Next Article in Journal
An Improved Time-Frequency Analysis Method for Hydrocarbon Detection Based on EWT and SET
Next Article in Special Issue
Fault Prediction and Diagnosis of Wind Turbine Generators Using SCADA Data
Previous Article in Journal
Optimizing the Structure of Distribution Smart Grids with Renewable Generation against Abnormal Conditions: A Complex Networks Approach with Evolutionary Algorithms
Previous Article in Special Issue
Optimal Power Transmission of Offshore Wind Power Using a VSC-HVdc Interconnection
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Predictive Power Control Strategy for DFIGs Based on a Wind Energy Converter System

1
College of Electrical and Information Engineering, Hunan University, Changsha 410082, China
2
College of Electrical and Information Engineering, Zhengzhou University of Light Industry, Zhengzhou 450002, China
3
College of Electrical and Information Engineering, Hunan Institute of Engineering, Xiangtan 411100, China
4
Institute of Research and Development, Duy Tan University, Da Nang 550000, Vietnam
5
Faculty of Electrical Engineering, Industrial University of Ho Chi Minh City, Ho Chi Minh City 700000, Vietnam
*
Author to whom correspondence should be addressed.
Energies 2017, 10(8), 1098; https://doi.org/10.3390/en10081098
Submission received: 7 June 2017 / Revised: 20 July 2017 / Accepted: 23 July 2017 / Published: 26 July 2017
(This article belongs to the Special Issue Wind Generators Modelling and Control)

Abstract

:
A feasible control strategy is proposed to control a doubly fed induction generator based on the wind energy converter system (DFIG-WECS). The main aim is to enhance the steady state and dynamic performance under the condition of the parameter perturbations and external disturbances and to satisfy the stator power response of the system. Within the proposed control method, the control scheme for the rotor side converter (RSC) is developed on the model predictive control. Firstly, the self-adaptive reference trajectory is established from the deduced discrete state-space equation of the generator. Then, the rotor voltage is calculated by minimizing the global performance index under the current prediction steps at the sampling instant. Through the control scheme for the grid side converter (GSC) and wind turbine, we have re-applied the conventional control. The effectiveness of the proposed control strategy is verified via time domain simulation of a 150 kW-575 V DFIG-WECS using Matlab/Simulink. The simulation result shows that the control of the DFIG with the proposed control method can enhance the steady and dynamic response capability better than the conventional ones when the system faces errors due to the parameter perturbations, external disturbances and the rotor speed.

1. Introduction

1.1. Motivation

In previous years, there has been rapid growth in the renewable power generation industry, especially the wind power generation industry. It is reported that the global annual installed wind power capacity crossed the 60 million kilowatt (GW) mark in 2015 compared to 51.7 GW in 2014, and more than 63 GW of new wind power capacity was brought on line. Its market share and installed capacity continuously increase. Thanks to this, 2015 ranks as an unparalleled year for wind power generation industry as annual installations increased for the first time in history after a slowdown during the past few years [1]. According to the Global Wind Energy Council (GWEC), top markets in the world include PR China, USA, Germany, India, Spain, among which PR China and USA passed the 145 and 50 GW of wind energy installed mark by the end of 2015, respectively. With such a penetration of large-scale wind power in the grid, more and more posed supposition should be considered to enhance the operating wind farms regarding the electrical system. Therefore, the wind energy conversion systems (WECS) should control and monitor to the best of their ability under various operating conditions of the electrical system when they are connected to the power grid.
During the last decades, several solutions for the renewable electricity generation have been exploited with the main aim of obtaining energy from wind speed under optimal conditions. Due to the wind speed variability, the most popular configuration for wind power generation is currently the doubly fed induction generator (DFIG) as shown in Figure 1. The WECS includes a wound rotor induction generator (WRIG) together with slip rings and a back-to-back voltage source converter (VSC), in which the WRIG’s rotor is connected to the grid through a back-to-back (BTB) converter, whereas the stator is directly connected to one, and this BTB is controlled by several schemes. In this way, DFIGs can operate over a range of speed between about 70% and 130% of the synchronous speed, so that they can carry up to 30% of the total power [2,3,4].
In general, as shown in Figure 2, a variable-speed and-pitch DFIG-WECS has four operating zones, in which zones 2 and 3 are the most notable operating ones since the system operates in the variable-speed and -pitch modes, respectively. In a comparison with another wind turbine types, such as fixed-speed, variable-slip, and full-converter [5,6,7], DFIG has more advantageous characteristics. For example, it operates at optimal rotational speed for each given wind speed, reduces mechanical stresses, compensates for torque and power oscillations, and in particular, has the ability to control reactive power and decouple active and reactive power [8]. However, this system has a number of drawbacks, such as the limitation of the fault ride through capability, the inevitable need for slip rings, and more particularly in the complex control scheme for the converters to obtain the optimal generated power.

1.2. State of the Science

Based on these facts, the control of a WSEC becomes more significant, especially when using the electrical generator based on DFIG. With many different purposes, the DFIG is controlled through many various control strategies. For example, vector control is used based on either a stator voltage oriented [9,10] or stator flux oriented [11,12,13] vector by using a d-q synchronous frame for separately controlling the active and reactive power through a current controller. However, this method has the main disadvantage that depends highly on the parameters, such as the stator and rotor resistances and inductances. In order to overcome drawbacks from the vector method, in the mid-1980s, direct torque control (DTC) was examined in literature [14,15,16] to directly control the electromagnetic torque and the rotor flux of the DFIG by selecting the voltage vector from a predefined lookup table based on the stator flux and torque information. This control strategy has good characteristics, such as fast dynamic response, reliability, good perturbation rejection, and non-constant switching frequency behavior [5]. Nevertheless, its performance deteriorates during operation at low-speed. The predictive techniques [17], dither signal [18], and modified switching table [19] were proposed in order to solve this drawback. However, these strategies still have some disadvantages related to the hysteresis controllers that can cause the torque and current distortions and limit the steady-state accuracy [20]. Based on the same fundamentals of the DTC technique, direct power control (DPC) was proposed to independently and directly control the active and reactive power of DFIG based on the estimated reactive and active power and their errors. This control strategy has preponderant characteristics, such as fast dynamic response, grid disturbance, and robustness against parameter variations [21,22]. However, the performance of conventional DPC deteriorates due to the variable switching frequency. Moreover, the generated stator power can be controlled based on a portion of the turbine power by employing the feedback variable in the DPC controller [23]; the change in the turbine speed depends on the difference between turbine power and total generated power. Hence, this method can be degraded for controlling the generator speed and complicating the AC filter design. For improving the power control, the authors in [24,25] have proposed the scheme using the model-based predictive DPC technique.
For the purpose of excellent achievement of controlling the power for DFIG system under satisfactory stator power response, predictive control is an alternative control strategy. A new strategy based on the predictive direct power control (P-DPC) method is proposed in [26] to control the power at low constant switching frequency. The obtained results are satisfactory. However, the active and reactive power output is directly predicted. Authors in [27] introduced a direct power control method based on the finite model predictive control by using a discrete prediction model and a cost function to select the switching vector and to realize the optimal tracking control. In this way, the multi-objective optimization can easily be obtained by selecting different cost functions such that it does not have to use the coordinate transformation and the pulse wave modulation with a fast response [28]. However, this method still has drawbacks, such as the long calculation time of multi-step prediction, strong dependence on model parameters, and unfixed switching frequency. Besides, in order to realize the rapid power tracking, authors in [29] improved the predictive control for DC/AC converters based on DPC that was presented in [30]. Nevertheless, the calculated output reactive and active power and the time calculation still depend on the generator parameters and the compensative feedback of disturbance is not designed, and these are its main drawbacks.
Generally, the stator power and state-space equations of DFIG play an important role in directly controlling the stator active and reactive power. Based on such that, the author in [31] proposed a model predictive control method based on the state-space equations of stator power and rotor voltage to realize the power tracking control. Nonetheless, they failed to measure the error feedback and input limitation and to control the flexibly dynamic response. Having the same issue, the sliding-mode control method was introduced in [32,33] to perform tracking power control. The redemption of these methods is to establish the state-space equations of power and rotor voltage into the approximate equations, so that the internal uncertainties and external disturbances are large in practical operation, resulting in the serious oscillations and the secure over-boundary of the system.

1.3. Contribution

To enhance the steady-state and transient control performance of DFIG-WCES for the purpose of satisfying the stator power output response according to given wishful values under the impact of the errors due to the parameter perturbations and external disturbances, in this context, the authors propose a relevant control scheme for the rotor-side converter (RSC). This proposed method is developed based on: Firstly, to establish a novel discrete state-space model of DFIG in the stator voltage oriented reference frame, considering the stator power and the rotor voltage as the state and control variables, respectively. Secondly, to propose the self-adaptive model predictive control scheme based on the model predictive control (MPC) using the discrete state-space model considering the impact of errors and performance index. Then, the stability condition of the obtained control signal for the closed-loop of the whole system is carried for analysis. For the grid side converter (GSC) and wind turbine control strategies, we have re-applied the conventional control strategy as proposed by authors in [34].
The remainder of the paper is organized as follows: in Section 2, we explain the mathematical model of WECS-DFIG including the wind turbine and generator. The methodology is introduced in Section 3 to establish the relevant control scheme for the RSC. The case studies and results are displayed in Section 4. Finally, the conclusions are given in Section 5, and the parameters of the controllers and studied system are listed in Appendix A.

2. Mathematical Model of the Wind Energy Converter System

Figure 1 illustrates a wind energy converter system based on the doubly fed induction generator (WECS-DFIG), including the wind turbine, the control systems, electric generator, connected to the grid.

2.1. Dynamic Model of the Wind Turbine

The presentation of the mechanical system of the whole wind turbine is complex. For the purpose of modeling and simulation, the two-mass drive train model is proposed to study the dynamic stability of the mechanical system. The electromechanical dynamics are presented by the following equations [35]:
J d ω m d t = T m T e C f ω m ,
where J is the inertia of the generator-turbine system, Te is the electromagnetic torque, Cf is the frictional coefficient, ωm is the rotor mechanical angular speed, Pm is the turbine mechanical power and is given as [36,37]:
P m = P w C p ( β , λ ) ,
The wind power swept can be converted depending on the air density ρ, the turbine blade radius R, the wind speed Vw, as:
P w = 1 2 ρ π R 2 V w 3 .
The power coefficient can be defined as:
C p ( β , λ ) = i = 0 4 j = 0 4 α i j β i λ j .
The turbine tip-speed ratio λ is defined as:
λ = ω t R V w ,
The factors αi,j are listed in Table 1 [36].
The turbine output mechanical torque of WECS-DFIG can be derived as follows
T m = P m ω t ,
where ωt is the turbine rotational angular speed.

2.2. Generator Model

The generator is used for the objective of this study to be the wound rotor induction generator (WRIG); its expressions are written in the synchronous rotating d-q reference frame and can be expressed as [5,34,38]:
The d-q components of stator and rotor voltages are, respectively:
{ u s d = R s i s d + d λ s d d t ω s λ s q u s q = R s i s q + d λ s q d t + ω s λ s d u r d = R r i r d + d λ r d d t ( ω s ω r ) λ r q u r q = R r i r q + d λ r q d t + ( ω s ω r ) λ r d .
The d-q components of stator and rotor fluxes are, respectively:
{ λ s d = L s i s d + L m i r d λ s q = L s i s q + L m i r q λ r d = L m i s d + L r i r d λ r q = L m i s q + L r i r q .
The stator active and reactive powers are, respectively:
{ P s = 3 2 ( u s d i s d + u s q i s q ) Q s = 3 2 ( u s q i s d u s d i s q ) .
where Ls, Lr and Lm are the stator, rotor, and mutual inductances, respectively; Rs and Rr are the stator and rotor resistances, respectively; ωs the synchronous angular speed; and ωr is the angular frequency of the rotor calculated as pωm, where p is number of pole pairs.

2.3. Modeling of Generator for Predictive Power Control

The WECS-DFIG power control guides the independent stator active and reactive powers by regulating the rotor flux. For this purpose, the stator active and reactive powers are represented as functions of each individual rotor flux. We use the stator voltage vector oriented control (usd = us and usq = 0) that decouples the dq axis. Thus, Equation (8) becomes
{ i s d = L m L m 2 L s L r λ r d i s q = L m L m 2 L s L r ( λ r q + u s L r L m ω s ) ,
The stator active and reactive powers can be calculated by substituting Equations (10) into (9); we have:
{ P s = 3 2 u s K σ λ r d Q s = 3 2 u s K σ ( λ r q + u s L r L m ω s ) ,
where K σ = L m / σ L s L r is constant and σ = 1 ( L m 2 / L s L r ) is the leakage factor.
Equation (7) indicates that the rotor voltage directly controls rotor fluxes when neglecting the rotor resistance. In addition, as seen in Equation (11), the rotor fluxes will reflect on the stator active and reactive powers. Thus, this basis can be used in controlling the stator active and reactive power of the WECS-DFIG on its rotor side.
Taking the time derivative of Equation (11) along the trajectory of the rotor flux and combining Equation (7) under the stator voltage vector oriented control mode, neglecting the rotor resistance, the stator active and reactive power becomes:
d d t [ P s ( t ) Q s ( t ) ] = [ 0 ( ω s ω r ) ( ω s ω r ) 0 ] [ P s ( t ) Q s ( t ) ] + [ 3 2 u s K σ 0 0 3 2 u s K σ ] [ u r d ( t ) u r q ( t ) ] + [ 1 0 0 1 ] [ ( ω s ω r ω s ) ( 3 2 u s 2 K σ L r L m ) 0 ] ,
Assume that the mechanical angular speed of the rotor is greater than that of the electricity [39], so that the mechanical angular speed is constant and is a valid approximation to each sample period [40,41]. Hereby, the slip speed is constant, due to the synchronous speed being clamped by the grid frequency.
Apply the zero order hold with no delay to discretize Equation (12) considering the sampling period T and the sampling time k [42]. In addition, due to the applied rotor side, the voltage is constant during a power control period for the pulse width modulation (PWM) converter. Therefore, Equation (12) becomes
[ P s ( k + 1 ) Q s ( k + 1 ) ] x ( k + 1 ) = [ 1 ( ω s ω r ) T ( ω s ω r ) T 1 ] A [ P s ( k ) Q s ( k ) ] x ( k ) + [ 3 2 u s K σ T 0 0 3 2 u s K σ T ] B [ u r d ( k ) u r q ( k ) ] u ( k ) + [ T 0 0 T ] G [ ( ω s ω r ω s ) ( 3 2 u s 2 K σ L r L m ) 0 ] . w ( k )
Equation (13) can be rewritten under the following space-state form
{ x ( k + 1 ) = A x ( k ) + B u ( k ) + G w ( k ) , y ( k + 1 ) = C x ( k + 1 ) ,
where x(.), u(.) and w(.) 2 are state, input vector, and measurable vectors, respectively; y(.) is the output signal; A, B and G 2 × 2 are the state, control, and measurable matrices, respectively; and C is the identity matrix. The corresponding equations for all components are as follows:
{ x ( k ) = [ P s ( k ) Q s ( k ) ] , u ( k ) = [ u r d ( k ) u r q ( k ) ] w ( k ) = [ ( ω s ω r ω s ) ( 3 2 u s 2 K σ L r L m ) 0 ] A = e A T [ 1 0 0 1 ] + A T = [ 1 ( ω s ω r ) T ( ω s ω r ) T 1 ] B = 0 T e A T B d τ B T = [ 3 2 u s K σ T 0 0 3 2 u s K σ T ] G = 0 T e A T G d τ G T = [ T 0 0 T ] .
Therefore, the DFIG-WECS was modeled as predictive power control, as shown in Equation (14), in which the active and reactive power is considered as the state variables and the rotor voltage is considered as the input signals. Therefore, the model in the system of Equation (14) can be applied to establish the control scheme for the RSC controller based on the self-adaptive model predictive control for the predictive power control.

3. Proposed Predictive Power Control Strategy

Figure 3 illustrates the block diagram for the completely proposed predictive power control system of the WESC-DFIG, which includes the main control system as the RSC, GSC, and wind turbine. The detailed contents are presented as follows.

3.1. RSC Controller

The control system of the RSC is designed to predict the power flow between the stator and grid based on the self-adaptive model predictive control developed from the model in Equation (14) considering: (i) analyzing the impact of the errors due to the parameter perturbations and external disturbances; (ii) designing the self-adaptive reference trajectory on the model predictive method. Figure 4 illustrates the relationship between the input and output of the system model, and the procedure is performed as follows:

3.1.1. Impact of Errors

Suppose that the model in Equation (14) is influenced by the parameter perturbation and external disturbances. The discrete-time predictive model can be obtained due to these errors as a state-space model as follows:
{ x ( k + 1 ) = ( A + Δ A ) x ( k ) + ( B + Δ B ) u ( k ) + G w ( k ) + f ( k ) y ( k + 1 ) = C x ( k + 1 ) ,
where ∆A and ∆B 2 × 2 are the parameter perturbations matrices and f(k) is the external disturbances vector.
The system in Equation (16) contains the state vector x(k). Calculate the difference between this state vector x(k) and the desired state vector x*(k); the error state-space model is generated under the condition of the error state-space functions e(k) = x(k) − x*(k) and e(k + 1) = x(k + 1) − x*(k + 1), and then e substitutes these error state-space functions into Equation (16). Therefore, the error state-space model can be obtained as follows:
{ e ( k + 1 ) = A e ( k ) + B u ( k ) + x ˜ ( k ) + G w ( k ) + d ( k ) y e ( k + 1 ) = C e e ( k + 1 ) ,
where the corresponding components are:
{ d ( k ) = Δ A x ( k ) + Δ B u ( k ) + f ( k ) x ˜ ( k ) = A x * ( k ) x * ( k + 1 ) .
Supposing that if the system in Equation (17) operates under the nominal condition, in other words d(k) = 0, the error state-space model becomes:
{ e ( k + 1 ) = A e ( k ) + B u ( k ) + x ˜ ( k ) + G w ( k ) y e ( k + 1 ) = C e e ( k + 1 ) ,
where ye(.) 2 and Ce 2 × 2 are the output vector and matrix, repectively.
Therefore, the system in Equation (19) is used as the basis to design the RSC controller whose objective is to obtain the output vector y e ( k ) equal to zero. In order to reach this objective, the output matrix C e can be determined from the pole assignment according to the design method of sliding mode surface, which was described in [43].

3.1.2. Design Self-Adaptive Model Predictive Controller

The basic idea of a self-adaptive model predictive controller is to control the active and reactive power flow between the stator and grid according to a given value based on the model predictive control (MPC). As above-mentioned, the objective is to control the output vector y e ( k ) of the state-space model in Equation (19) to reach zero. The procedure is done as follows:

Output Prediction

MPC is based on the predictions of future outputs over a prediction horizon having length P and the effect of changing the control horizon move M, as shown in Figure 5 [44]. In this study, we consider P ≥ M. The current control horizon move M happens in the system at the current sampling instant k and the future control move is kept invariant. The predictions of the whole system (19) can be obtained as [45]:
y P ( k + P ) = C e A P e ( k ) + i = 1 P C e A i 1 B u ( k + P i ) + i = 1 P C e A i 1 x ˜ ( k + P i ) + i = 1 P C e A i 1 G w ( k + P i ) .
The dimension of the P in Equation (20) plays an important role in improving controller performance. In this study, this value is set equal to 2 and the control horizon has a value of 1.
The output prediction state when having a control move from time (k − P) to time k can be obtained as [46]
y y ( k + P ) = C e A P e ( k P ) + i = 1 P C e A i 1 B u ( k i ) + i = 1 P C e A i 1 x ˜ ( k i ) + i = 1 P C e A i 1 G w ( k i ) ,
We now consider the internal and external uncertain factors of the prediction model that results in the output at a future time of the system in Equation (20), so that the accuracy of the prediction is affected. The error between the current actual output y e ( k ) of the error state-space model in Equation (19) at time k and the predictive output y y ( k + P ) in Equation (21) is used as the feedback correction of the predicted output y P ( k + P ) . Therefore, the predictive output of the closed-loop model can be obtained as follows [46]:
y ^ P ( k + P ) = y P ( k + P ) + H P ( y e ( k ) y y ( k + P ) ) ,
where H P 2 P × 2 P is the diagonal coefficient matrix used to adjust the proportion of the feedback errors. Applying engineering, the initial value of HP is usually selected between 0 and 1 [46], and for this study, the first and second values are chosen:
H 1 = [ 0.9 0 0 0.9 ] , H 2 = [ 0.45 0 0 0.45 ] .
As known, the existing feedback correction mechanism could produce the tracking delay and overshoot under an input step and so, for the rapid dynamic response system, this feedback correction mechanism is removed to enhance the dynamic response performance, whereas, the anti-disturbance performance does not take notice during processing. Therefore, in order to solve this problem, in this study, we propose an appropriate control threshold for Hp, that is, the feedback correction mechanism is removed when e ( k ) 1 10 4 and vice versa.

Reference Trajectory

In MPC applications, the reference trajectory is one of the advantages of a predictive control scheme. The reference trajectory denotes a first order exponential curve used to make a gradual transition to the desired set-point value. If the value of the output function y ( k ) should move to the desired value r ( k ) along a reference trajectory with respect to the sampling time instant k, the output reference trajectory over the prediction horizon can be denoted as [46]:
y r ( k + P ) = ζ y r ( k + P 1 ) + ( 1 ζ ) r ( k + P ) y r ( k ) = y e ( k )
where ζ = d i a g { γ + τ e ( k ) 1 μ + e ( k ) 1 γ + τ e ( k ) 1 μ + e ( k ) 1 } is an adjustable variable, in which 0 < γ < μ , 0 < τ < 1 , this value constitutes an adjustable value 0 < ( γ + τ e ( k ) 1 ) / ( μ + e ( k ) 1 ) < 1 that could influence the response of the system. Figure 6 plots two trajectory forms according to two different values of ζ when the reference r ( k + P ) is constant. Observed from this figure, the reference trajectory is fast tracked according to the small values of ζ as shown in the curve of y r _ 1 ( k + P ) ; if this value of ζ is increased, the reference trajectory becomes the curve of y r _ 2 ( k + P ) , slowly giving rise to a smoother response.

Performance Index

The MPC is one of the few control strategies having the ability to cope with the constrained system providing an optimal control for a certain performance index. The objective of the whole system is to regulate the system output to the wishful values while keeping the performance index minimal and satisfying the above constraints. We now consider an MPC design problem with the global optimization performance index of the whole system at the sampling time instant k as [45]:
J ( k ) = i = 1 P y r ( k + i ) y ^ P ( k + i ) Q i 2 + j = 1 M u ( k + j 1 ) R j 2 ,
where Q and R are the weighting matrices used to measure the importance degree of the tracking error and control variable in performance indexes.
The local performance index of the whole system can be rewritten under the matrix form using quadratic programming notation [47], that is:
J ( k ) = ( Y r ( k + 1 ) Y ^ P ( k + 1 ) ) T Q ( Y r ( k + 1 ) Y ^ P ( k + 1 ) ) + U ( k ) T R U ( k ) ,
where the corresponding components are the follows:
{ Y ^ P ( k + 1 ) = [ y ^ P ( k + 1 ) , , y ^ P ( k + P ) ] T Y r ( k + 1 ) = [ y r ( k + 1 ) , , y r ( k + P ) ] T U ( k ) = [ u ( k ) , , u ( k + M 1 ) ] T Q = d i a g { Q 1 , , Q P } R = d i a g { R 1 , , R M } .
Transforming Equations (20)–(22) and (24) into the state-space form and then substituting them into Equation (26), we have:
J ( k ) = ( Z y e ( k ) F e ( k ) G U ( k ) V X ˜ ( k ) L W ( k ) H E ( k ) ) T Q ( Z y e ( k ) F e ( k ) G U ( k ) V X ˜ ( k ) L W ( k ) H E ( k ) ) + U ( k ) T R U ( k ) ,
where
{ F = [ C e A , , C e A P ] T , G = [ C e B 0 0 0 C e A M 1 B C e B C e A P 1 B i = 1 P M + 1 C e A i 1 B ] , V = [ C e 0 0 C e A C e 0 C e A P 1 C e A P 2 C e ] , L = [ C e G 0 0 C e A G C e G 0 C e A P 1 G C e A P 2 G C e G ] , H = d i a g { H 1 , , H P } , Z = [ ζ 1 , , ζ P ] T , X ˜ ( k ) = [ x ˜ ( k ) , , x ˜ ( k + P 1 ) ] T , W ( k ) = [ w ( k ) , , w ( k + P 1 ) ] T , E ( k ) = [ y e ( k ) y y ( k ) , , y e ( k ) y y ( k + P ) ] T , U ( k ) = [ u ( k + 1 ) , , u ( k + M ) ] T .
Determining the voltage value U based on the control objective of the system by mean of minimizing the global performance index (28) at time k, in other words, J / U = 0 and the explicit solution, we can obtain the following equation:
U ( k ) = ( G T Q G + R ) 1 G T Q ( Z y e ( k ) F e ( k ) V X ˜ ( k ) L W ( k ) H E ( k ) ) .
Thus, in each control period, the manipulated variable can obtain as follows:
u ( k ) = D ( G T Q G + R ) 1 G T Q ( Z y e ( k ) F e ( k ) V X ˜ ( k ) L W ( k ) H E ( k ) ) ,
where D = [ I 0 0 ] .

3.1.3. Stability Analysis of the Self-Adaptive Model Predictive Controller

The stability condition of the above-mentioned closed-loop of the whole system is analyzed in this section; considering the system (17), the predicted actual output at p-step can be obtained as follows:
y ( k + P ) = C e A P e ( k ) + i = 1 P C e A i 1 B u ( k + P i ) + i = 1 P C e A i 1 x ˜ ( k + P i ) + i = 1 P C e A i 1 G w ( k + P i ) + i = 1 P C e A i 1 d ( k + P i ) .
The system (32) can be expressed under the following state-space form
Y ( k + 1 ) = F e ( k ) + G U ( k ) + V X ˜ ( k ) + L W ( k ) + V D ( k ) ,
Merging Equations (33) and (30), the predicted actual output of the closed-loop of system can be expressed as follows:
Y ( k + 1 ) = F e ( k ) + G ( ( G T Q G + R ) 1 G T Q ( Z y e ( k ) F e ( k ) V X ˜ ( k ) L W ( k ) H E ( k ) ) ) + V X ˜ ( k ) + L W ( k ) + V D ( k ) .
According to the performance index (26), there exists the condition depending on the weight coefficient matrix R that can limit the control input value U(k). When it is equal to zero, the control input U(k) will be unlimited [46]. Applying this condition to Equation (34), we have:
Y ( k + 1 ) = Z y e ( k ) H E ( k ) + V D ( k ) .
In addition, Equation (17) is calculated according to the time that is a start point (k − p); the actual output can be obtained at time k as follows:
y ( k ) = C e A P e ( k P ) + i = 1 P C e A i 1 B u ( k i ) + i = 1 P C e A i 1 x ˜ ( k i ) + i = 1 P C e A i 1 G w ( k i ) + i = 1 P C e A i 1 d ( k i ) .
Combining Equations (32) and (36), and the matrix E ( k ) in Equation (29), we have
E ( k ) = i = 1 P C e A i 1 d ( k i ) = D ˜ ( k ) ,
where
= [ C e 0 0 C e C e A 0 C e C e A C e A P 1 ]   and   D ˜ ( k ) = [ d ( k 1 ) , d ( k 2 ) , , d ( k P ) ] T .
Therefore, the actual output of the closed-loop system can be described as follows:
y ( k + 1 ) = D ( k ) ( Z y e ( k ) H D ˜ ( k ) + V D ( k ) ) .
Equation (38) can be rewritten under another form as follows:
y ( k + 1 ) = ζ 1 y e ( k ) + C e d ( k ) H 1 C e d ( k 1 ) .
It can be concluded that from Equation (39), the following inequality holds, if the disturbance value or its change rate is limited
C e d ( k ) H 1 C e d ( k 1 ) ξ ,
so that the closed-loop control system in Equations (17) and (31) is stable, where ξ is a positive constant.
In order to prove the above conclusion is right, we decompose the system in Equation (39) into two parts as follows:
{ y 1 ( k + 1 ) = ζ 1 y e ( k ) , y 2 ( k + 1 ) = C e d ( k ) H 1 C e d ( k 1 ) .
Obviously, 0 < ( γ + τ e ( k ) 1 ) / ( μ + e ( k ) 1 ) < 1 , thus k 0 < such that y 1 ( k + 1 ) 0 when k > k 0 . This given condition implies that y 2 ( k + 1 ) ξ . Thus, y ( k + 1 ) ξ when k > k 0 . It can be concluded that the actual status of the closed-loop control system will certainly be converged and stabilized within the neighborhood of ξ . Therefore, the closed-loop control system is constructed by the system in Equations (17) and (31) is stable.
Therefore, the steady and dynamic response capability of power follows between the DFIG-WECS, and the grid is enhanced by the proposed control scheme for RSC is as shown in Figure 3. The control signal u(k) in Equation (31) is the closed-loop system.

3.2. GSC Controller

The GSC is connected between the DC-link and grid via the grid filter, as shown in Figure 1. The main task is to maintain the reactive power flow between the GSC and grid at zero and the DC-link voltage at a given value. The GSC is controlled by using the inner current control loop that is used to control the current and outer control loop that is used to control the DC-link voltage. The control strategy is implemented in the synchronously rotating d-q reference frame with its d-axis oriented with the grid voltage vector based on the vector control technique that was introduced by authors in [34]. This control strategy is re-used for this study as shown in Figure 3, in which the reactive power is controlled on the remaining component q axis, whereas the d component is used to control the active power and the outer DC-link voltage loop by the PI regulators.

3.3. Turbine Control

In order to limit over produced power at high wind speeds and to optimize the extracted power from incoming winds, more recently, the authors in [34,48,49] have proposed the strategies to control the pitch angle. For this study, the maximum power point tracking (MPPT) model is used to control the turbine system with the pitch angle control scheme introduced by the author in [34], as shown in Figure 7. When winds are between about the cut-in speed and at a low limit speed, the reference speed of the generator rotor is set to a minimum value to ensure that the slip is smaller than 30%. When winds are between the low limit speed and the rated speed, the generator is operated in the variable speed model; the maximum power is obtained according to the reference speed that can be calculated as follows:
ω r _ r ef = P m K opt 3 ,
where Kotp = (1/2)(R2/λotp3)ρπ Cpmax(β,λ) is the optimal constant of turbine corresponding to the pitch angle equal to zero, while λ is adjusted to λopt according to different wind speeds by adapting the ωr_ref. In addition, when winds increase larger than the rated speed, the ωr_ref is set at the rated value, so that the over produced power is limited by adjusting the pitch angle resulting in the over speed of generator being limited.

4. Case Study and Results

In order to verify the performance of the proposed method, the simulation modeling setup for the tested system including a 150 kW-575 V DFIG-WCES and 50 Hz-20 MVA/25 kV network is built in the Matlab/Simulink, as shown in Figure 6. The parameters are listed in Appendix A. In this paper, we only consider the following two scenarios:
(i)
The impact of the rotor speed variation,
(ii)
The impact of the parameter variation of the generator.
The effectiveness of the proposed control strategy is tested based on the various active and reactive power steps. Suppose that the stator active power output reference is maintained at 40% of the generator rated power, increased to 67% at 0.8 s, and then continued to increase to 100% at 1.05 s corresponding to the power factor reference value PFref of 85%, −85%, and 100%, respectively. The reference value of the stator reactive power out can be computed according to PFref as follows
Q s . r ef = P s . r ef 1 P F r e f 2 1 .
The obtained result is compared to two difference methods that are the model predictive control introduced by authors in [31] and the discrete sliding-mode control introduced by authors in [32]. All necessary parameters of these methods are listed in the Appendix A.

4.1. Case 1

The first scenario is carried out to verify the response of the system considering the variation in rotor speed. The DFIG-WSEC was operating under the speed control mode; for this study, the wind speeds were changed to from the sub-rated of 7 m/s to super-rated 15 m/s at a threshold value 0.7 s (the rated wind speed is 12 m/s), which corresponds to the increase of rotor speed from 151.2 to 172.8 rad/s at time from 0.7 s to 1.15 s, as shown in Figure 8. As known, during the period of variation wind speed, the rotor speed changes slowly since the turbine inertia is high.
Figure 9 plots the results of the step reference test of the stator power response, which for the steady state, a zoomed-in image of the power waveforms over period time from 0.65 to 0.69 s, the reference active power is maintained at 40% of the generator rated active power. For the transient, a zoomed-in image of the waveforms over period time from 0.798 to 0.804 s, which corresponds to the reference active power that changes the power suddenly from 40% to 67% rated power at 0.8 s. The improved steady and state-transient response characteristic can be closely observed when applying the proposed method.
Figure 10 presents the response of DC-link voltage with the given reference Uref of 500 V during the steady-state and transient period. The obtained result shows that DC-link voltage oscillations have appeared as a small backward overshoot. The PI controllers of GSC, compensating the disturbances due to changing the reference active power, dampen them. It can be noticed clearly from this figure that the proposed control scheme of GSC is suitable.
The rotor and stator three-phase currents are plotted in Figure 11. Observe from Figure 11a and two zoomed-in images of the stator current waveforms of over period time from at 0.805 to 0.825 s and from 1.025 to 1.045 s in Figure 11b that the steady-state and transient responses of currents are improved when applying the proposed method.

4.2. Case 2

The second scenario is carried out to verify the effectiveness of the proposed control strategy through the same tests of step reference of active and reactive powers considering: (i) the constant rotor speed at 172.8 rad/s corresponds to the wind speed of 15 m/s and (ii) the impact of the parameter variation was introduced by increasing 20% of the nominal values of both the rotor resistance and mutual inductance parameters of the DFIG.
The result of the step reference test of stator power response is plotted in Figure 12, in which for the steady state, a zoomed-in image of the power waveforms over period time from 0.665 to 0.705 s, the reference active power is maintained at 40% of the generator rated active power. For the transient, a zoomed-in image of the power waveforms over period time from 1.04 to 1.06 s, corresponds to the reference active power that changes suddenly from 67% to 100% rated power. Figure 13 plots the detailed steady-state and transient response of the DC-link voltage and the rotor. The detailed steady-state and transient responses of three-phase currents are shown in Figure 14, in which Figure 14a shows the oscillations of rotor currents and Figure 14b; for the steady-state, a zoomed-in image of the power waveforms over time from 0.8 to 0.83 s, the reference active power is maintained at 40% of the generator rated active power. For the transient, a zoomed-in image of the waveforms over time from 1.03 to 1.06 s, corresponding to the reference active power that suddenly changes the power from 40% to 67% rated power at 1.05 s.
Comparing Figure 9 and Figure 12, Figure 10 and Figure 13, and Figure 11 and Figure 14, there can difficulty in noticing any difference. Even when the variations of the rotor resistance and mutual inductance are large, the system maintains satisfactory performance under steady state and transient response.
The simulation results show that the steady state and transient responses of the active and reactive power when applying the proposed method are better than compared with two other methods, and this is because the mechanism feedback error is considered in this proposed method. In addition, it can be observed clearly that the steady-state and transient response of the stator and rotor currents are good although the proposed method does not use the current loops to control them.

5. Conclusions

In this paper, a feasible and efficient control strategy for the rotor converter of DFIG, making full use of properties within the generator-turbine system without using any extra, is proposed. This proposed method is developed on the model predictive control and is compared to two other methods. Based on the obtained results through the simulation of a 150 kW-575 V doubly fed induction generator based on the wind energy converter system (DFIG-WECS) using MATLAB/Simulink, the main features of the self-adaptive model predictive control strategy are listed as follows. (i) To propose the discrete state-space model of DFIG with using the voltage oriented control mode and considering the stator power and the rotor voltage as the state and control variables is feasible and efficient, in which the stator flux was no longer explicit to avoid the error caused by flux observation; (ii) The steady-state and transient response characteristic when applying the proposed control strategy has been significantly improved compared to two conventional methods, especially when the system faces errors due to the parameter perturbations (variation of the rotor resistance and mutual inductance) and external disturbances (rotor speed verifies according to the changes of wind speed); (iii) The control of the active and reactive power does not need to use the rotor current loops. Hence, this proposed control strategy becomes a helpful power control strategy for the renewable power generation based on the WECS, and especially to DFIG.

Acknowledgments

The authors sincerely acknowledge the financial support provided by the National Natural Science Foundation of China (NSFC) Changsha, China under project No. 51177040.

Author Contributions

All the authors have contributed in the article.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Symbols
AState matrix of discrete state-space model
BControl matrix of discrete state-space model
COutput matrix of discrete state-space model
CeOutput matrix of error discrete state-space model
CfFrictional coefficient
e(.)State vector of error state-space model
GMeasurable matrix of discrete state-space model
HpDiagonal coefficient matrix
JInertia of the generator-turbine system
KotpOptimal constant of turbine corresponding to the pitch angle equal to zero
LsStator inductance
LrRotor inductance
LmMutual inductance
MControl horizon
PPrediction horizon
PFPower factor
PmTurbine mechanical power
PsStator active power
Q, RPair of weight matrices in the cost function of predictive control
QsStator reactive power
RTurbine blades radius
RrRotor resistance
RsStator resistance
TeElectromagnetic torque
VwWind speed
irRotor current
isStator current
f(k)External disturbances vector
u(.)Input vector
urRotor voltage
usStator voltage
w(.)Measurable vector
x(.)State vector
y(.)Output vector
ye(.)Output vector of error state-space model
AState parameter perturbations matrix
BInput parameter perturbations matrix
αi,jFactors of power coefficient
γTuning parameter of adjustable variable of reference trajectory
λTurbine tip-speed ratio
λrRotor flux
λsStator flux
µTuning parameter of adjustable variable of reference trajectory
ρAir density
σLeakage factor
τTuning parameter of adjustable variable of reference trajectory
ωmRotor mechanical angular speed
ωrRotor angular speed
ωsSynchronous angular speed
ωtTurbine rotational angular speed
ζAdjustable variable of reference trajectory
Acronyms
BTBBack-to-back
DFIGDoubly fed induction generator
DFIG-WECSDoubly fed induction generator based on the wind energy converter system
DPCDirect power control
DTCDirect torque control
GSCGrid side converter
GWECGlobal Wind Energy Council
MPCModel predictive control
MPPTMaximum power point tracking
P-DPCPredictive direct power control
PWMPulse width modulation
RSCRotor side converter
VSCVoltage source converter
WECSWind energy converter system
WRIGWound rotor induction generator

Appendix A

The simulation parameters of the tested system are listed below:
  • DFIG. Nominal power is 150 kW, voltage is 575 V, stator resistance is 0.02475 Ω, rotor resistance 0.0133 Ω, stator leakage inductance is 0.000284 H, rotor leakage inductance is 0.00284 H, mutual inductance is 0.01425 H, and inertia constant is 2.6 kg.m2.
  • Converter. Resistance of grid filter is 0.03 p.u., inductance of grid filter is 0.3 p.u., DC-link’s rated voltage is 500 V, and DC-link capacitor 0.01 F.
  • GSC control. The DC-link voltage regulator: Kp = 112.4, Ki = 25.6; the current power regulator (d-axis): Kp = 9.7, Ki = 0.04; the current power regulator (q-axis): Kp = 9.7, Ki = 0.04.
  • The pitch angle controller. Kp = 100, Ki = 8, βmax = 45 degrees, βmin = 0 degrees, Tβ = 0.1 s.
  • Other Parameters of Per Control method.
Table A1. Other parameters of per control method.
Table A1. Other parameters of per control method.
ParametersMethods
ProposedModel PredictiveSliding-Mode
Value
The control period T c = 5 × 10 5 s T c = 5 × 10 5 s T c = 5 × 10 5 s
The weighting matrices Q = [ 10 0 0 1 ] R = [ 25 0 0 15 ] Q = [ 10 0 0 1 ] R = [ 25 0 0 15 ] -
The prediction P and control horizon M P = 2 M = 1 P = 2 M = 1 -
The first and second coefficient diagonal matrices H 1 = [ 0.90 0 0 0.90 ] H 2 = [ 0.45 0 0 0.45 ] --
The output matrix C = [ 1 0 0 1 ] C = [ 1 0 0 1 ] C = [ 1 0 0 1 ]
Another condition constant μ = 1000 , γ = 700 , and   τ = 0.3 - ε T c = 0.1 ,   and δ T c = 0.6

References

  1. The Global Wind Report Annual Market Update 2015. Available online: http://www.gwec.net (accessed on 25 April 2016).
  2. Soliman, M.; Malik, O.P.; Westwick, D.T. Multiple model predictive control for wind turbines with doubly fed induction generators. IEEE Trans. Sustain. Energy 2011, 2, 215–225. [Google Scholar] [CrossRef]
  3. Vinothkumar, K.; Selvan, M.P. Novel scheme for enhancement of fault ride-through capability of doubly fed induction generator based wind farms. Energy Convers. Manag. 2011, 52, 2651–2658. [Google Scholar] [CrossRef]
  4. Muller, S.; Deicke, M.; De Doncker, R.W. Doubly fed induction generator systems for wind turbines. IEEE Ind. Appl. Mag. 2002, 8, 26–33. [Google Scholar] [CrossRef]
  5. Abad, G.; Lopez, J.; Rodríguez, M.; Marroyo, L.; Iwanski, G. Doubly Fed Induction Machine: Modeling and Control for Wind Energy Generation; John Wiley & Sons: Hoboken, NJ, USA, 2011. [Google Scholar]
  6. Petru, T.; Thiringer, T. Modeling of wind turbines for power system studies. IEEE Trans. Power Syst. 2002, 17, 1132–1139. [Google Scholar] [CrossRef]
  7. Qiao, W.; Harley, W.; Venayagamoorthy, G.K. Dynamic modeling of wind farms with fixed-speed wind turbine generators. In Proceedings of the 2007 IEEE Power Engineering Society General Meeting, Tampa, FL, USA, 24–28 June 2007; pp. 1–8. [Google Scholar]
  8. Ackermann, T. Wind Power in Power Systems; John Wiley & Sons: Hoboken, NJ, USA, 2005. [Google Scholar]
  9. Hu, J.; He, Y.; Xu, L.; Williams, B.W. Improved control of DFIG systems during network unbalance using PI–R current regulators. IEEE Trans. Ind. Electron. 2009, 56, 439–451. [Google Scholar] [CrossRef]
  10. Chondrogiannis, S.; Barnes, M. Stability of doubly-fed induction generator under stator voltage orientated vector control. IET Renew. Power Gener. 2008, 2, 170–180. [Google Scholar] [CrossRef]
  11. Hao, S.; Abdi, E.; Barati, F.; McMahon, R. Stator-flux-oriented vector control for brushless doubly fed induction generator. IEEE Trans. Ind. Electron. 2009, 56, 4220–4228. [Google Scholar]
  12. Hopfensperger, B.; Atkinson, D.J.; Lakin, R.A. Stator-flux-oriented control of a doubly-fed induction machine with and without position encoder. IEE Proc. Electr. Power Appl. 2000, 147, 241–250. [Google Scholar] [CrossRef]
  13. Pena, R.; Clare, J.C.; Asher, G.M. Doubly fed induction generator using back-to-back PWM converters and its application to variable-speed wind-energy generation. IEE Proc. Electr. Power Appl. 1996, 143, 231–241. [Google Scholar] [CrossRef]
  14. Zhi, D.; Xu, L. Direct power control of DFIG with constant switching frequency and improved transient performance. IEEE Trans. Energy Convers. 2007, 22, 110–118. [Google Scholar] [CrossRef]
  15. Takahashi, I.; Noguchi, T. A new quick-response and high-efficiency control strategy of an induction motor. IEEE Trans. Ind. Appl. 1986, 820–827. [Google Scholar] [CrossRef]
  16. Depenbrock, M. Direct self-control (DSC) of inverter-fed induction machine. IEEE Trans. Power Electron. 1988, 3, 420–429. [Google Scholar] [CrossRef]
  17. Baader, U.; Depenbrock, M.; Gierse, G. Direct self control (DSC) of inverter-fed induction machine: A basis for speed control without speed measurement. IEEE Trans. Ind. Appl. 1992, 28, 581–588. [Google Scholar] [CrossRef]
  18. Kazmierkowski, M.P.; Kasprowicz, A.B. Improved direct torque and flux vector control of PWM inverter-fed induction motor drives. IEEE Trans. Ind. Electron. 1995, 42, 344–350. [Google Scholar] [CrossRef]
  19. Vas, P. Sensorless Vector and Direct Torque Control; Oxford Univercity Press: Oxford, UK, 1998. [Google Scholar]
  20. Buja, G.S.; Kazmierkowski, M.P. Direct torque control of PWM inverter-fed AC motors—A survey. IEEE Trans. Ind. Electron. 2004, 51, 744–757. [Google Scholar] [CrossRef]
  21. Datta, R.; Ranganathan, V.T. Direct power control of grid-connected wound rotor induction machine without rotor position sensors. IEEE Trans. Power Electron. 2001, 16, 390–399. [Google Scholar] [CrossRef]
  22. Xu, L.; Cartwright, P. Direct active and reactive power control of DFIG for wind energy generation. IEEE Trans. Energy Convers. 2006, 21, 750–758. [Google Scholar] [CrossRef]
  23. Mohd Zin, A.A.B.; Mahmoud Pesaran, H.A.; Khairuddin, A.B.; Jahanshaloo, L.; Shariati, O. An overview on doubly fed induction generators′ controls and contributions to wind based electricity generation. Renew. Sustain. Energy Rev. 2013, 27, 692–708. [Google Scholar] [CrossRef]
  24. Zhi, D.; Xu, L.; Williams, B.W. Model-based predictive direct power control of doubly fed induction generators. IEEE Trans. Power Electron. 2010, 25, 341–351. [Google Scholar]
  25. Hu, J.; Zhu, J.; Dorrell, D.G. Model-predictive direct power control of doubly-fed induction generators under unbalanced grid voltage conditions in wind energy applications. IET Renew. Power Gener. 2014, 8, 687–695. [Google Scholar] [CrossRef]
  26. Abad, G.; Rodríguez, M.Á.; Poza, J. Three-level NPC converter-based predictive direct power control of the doubly fed induction machine at low constant switching frequency. IEEE Trans. Ind. Electron. 2008, 55, 4417–4429. [Google Scholar] [CrossRef]
  27. Cortés, P.; Kazmierkowski, M.P.; Kennel, R.M.; Quevedo, D.E.; Rodríguez, J. Predictive control in power electronics and drives. IEEE Trans. Ind. Electron. 2008, 55, 4312–4324. [Google Scholar] [CrossRef]
  28. Rodriguez, J.; Cortes, P. Predictive Control of Power Converters and Electrical Drives; John Wiley & Sons: Hoboken, NJ, USA, 2012; Volume 40. [Google Scholar]
  29. Wang, X.; Sun, D. Three-Vector-Based Low-Complexity Model Predictive Direct Power Control Strategy for Doubly Fed Induction Generators. IEEE Trans. Power Electron. 2017, 32, 773–782. [Google Scholar] [CrossRef]
  30. ALarrinaga, S.; Vidal, M.A.R.; Oyarbide, E.; Apraiz, J.R.T. Predictive control strategy for DC/AC converters based on direct power control. IEEE Trans. Ind. Electron. 2012, 54, 1261–1271. [Google Scholar] [CrossRef]
  31. Sguarezi Filho, A.J.; Ruppert Filho, E. Model-based predictive control applied to the doubly-fed induction generator direct power control. IEEE Trans. Sustain. Energy 2012, 3, 398–406. [Google Scholar] [CrossRef]
  32. Hu, J.; Nian, H.; Hu, B.; He, Y.; Zhu, Z.Q. Direct active and reactive power regulation of DFIG using sliding-mode control approach. IEEE Trans. Energy Convers. 2010, 25, 1028–1039. [Google Scholar] [CrossRef]
  33. Shang, L.; Hu, J. Sliding-mode-based direct power control of grid-connected wind-turbine-driven doubly fed induction generators under unbalanced grid voltage conditions. IEEE Trans. Energy Convers. 2012, 27, 362–373. [Google Scholar] [CrossRef]
  34. Le, V.; Li, X.; Li, Y.; Dong, T.L.T.; Le, C. An Innovative Control Strategy to Improve the Fault Ride-Through Capability of DFIGs Based on Wind Energy Conversion Systems. Energies 2016, 9, 69. [Google Scholar] [CrossRef]
  35. Iov, F.; Hansen, A.D.; Sorensen, P.; Blaabjerg, F. Wind Turbine Blockset in Matlab/Simulink; Aalborg University: Aalborg, Denmark, 2004. [Google Scholar]
  36. Miller, N.W.; Price, W.W.; Sanchez-Gasca, J.J. Dynamic Modeling of GE 1.5 and 3.6 Wind Turbine-Generators; GE—International, Power Systems Energy Consulting: Schenectady, NY, USA, 2003. [Google Scholar]
  37. Tohidi, A.; Abedinia, O.; Bekravi, M.; Ojaroudi, N. Multivariable adaptive variable structure disturbance rejection control for DFIG system. Complexity 2014. [CrossRef]
  38. Wu, B.; Lang, Y.; Zargari, N.; Kouro, S. Power Conversion and Control of Wind Energy System; John Wiley & Sons: Hoboken, NJ, USA, 2011. [Google Scholar]
  39. Hindmarsh, J. Worked Examples in Electrical Machines and Drives: Applied Electricity and Electronics; Elsevier: Amsterdam, The Netherlands, 1982. [Google Scholar]
  40. Yamamura, S. Spiral Vector Theory of AC Circuits and Machines; Oxford University Press: Oxford, UK, 1992. [Google Scholar]
  41. Holtz, J.; Quan, J.; Pontt, J.; Rodr´ıguez, J.; Newman, P.; Miranda, H. Design of fast and robust current regulators for high-power drivesbased on complex state variables. IEEE Trans. Ind. Appl. 2004, 40, 1388–1397. [Google Scholar] [CrossRef]
  42. Franklin, G.F.; Powel, J.D.; Workman, M.L. Digital Control of Dynamic Systems; Addison-Wesley: Boston, MA, USA, 1998; Volume 3. [Google Scholar]
  43. Perruquetti, W.; Barbot, J.P. Sliding Mode Control in Engineering; CRC Press: Beijing, China, 2002. [Google Scholar]
  44. Seborg, D.E.; Mellichamp, D.A.; Edgar, T.F.; Doyle, F.J., III. Process Dynamics and Control; John Wiley & Sons: Hoboken, NJ, USA, 2010. [Google Scholar]
  45. Li, S.; Zheng, Y. Distributed Model Predictive Control for Plant-Wide Systems; John Wiley & Sons: Hoboken, NJ, USA, 2016. [Google Scholar]
  46. Xi, Y.G. Predictive Control; PRC Press: Beijing, China, 1993. [Google Scholar]
  47. Maciejowski, J.M. Predictive Control with Constraints; Prentice-Hall: Harlow, UK, 2002. [Google Scholar]
  48. Duong, M.Q.; Grimaccia, F.; Leva, S.; Mussetta, M.; Ogliari, E. Pitch angle control using hybrid controller for all operating regions of SCIG wind turbine system. Renew. Energy 2014, 70, 197–203. [Google Scholar] [CrossRef]
  49. Duong, M.Q.; Grimaccia, F.; Leva, S.; Mussetta, M.; Le, K.H. Improving transient stability in a grid-connected squirrel-cage induction generator wind turbine system using a fuzzy logic controller. Energies 2015, 8, 6328–6349. [Google Scholar] [CrossRef] [Green Version]
Figure 1. Schematic diagram of the DFIG-WECS.
Figure 1. Schematic diagram of the DFIG-WECS.
Energies 10 01098 g001
Figure 2. Ideal static curves for a DFIG-WECS.
Figure 2. Ideal static curves for a DFIG-WECS.
Energies 10 01098 g002
Figure 3. The proposed control scheme for the DFIG based on WCES.
Figure 3. The proposed control scheme for the DFIG based on WCES.
Energies 10 01098 g003
Figure 4. General concept of the proposed rotor side converter (RSC) control method: (a) General schematic; (b) Discrete-time system overview with disturbances.
Figure 4. General concept of the proposed rotor side converter (RSC) control method: (a) General schematic; (b) Discrete-time system overview with disturbances.
Energies 10 01098 g004
Figure 5. General concept for model predictive control (MPC).
Figure 5. General concept for model predictive control (MPC).
Energies 10 01098 g005
Figure 6. Reference trajectory according to the different values of ζ.
Figure 6. Reference trajectory according to the different values of ζ.
Energies 10 01098 g006
Figure 7. The pitch angle control scheme for the DFIG-WCES [34].
Figure 7. The pitch angle control scheme for the DFIG-WCES [34].
Energies 10 01098 g007
Figure 8. The rotor speed of DFIG according to the changes in wind speed.
Figure 8. The rotor speed of DFIG according to the changes in wind speed.
Energies 10 01098 g008
Figure 9. Detailed steady- and transient-state response of stator power output in Case 1: (a) Active; (b) Reactive.
Figure 9. Detailed steady- and transient-state response of stator power output in Case 1: (a) Active; (b) Reactive.
Energies 10 01098 g009aEnergies 10 01098 g009b
Figure 10. Detailed steady-state and transient response of the DC-link voltage in Case 1.
Figure 10. Detailed steady-state and transient response of the DC-link voltage in Case 1.
Energies 10 01098 g010
Figure 11. Detailed steady-state and transient response of three-phase currents in Case 1: (a) Rotor; and (b) Stator.
Figure 11. Detailed steady-state and transient response of three-phase currents in Case 1: (a) Rotor; and (b) Stator.
Energies 10 01098 g011
Figure 12. Detailed steady-state and transient response of stator power output in Case 2: (a) Active; and (b) Reactive.
Figure 12. Detailed steady-state and transient response of stator power output in Case 2: (a) Active; and (b) Reactive.
Energies 10 01098 g012
Figure 13. Detailed steady-state and transient response of the DC-link voltage in Case 2.
Figure 13. Detailed steady-state and transient response of the DC-link voltage in Case 2.
Energies 10 01098 g013
Figure 14. Detailed steady-state and transient response of three-phase currents in Case 2: (a) Rotor; and (b) Stator.
Figure 14. Detailed steady-state and transient response of three-phase currents in Case 2: (a) Rotor; and (b) Stator.
Energies 10 01098 g014
Table 1. The coefficients of αij for i,j = 0, 1, ..., 4.
Table 1. The coefficients of αij for i,j = 0, 1, ..., 4.
i/j01234
0−4.1909 × 10−12.1808 × 10−1−1.2406 × 10−2−1.3365 × 10−41.1524 × 10−5
1−6.7606 × 10−26.0405 × 10−2−1.3934 × 10−21.0683 × 10−3−2.3895 × 10−5
21.5727 × 10−2−1.0996 × 10−22.1495 × 10−3−1.4855 × 10−42.7937 × 10−6
3−8.6018 × 10−45.7051 × 10−4−1.0479 × 10−45.9924 × 10−6−8.9194 × 10−8
41.4787 × 10−5−9.4839 × 10−61.6167 × 10−6−7.1535 × 10−84.9686 × 10−10

Share and Cite

MDPI and ACS Style

Yang, X.; Liu, G.; Li, A.; Dai, L.V. A Predictive Power Control Strategy for DFIGs Based on a Wind Energy Converter System. Energies 2017, 10, 1098. https://doi.org/10.3390/en10081098

AMA Style

Yang X, Liu G, Li A, Dai LV. A Predictive Power Control Strategy for DFIGs Based on a Wind Energy Converter System. Energies. 2017; 10(8):1098. https://doi.org/10.3390/en10081098

Chicago/Turabian Style

Yang, Xiaoliang, Guorong Liu, Anping Li, and Le Van Dai. 2017. "A Predictive Power Control Strategy for DFIGs Based on a Wind Energy Converter System" Energies 10, no. 8: 1098. https://doi.org/10.3390/en10081098

APA Style

Yang, X., Liu, G., Li, A., & Dai, L. V. (2017). A Predictive Power Control Strategy for DFIGs Based on a Wind Energy Converter System. Energies, 10(8), 1098. https://doi.org/10.3390/en10081098

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop