (DOCRs) with uncertainty analysis introduces a pioneering methodology that seamlessly merges DOCRs with uncertainty modeling utilizing fuzzy Monte Carlo methods, which incorporates fuzzy Monte Carlo simulation to effectively model and address uncertainties stemming from factors such as load variations, intermittent renewable energy generation, and equipment failures. By doing so, it enhances the adaptability of relay coordination to fluctuating operating conditions, consequently bolstering the system reliability and performance. Moreover, the proposed fuzzy Monte Carlo simulation possesses several distinctive capabilities that have been overlooked in previous state-of-the-art studies. The primary contributions of our study can be succinctly outlined as follows:
  • Capturing Imprecise Information: Unlike conventional probabilistic methods that rely on precise probability distributions, fuzzy logic enables the representation of imprecise or vague information inherent in real-world systems. This feature proves invaluable in scenarios where obtaining precise data is challenging.
  • Flexibility in Modeling: Fuzzy Monte Carlo offers unparalleled flexibility in modeling uncertainties by accommodating expert knowledge or subjective assessments. This adaptability allows for the inclusion of qualitative factors, thereby enhancing the realism and accuracy of the uncertainty model. Fuzzy logic excels in handling the nonlinear and complex relationships often encountered in engineering and decision-making contexts.
  • Robustness to Data Limitations: In situations where data availability is limited or uncertain, fuzzy Monte Carlo remains robust by incorporating expert knowledge or heuristic information. This resilience to data limitations renders fuzzy Monte Carlo indispensable in scenarios where empirical data may be scarce or unreliable.
  • Integration with Monte Carlo Simulation: By integrating fuzzy logic with Monte Carlo simulation, fuzzy Monte Carlo harnesses the strengths of both approaches. This integration ensures the efficient generation of probabilistic outcomes while capturing qualitative aspects of uncertainty.
Additionally, this study contributes to the practical application of uncertainty modeling by employing a Weibull distribution to accurately depict the variability and unpredictability of DG power generation and demand in real-world scenarios. Furthermore, a Monte Carlo simulation approach with a fixed number of iterations was utilized to address uncertainties in the input variables, such as DG output and load demand. This simulation technique guarantees the accurate and efficient sampling of uncertain variables, leading to enhanced convergence and a comprehensive understanding of the potential outcomes and behaviors of the power system under varying conditions. Finally, the proposed methodology enhances the efficiency and resilience of protection schemes by offering insights into the impact of uncertainties on protection coordination and presenting practical solutions for their mitigation. Conventional relay coordination typically involves fixed relay settings based on predetermined system parameters. It is proposed that dual-setting relay coordination allows for the dynamic adjustment of relay settings in response to changing system conditions or events. This dynamic adaptation enhances the flexibility and robustness of the coordination scheme, enabling better fault detection and isolation, particularly in systems with a high DG penetration and variable generation patterns.

1.4. Organization

The rest of the paper is organized as follows. Section 2 discusses the conceptual framework and the probabilistic model underpinning the fuzzy Monte Carlo method. In Section 3, we detail the mathematical formulation of our proposed technique. Section 4 presents the simulation results and a thorough discussion of these findings. Lastly, Section 5 summarizes the key conclusions drawn from the study.

2. Probabilistic Model of Fuzzy Monte Carlo

The probabilistic model of fuzzy Monte Carlo (PFMC) is a pivotal approach in the realm of power system protection that directly handles the dual challenges posed by randomness and vagueness. In essence, probabilistic modeling takes the center stage, offering a method to encapsulate uncertainties stemming from randomness. Here, probability distributions, including Weibull, exponential, and log-normal distributions, serve as robust tools to depict the uncertainties linked to equipment failure rates and fault occurrence probabilities, as elucidated subsequently. In this vein, this study amalgamates both probabilistic and fuzzy logic methodologies, crafting a holistic framework tailored to model uncertainties in power system protection. Furthermore, the use of Monte Carlo simulations serves as a cornerstone, facilitating the dissemination of uncertainties throughout the protection system, thereby evaluating its efficacy across diverse operational scenarios. Random samples are drawn from the probability distributions of the input parameters, whereas fuzzy inference systems process fuzzy inputs adeptly, yielding fuzzy outputs. Through the simulation of myriad scenarios, the Monte Carlo methodology provides a thorough assessment of the protection system’s reliability, resilience, and effectiveness in navigating risks under uncertain conditions. Illustrating the conceptual underpinning of the proposed protection scheme, Figure 1 offers a visual depiction outlining the framework’s key components and their interrelationships.

2.1. Calculation of Weibull Distribution Parameters

Robust modeling techniques are employed to address the variability and unpredictability inherent in power system parameters such as load demands and DG output. This section outlines the approach for modeling uncertain variables and provides insights into the methodologies utilized. The DG output pattern follows a Weibull probability density function (PDF) [41], as shown in Equation (1).
f ( x ) = β α β x β 1 exp x α β
The uncertainty associated with the load can be represented using a normal PDF, as shown in Equation (2).
f ( x ) = 1 σ 2 π e ( x μ ) 2 2 σ 2
In this method, y = f(x) is regarded as a multivariate function, where x = x 1 , x 2 , x 3 , , x n represents a vector of uncertain random input variables. It is assumed that the PDFs of the input variables are known. The objective was to derive the PDF of y, the output variable.

2.2. Monte Carlo Simulation with PDFs

In addition to calculating the Weibull distribution parameters, the probabilistic modeling method incorporates uncertainty modeling using the fuzzy Monte Carlo method. A straightforward approach with a fixed number of iterations was adopted to perform the Monte Carlo simulation. This technique facilitates the accurate and efficient sampling of uncertain variables, resulting in improved convergence and reliability of the analysis. In each iteration of the Monte Carlo simulation, the values for the uncertain input variables were sampled from their respective probability distributions or fuzzy sets. Generating a large number of samples allows a comprehensive understanding of the potential outcomes and behaviors of the system under varying conditions. Over the past decade, the increasing penetration of DG has fundamentally changed the operation and protection of distribution networks. In this study, the previous research on single-setting DOCRs was extended by developing a methodology for optimal coordination using dual-setting DOCRs. This methodology involves the integration of advanced optimization techniques with uncertainty analysis to ensure robust and reliable protection coordination in the presence of a DG source. Incorporating uncertainty modeling using fuzzy Monte Carlo methods allows accounting for the variability and unpredictability associated with DG output and system conditions. This allows the identification of optimal relay settings that are adaptive to changing operating conditions and can mitigate the effects of uncertainties on protection coordination. Overall, this work builds upon the foundation of previous research on single-setting DOCRs and advances the state-of-the-art in power system protection by introducing dual-setting DOCRs with enhanced flexibility, adaptability, and robustness in coordinating protection schemes in the presence of distributed generation and uncertainty. The contribution of DG sources to faults depends on factors such as the generating capacity of the DG source (size of the DG source), the distance from the DG source to the fault location and the type of DG source. To represent the variability and uncertainty of (DG) power generation and demand in real world scenarios, we used a Weibull distribution. In addition, a simple Monte Carlo simulation approach with a fixed number of iterations was employed. This technique provides an accurate and efficient sampling of uncertain variables, leading to better convergence. A Monte Carlo simulation was performed to account for the uncertainty in the input variables. In each simulation iteration, the sample values for the uncertain input variables are obtained from their respective probability distributions or fuzzy sets.

3. Problem Formulation

The operating time of a DOCR typically inversely correlates with the short-circuit current it experiences, a relationship that has been thoroughly explored in numerous studies on protection systems. The time–current characteristic of the relay is generally described as in Equation (3) [42].
T i k = TMS i × A I F , i k PS i B 1
where i denotes the relay identifier, and k signifies the fault location identifier. The constants A and B, which are often adjusted to 0.14 and 0.02, respectively, depend on the kind of OCR. The relay fault current is denoted by I F , i k , while P S i represents the relay pickup current.

3.1. Modeling Dual-Setting DOCR Characteristics

Dual-setting directional overcurrent relays (DS-DOCRs) represent a significant leap forward in protective relay technology. These relays, designed to operate in both the forward and reverse directions, offer primary and backup protection functionalities. In contrast to conventional DOCRs restricted to one direction, DS-DOCRs provide bidirectional fault detection capabilities. Leveraging advanced mechanisms, DS-DOCRs are adept at detecting faults in both directions and triggering responses based on pre-defined time and pickup settings.
Primary Protection: This denotes the principal function of the relay, triggered when the fault current flows in the forward direction. The settings for primary protection are designated as T M S f w and P S f w , where T M S f w represents the time multiplier setting, and P S f w represents the pickup setting.
Backup Protection: This serves as a secondary protection function of the relay and is activated when the fault current flows in the reverse direction. The settings for backup protection are indicated as T M S r v and P S r v , where T M S r v represents the time multiplier setting and P S r v represents the pickup setting.
Time–Current Characteristic: This refers to a graphical representation illustrating how the relay responds to various fault currents over time. Figure 2 illustrates the time–current characteristic curve of the relay, depicting its response for both primary and backup protection operations.
Figure 3 illustrates an example of a dual-setting directional overcurrent relay equipped with the relay characteristics depicted in the same figure. Each relay is represented by two arrows, indicating the two directions of the fault current flow for which the relay can operate. The red-colored parts of the DOCRs represents the forward-directed protection section, while the green-colored parts indicates the reverse-directed protection section. In the event of a fault occurring at point F, the relay configurations are as follows: R 3 serves as the backup relay for R 1 , and R 4 , R 5 , and R 6 function as backup relays for R 2 . In such scenarios, R 3 utilizes settings associated with reverse operation ( T M S r v 3 and P S r v 3 ), whereas R 1 employs settings linked with forward operation ( T M S f w 1 and P S f w 1 ), and similarly for other relays. This configuration ensures comprehensive protection coverage for fault occurrences in both forward and reverse directions.
Previous research, e.g., [43], has highlighted the challenges in ensuring proper coordination between relays with dual settings. Therefore, the proposed scheme emphasizes the importance of efficient communication even in low-bandwidth scenarios to ensure effective coordination for backup operations, as discussed in [44]. Figure 4 illustrates a section of the test system, emphasizing the communication strategy employed between the dual-setting relays. The essence of this strategy lies in establishing communication between the relays operating in the reverse and forward directions along the same lines. This communication ensures that the reverse direction characteristic of each relay communicates with the forward direction characteristic of the adjacent relay, effectively blocking its operation when necessary. By implementing this communication strategy across all relays in the system, we aim to prevent scenarios such as the unintended operation of a relay (e.g., R 13 in the forward direction) for a fault at a specific location (e.g., F 8 ). This proactive approach not only maintains the achieved reduction in fault isolation time but also ensures proper protection coordination among the relays. It is important to note that the communication mechanism primarily applies to the backup relay operations. Therefore, in the event of a communication failure or delay, the primary relays remain unaffected, and the protection scheme can still isolate faults in a timely manner. For instance, in the case of a fault at F 8 , the R 15 ’s forward characteristic will operate and isolate the fault regardless of the communication link’s status. Even if R 15 fails to operate because of a malfunction and the communication link is lost, R 13 will still operate before relay R 14 , guaranteeing fault isolation, albeit with temporary coordination discrepancies.

3.2. Objective Function

Due to the presence of fault currents flowing in both the forward and reverse directions, certain manufacturers have proposed dual-setting DOCRs to respond differently in each direction. In [34], the following objective function is present in Equation (4):
OBJ = min k = 1 M i = 1 N f w T i , k f w + j = 1 N r v T j , k r v ( i , j ) ω
In this context, ω represents the set of relay P/B pairs and N denotes the total number of relays, while M indicates the total number of fault locations along all lines. The terms T i , k f w , and T j , k r v correspond to the tripping times of relays i, and j for a fault at location k during forward and reverse operations, respectively, as described by Equations (5) and (6):
T i , k f w = TMS i f w × A I F , i f w PS i f w B 1
T j , k r v = TMS j r v × A I F , j r v PS j r v B 1
In this context, T M S i f w and T M S j r v are the time multiplier settings for relays i and j in the forward and reverse directions, respectively. Similarly, P S i f w and P S j r v denote the plug settings of relays i and j for forward and reverse operations, respectively. The fault current at location k, passing through relay i in the forward direction, is represented as I F , i f w . Likewise, I F , j r v indicates the fault current passing through relay j in the reverse direction due to a fault at location k. The coordination constraints, which must be met to solve the protection coordination problem, can be expressed by Equation (7).
T j , k r v T i , k f w CTI i , j , k
The coordination time interval C T I represents the minimum time difference between the operation of primary and backup relays. Typically, the C T I ranges from 0.2 to 0.5 s; in this study, it was set to 0.2 s. Furthermore, there are upper and lower bounds on the relay settings, defined by Equations (8) and (9), respectively.
PS min ( PS i fw , PS j rv ) PS max
TMS min ( TMS i fw , TMS j rv ) TMS max
In this context, P S min and P S max denote the lower and upper bounds, respectively, for relay i’s plug setting. Similarly, T M S min and T M S max represent the lower and upper bounds for the time multiplier setting for relay i.

3.3. ALO Optimization Approach for Addressing Coordination Issues

This study introduces an optimization algorithm referred to as the ant lion optimizer (ALO), which is meticulously crafted to effectively address coordination challenges. In particular, the ALO method is employed to determine the optimal values for both the pickup current and Time Multiplier Setting ( T M S ) of dual-setting DOCRs deployed within distribution systems integrated with DG sources [45]. The ALO used in this study employs an initial population of 250 antlions. As a population-based metaheuristic algorithm, ALO operates on a matrix of multiple antlion and ant individuals. The number of antlions in the initial population was set to 250, which is within the common range of 20–500 individuals used for population-based optimization algorithms. This population size of antlions, along with the population of ants, forms the basis for the cooperative hunting mechanism at the core of the ALO optimization approach. The operational steps of the proposed ALO algorithm, designed to minimize the operating time of the dual-setting DOCRs, are outlined as follows:
  • Step 1: Input Acquisition and System Data Analysis:
    • Acquire input parameters, encompassing distribution system data and relay specifications.
    • Establish primary/backup relay pairs based on gathered data.
    • Calculate both the full load and short circuit currents for each relay to ascertain their operational conditions.
  • Step 2: Initializing Population:
    • Generate initial populations of both antlions and ants, distributing them randomly while adhering to the defined upper and lower parameter constraints.
  • Step 3: Evaluating Fitness Function:
    • Evaluate the fitness function, representing the total relay operating time, for all ants and antlions by employing the objective function index for assessment.
  • Step 4: Identifying Elite Antlions:
    • Identify elite antlion solutions by discerning the top-performing candidates.
  • Step 5: Updating Positions:
    • Adjust parameters to steer ants toward the central point of attraction, represented by antlion.
  • Step 6: Generating Random Walk:
    • Devise a random-walk mechanism to normalize the movement patterns of both ants and antlions.
  • Step 7: Adjusting Positions for Antlions:
    • Update the positions of antlions utilizing a predefined formula to refine their spatial locations.
  • Step 8: Evaluating Solutions:
    • Assess the best solution and substitute the antlion with the corresponding ant if it outperforms an elite candidate.
  • Step 9: Storage and Termination:
    • If the maximum iterations are attained, store and present the optimal results achieved through the algorithm.
A flowchart detailing the operational steps of the ALO algorithm is presented in Figure 5.

4. Case Study and Results

4.1. Case 1: IEEE 14-Bus System

In this case study, the adapted distribution section of the IEEE-14 bus system, representing a 7-bus microgrid setup as illustrated in Figure 6, was utilized to analyze the proposed protection method. This configuration includes three (DG sources with a capacity of 20 MVA each linked to buses B4, B5, and B6. Moreover, the 7-bus microgrid system is connected to the sub-transmission network via buses B1 and B2, each with a generation capacity of 60 MVA. Further specifications of the test system can be found in Ref. [46]. This test setup comprised eight lines, protected by 16 dual-setting DOCRs positioned at both line ends. There are 22 relay pairs ( R P 1 R P 22 ). Specifics of the number of primary and backup relays are outlined in Table 1.

Simulation Result, Using ALO Algorithm

In this scenario, the metaheuristic ALO algorithm was applied to attain the optimal coordination of dual-setting DOCRs within the test network. A comprehensive, step-by-step elucidation of the implemented algorithm is as follows.
  • Step 1: Optimal Setting Without Considering Uncertainty:
The fault current values recorded via the primary and backup relays for the distribution part of the IEEE-14-bus system are presented in Table 2. The operating times of the primary and backup relay pairs and their associated CTI values are listed in Table 3. The optimal relay setting values for the dual-setting DOCRs are presented in Table 4.
  • Step 2: Optimal Relay Setting Considering Uncertainty:
The stochastic nature of DG sources and electrical loads introduces uncertainties that profoundly affect the operation of microgrids and distribution networks. Failure to address these uncertainties can result in unrealistic and inaccurate modeling outcomes. Consequently, in this phase, the uncertainties linked to the DG sources and electrical loads were taken into account to effectively optimize the relay settings. To address the challenges posed by uncertainty, a probabilistic analysis is seamlessly integrated into the relay coordination process. By factoring in the variability in DG output power and load demand, the approach ensures that relay settings exhibit robustness and adaptability to a spectrum of operating conditions. This method not only bolsters the reliability and resilience of the distribution network but also fortifies it against unforeseeable fluctuations in both power generation and consumption. The subsequent sections provide a detailed overview of the input data used in the analysis, with a specific focus on the uncertainties associated with the load demand and output power of DG sources within the IEEE 14-bus test system.
  • Load Uncertainties
    The uncertainties surrounding the load demand at each bus within the test system are critical for precise modeling and analysis. To visually represent these uncertainties, PDFs for both active and reactive power of load demands at each bus are presented. In Figure 7a, the fluctuation in active power load demand across numerous iterations is showcased, offering insights into its variability over time. Additionally, the 3D plot in Figure 7b illustrates the PDF of the active power load demand for each bus. Each curve in this plot represents the PDF of active power load demand at a specific bus, offering a graphical representation of the uncertainties associated with the active power load demand.
    Likewise, Figure 8a portrays the fluctuation in the reactive power load demand across various iterations, providing insight into its variability over time. The 3D plot in Figure 8b presents the PDF of the reactive power load demand for each bus in the test network. These graphical depictions serve to elucidate the uncertainties inherent in load demand across different buses within the network, thereby facilitating more robust modeling and analysis processes.
  • Distributed Generation Source Output Power Uncertainties
    In addition to load uncertainties, uncertainties exist in the output power of DG sources. Figure 9 illustrates the variation in DG source output power across multiple iterations, offering insights into the variability of DG source power output. Each subplot in the figure represents the output power of a specific DG source throughout the iterations, effectively showcasing the uncertainties associated with DG source power generation.
  • Monte Carlo Simulation
    One of the most prevalent and accurate stochastic methods used in this study is Monte Carlo simulation (MCS), where the sample sizes are typically set to N s = 500 . The MCS is an iterative process that encompasses the following steps:
    • The behavior of the power system for each sample scenario was simulated by considering the generated samples of uncertain parameters.
    • Short-circuit analysis was conducted to ascertain the fault currents in the system for each sample scenario and store these fault currents in a cell array corresponding to each scenario.
    • An optimization algorithm (such as ALO) is utilized to determine the optimal settings for relay coordination based on the fault currents obtained from short circuit analysis. The objective is to minimize the operating time while ensuring proper relay coordination.
    • After obtaining the optimal settings for relay coordination for each sample scenario, the PDFs for the TMS and PS parameters were obtained for both forward and reverse relays. This facilitates the analysis of the distribution of optimal settings across all sample scenarios.
    • The best optimal settings were identified by locating the peaks of the PDFs for the TMS and PS parameters. These settings represent the most frequently occurring optimal configurations across all the sample scenarios.
The optimal relay settings obtained in this process consider the probabilistic distribution of the fault currents and operating conditions. By integrating uncertainty-aware strategies, the coordination of dual-setting DOCRs is optimized to mitigate the risks associated with potential faults and disturbances in the distribution system. The PDFs of the T M S and P S were analyzed for both forward and reverse relays. Additionally, the combined PDFs of the optimal T M S and P S settings are plotted, highlighting the maximum probability density and their respective optimal settings. These PDFs provide valuable insights into the distribution of the optimal relay settings throughout the network. Through a comprehensive analysis, the optimal T M S and P S values for forward-direction relays were determined, as illustrated in Figure 10. Similarly, Figure 11 presents the optimal T M S and P S values for reverse-direction relays.
As depicted in Figure 10 and Figure 11 the optimized values for the T M S and P S with the maximum PDF considering uncertainties are notably lower compared to the T M S and P S values without accounting for uncertainties, as indicated in Table 4. This observation underscores the significance of incorporating uncertainties into relay settings, particularly when there are variations in the input data, such as load and generation uncertainties. This highlights the necessity of accounting for uncertainties to ensure a more accurate and reliable relay coordination in the face of varying system conditions. Figure 12 and Figure 13 depict the boxplot graphical representation of the relay operation times in states where uncertainties are considered and not considered, respectively. In Figure 12, all C T I ranges (boxplots) of relay pairs in the state considering uncertainties meet the threshold of C T I m i n = 0.2 (highlighted by a red line). However, in Figure 13, relay pairs such as R P . 3 , R P . 6 , R P . 9 , R P . 10 , R P . 16 , R P . 17 , R P . 19 , and R P . 20 do not satisfy the minimum value of C T I m i n = 0.2 when uncertainties are not taken into account.

4.2. Case 2: IEEE-30 Bus System

To validate the effectiveness of the newly proposed protection strategy, its application was extended from the distribution section of the IEEE-14 bus test system to a larger microgrid setup. Specifically, the novel protection technique was deployed within the distribution segment of the IEEE-30 bus test system, which represents a 17-bus microgrid configuration [46]. This system consists of 21 lines, safeguarded by 42 dual-setting DOCRs positioned at both ends of the lines, providing a more thorough validation of the proposed methodology. Within this setup, four DG sources are integrated, each with a capacity of 15 MVA and connected to buses B3, B7, B11, and B16. Additionally, the system is linked to the utility grid through buses B1, B6, and B14, as illustrated in Figure 14. Detailed information regarding the number of primary and backup relays can be found in Table 5.
In this case study, two scenarios are examined, one in which uncertainties are considered and one in which they are not. The ALO algorithm was utilized to optimize the coordination of dual-setting DOCRs within the test network. Initially, the relay settings were determined without considering the uncertainties. Fault current readings obtained from the P/B relays in the distribution section of the IEEE-30 bus system is shown in Table 6. Furthermore, Table 7 provides information on the operating times of the P/B relay pairs and their corresponding CTI values. The optimal settings for dual-setting DOCRs are presented in Table 8. This analysis aims to evaluate the performance of the proposed protection strategy under different conditions, shedding light on its effectiveness in mitigating faults and enhancing the system reliability.
In the subsequent phase, aimed at assessing and comparing the effectiveness of the proposed protection scheme, particularly in addressing uncertainties about demand load and generation, the fuzzy Monte Carlo technique, as detailed in a previous case study, was employed to analyze the input parameters of the current investigation. To visually depict these uncertainties, PDFs for both active and reactive power of load demands at each bus are presented. Figure 15a illustrates the fluctuation of active power load demand across numerous iterations, offering valuable insights into its temporal variability. Furthermore, the 3D plot in Figure 15b shows the PDF of the active power load demand for each bus. Each curve in this plot represents the PDF of the active power load demand at a specific bus, offering a graphical depiction of the uncertainties associated with the active power load demand. Similarly, Figure 16a illustrates the dynamic fluctuation of reactive power load demand across diverse iterations, offering valuable insights into its temporal variability. Concurrently, the 3D plot in Figure 16b delineates the PDF of the reactive power load demand for each bus within the test network. These visual representations serve to elucidate the inherent uncertainties associated with load demand across various buses within the network, thus enhancing the comprehensiveness and reliability of modeling and analysis.
Conversely, uncertainties are also present in the output power of DG sources. Figure 17 depicts the fluctuations in DG source output power across numerous iterations, providing valuable insights into the variability of their power generation. Each subplot in the figure corresponds to the output power of a specific DG source through iterations, effectively highlighting the uncertainties inherent in the DG source power generation. These visual representations offer a comprehensive understanding of the variability in DG source power output, contributing to a more nuanced analysis of the system.
The optimal relay settings derived through the fuzzy Monte Carlo technique consider the probabilistic distribution of fault currents and operating conditions. Incorporating strategies that acknowledge the uncertainty, the coordination of dual-setting DOCRs is fine-tuned to mitigate the risks associated with potential faults and disturbances in the distribution system. An analysis of PDFs for T M S and P S was conducted for both forward and reverse relays. Moreover, combined PDFs showing the optimal T M S and P S settings were plotted, highlighting the maximum probability density with their corresponding optimal configurations. These PDFs offer valuable insight into the spread of optimal relay settings across networks. Through examination, the optimal T M S and P S values for forward-direction relays were determined, as depicted in Figure 18. Similarly, Figure 19 illustrates the optimal T M S and P S values for reverse-direction relays.
As illustrated in Figure 18 and Figure 19, the optimized values for the T M S and P S maximize the PDF while considering uncertainties, are notably lower than the TMS and PS values when uncertainties are not accounted for, as indicated in Table 8. This observation underscores the critical importance of integrating uncertainties into relay settings, particularly in scenarios where there are fluctuations in the input data, such as load and generation uncertainties. This emphasizes the imperative need to address uncertainties to ensure a more precise and dependable relay coordination amid varying the system conditions. Figure 20 and Figure 21 present boxplot graphical representations of relay operation times in states in which uncertainties are considered and not considered, respectively. In Figure 20, all C T I ranges (boxplots) of relay pairs in the state considering uncertainties fulfill the threshold of C T I m i n = 0.2 (highlighted by a red line). However, in Figure 21, relay pairs such as RP.12, RP.13, RP.14, RP.25, RP.26, and RP.59 fail to meet the minimum value of C T I m i n = 0.2 when the uncertainties are not factored in.

5. Conclusions

In today’s evolving power networks, the integration of distributed generation resources introduces a unique set of challenges in ensuring reliable and effective protection. As discussed in this paper, optimizing the coordination of directional overcurrent relays (DOCRs) become increasingly complex when confronted with uncertainties stemming from both distributed generation (DG) outputs and load consumption patterns. Consequently, this study underscores the importance of integrating uncertainties into the optimization process of dual-setting DOCRs. By employing advanced techniques, such as the fuzzy Monte Carlo method, it is demonstrated that considering uncertainties in relay settings significantly impacts the resulting values of the Time Multiplier Setting (TMS) and Pickup Current Setting (PS). The analysis, as evidenced by the simulation results, indicates that optimized relay settings, when accounting for uncertainties, tend to be notably lower than those obtained without considering uncertainties. This observation highlights the necessity of incorporating uncertainties, especially in environments where variations in input data, such as load and generation uncertainties prevail. The fuzzy Monte Carlo method plays a critical role in this study by simulating the various uncertainties associated with DG and load patterns. These simulations generate a range of possible scenarios, reflecting the real-world variability of power networks. To efficiently handle and optimize these scenarios, the ant lion optimization (ALO) Algorithm is employed. The ALO algorithm is particularly suited for this task due to its robustness in finding optimal solutions in complex, multidimensional search spaces. By integrating the results from the fuzzy Monte Carlo simulations with the ALO algorithm, the study ensures that the optimization process accounts for the inherent uncertainties, thereby enhancing the reliability and accuracy of the relay settings. The findings emphasize the pivotal role of uncertainty-aware strategies in enhancing the accuracy and reliability of relay coordination, thereby ensuring robust protection against potential faults and disturbances in distribution systems. Furthermore, graphical representations illustrate the tangible benefits of accounting for uncertainties in relay operation times. The disparities observed between relay pairs when uncertainties are considered and when they are not underscore the potential risks associated with disregarding uncertainties in relay settings. In essence, this study advocates for a paradigm shift towards embracing uncertainty-aware approaches in the design and optimization of relay settings. By doing so, the power system can better adapt to its dynamic nature, ultimately enhancing its resilience and reliability in the face of uncertain operating conditions.

Author Contributions

F.A.-B.: Conceptualization, methodology, experimentation, validation, formal analysis, investigation, data curation, writing—original draft, writing—review and editing, and visualization. A.İ.: Conceptualization, methodology, validation, investigation, resources, writing—original draft, writing—review and editing, visualization, supervision, and project administration. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data are contained within the article.

Acknowledgments

The authors would like to acknowledge that this paper is submitted in partial fulfilment of the requirements for the PhD degree at Yildiz Technical University.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
ADNActive distribution networks.
ALOAnt lion optimizer algorithm.
CTICoordination time interval.
DOCRsDirectional overcurrent relays.
DGDistributed generation.
DS-DOCRsDual-setting directional overcurrent relays.
MCSMonte Carlo simulation.
MGsMicrogrids.
OLFOverload factor.
OCROvercurrent relay.
PSpickup (plug) setting.
PFMCProbabilistic model of fuzzy Monte Carlo.
PDFProbability density function.
P/BPrimary/backup.
SGsSmart grids.
TMSTime multiplier setting.

References

  1. Kida, A.A.; Rivas, A.E.L.; Gallego, L.A. An improved simulated annealing–linear programming hybrid algorithm applied to the optimal coordination of directional overcurrent relays. Electr. Power Syst. Res. 2020, 181, 106197. [Google Scholar] [CrossRef]
  2. ElSayed, S.K.; Elattar, E.E. Hybrid Harris hawks optimization with sequential quadratic programming for optimal coordination of directional overcurrent relays incorporating distributed generation. Alex. Eng. J. 2021, 60, 2421–2433. [Google Scholar] [CrossRef]
  3. Habib, K.; Lai, X.; Wadood, A.; Khan, S.; Wang, Y.; Xu, S. An improved technique of Hybridization of PSO for the Optimal Coordination of Directional Overcurrent Protection Relays of IEEE bus system. Energies 2022, 15, 3076. [Google Scholar] [CrossRef]
  4. Wang, Y.; Habib, K.; Wadood, A.; Khan, S. The hybridization of PSO for the optimal coordination of directional overcurrent protection relays of the IEEE bus system. Energies 2023, 16, 3726. [Google Scholar] [CrossRef]
  5. Godwal, S.D.; Pandya, K.S.; Vora, S.C.; Mehta, C.R.; Rajput, V.R. Optimal overcurrent relay coordination for interconnected power systems: A proper approach and improved technique. e-Prime-Adv. Electr. Eng. Electron. Energy 2023, 5, 100248. [Google Scholar] [CrossRef]
  6. Abdelfattah, W.; Nagy, A.; Salama, M.; Lotfy, M.E.; Abdelhadi, H. Artificial intelligence based optimal coordination of directional overcurrent relay in distribution systems considering vehicle to grid technology. Ain Shams Eng. J. 2024, 15, 102372. [Google Scholar] [CrossRef]
  7. Biswal, S.; Sharma, N.K.; Samantaray, S. Optimal overcurrent relay coordination scheme for microgrid. In Proceedings of the 2020 21st National Power Systems Conference (NPSC), Gandhinagar, India, 17–19 December 2020; pp. 1–6. [Google Scholar]
  8. Patnaik, B.; Mishra, M.; Bansal, R.C.; Jena, R.K. AC microgrid protection—A review: Current and future prospective. Appl. Energy 2020, 271, 115210. [Google Scholar] [CrossRef]
  9. Beder, H.; Mohandes, B.; El Moursi, M.S.; Badran, E.A.; El Saadawi, M.M. A new communication-free dual setting protection coordination of microgrid. IEEE Trans. Power Deliv. 2020, 36, 2446–2458. [Google Scholar] [CrossRef]
  10. Foqha, T.; Alsadi, S.; Omari, O.; Refaat, S.S. Optimization Techniques for Directional Overcurrent Relay Coordination: A Comprehensive Review. IEEE Access 2023, 12, 1952–2006. [Google Scholar] [CrossRef]
  11. Tiwari, R.; Singh, R.K.; Choudhary, N.K. Coordination of dual setting overcurrent relays in microgrid with optimally determined relay characteristics for dual operating modes. Prot. Control Mod. Power Syst. 2022, 7, 1–18. [Google Scholar] [CrossRef]
  12. Tiwari, R.; Singh, R.K.; Choudhary, N.K. Optimal coordination of dual setting directional over current relays in microgrid with different standard relay characteristics. In Proceedings of the 2020 IEEE 9th Power India International Conference (PIICON), Sonepat, India, 28 February–1 March 2020; pp. 1–6. [Google Scholar]
  13. Singh, D.K.; Sarangi, S.; Singh, A.K.; Mohanty, S.R. Coordination of dual-setting overcurrent and distance relays for meshed distribution networks with distributed generations and dynamic voltage restorer. Smart Sci. 2023, 11, 135–153. [Google Scholar] [CrossRef]
  14. Martin, K.T.; Marchesan, A.C.; de Araújo, O.C.B.; Cardoso, G.; da Silva, M.F. Mixed integer linear programming applied to adaptive directional overcurrent protection considering N-1 contingency. IEEE Trans. Ind. Appl. 2023, 59, 2807–2821. [Google Scholar] [CrossRef]
  15. Langazane, S.N.; Saha, A.K. Effects of particle swarm optimization and genetic algorithm control parameters on overcurrent relay selectivity and speed. IEEE Access 2022, 10, 4550–4567. [Google Scholar] [CrossRef]
  16. Akdag, O.; Yeroglu, C. Optimal directional overcurrent relay coordination using MRFO algorithm: A case study of adaptive protection of the distribution network of the Hatay province of Turkey. Electr. Power Syst. Res. 2021, 192, 106998. [Google Scholar] [CrossRef]
  17. Wong, J.Y.R.; Tan, C.; Che, H.S. Selectivity problem in adaptive overcurrent protection for microgrid with inverter-based distributed generators (IBDG): Theoretical investigation and HIL verification. IEEE Trans. Power Deliv. 2021, 37, 3313–3324. [Google Scholar] [CrossRef]
  18. Alasali, F.; El-Naily, N.; Saidi, A.S.; Itradat, A.; Holderbaum, W.; Mohamed, F.A. Highly sensitive multifunction protection coordination scheme for improved reliability of power systems with distributed generation (PVs). IET Renew. Power Gener. 2023, 17, 3025–3048. [Google Scholar] [CrossRef]
  19. Barranco-Carlos, A.; Orozco-Henao, C.; Marín-Quintero, J.; Mora-Flórez, J.; Herrera-Orozco, A. Adaptive protection for active distribution networks: An approach based on fuses and relays with multiple setting groups. IEEE Access 2023, 11, 31075–31091. [Google Scholar] [CrossRef]
  20. Aghaei, H.; Hashemi-Dezaki, H. Optimal communication-aided protection of meshed smart grids considering stability constraints of distributed generations incorporating optimal selection of relay characteristics. IET Renew. Power Gener. 2022, 16, 2313–2337. [Google Scholar] [CrossRef]
  21. Purwar, E.; Singh, S.P.; Vishwakarma, D.N. A robust protection scheme based on hybrid pick-up and optimal hierarchy selection of relays in the variable DGs-distribution system. IEEE Trans. Power Deliv. 2019, 35, 150–159. [Google Scholar] [CrossRef]
  22. Jamali, S.; Borhani-Bahabadi, H. Protection method for radial distribution systems with DG using local voltage measurements. IEEE Trans. Power Deliv. 2018, 34, 651–660. [Google Scholar] [CrossRef]
  23. Shen, S.; Wang, H.; Jiang, K.; Zhu, L.; Gan, C.; Markham, P.N.; Liu, Y.; He, B. Regional area protection scheme for modern distribution system. IEEE Trans. Smart Grid 2018, 10, 5416–5426. [Google Scholar] [CrossRef]
  24. George, S.P.; Ashok, S. Forecast-based overcurrent relay coordination in wind farms. Int. J. Electr. Power Energy Syst. 2020, 118, 105834. [Google Scholar] [CrossRef]
  25. Balyith, A.A.; Sharaf, H.M.; Shaaban, M.; El-Saadany, E.F.; Zeineldin, H.H. Non-communication based time-current-voltage dual setting directional overcurrent protection for radial distribution systems with DG. IEEE Access 2020, 8, 190572–190581. [Google Scholar] [CrossRef]
  26. Sarwagya, K.; Nayak, P.K.; Ranjan, S. Optimal coordination of directional overcurrent relays in complex distribution networks using sine cosine algorithm. Electr. Power Syst. Res. 2020, 187, 106435. [Google Scholar] [CrossRef]
  27. Ghotbi-Maleki, M.; Chabanloo, R.M.; Zeineldin, H.H.; Miangafsheh, S.M.H. Design of setting group-based overcurrent protection scheme for active distribution networks using MILP. IEEE Trans. Smart Grid 2020, 12, 1185–1193. [Google Scholar] [CrossRef]
  28. Vijayachandran, V.V.; Shenoy, U.J. Implementation of support-vector-machine-based relay coordination scheme for distribution system with renewables. IEEE J. Emerg. Sel. Top. Ind. Electron. 2020, 2, 324–333. [Google Scholar] [CrossRef]
  29. Abbaspour, E.; Fani, B.; Sadeghkhani, I.; Alhelou, H.H. Multi-agent system-based hierarchical protection scheme for distribution networks with high penetration of electronically-coupled DGs. IEEE Access 2021, 9, 102998–103018. [Google Scholar] [CrossRef]
  30. Hong, L.; Rizwan, M.; Wasif, M.; Ahmad, S.; Zaindin, M.; Firdausi, M. User-defined dual setting directional overcurrent relays with hybrid time current-voltage characteristics-based protection coordination for active distribution network. IEEE Access 2021, 9, 62752–62769. [Google Scholar] [CrossRef]
  31. Ataee-Kachoee, A.; Hashemi-Dezaki, H.; Ketabi, A. Optimized adaptive protection coordination of microgrids by dual-setting directional overcurrent relays considering different topologies based on limited independent relays’ setting groups. Electr. Power Syst. Res. 2023, 214, 108879. [Google Scholar] [CrossRef]
  32. El-Naily, N.; Saad, S.M.; Elhaffar, A.; Zarour, E.; Alasali, F. Innovative Adaptive Protection Approach to Maximize the Security and Performance of Phase/Earth Overcurrent Relay for Microgrid Considering Earth Fault Scenarios. Electr. Power Syst. Res. 2022, 206, 107844. [Google Scholar] [CrossRef]
  33. Entekhabi-Nooshabadi, A.M.; Hashemi-Dezaki, H.; Taher, S.A. Optimal microgrid’s protection coordination considering N-1 contingency and optimum relay characteristics. Appl. Soft Comput. 2021, 98, 106741. [Google Scholar] [CrossRef]
  34. Torshizi, N.H.; Najafi, H.; Noghabi, A.S.; Sadeh, J. An adaptive characteristic for overcurrent relays considering uncertainty in presence of distributed generation. Int. J. Electr. Power Energy Syst. 2021, 128, 106688. [Google Scholar] [CrossRef]
  35. Sadeghi, M.H.; Dastfan, A.; Damchi, Y. Robust and adaptive coordination approaches for co-optimization of voltage dip and directional overcurrent relays coordination. Int. J. Electr. Power Energy Syst. 2021, 129, 106850. [Google Scholar] [CrossRef]
  36. Alasali, F.; El-Naily, N.; Saidi, A.S.; Itradat, A.; Saad, S.M.; Holderbaum, W. An advanced dual-setting protection scheme for microgrid resilience based on nonstandard tripping characteristics of overcurrent relays. Electr. Power Syst. Res. 2023, 225, 109869. [Google Scholar] [CrossRef]
  37. Momesso, A.E.; Bernardes, W.M.S.; Asada, E.N. Adaptive directional overcurrent protection considering stability constraint. Electr. Power Syst. Res. 2020, 181, 106190. [Google Scholar] [CrossRef]
  38. Aazami, R.; Esmaeilbeigi, S.; Valizadeh, M.; Javadi, M.S. Novel intelligent multi-agents system for hybrid adaptive protection of micro-grid. Sustain. Energy Grids Netw. 2022, 30, 100682. [Google Scholar] [CrossRef]
  39. Merabet, O.; Kheldoun, A.; Bouchahdane, M.; Eltom, A.; Kheldoun, A. An adaptive protection coordination for microgrids utilizing an improved optimization technique for user-defined DOCRs characteristics with different groups of settings considering N-1 contingency. Expert Syst. Appl. 2024, 248, 123449. [Google Scholar] [CrossRef]
  40. Hong, Y.-Y.; Yu, C.-W.; Lee, Y.-D.; Jiang, J.-L.; Wang, S.-S. Coordination of protective relays in distribution systems considering uncertainty caused by renewables and demands based on orthogonal experiments. Sustain. Energy Grids Netw. 2023, 36, 101206. [Google Scholar] [CrossRef]
  41. Aien, M.; Hajebrahimi, A.; Fotuhi-Firuzabad, M. A comprehensive review on uncertainty modeling techniques in power system studies. Renew. Sustain. Energy Rev. 2016, 57, 1077–1089. [Google Scholar] [CrossRef]
  42. Yazdaninejadi, A.; Nazarpour, D.; Talavat, V. Optimal coordination of dual-setting directional over-current relays in multi-source meshed active distribution networks considering transient stability. IET Gener. Transm. Distrib. 2019, 13, 157–170. [Google Scholar] [CrossRef]
  43. Aghdam, T.S.; Karegar, H.K.; Abbasi, A. Discussion on “Optimal Protection Coordination for Meshed Distribution Systems with DG Using Dual Setting Relays”. IEEE Trans. Smart Grid 2016, 7, 1756. [Google Scholar] [CrossRef]
  44. Sharaf, H.M.; Zeineldin, H.H.; El-Saadany, E. Protection coordination for microgrids with grid-connected and islanded capabilities using communication assisted dual setting directional overcurrent relays. IEEE Trans. Smart Grid 2016, 9, 143–151. [Google Scholar] [CrossRef]
  45. Hatata, A.Y.; Lafi, A. Ant lion optimizer for optimal coordination of DOC relays in distribution systems containing DGs. IEEE Access 2018, 6, 72241–72252. [Google Scholar] [CrossRef]
  46. Al-Bhadely, F.; İnan, A. Improving Directional Overcurrent Relay Coordination in Distribution Networks for Optimal Operation Using Hybrid Genetic Algorithm with Sequential Quadratic Programming. Energies 2023, 16, 7031. [Google Scholar] [CrossRef]
Figure 1. Conceptual Model of Proposed Protection scheme Using Fuzzy Monte Carlo Probabilistic Model.
Figure 1. Conceptual Model of Proposed Protection scheme Using Fuzzy Monte Carlo Probabilistic Model.
Sensors 24 04109 g001
Figure 2. Time–current characteristics for the dual-setting DOCR.
Figure 2. Time–current characteristics for the dual-setting DOCR.
Sensors 24 04109 g002
Figure 3. Protection with dual-setting directional relays.
Figure 3. Protection with dual-setting directional relays.
Sensors 24 04109 g003
Figure 4. Illustration of a segment from the test system, emphasizing the communication approach employed.
Figure 4. Illustration of a segment from the test system, emphasizing the communication approach employed.
Sensors 24 04109 g004
Figure 5. Flowchart of the ant lion optimization (ALO) algorithm.
Figure 5. Flowchart of the ant lion optimization (ALO) algorithm.
Sensors 24 04109 g005
Figure 6. Modified distribution portion of the IEEE 14-bus system.
Figure 6. Modified distribution portion of the IEEE 14-bus system.
Sensors 24 04109 g006
Figure 7. Variation in and PDF of Active Power Load Demand in IEEE-14 Bus system.
Figure 7. Variation in and PDF of Active Power Load Demand in IEEE-14 Bus system.
Sensors 24 04109 g007
Figure 8. Variation in and PDF of Reactive Power Load Demand in IEEE-14 Bus system.
Figure 8. Variation in and PDF of Reactive Power Load Demand in IEEE-14 Bus system.
Sensors 24 04109 g008
Figure 9. Variation in DG Outputs Across MCS Iterations in IEEE-14 Bus system.
Figure 9. Variation in DG Outputs Across MCS Iterations in IEEE-14 Bus system.
Sensors 24 04109 g009
Figure 10. PDF and combined PDF of optimal setting for forward relays in IEEE-14 Bus system.
Figure 10. PDF and combined PDF of optimal setting for forward relays in IEEE-14 Bus system.
Sensors 24 04109 g010
Figure 11. PDF and combined PDF of optimal setting for reverse relays in IEEE-14 Bus system.
Figure 11. PDF and combined PDF of optimal setting for reverse relays in IEEE-14 Bus system.
Sensors 24 04109 g011
Figure 12. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting Under Uncertainty.
Figure 12. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting Under Uncertainty.
Sensors 24 04109 g012
Figure 13. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting without considering uncertainty.
Figure 13. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting without considering uncertainty.
Sensors 24 04109 g013
Figure 14. Modified distribution portion (17-Bus Network) of the IEEE-30 Bus system.
Figure 14. Modified distribution portion (17-Bus Network) of the IEEE-30 Bus system.
Sensors 24 04109 g014
Figure 15. Variation in and PDF of Active Power Load Demand in IEEE-30 Bus system.
Figure 15. Variation in and PDF of Active Power Load Demand in IEEE-30 Bus system.
Sensors 24 04109 g015
Figure 16. Variation in and PDF of Reactive Power Load Demand in IEEE-30 Bus system.
Figure 16. Variation in and PDF of Reactive Power Load Demand in IEEE-30 Bus system.
Sensors 24 04109 g016
Figure 17. Variation in DG Outputs Across MCS Iterations in IEEE-30 Bus system.
Figure 17. Variation in DG Outputs Across MCS Iterations in IEEE-30 Bus system.
Sensors 24 04109 g017
Figure 18. PDF and combined PDF of optimal setting for forward relays in IEEE-30 Bus system.
Figure 18. PDF and combined PDF of optimal setting for forward relays in IEEE-30 Bus system.
Sensors 24 04109 g018
Figure 19. PDF and combined PDF of optimal setting for reverse relays in IEEE-30 Bus system.
Figure 19. PDF and combined PDF of optimal setting for reverse relays in IEEE-30 Bus system.
Sensors 24 04109 g019
Figure 20. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting Under Uncertainty.
Figure 20. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting Under Uncertainty.
Sensors 24 04109 g020
Figure 21. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting without considering uncertainty.
Figure 21. Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting without considering uncertainty.
Sensors 24 04109 g021
Table 1. The primary/backup protective relays.
Table 1. The primary/backup protective relays.
Relay PairPrimary
Relay
Backup RelayRelay PairPrimary
Relay
Backup Relay
RP1R1R3RP12R8R11
RP2R1R5RP13R9R7
RP3R2R12RP14R10R16
RP4R3R1RP15R11R8
RP5R3R5RP16R12R2
RP6R4R13RP17R13R4
RP7R5R1RP18R14R15
RP8R5R3RP19R14R6
RP9R6R14RP20R15R6
RP10R6R15RP21R15R14
RP11R7R9RP22R16R10
Table 2. Fault currents through primary and backup relay pairs.
Table 2. Fault currents through primary and backup relay pairs.
Primary
Relay
Fault
Current (A)
Backup RelayFault
Current (A)
Primary
Relay
Fault
Current (A)
Backup RelayFault
Current (A)
R110,653.6R31222.4R84713.5R114704.0
R110,653.6R52649.6R98183.2R71255.2
R27324.3R122555.1R102892.0R163040.1
R38858.6R11480.5R116593.3R86593.2
R38858.6R51647.9R127922.3R23363.8
R46079.3R132093.6R136530.3R42051.0
R513,330.2R12246.6R147981.2R152656.4
R513,330.2R3974.1R147981.2R6940.0
R69472.2R141877.4R156729.0R62025.4
R69472.2R151413.2R156729.0R14933.4
R714,970.6R91444.0R163232.1R103074.6
Table 3. Operational times between P/B relay pairs with CTI.
Table 3. Operational times between P/B relay pairs with CTI.
Relay PairsALORelay PairsALO
Primary Backup Tp (s) Tb (s) CTI (s) Primary Backup Tp (s) Tb (s) CTI (s)
R1R30.1010.3020.201R8R110.1060.3090.204
R1R50.1010.3020.201R9R70.1040.3140.210
R2R120.1410.3470.206R10R160.1040.3090.205
R3R10.1280.3420.213R11R80.1030.3070.205
R3R50.1280.3540.226R12R20.1090.3100.202
R4R130.1160.3280.212R13R40.1030.3190.216
R5R10.1030.3040.201R14R150.1030.3580.255
R5R30.1030.3290.226R14R60.1030.3040.200
R6R140.1010.3020.201R15R60.1170.3250.208
R6R150.1010.3010.200R15R140.1170.3700.253
R7R90.1050.3130.208R16R100.1030.3070.204
Table 4. Optimal setting for dual-setting DOCRs in distribution part of the IEEE-14 Bus System using ALO.
Table 4. Optimal setting for dual-setting DOCRs in distribution part of the IEEE-14 Bus System using ALO.
Relay No.ForwardReverseRelay No.ForwardReverse
TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu)
R10.0740.0450.1780.025R90.0780.0320.1620.025
R20.1130.0210.1480.075R100.0410.1090.1990.023
R30.1020.0260.1250.042R110.0800.0210.0990.302
R40.0820.0310.1670.034R120.0880.0210.1570.068
R50.0820.0380.1490.054R130.0700.0400.1570.047
R60.0790.0290.1930.022R140.0630.0770.1740.022
R70.0940.0230.1640.021R150.0870.0270.1160.059
R80.0540.0850.2140.036R160.0400.1340.1910.028
OF (s) = 1.747 s
Table 5. The primary/backup protective relays.
Table 5. The primary/backup protective relays.
Relay
Pair
Primary
Relay
Backup
Relay
Relay
Pair
Primary
Relay
Backup
Relay
Relay
Pair
Primary
Relay
Backup
Relay
RP1R1R3RP25R14R18RP49R31R38
RP2R1R19RP26R15R12RP50R31R41
RP3R1R21RP27R15R13RP51R32R27
RP4R2R5RP28R16R17RP52R33R29
RP5R3R1RP29R17R16RP53R33R35
RP6R3R19RP30R18R14RP54R34R31
RP7R3R21RP31R19R1RP55R34R38
RP8R4R6RP32R19R3RP56R34R41
RP9R4R7RP33R19R21RP57R35R29
RP10R5R2RP34R20R26RP58R35R33
RP11R6R4RP35R21R1RP59R36R37
RP12R6R7RP36R21R3RP60R37R36
RP13R7R4RP37R21R19RP61R38R31
RP14R7R6RP38R22R24RP62R38R34
RP15R8R9RP39R23R28RP63R38R41
RP16R8R40RP40R24R22RP64R39R42
RP17R9R8RP41R25R30RP65R40R8
RP18R9R40RP42R26R20RP66R40R9
RP19R10R11RP43R27R32RP67R41R31
RP20R11R10RP44R28R23RP68R41R34
RP21R12R13RP45R29R33RP69R41R38
RP22R12R15RP46R29R35RP70R42R39
RP23R13R12RP47R30R25
RP24R13R15RP48R31R34
Table 6. Fault currents through primary and backup relay pairs.
Table 6. Fault currents through primary and backup relay pairs.
Primary
Relay
Fault
Current (A)
Backup
Relay
Fault
Current (A)
Primary
Relay
Fault
Current (A)
Backup
Relay
Fault
Current (A)
R111,648.9R3670.7R218446.1R3829.0
R111,648.9R191839.0R218446.1R191008.5
R111,648.9R211954.9R223676.2R243675.5
R25493.0R55475.9R235633.3R282643.6
R38454.8R11771.5R244773.9R224772.4
R38454.8R191516.9R254048.0R304049.4
R38454.8R211613.0R266137.9R206140.3
R46141.8R61777.1R273572.0R323567.2
R46141.8R71962.6R285828.0R233212.8
R57080.3R27059.4R298237.6R331484.9
R69107.0R43339.6R298237.6R35983.7
R69107.0R72640.4R303428.9R253426.2
R77561.2R42217.5R316177.5R343560.5
R77561.2R63389.4R316177.5R381519.4
R83677.8R91865.3R316177.5R411128.8
R83677.8R401806.4R323462.9R273464.2
R94173.4R82826.2R339327.5R291477.9
R94173.4R401348.9R339327.5R35499.0
R103220.9R113224.8R345175.9R312035.3
R112409.6R102407.2R345175.9R381533.1
R127288.1R13630.8R345175.9R411605.4
R127288.1R15437.4R356880.3R291154.0
R133670.6R12602.9R356880.3R33347.3
R133670.6R15457.7R363876.2R371603.8
R142386.1R18456.5R374450.0R362095.1
R154879.3R12732.7R385488.5R311509.8
R154879.3R1381.5R385488.5R342801.4
R161467.2R171466.0R385488.5R411196.5
R171937.1R161936.4R393238.3R423237.9
R182961.1R14963.7R404514.0R83056.0
R1912,808.9R11957.7R404514.0R91464.7
R1912,808.9R31279.3R416597.0R311478.5
R1912,808.9R211756.7R416597.0R343613.4
R202892.6R262878.5R416597.0R381537.6
R218446.1R11266.0R422596.3R392592.7
Table 7. Operational times between P/B relay pairs with CTI.
Table 7. Operational times between P/B relay pairs with CTI.
Relay PairsALORelay PairsALO
Primary Backup Tp (s) Tb (s) CTI (s) Primary Backup Tp (s) Tb (s) CTI (s)
R1R40.1300.4630.332R21R40.1680.3750.206
R1R200.1300.3810.251R21R200.1680.3820.213
R1R220.1300.3720.242R22R230.1130.4400.327
R2R60.1880.4670.279R23R270.1160.5510.435
R3R20.1190.3690.250R24R210.1040.4970.393
R3R200.1190.4080.289R25R290.3160.5210.205
R3R220.1190.3960.277R26R190.1340.3570.223
R4R50.1770.5200.343R27R310.1010.3710.270
R4R80.1770.4920.315R28R240.2840.5010.216
R5R10.1800.4990.318R29R340.1080.3160.208
R6R30.1530.4210.268R29R360.1080.3830.275
R6R80.1530.4390.286R30R260.1160.7320.616
R7R30.1580.4760.318R31R330.1120.3450.233
R7R50.1580.4130.255R31R370.1120.3320.220
R8R100.1490.4050.256R31R420.1120.3430.231
R8R390.1490.4250.277R32R280.1380.3920.254
R9R70.1740.4560.282R33R300.1160.3160.200
R9R390.1740.4660.292R33R360.1160.5150.399
R10R120.1940.5200.326R34R320.1000.3010.201
R11R90.1780.5040.327R34R370.1000.3310.231
R12R140.1470.4860.339R34R420.1000.3180.218
R12R160.1470.5160.368R35R300.1310.3480.217
R13R110.1730.4670.293R35R340.1310.5210.389
R13R160.1730.5060.333R36R380.2120.5230.312
R14R170.1990.6270.428R37R350.1200.4340.314
R15R110.1630.4110.248R38R320.1230.3270.204
R15R140.1631.3161.154R38R330.1230.3670.244
R16R180.1750.5900.415R38R420.1230.3390.216
R17R150.1910.5160.325R39R410.1510.3560.205
R18R130.1820.5690.387R40R70.2180.4430.225
R19R20.1260.3560.231R40R100.2180.4210.203
R19R40.1260.3570.231R41R320.1190.3290.210
R19R220.1260.3850.260R41R330.1190.3440.225
R20R250.1860.4800.294R41R370.1190.3310.212
R21R20.1560.4200.264R42R400.1130.3590.245
Table 8. Optimal setting for dual-setting DOCRs in distribution part of the IEEE-30 bus system using ALO.
Table 8. Optimal setting for dual-setting DOCRs in distribution part of the IEEE-30 bus system using ALO.
Relay No.ForwardReverseRelay No.ForwardReverse
TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu)
R10.0760.0550.0790.209R220.0400.1880.3430.027
R20.1300.0380.5050.067R230.0380.3380.2260.086
R30.0910.0260.1620.025R240.0710.0290.2050.090
R40.0500.1240.2420.041R250.2040.0300.4450.033
R50.1930.0710.1540.238R260.0950.0310.2520.041
R60.0600.1330.1700.108R270.0720.0180.1510.144
R70.1200.0600.1510.064R280.1960.0330.2290.089
R80.0550.1050.1990.083R290.0560.1450.1280.054
R90.0450.1130.1440.080R300.0430.1590.2550.084
R100.1290.0850.1450.129R310.0810.0280.1760.023
R110.0500.1540.2870.094R320.0940.0210.2500.022
R120.0590.0840.0990.070R330.0820.0470.1780.019
R130.1030.0050.2390.003R340.0630.0430.2180.029
R140.0780.0300.1220.055R350.0900.0410.1520.037
R150.0720.0910.2380.004R360.0980.0960.3430.006
R160.0470.0390.1570.055R370.0750.0390.3160.016
R170.0580.0260.3740.048R380.0930.0200.2150.011
R180.1340.0030.1810.008R390.1190.0100.2940.006
R190.0780.0980.1390.048R400.1730.0130.2030.019
R200.0600.0300.2340.044R410.0870.0300.2460.005
R210.1150.0510.1580.040R420.0900.0080.3010.007
OF (s) = 6.084 s
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Al-Bhadely, F.; İnan, A. Enhancing Coordination Efficiency with Fuzzy Monte Carlo Uncertainty Analysis for Dual-Setting Directional Overcurrent Relays Amid Distributed Generation. Sensors 2024, 24, 4109. https://doi.org/10.3390/s24134109

AMA Style

Al-Bhadely F, İnan A. Enhancing Coordination Efficiency with Fuzzy Monte Carlo Uncertainty Analysis for Dual-Setting Directional Overcurrent Relays Amid Distributed Generation. Sensors. 2024; 24(13):4109. https://doi.org/10.3390/s24134109

Chicago/Turabian Style

Al-Bhadely, Faraj, and Aslan İnan. 2024. "Enhancing Coordination Efficiency with Fuzzy Monte Carlo Uncertainty Analysis for Dual-Setting Directional Overcurrent Relays Amid Distributed Generation" Sensors 24, no. 13: 4109. https://doi.org/10.3390/s24134109

APA Style

Al-Bhadely, F., & İnan, A. (2024). Enhancing Coordination Efficiency with Fuzzy Monte Carlo Uncertainty Analysis for Dual-Setting Directional Overcurrent Relays Amid Distributed Generation. Sensors, 24(13), 4109. https://doi.org/10.3390/s24134109

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop