Next Article in Journal
3D Evolutionary Reconstruction of Scalar Fields in the Gas-Phase
Next Article in Special Issue
Energy and Economics Analyses of Condenser Evaporative Precooling for Various Climates, Buildings and Refrigerants
Previous Article in Journal
Control Strategy for Active Hierarchical Equalization Circuits of Series Battery Packs
Previous Article in Special Issue
Supporting the Smart Readiness Indicator—A Methodology to Integrate A Quantitative Assessment of the Load Shifting Potential of Smart Buildings
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Integration of Measurements and Time Diaries as Complementary Measures to Improve Resolution of BES

1
Division of Building, Energy and Environment Technology, Department of Technology and Environment, University of Gävle, 80176 Gävle, Sweden
2
Technology and Social Change, Linköping University, 58183 Linköping, Sweden
3
Division of Energy Systems, Department of Management and Engineering, Linköping University, 58183 Linköping, Sweden
*
Author to whom correspondence should be addressed.
Energies 2019, 12(11), 2072; https://doi.org/10.3390/en12112072
Submission received: 23 April 2019 / Revised: 27 May 2019 / Accepted: 27 May 2019 / Published: 30 May 2019
(This article belongs to the Special Issue Energy Performance and Indoor Climate Analysis in Buildings)

Abstract

:
Building energy simulation (BES) models rely on a variety of different input data, and the more accurate the input data are, the more accurate the model will be in predicting energy use. The objective of this paper is to show a method for obtaining higher accuracy in building energy simulations of existing buildings by combining time diaries with data from logged measurements, and also to show that more variety is needed in template values of user input data in different kinds of buildings. The case studied in this article is a retirement home in Linköping, Sweden. Results from time diaries and interviews were combined with logged measurements of electricity, temperature, and CO2 levels to create detailed occupant behavior schedules for use in BES models. Two BES models were compared, one with highly detailed schedules of occupancy, electricity use, and airing, and one using standardized input data of occupant behavior. The largest differences between the models could be seen in energy losses due to airing and in household electricity use, where the one with standardized user input data had a higher amount of electricity use and less losses due to airing of 39% and 99%, respectively. Time diaries and interviews, together with logged measurements, can be great tools to detect behavior that affects energy use in buildings. They can also be used to create detailed schedules and behavioral models, and to help develop standardized user input data for more types of buildings. This will help improve the accuracy of BES models so the energy efficiency gap can be reduced.

1. Introduction

In the European Union (EU), buildings are responsible for approximately 40% of energy use and 36% of CO2 emissions [1]. The building sector is also responsible for about 60% of electricity consumption, and about one-third of the total energy use in the building sector can be related to non-domestic buildings [2]. In 2016, the total energy use in the building sector in Sweden was 80.5 TWh, and approximately 27% of this energy use was from public buildings [3]. When renovating or constructing new buildings, it is important to have an idea on how the energy use will be affected by the users. One way to do this is with building energy simulation (BES). However, BES models rely on a variety of different input data, and the more accurate the input data are, the more accurate the model will be in predicting energy use. In many cases, when it comes to whole-building simulation, there are significant discrepancies between simulated results and actual energy use of the real buildings [4]; this is called the “energy performance gap” [5]. However, whole-building simulation is often held as the best approach when it comes to analyzing performance in the building industry [6]. Many times, these differences come from the behavioral patterns of the residents, which are hard to predict and to simulate [7]. In Sweden, it is now standard to use template values and schedules for user behavior. The template values used in Sweden are usually from Sveby´s reports on standardized user input data, which are available for residential housing, office buildings, and schools [8,9,10]. Sveby stands for “standardize and verify energy performance in buildings”, and it is a branch overlapping program that produces instruments that aid and standardize energy use. However, these template values and schedules were only developed for residential buildings in the form of apartment buildings and detached homes, and not for other types of residential buildings such as retirement homes or homes for people with special needs. In Reference [11], the authors made a review article where they studied research articles which dealt with the impact of occupant behaviors on building energy analysis. They concluded that most research in the field studied residential and office buildings, while a small number studied commercial and educational buildings, and sparse attention was given to recreational and healthcare facilities. As this paper shows, the available template values from Sveby do not always provide a good prediction of user behavior and, therefore, the simulations lack in accuracy compared to real buildings.
Another way to simulate user behavior and its impact on energy use in a building is to use behavioral models. Many behavioral models that has been developed uses data from large national surveys based on time diaries [12,13,14,15]. However, these behavioral models were also only developed for residential housing. In Reference [12], the authors presented a method for generating realistic occupancy schedules and electricity load profiles for United Kingdom (UK) households, where they used data from a large time-use survey (TUS) on how people used their time, which was conducted in the UK in 2000. The data used included location of participants and if they were active (not asleep) for each ten-minute diary period. The data did not contain any information on electricity use; however, according to the article, electricity use is highly connected to active occupants. Their conclusions were that the simulated output and original TUS data correlate very closely, and that the technique of building transaction matrices from such data in order to generate synthetic data series is very effective and computationally efficient. The authors of Reference [13] presented a method to generate load profiles for household electricity and domestic hot-water (DHW) use from time-use data. The profiles were generated from a detailed dataset on the time use for everyday activities in Swedish households, and the results were compared to electricity and hot-water profiles from recently performed measurements. They said that their model makes realistic reproductions of electricity demand for individual households and generates well-corresponding load distributions when compared to available measurement data. “The overall energy-use pattern found in measured data is well described by the model, while magnitudes sometimes deviate” [13]. In Reference [14], the authors developed a high-spatial-resolution model of energy use in residential buildings using data from national TUS data from the United States (US) residential sector. Their model was more detailed then previous models in the way that it was used down to a zone level in a building rather than an entire building. One conclusion they drew is that, if energy simulation tools can result in better decisions in energy-efficient renovations of single-unit structures where owners have full control over their property (in the US, this is approximately 65 million properties), it can have substantial societal impact. In Reference [15], the authors also made a probabilistic occupancy model for residential buildings, and tested it against Belgian TUS data. However, none of these studies or behavioral models were made for specific types of buildings; rather, they were made from large datasets and only from regular residential buildings. To the best knowledge of the authors of this article, such behavioral models are not widely used compared to the use of template values in the building industry.
The aim of this article is to show a method on how to improve the resolution of BES models on existing buildings by integrating measurements of electricity use, indoor temperature, and CO2 levels with time diaries. The aim is also to show how occupant behavior in a retirement home can differ from occupant behavior according to template values for regular residential buildings, and how these differences can affect energy use in a building. It shows the need for the development of template values to use in BES models for more types of buildings than currently available. The article will also contribute to the knowledge on occupant behavior in retirement homes, which according to Reference [11] is sparse.

2. Method and Case Description

In the present study, a model of an existing building was created in the general simulation software IDA-ICE (IDA Indoor Climate and Energy) version 4.8 [16]. Input data for the model were obtained through interviews and time diaries, logged measurements, blueprints, and onsite observations. IDA-ICE is a dynamic whole-building energy simulation software that was released in 1998, in which building energy use, indoor climate, and heating and cooling loads can be simulated. The validity of IDA-ICE was tested several times throughout the years with good results [16,17,18].

2.1. Theory and Related Research

2.1.1. Validation of BES Models

There are three basic approaches for validating BES models. The first one is analytical validation, where the model is compared to a given and exact solution, the second approach is peer model validation, where the model is compared to peer models with the same input data, and the third approach is empirical/realistic validation, where the model is compared to empirically collected data [19,20]. When performing a realistic validation, one can use metering and auditing data from actual residential and commercial buildings to compare the model [19]. User behavior is usually also included in these models, but setting occupant behavior schedules is difficult due to the variable nature of occupants [19]. In their conclusion, Sanquist and Ryan [19] stated that realistic validation cases need to be included in building energy validation procedures to improve the accuracy of building energy models. Sanquist and Ryan [19] also stated that there were not any major improvements in the methods used to model occupant behavior, and that the use of stochastic and other detailed behavior models could improve predictions of energy models, but at a much greater cost than current schedule-based occupant models. There were not many attempts at empirical validation of occupied buildings [21]. A few examples on studies that used empirical validation include References [21,22,23,24]. La Fleur, Moshfegh, and Rohdin [21] measured electricity, indoor temperature, and CO2 level in two apartments, both before and after renovation. The aim of their study was to present numerical predictions, validation, and evaluation of energy use and indoor climate for the building before and after renovation. Good agreement was reported, both in annual heat demand and indoor temperature, between simulation results and measurements. La Fleur, Moshfegh, and Rohdin [21] concluded that assumptions on user behavior have significant impact on energy-saving potential. In the article by Liu et al. [22], two almost identical buildings built in the 1970s in Sweden were studied. One building was retrofitted during 2009‒2010, and the other was not yet retrofitted. In the study, a mixed-methods approach was used, i.e., conducted measurements and simulations on the buildings, as well as handing out questionnaires with questions about the indoor environment to the residents of both buildings. The electricity use and indoor temperature were measured. Based on the electricity measurements, schedules for electricity use were created and compared with the predicted results of indoor temperature and heat demand; good agreement was achieved between them. A similar approach was conducted by Reference [23], as they validated their BES model against detailed measurements of electricity at the appliance level in a passive house, with good agreement. Some of the differences in simulated and real results in building simulation models can, as previously stated by Reference [21] amongst others, be due to behavior of the building’s occupants. Large offsets between simulated results and actual energy use, due to differences between actual and simulated behavior, can be a problem [7]. Gauthier and Shipworth [25] described a couple of different behavioral responses connected with thermal discomfort according to the following factors: increasing/decreasing clothing insulation level (clo), operative temperature, and increasing frequency, duration, and/or amplitude of localized behavioral responses such as consuming hot food and/or liquids, changing location to another room in the dwelling, opening and closing of curtains and/or windows, and changing body position. Some of these responses have a direct impact on energy use in the dwelling, such as opening and closing of windows [26]. A lot of behavior models were designed for use in energy simulations, and many of them use data from national time-use surveys, which are based on data from time diaries [12,13,14,15], as described above. These models rarely took opening of windows and doors into account; however, other models were developed for this purpose (e.g., Reference [26]). A method on how to model and validate BES models was proposed by Raftery et al. [4]. The proposed approach was evidence-based, which means that changes to the input parameters could only be made according to available evidence under clearly defined priorities. This was done to minimize the differences between real and simulated energy use for buildings [4]. The proposed method follows a certain sequence of steps that should be done in order to get as good results as possible. The first step is preparation, where an initial model is constructed, and historical weather data and calibration data are gathered, in addition to setting acceptance criteria for the model. Calibration data should be gathered and used according to the following hierarchy: (1) data-logged measurement; (2) spot or short-term measurement; (3) direct observation; (4) operator and personnel interviews; (5) operation documents; (6) commissioning documents; (7) benchmark studies and best practice guides; (8) standards, specifications, and guidelines; (9) design stage information. The acceptance criteria are values of, for instance, energy use and zonal indoor temperatures during a certain period of time, whereby the model should match to be called validated. In the second step, the model is updated with the information gathered, and the simulation is run. The model is tested against the acceptance criteria, and, if it checks out, the model is validated. If it does not meet the acceptance criteria, an iterative process is started where new measurements or data are obtained, and the model is updated and tested until it meets the acceptance criteria. According to Reference [4], the proposed methodology was based on some of the best techniques from the reviewed literature of their study, and it combined these with an evidence-based approach that used version control software to track the calibration process.
Standards, specifications, guidelines, and template values, such as Sveby’s standardized user input data, come in at place eight out of nine in the hierarchy proposed by Reference [4] for input data in building energy simulations. Despite this, standards such as user input data for housing, office buildings, and schools from Sveby are consistently used when new building energy performance is simulated in the design phase of a project. They are also used when renovations and/or retrofits are done in existing buildings. This is mainly because more accuracy is not required by the Swedish Boverket (National Board of Housing, Building, and Planning).

2.1.2. Time Diaries and Interviews

Time diaries are a method developed from the time-geographical perspective, and are commonly used in everyday life studies on energy use with a time-geographical approach (e.g., References [27,28,29]). With this method, it is possible to describe and analyze the relationship between activity, location, and movements of individuals. On the individual level, a rhythmic pattern may occur, which shows the central role of the dwelling, the workplace, and, for shorter visits, the places where friends and relatives live and where shops are located. It is also of interest to understand how often or for how long a social activity occurs, and how these social activities relate to other events that are involved in structuring an individual’s daily, weekly, or monthly pattern (e.g., how a coffee break with a friend in the apartment affects energy use). The difference between a time diary and an ordinary diary is that it is a written biography that describes a period of an individual’s life more or less systematically. Even though the time diary often has a certain aim related to the study objectives, and the researchers specify what they want the respondent to reflect upon, in the end, it is the respondent who decides what will be written and what will be left out [30]. Asking people to write diaries will make people more aware of the practices they are involved in (e.g., how many times they open the window (routines)). A time diary offers a chance to reflect upon their everyday life, which might get them to remember things and why they are doing things in a specific way. This can also help the respondents explain why they do certain things. Today, a time diary might be in paper or digital format. In a digital format time diary, people record their activities on their mobile phone or computer and then share those electronically [31]. This is less time-consuming for both the respondent and the researcher.

2.1.3. Energy Affecting Behavior in Swedish Households

According to Reference [10], the general population in Sweden has the following routines and behavior which affect energy: they are at home for about 14 h per day and use annually around 30 kWh/m2 of household electricity, with about 4 kWh/m2 of energy losses due to airing and 25 kWh/m2 due to DHW use.

2.2. The Case Study

Comparable with many countries around the world, the population of Sweden is aging [32,33]. The city block consists of tenants with different types of rental forms and, in the building, both housing and care homes (dementia housing) and service dwellings are present. Some tenants rent directly from the private property owner, while other tenants rent through the municipality (service and dementia housing and special housing). Most people who live in the housing complex are age 65 or older. Older people in Sweden are more reluctant to change housing than younger age groups [34,35]. In Sweden, aging in place was a political goal for a long time; hence, most older people in Sweden live in their ordinary homes with the assistance of home and medical care when needed. How many people live in assisted-living accommodation and how many have assistance in home can be seen in Table 1.
The city block that was the case for this study contains 99 apartments, of which 35 are assisted-living accommodation for elderly people. Elderly people have their own apartments with a safety alarm, and two healthcare providers (private and public) operate in the building, as well as a nurse. The building complex consist of five different buildings, where it is possible to walk between three of them without having to go outside (they are in the same building body); the other two buildings are detached three-story buildings with 15 apartments in each, evenly distributed on the three stories. No renovation was done since the block was built in 1983, with only minor repairs taking place. This type of housing includes a canteen where lunch is served, and there are also leisure activities in which all elderly people in the municipality can take part. Most of the people living in the block are at least 65 years old. Tenants in this specific building complex rent an apartment directly from the property owner, and the people in need of assisted living rent their apartment from the municipality. There is also a residence for elderly people with dementia in a separate part of the building complex. The building that was modeled and simulated was one of the two detached buildings. The building and the simulation model can be seen in Figure 1. Technical data of the modeled building, as well as data of its location, can be found in Table 2. This specific city block is geographically located in Östergötland, a county in the south of Sweden that has a continental climate and belongs to the northern part of the temperate zone.

2.3. Data Collection

The data for this study were obtained through interviews and time diaries, logged measurements, blueprints, and onsite observations. The data were largely collected between 2014 and 2016, based on a pilot study carried out in 2013.

2.3.1. Conducting Time Diaries and Interviews

All tenants received an invitation to participate in the study (except those in the residence for dementia) by participating in interviews and/or by writing time diaries for a week. The interviews each lasted for at least one hour. Interviews were used to understand social phenomena and to complement the time diaries. For the interviews and time diaries, a total of 16 tenants agreed to participate. Ultimately, 11 of them participated in both the interviews and the time diaries. The tenants that agreed to participate kept a time diary for one week in which they wrote time, activity, place, with whom, which electrical appliances were used, and other comments. Two of the subjects lived with their spouse and also wrote their spouse’s activities in the time diary. Table 3 presents general information on the subjects that participated in both time diaries and interviews.

2.3.2. Field Measurements

At the same time as the tenants wrote time diaries, measurements of CO2 levels, relative humidity, indoor temperature, and electricity use were logged in their apartment. Temperature was measured with three loggers, one in the kitchen, one in the living room, and one in the bedroom. In some apartments, there were more than one bedroom, as a result, the temperature logger was set up in the master bedroom or the one that was used as bedroom. Relative humidity was logged in the kitchen and CO2 levels were logged either in the living room or the hallway. Electricity use was logged with an EliQ optical eye at five-minute intervals for each apartment. The logged measurements and time diaries were done between the period of 17 November and 2 February, two apartments at a time. Logged measurements were done in 12 of the 15 apartments in the building, and 11 of these tenants also kept a time diary; the tenants in the three remaining apartments did not wish to participate in the study. An energy mapping was also performed for the city block to allocate the different uses of electricity, energy for heating of domestic hot water (DHW), and energy for space heating. Some data could only be obtained for the entire block, such as energy for space heating and DHW use. Electricity meters of 15 apartments were, therefore, read once a week for two months, with approval from the tenants. The same was done with the electricity meters measuring the facility electricity, which includes electricity for the lighting of stairwells, corridors, common areas, and outside lighting, electricity for operation of automatic doors, elevators, and laundry rooms, and electricity used for a central ventilation system in the common area and offices of the block. Apart from the energy mapping, the tightness of the building envelope was measured by using the blower door technique in one apartment. Readings, measurements, and used measurement equipment can be found in Table 4, and each measuring equipment’s accuracy can be found in Table 5. On-site observations were made throughout the building complex, as it was useful in terms of understanding how the building was used by the tenants and the people working there, as well as also to check that the construction matched the provided blueprints of the building. Photographs were also taken to enrich the data material (see Reference [30]). Which data were used and for what purpose can be seen in Table 6.

2.4. Modeling and Validation of BES Models for This Study

Two models of the same building were created in this study: one reference model, BES-ref (building energy simulation reference model), which used template values for occupancy, airing, and electricity use, and one model where detailed schedules for occupancy, airing, and electricity were used, BES-v.2 (building energy simulation model version 2). The modeling of both BES-ref and BES v.2 was inspired by the method developed by Reference [4]. An initial model was built according to blueprints made available from the housing company, and the construction in the blueprints was confirmed with on-site observations where possible.

2.4.1. Model Input Data and Creation of Detailed Schedules

Input data for BES-ref and BES-v.2 can be seen in Table 7. Input data in the form of schedules for occupancy (absent from 7:00 a.m. to 5:00 p.m.) and electricity use (electricity use between 6:00 and 8:00 a.m. and between 3:00 and 11:00 p.m.) in BES-ref were set according to Sveby’s [10] user input data, and losses due to airing were added after simulations according to Sveby’s [10] user input data. For both BES-ref and BES-v.2, temperature was set according to logged measurements from 12 apartments, while ventilation air flows were set according to measurements at the inlets and outlets, DHW use was set according to the mean use per square meter for the city block, the heat exchanger efficiency was approximated for each apartment by analyzing the electricity use of the air handling unit (AHU), and the building airtightness was set according to measurements with the blower door technique. For BES-v.2, input data in the form of schedules for occupancy, electricity use, and airing were created by combining information from time diaries and interviews, with logged measurements of electricity use, indoor temperature, and CO2 levels. In cases where there were multiple people living in an apartment, several occupants were used in the simulations, each with their own unique occupancy schedule. An example on how the detailed schedules were created is presented below. The example follows the creation of detailed schedules for one day and one apartment. The first thing one needs to do is analyze the logged measurements and check the time diaries for reasons on why drops and peaks occur in temperature, CO2 levels, and electricity use. In Figure 2, we can see the logged measurements from apartment 5 on the second floor for 19 November, and Table 8 shows a transcription of the time diary from the same day written by the tenant living in that specific apartment.
The first interesting thing in the measurements for CO2 levels and temperature occurred around 8:30 a.m., as can be seen in Figure 2. To see the reason for the drop in CO2 and temperature, we can look at the entries from the time diary in Table 8. The tenant wrote that she put out linen on the balcony and left the balcony door open from 8:30‒8:50 a.m. This is the most probable cause for the drop in both temperature and CO2 level. To represent this in the model, an opening of the balcony door from 8:30 to 8:50 a.m. was entered into the opening schedule.
At around 9:30 a.m., we can see that the CO2 level slightly decreased, and it coincided with the tenant leaving the apartment and returning around 12:00 p.m., which is written in the time diary. The occupancy schedule was updated according to measurements and time diary entries. When the tenant returned around 12:00 p.m., one can see that both the temperature and CO2 levels started to increase; then, there was a drop around 1:30 p.m., which once again can be traced to the opening of the balcony door. Another observation was that the CO2 level increased even more and it peaked at around 4:00 p.m. This can be traced to the tenant having a friend over, which she also wrote in her time diary. This was modeled by inserting an extra occupant into the zone, who was only present from 1:45–4:00 p.m. on Wednesday. The peaks in electricity use can be traced to the tenant using the microwave, water boiler, and stove. The base load is most likely from the fridge and also the ventilation system, which is connected to the tenant’s electricity since each apartment has its own ventilation system (this conclusion was based on the fact that the base load was approximately the same in each apartment). The electricity schedule was created by reading the maximum amount of power and inserting equipment with the same maximum power into the zone in the model. The schedules were made for one week. If there were drops in temperature in the logged measurements, but no entry in the time diaries of any specific behavior that could be linked to a drop in temperature, these drops were considered to be due to airing. In cases where occupancy could not be determined by time diaries, it was determined by drops and peaks in the logged measurements of CO2 level.

2.4.2. Validation and Calibration of BES-ref and BES-v.2

The process of calibrating the schedules for electricity use, airing, and occupancy was then done. The schedule for electricity use was altered slightly after each simulation so that the simulated graph eventually mimicked the graph from the measurements as closely as possible, and the total amount of used electricity for each day was compared to the total simulated electricity use for the same day after each simulation, making sure that they matched. In the same way, the airing and occupancy schedules were slightly altered after each simulation until the simulated temperature and CO2 graphs corresponded with the measured temperature and CO2 graphs in a satisfying way (see Figure 3). The simulated mean temperature for the week was also checked against the measured mean temperature to make sure that they corresponded. The validation criteria for mean indoor temperature was ±0.1 °C for both BES-ref and BES-v.2, while the criteria for highest and lowest indoor temperature was ±0.1 °C for BES-v.2 if it was feasible. For electricity use, it was ±5% kWh, and, for the start and end time of drops and peaks in temperature, CO2 levels, and electricity use, it was ±30 min. The same procedure was performed for each apartment and its corresponding zone in the model.
As can be seen in Figure 3, the CO2 levels in the simulations are somewhat lower than the measurements, but the curves have a very similar shape. This was the same for all apartments, both in BES-ref and BES-v.2, and is probably due to a higher background level of CO2 in the measurements than that which was used in the simulations. This, however, does not interfere much with the results since the objective in this study was not to compare simulated CO2 levels to measurements, but rather to compare them to other simulated results, and the CO2 measurements were used as a guide to see that the occupancy and airing schedules were done properly.
The validation of the BES models was done with empirical validation. BES-ref was validated against mean indoor temperature from the measurements, and BES-v.2 was validated against temperature and CO2 graphs from the measurements, making sure that the graphs from the simulations followed the graphs from the measurements as described above. The validation and calibration process used in this study can be seen in Figure 4.

2.4.3. Comparison of the Two Models

After both models were validated, several simulations were conducted, and the two models were compared at three different levels: (1) building level, (2) apartment level, and (3) room level. This meant that all apartments were originally modeled as one zone; however, to compare at room level, one apartment was later modeled with separate zones for each room (see Figure 5). The parameters that were compared at each level can be seen in Table 9.

3. Results and Discussion

3.1. Measurements, Interviews, and Time Diaries

The mean temperature in the 12 apartments varied between 19.5 °C in the coldest apartment to 22.1 °C in the warmest apartment during the measuring period. This may seem odd; however, in interviews, some of the tenants stated that they used to turn down their radiators since they liked it a bit cooler inside. Domestic hot-water use was calculated from the total use for the city block to 345 L/m2 and year, which led to a total energy use for heating of water as 34.9 MWh in the modeled building. From all 12 apartments, logged measurements of indoor temperature, CO2 levels, relative humidity, and electricity use were collected for a week, and results from 19 November in apartment 5 on the second floor can be seen in Figure 2 (see Figure 5 for construction plan).
The level of detail in the time diaries varied between the different apartments, and one day from one of the most detailed time diaries was transcribed, as can be seen in Table 8. This is the time diary written by the tenant of the apartment from which the measurements in Figure 2 were collected. It is also from the same day, 19 November, as the results in Figure 2.
From the time diaries and the measurements, clear patterns could be seen for each household. Even though the patterns differed between the households, some clear differences compared to the general population of Sweden, henceforth called the general population, could be seen. For instance, many of them stated during the interviews and/or wrote in their time diaries that they aired their apartments a couple of times a day to get fresh air in. This could be seen in the measurements as drops in temperature and CO2 levels. This behavior is something that seems to be connected to something they “used to do” in their old house or apartment. As stated earlier, most of the tenants are over 65 years old and moved to this city block upon getting older; thus, this is probably a behavior that they grew up with, since it was common practice in Sweden to ventilate homes in this way. They also stayed at home for a longer time each day than the general population. The tenants are at home for approximately 20 h/day in this case, which is a difference of 6 h/day compared to Sveby´s user input data, which say that occupancy should be entered as 14 h/day. This was expected and does not seem strange since it is a retirement home and most of the tenants do not work anymore. If the household electricity use, which was read weekly for two months, is scaled up to be the same use for an entire year, this will also show large differences compared to the general population. The tenants in this study had an electricity use of approximately 19 kWh/m2∙year, while Sveby´s standard user input data say 30 kWh/m2∙year for the general population. The reasons for this might be many, but the most probable cause is that, since this is an elderly population, they do not seem to own as many electrical appliances as the general population. According to Sveby´s reports of user input data [36], electricity use can differ by around 30% between the summer and winter. This is, among other things, due to the large difference in daylight and the fact that people spend more time indoors during winter, since Sweden is situated in the northern part of the temperate and polar climate zone. This means that the difference between the occupants in the study and the regular population might differ even more since they probably have an even lower electricity use during the summer.

3.2. Comparing BES-ref to BES-v.2

3.2.1. Building Level

At building level, the simulated values of energy for space heating, electricity use, and energy loss due to airing were compared between BES-ref and BES v.2. The results show an increase in energy supplied by water radiators, district heating (DH), with 20%, an increase in air handling unit (AHU) heating (electrical) with 85%, a decrease in tenant electricity use with 39% (this is an input value, see Table 7), and an increase in energy loss due to airing with 99%from BES-ref to BES v.2 (see Table 10).
The two things that really stand out are losses due to airing and the increase in heating from the AHU. The reasons for the increase in electrical heating from the AHU can be traced back to the difference in input data between the two models. In many apartments, the efficiency of the heat exchanger was lowered after measurements showed a higher electricity baseload in these apartments that could only be traced to the AHU. In apartment 1 on the second floor, the heater in the AHU was set a lot higher than in the remaining apartments, which gave the tenant a temperature of 20 °C in the supply air from the AHU (this was entered into BES-v.2); this also led to a higher electricity use from the AHU. The difference in the amount of energy losses from airing might seem odd at a first glance; however, taking into account that, according to time diaries and interviews, they seem to air a lot more than the general population, it does not seem as odd anymore. However, this type of airing should not be needed in a building with an exhaust and supply air ventilation system with heat recovery. In a previous study of the same building block made by Carlander and Tullsson [37], where they conducted a survey using questionnaires of indoor climate, they got evidence pointing out that the AHUs do not work as well as they are supposed to, which might also contribute to more excessive airing than usual. The difference could also be due to the fact that the schedules could only be validated for one specific week in each apartment, but the schedules were then also used for full-year simulations; thus, it is possible that the tenants air less during colder days and more during warmer days. However, since the measurements and time diaries were all done during the heating season, the authors are confident that the tenants air quite a lot even during this period. The third interesting thing is the household electricity use. In BES-v.2, the input value was 39% less than in BES-ref. The value for BES-v.2 was acquired by reading the electricity meters of each apartment, and through the logged measurements. The input value of household electricity for BES-ref was taken from Sveby´s reports on standardized user input data. As can be seen, the standardized user input data are much higher than the actual use in this case. Electricity use can be 30% higher than average during the winter and 30% less than average during the summer according to Reference [10]. If this applies for the tenants in this case, it means even less internal gains during the summer and, therefore, probably even higher energy use for space heating. The tenants are, however, home a lot more than the average population. This means higher internal gains from occupancy than what you get from using template values; however, in the end, there was still a difference in total energy use for space heating of 24% between the two models, where BES-v.2 had the highest use.

3.2.2. Apartment Level

When analyzing the models on an apartment level, quite big differences can be seen between the two models (BES-ref and BES-v.2), as well as between the apartments themselves, especially in BES-v.2. The results from the five-day simulation periods can be seen in Table 11, and the results for the full-year simulation can be seen in Table 12. The apartment with the biggest difference in total energy use for space heating between BES-ref and BESv.2 was apartment 5 on the second floor, which is the apartment with the tenant who made the most detailed time diary. The difference in total energy use for space heating in this apartment was 170% according to the simulations. This seems to be due to the fact that she is one of the tenants with the lowest indoor temperature, which means that the BES-ref model of this apartment hardly used any energy for space heating at all (only 6.6 kWh including losses due to airing in the five-day simulation period). However, when airing, occupancy, and schedules for electricity use according to logged measurements and the time diary were added, the energy use for space heating increased with 329%. This is a product of the tenant using about 60% less electricity, and airing quite a lot more in BES-v.2 than in BES-ref. However, this tenant is not the one that seems to be doing the most airing. In the apartment with the highest losses due to airing, the difference between BES-ref and BES-v.2 was 991%. This, however, might not be as strange as it sounds, as the tenants in this apartment wrote in their time diary that they always had a window open during the night when they were sleeping, which can be seen quite clearly in the temperature measurements from their apartment. A distinct pattern of dropping temperature during the nights can be seen in Figure 6, which corresponds to the tenants’ entry of opening windows in their time diary. Figure 6 also shows the simulated temperature curves from the models BES-ref and BES-v.2. The temperature curve from BES-v.2 follows the logged measurement curve in a good way, while the curve from BES-ref has much less fluctuation in temperature compared to the logged measurements and BES-v.2.
The average difference in total energy use for space heating in the 15 apartments for the five-day simulations was 47%, and, for a full-year simulation, it was 37%. In general, the biggest differences between the models can be found in the amount of energy loss due to airing, both in full-year simulations and in the simulations of the validation periods. Since this was also the case in the building-level simulations, no further discussion on this takes place here. To be able to see how well the two models, BES-ref and BES-v.2, could replicate the logged measurements of temperature during the measurement period, a statistical analysis was done by calculating the mean bias error (MBE), normalized mean bias error (NMBE), and coefficient of variance (CV) of the root-mean-square error (RMSE) according to Reference [38]. Table 13 shows the results of MBE, NMBE, and CV (RMSE), when comparing simulated results of temperature to logged measurements. As can be seen in Table 13, BES-v.2 had a lower MBE, NMBE, and CV (RMSE) in all cases, which shows that BES-v.2 is better for predicting indoor temperature than BES-ref. According to ASHRAE Guideline 14, the MBE for hourly data of energy use should not exceed 10, and the CV (RMSE) should not be more than 30. In this case, the data are from every five minutes and do not represent energy use; instead, the temperature is compared. However, all values for both models were under the recommended values from ASHRAE Guideline 14 [39].

3.2.3. Room Level

For the room-level simulations, the apartment with the most detailed time diary was chosen. The apartment was then modeled as four zones: living room (including hall), kitchen, bedroom, and bathroom together with a walk-in closet. The doors inside the apartment were set to never close since this seemed to be the case when visiting the tenant. Table 14 shows the comparison between BES-ref and BES-v.2 in apartment 5 on the second floor.
When comparing the models at the room level, there can also be seen large differences between the results. The living room is the room where the most difference can be seen in energy supplied by the radiators. Even though it does not have the highest losses due to airing, it does seem to use a lot of energy trying to heat up the other rooms in the apartment. This, in combination with airing through the balcony door (which in this apartment is very frequent, and the door is situated in the living room), and the fact that the occupant in BES-ref is only active in the living room, contributing to higher internal gains in that model, should be the most probable cause of this. In the kitchen, no energy is supplied by the water radiators during simulations for the validation period. This is because the tenant spends quite a lot of time in the kitchen, as well as using the stove and other household appliances there, which is all in the detailed schedules in BES-v.2, which results in all energy coming from internal gains. The bedroom is the room where the most airing losses occur in BES-v.2, which is probably due to the fact that the tenant sometimes has the window open during the nights.

3.3. General Discussion

La Fleur, Moshfegh, and Rohdin [21] concluded that assumptions on user behavior have a significant impact on energy-saving potential when renovating or retrofitting a building, and this study shows how much difference there can actually be due to assumptions of user behavior. The largest differences in energy use in this study between using standardized user input data and behavioral schedules based on data collected from the actual building were due to airing and electricity use. It seems as though the standardized user input data are a bit too generalized and cannot actually be used in this case where the studied object is a retirement home. Even so, when designing a building for elderly care, one is supposed to use template values for regular housing in the calculations and/or simulations, as was done in BES-ref. The results show that schedules created from using time diaries and logged measurements bring the simulated results much closer to reality than just using template values. There was, however, quite a difference between the level of detail in the time diaries. The time diary shown in this article was the most detailed one, but some of the tenants almost only wrote whether they were home or not, and some of them wrote activities with no time. It is, therefore, of great importance, when conducting a study with time diaries, that the participants are told what sort of activities they should write down and to make sure they understand the importance of the level of detail in their time diaries. Since logged measurements could only be done in two apartments at the same time in this study due to a lack of equipment, it means that the schedules for the apartments were validated during different weeks, and only for one week during the heating season. In future studies, one should try to use time diaries and logged measurements at least four times during a year, if the building is situated in the temperate climate zone, i.e., one week in each season of the year (winter, spring, summer, and autumn), to see if there are any changes in the user behavior and to be able to make even more detailed schedules which vary during full-year simulations. Since this is a case study, conducted on a single retirement home, it might be hard to generalize the findings of this study to all retirement homes. However, the authors believe that most of the behavioral patterns are probably quite similar in homes of elderly people and retirement homes in Sweden. More studies on this type of housing are, however, required to be able to generalize and to create template values for retirement homes or housing for elderly people. One thing that also needs to be accounted for is that people that are over 70 today might behave a lot differently from people that will turn 70, for example, in 30 years, since they probably will have other accustomed behaviors. It should also be pointed out that user behavior is not the only thing that can affect the energy performance gap; the building parameters themselves such as U-values, air flow in the ventilation system, temperature set-point, etc. are of great importance to have a model that can predict energy use well. In this study, however, the main focus was on user behavior and the difference in energy use when using standardized user input data compared to using schedules based on gathered data from the actual building. The building parameters that were measured were indoor temperature to determine temperature set-point, leakage through the building envelope with blower door technology, ventilation air flow, and temperature, while U-values for the walls and windows were not measured. The U-values are based on construction blueprints and product specifications of the used materials. This can of course affect how the different user input data affect the simulated energy use and could, therefore, give either higher or lower discrepancies between the two cases (BES-ref and BES-v.2).

4. Conclusions

Time diaries and interviews, together with logged measurements, can be great tools to detect behavior that affects energy use in buildings; as far as the authors are concerned, this was not done simultaneously before. The time diaries provide a way of determining what actually causes variations in logged measurements. This can greatly benefit researchers studying user behavior and energy use in buildings and/or people that work with BES models. The reason is that it eliminates a lot of assumptions about the user behavior and/or why variations occur in measurements. This can also be good when deciding on which measures should be taken if the building is being retrofitted, since it gives a clear view on how the building is being used. They can also be used to create detailed schedules and behavioral models for BES models so that they are better at predicting actual energy use. However, using and creating these schedules from scratch is time-consuming and costly, which means that this method would probably not be viable in industry. Because of this, we believe that standardized user input data are still necessary, but there needs to be more variety in these standards. As shown in this article, user data for regular residential housing did not work well when used in this particular retirement home. Therefore, we believe that more studies of this nature need to be done on these sorts of buildings and also different kinds of buildings, both public and domestic. Thus, when designing new buildings or planning to renovate or retrofit old ones, there will be standardized user input data for that exact type of building. The largest offsets between using standardized user input data and input data from actual logged measurements and time diaries in this case could be seen in energy losses due to airing, and the amount of household electricity use. The tenants in this study aired a lot more and used a lot less electricity than the general population living in residential houses, according to Reference [10], which affected the energy use quite substantially. Based on the present findings, an update to the source hierarchy is also suggested for input data to BES models described by Raftery et al. [4]. Since time diaries represent a sort of in situ measurement (but not technical, since it is also behavioral), it should be in second place in the source hierarchy created by Raftery et al. [4], together with spot and short-term measurements. With time diaries, short-term measurements can be greatly expanded, since one can actually determine why drops and peaks occur in the different measurements. This would create the following source hierarchy: data-logged measurements, spot or short-term measurements and time diaries, direct observation, operator and personnel interviews, operation documents, commissioning documents, benchmark studies and best practice guides, standards, specifications, and guidelines, and design stage information.

Author Contributions

Conceptualization, J.C. and B.M.; data curation, J.C.; funding acquisition, B.M.; investigation, J.C. and K.T.; methodology, J.C.; project administration, B.M.; supervision, B.M.; writing—original draft, J.C. and K.T.

Funding

This work was funded by the KK foundation (KK-stiftelsen, Stiftelsen för Kunskaps och Kompetensutveckling), grant number 20150133, and the Swedish Energy Agency (Energimyndigheten), grant number 37492-1.

Acknowledgments

The authors of this article would like to thank Jakob Rosenquist, previously employed at Linköping University’s department of energy system, for the great help while conducting measurements at the studied site. We would also like to thank Patrik Rohdin for helping with the IDA-ICE simulations and for initiating the project together with Kajsa Ellegård at Linköping University, Sweden. Also, huge thanks goes out to all the residents and staff at Räknestickan Retirement Home for their participation in the study and for letting us into their homes and their workplace to do our measurements.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. European Commission Buildings. Available online: https://ec.europa.eu/energy/en/topics/energy-efficiency/energy-performance-of-buildings (accessed on 29 May 2019).
  2. Gynther, L.; Lappillone, B.; Pollier, K. Energy Efficiency Trends and Policies in the Household and Tertiary Sectors. An Analysis Based on the ODYSSEE and MURE Databases. Available online: http://www.odyssee-mure.eu/publications/br/energy-efficiency-trends-policies-buildings.pdf (accessed on 29 May 2019).
  3. Energimyndigheten flerbostadshus och lokaler 2016; Energimyndigheten: Eskilstuna, Sweden, 2016.
  4. Raftery, P.; Keane, M.; O’Donnell, J. Calibrating whole building energy models: An evidence-based methodology. Energy Build. 2011, 43, 2356–2364. [Google Scholar] [CrossRef]
  5. van den Brom, P.; Meijer, A.; Visscher, H. Performance gaps in energy consumption: household groups and building characteristics. Build. Res. Inf. 2017, 46, 1–17. [Google Scholar] [CrossRef]
  6. Clarke, J.A.; Joe, A. Energy Simulation in Building Design; Butterworth-Heinemann: Oxford, UK, 2001; ISBN 9780750650823. [Google Scholar]
  7. Andersen, R.V.; Olesen, B.W.; Toftum, J. Simulation of the Effects of Occupant Behaviour on Indoor Climate and Energy Consumption. In Proceedings of the Clima 2007: 9th REHVA world congress: WellBeing Indoors, Helsinki, Finland, 10–14 June 2007. [Google Scholar]
  8. Svebyprogrammet. Brukarindata Undervisningsbyggnader; Sveby: Stockholm, Sweden, 2016. [Google Scholar]
  9. Sveby. Brukarindata Kontor: Version 1.1; Sveby: Stockholm, Sweden, 2013. [Google Scholar]
  10. Sveby. Brukarindata Bostäder; Sveby: Stockholm, Sweden, 2012. [Google Scholar]
  11. Delzendeh, E.; Wu, S.; Lee, A.; Zhou, Y. The impact of occupants’ behaviours on building energy analysis: A research review. Renew. Sustain. Energy Rev. 2017, 80, 1061–1071. [Google Scholar] [CrossRef]
  12. Richardson, I.; Thomson, M.; Infield, D. A high-resolution domestic building occupancy model for energy demand simulations. Energy Build. 2008, 40, 1560–1566. [Google Scholar] [CrossRef] [Green Version]
  13. Widén, J.; Lundh, M.; Vassileva, I.; Dahlquist, E.; Ellegård, K.; Wäckelgård, E. Constructing load profiles for household electricity and hot water from time-use data-Modelling approach and validation. Energy Build. 2009, 41, 753–768. [Google Scholar] [CrossRef]
  14. Chiou, Y.-S.; Carley, K.M.; Davidson, C.I.; Johnson, M.P. A high spatial resolution residential energy model based on American Time Use Survey data and the bootstrap sampling method. Energy Build. 2011, 43, 3528–3538. [Google Scholar] [CrossRef]
  15. Aerts, D.; Minnen, J.; Glorieux, I.; Wouters, I.; Descamps, F. A method for the identification and modelling of realistic domestic occupancy sequences for building energy demand simulations and peer comparison. Build. Environ. 2014, 75, 67–78. [Google Scholar] [CrossRef]
  16. Sahlin, P.; Eriksson, L.; Grozman, P.; Johnsson, H.; Shapovalov, A.; Vuolle, M. Whole-building simulation with symbolic DAE equations and general purpose solvers. Build. Environ. 2004, 39, 949–958. [Google Scholar] [CrossRef]
  17. Kropf, S.; Zweifel, G. Validation of the Building Simulation Program IDA-ICE According to CEN 13791 “Thermal Performance of Buildings—Calculation of Internal Temperatures of a Room in Summer Without Mechanical Cooling—General Criteria and Validation Procedures”; Fachhochschule Zentralschweiz: Luzern, Schweiz, 2001. [Google Scholar]
  18. Achermann, M. Validation of IDA ICE, Version 2.11.06 With IEA Task 12—Envelope BESTEST; Fachhochschule Zentralschweiz: Luzern, Schweiz, 2000. [Google Scholar]
  19. Ryan, E.M.; Sanquist, T.F. Validation of building energy modeling tools under idealized and realistic conditions. Energy Build. 2012, 47, 375–382. [Google Scholar] [CrossRef]
  20. Coakley, D.; Raftery, P.; Keane, M. A review of methods to match building energy simulation models to measured data. Renew. Sustain. Energy Rev. 2014, 37, 123–141. [Google Scholar] [CrossRef] [Green Version]
  21. La Fleur, L.; Moshfegh, B.; Rohdin, P. Measured and predicted energy use and indoor climate before and after a major renovation of an apartment building in Sweden. Energy Build. 2017, 146, 98–110. [Google Scholar] [CrossRef] [Green Version]
  22. Liu, L.; Rohdin, P.; Moshfegh, B. Evaluating indoor environment of a retrofitted multi-family building with improved energy performance in Sweden. Energy Build. 2015, 102, 32–44. [Google Scholar] [CrossRef]
  23. Molin, A.; Rohdin, P.; Moshfegh, B. Investigation of energy performance of newly built low-energy buildings in Sweden. Energy Build. 2011, 43, 2822–2831. [Google Scholar] [CrossRef]
  24. Rohdin, P.; Molin, A.; Moshfegh, B. Experiences from nine passive houses in Sweden—Indoor thermal environment and energy use. Build. Environ. 2014, 71, 176–185. [Google Scholar] [CrossRef]
  25. Gauthier, S.; Shipworth, D. Behavioural responses to cold thermal discomfort. Build. Res. Inf. 2015, 43, 355–370. [Google Scholar] [CrossRef]
  26. Andersen, R.V.; Toftum, J.; Olesen, B.W. Simulation of the effects of window opening and heating set-point behaviour on indoor climate and building energy performance. In Proceedings of the Healthy Buildings 2009, Syracuse, NY, USA, 13–17 September 2009. [Google Scholar]
  27. Isaksson, C.; Ellegård, K. Anchoring energy efficiency information in households’ everyday projects: Peoples’ understanding of renewable heating systems. In Energy Efficiency; Springer: Berlin/Heidelberg, Germany, 2015; pp. 353–364. [Google Scholar]
  28. Ellegård, K.; Palm, J. Visualizing energy consumption activities as a tool for making everyday life more sustainable. Appl. Energy 2011, 88, 1920–1926. [Google Scholar] [CrossRef] [Green Version]
  29. Hellgren, M. Energy Use as a Consequence of Everyday Life; Linköping University: Linköping, Sweden, 2015; ISBN 9789176859100. [Google Scholar]
  30. Clifford, N.; Cope, M.; Gillespie, T.; French, S. Key Methods in Geography, 3rd ed.; Sage Publications: Thousand Oaks, CA, USA, 2016; ISBN 9781446298602. [Google Scholar]
  31. Vrotsou, K.; Bergqvist, M.; Cooper, M. PODD: A Portable Diary Data Collection System. In Proceedings of the 2014 International Working Conference on Advanced Visual Interfaces, Como, Italy, 27‒29 May 2014; pp. 381–382. [Google Scholar]
  32. SCB. Statistikdatabas för Äldreomsorg. Available online: https://www.socialstyrelsen.se/statistik/statistikdatabas/aldreomsorg (accessed on 16 May 2019).
  33. United Nations, UN. Transforming our World: The 2030 Agenda for Sustainable Development; United Nations: New York, NY, USA, 2015. [Google Scholar]
  34. Abramsson, M.; Andersson, E.V.A. Changing preferences with ageing—housing choices and housing plans of older people. Hous. Theory Soc. 2016, 33, 217–241. [Google Scholar] [CrossRef]
  35. Abramsson, M.; Andersson, E.V.A.K. Residential mobility patterns of elderly—leaving the house for an apartment. Hous. Stud. 2012, 27, 582–604. [Google Scholar] [CrossRef]
  36. Sveby. Brukarindata för energiberäkningar i bostäder; Sveby: Stockholm, Sweden, 2009. [Google Scholar]
  37. Carlander, J.; Tullsson, F. Utredning av energi och inomhusklimat samt åtgärdsförslag för kvarteret Räknestickan 1; Linköping University: Linköping, Sweden, 2014. [Google Scholar]
  38. Ruiz, G.R.; Bandera, C.F. Validation of calibrated energy models: Common errors. Energies 2017, 10, 1587. [Google Scholar] [CrossRef]
  39. ASHRAE. Guideline 14-2002: Measurement of Energy and Demand Savings; ASHRAE: Atlanta, GA, USA, 2002. [Google Scholar]
Figure 1. (a) Building that was modeled. (b) Model of the building in IDA-ICE (IDA Indoor Climate and Energy).
Figure 1. (a) Building that was modeled. (b) Model of the building in IDA-ICE (IDA Indoor Climate and Energy).
Energies 12 02072 g001
Figure 2. The logged measurements from apartment 5, second floor, on 19 November. The green (full) curve shows temperature, the blue (dotted and dashed) curve shows CO2 level, and the red (dashed) curve shows electric power.
Figure 2. The logged measurements from apartment 5, second floor, on 19 November. The green (full) curve shows temperature, the blue (dotted and dashed) curve shows CO2 level, and the red (dashed) curve shows electric power.
Energies 12 02072 g002
Figure 3. Logged measurements compared to simulated output from apartment 5 on the second floor, for both reference building energy simulation (BES-ref) and building energy simulation version 2 (BES-v.2), from Wednesday 19 November to Sunday 23 November: (a) mean temperature; (b) CO2 levels.
Figure 3. Logged measurements compared to simulated output from apartment 5 on the second floor, for both reference building energy simulation (BES-ref) and building energy simulation version 2 (BES-v.2), from Wednesday 19 November to Sunday 23 November: (a) mean temperature; (b) CO2 levels.
Energies 12 02072 g003
Figure 4. The validation process for BES-ref and BES-v.2 models.
Figure 4. The validation process for BES-ref and BES-v.2 models.
Energies 12 02072 g004
Figure 5. The three different levels on which simulated results between BES-ref and BES v.2 were compared.
Figure 5. The three different levels on which simulated results between BES-ref and BES v.2 were compared.
Energies 12 02072 g005
Figure 6. Temperature curves from logged measurements, BES-ref, and BES-v.2 for the period of 21–25 January. The blue curve shows the logged measurements, the red curve shows results from BES-v.2, and the green curve shows results from BES-ref.
Figure 6. Temperature curves from logged measurements, BES-ref, and BES-v.2 for the period of 21–25 January. The blue curve shows the logged measurements, the red curve shows results from BES-v.2, and the green curve shows results from BES-ref.
Energies 12 02072 g006
Table 1. Number of people with assistance in their own home and number of people living in assisted-living accomodation in Sweden (men and women; 2016) [32].
Table 1. Number of people with assistance in their own home and number of people living in assisted-living accomodation in Sweden (men and women; 2016) [32].
AgePeople with Assistance in HomePeople in Assisted-Living Accommodation
65+228,654106,002
65–7968,53684,843
80+160,11821,159
Table 2. Technical data of the modeled building.
Table 2. Technical data of the modeled building.
Location Data
CountrySweden
CityLinköping
Longitude15.53 east (E)
Latitude58.4 north (N)
Annual mean temperature6.8 °C
Building
Model floor area1366.2 m2 (Atemp)
Floor area apartments1131.7 m2
Model volume3370.1 m2
Model ground area427.2 m2
Model envelope area1770 m2
Window/envelope5.5%
Average U-value0.42 W/m2K
Number of apartments15
Common area (Stairwell, entrance and storage)234.5 m2
Time Constant201 h
Winter Outdoor Design Temperature−13 °C
Qtot1036 W/K
Building Envelope
Envelope PartArea (m2)U (W/m2K)U × A (W/K)
Walls above ground775.380.25197.54
Roof427.880.1875.86
Floor towards ground427.200.45191.56
Windows97.811.91 (incl. frame)186.81
Doors38.060.259.61
Windows
DirectionArea (m2)Glazingg-factor
N21.323-pane0.68
E26.973-pane0.68
South (S)23.633-pane0.68
West (W)25.893-pane0.68
Construction
External wall 1Brick 87 mmAir gap 23 mmGypsum 9 mmLight insulation 170 mmGypsum 13 mm
External wall 2Wood 20 mmAir gap 16 mmGypsum 9 mmLight insulation 120 mmConcrete 160 mm
External wall 3Wood 20 mmAir gap 16 mmGypsum 9 mmLight insulation 120 mmGypsum 13 mm
External wall 4Brick 87 mmAir gap 23 mmLight insulation 120 mmConcrete 160 mm
Internal wallConcrete 160 mm
Internal floorConcrete 200 mmFloor coating 5 mm
External slabConcrete 250 mmFloor coating 5 mm
Roof 1Wood 25 mmLight insulation 250 mmConcrete 200 mm
Roof 2Wood 25 mmLight insulation 10 mmAluminum 1 mm
Table 3. Gender, age, civil status, and working status of the occupants in the present study.
Table 3. Gender, age, civil status, and working status of the occupants in the present study.
DescriptionFacts
GenderFemale (8), Male (5)
Age58–94 (mean 85, median 78)
Civil statusSingle (9), married (4: two couples)
Retired/working11/2
Table 4. Measurements at the city block and the modeled building, time resolution, and time span, as well as which measurement equipment was used.
Table 4. Measurements at the city block and the modeled building, time resolution, and time span, as well as which measurement equipment was used.
Measuring TypeMeasuring EquipmentAreaTime ResolutionTimespan
District heatingMeter at the city block’s heating centralEntire city block (one measuring point)weekly2 months
Domestic hot-water use and temperatureMeter at the city block’s heating centralEntire city block (one measuring point)weekly2 months
Domestic cold-water useMeter at the city block’s heating centralEntire city block (one measuring point)weekly2 months
Facility electricityElectricity meterEntire city block (six measuring points)weekly2 months
Apartment electricityElectricity meterEkholmsvägen 106 (15 apartments)weekly2 months
Total electricityEliqEntire city block (incoming electricity for each facility and for the central ventilation; 5 measuring points in total)Every 5 minutes1 week
Momentary total electricityFluke 41B Power harmonics analyzer + Universal Technic current clampsEntire city block (incoming electricity for each facility and for the central ventilation; 5 measuring points in total)--
Momentary temperatureSwema3000Stairwells, ventilation outtakes--
Logged temperatureTinytag Plus212 apartmentsEvery 5 minutes1 week
Logged apartment electricityEliq12 apartmentsEvery 5 minutes1 week
Relative humidityTinytag View2 Temp and RH logger12 apartmentsEvery 5 minutes1 week
CO2Tinytag CO2Dining hall + 12 apartmentsEvery 5 minutes1 week
Energy use from apartment ventilationEverflourish power meter EMT707CTLVentilation unit in one apartment1 week1 week
Momentary ventilation flowsSwema3000Outlets on roof + measured on central ventilation system--
Building envelope tightnessRetrotec DM32 Blower door1 apartment--
Table 5. Accuracy and area of use for measuring equipment used in the study. N/A—not applicable.
Table 5. Accuracy and area of use for measuring equipment used in the study. N/A—not applicable.
EquipmentMeasuresEquipment AccuracyManufacturer
EliQ optical eyeHousehold electricity useN/AEliq, Gothenburg, Sweden
Fluke 41B Power harmonics analyserFacility electricity±1% for active watts (VA) + probe specsFluke, Everett, WA, USA
Universal Technic current clampsFacility electricityN/AUniversal Technic, Paris, France
Swema3000Temperature and air speed±0.1 °C, ±0.03 m/sSwema, Stockholm, Sweden
Tinytag Plus2Temperature±0.35 °CIntab, Stenkullen, Sweden
Tinytag View2Temperature and relative humidity (RH)±0.4 °C, RH ±3%Intab, Stenkullen, Sweden
Tinytag CO2 loggerConcentration of carbon dioxide in air±3%Intab, Stenkullen, Sweden
Everflourish power meter EMT707CTLHousehold electricityN/AEverflourish, Friedrichsthal, Germany
Retrotec Blower Door 3100 with DM2 digital pressure gaugeBuilding envelope airtightness±5% flow rate accuracy, ±1% pressure reading accuracy (or ±0.15 Pa)Retrotec, Everson, WA, USA
Table 6. Part of the process in which the gathered data were used. BES—building energy simulation.
Table 6. Part of the process in which the gathered data were used. BES—building energy simulation.
Step in ProcessConstruction of ModelCreating Detailed User SchedulesValidating BES Model
Used dataBlueprints of the building and on-site observation of construction, measured ventilation airflows, temperature, number of occupants in each apartment, and measurements of building envelope tightness.Time diaries, interviews, and household electricity useLogged measurements of CO2 levels, indoor temperature, and household electricity use
Table 7. Input data for BES-ref and BES-v.2.
Table 7. Input data for BES-ref and BES-v.2.
Input dataFloor 1Floor 2Floor 3
Apartment 1BES-refBES-v.2DifferenceBES-refBES-v.2DifferenceBES-refBES-v.2Difference
Tenant electricity use/year (kWh)24891098−56%3000918−69%30001098−63%
Number of people in apartment22-11-22-
Heat exchanger efficiency (%)606006055−5.0060600.00
Temperature set-point (°C)21.4521.50.0521.221.30.1021.321.350.05
AHU scheduleAlways onAlways on-Always onAlways on-Always onAlways on-
Zone area (m2)8383-100100-100100-
Apartment 2
Tenant electricity use (kWh)23111859−20%23111858−20%23111849−20%
Number of people in apartment11-22-22-
Heat exchanger efficiency (%)6055−5.006055−5.006050−10.0
Temperature set-point (°C)19.819.90.1019.619.80.2021210.00
AHU scheduleAlways onAlways on-Always onAlways on-Always onAlways on-
Zone area (m2)77.577.5-77.577.5-77.577.5-
Apartment 3
Tenant electricity use (kWh)23111714−26%2311645−72%23111629−30%
Number of people in apartment11-22-11-
Heat exchanger efficiency (%)6045−15.00%60600.0060600.00
Temperature set-point (°C)19.619.60.0020.320.30.0021.521.60.10
AHU scheduleAlways onAlways on-Always onAlways on-Always onAlways on-
Zone area (m2)77.577.5-77.577.5-77.577.5-
Apartment 4
Tenant electricity use (kWh)19821389−30%19821848−7%1982456−77%
Number of people in apartment11-22-11-
Heat exchanger efficiency (%)60600.006050−10.060600.00
Temperature set-point (°C)21.521.60.1021210.0020.320.40.10
AHU scheduleAlways OnAlways On-Always OnAlways On-Always OnAlways On-
Zone area (m2)6666-6666-6666-
Apartment 5
Tenant electricity use (kWh)1562285283%1978789−60%1978744−62%
Number of people in apartment11-11-11-
Heat exchanger efficiency (%)60600.0060600.006050−10.0
Temperature set-point (°C)18.518.750.2518.718.6−0.102020.10.10
AHU scheduleAlways onTenant-specific-Always onAlways on-Always onAlways on-
Zone area (m2)5353-6666-6666-
Schedules for all apartmentsBES-refBES-v.2 BES-refBES-v.2 BES-refBES-v.2
Tenant electricity use schedule6:00‒8:00 a.m. and 3‒11 p.m. Tenant-specific 6:00‒8:00 a.m. and 3‒11 p.m. Tenant-specific 6:00‒8:00 a.m. and 3‒11 p.m. Tenant-specific
occupancy scheduleabsent 7:00 a.m. to 5:00 p.m.Tenant-specific absent 7:00 a.m. to 5:00 p.m. Tenant-specific absent 7:00 a.m. to 5:00 p.m.Tenant-specific
Ventilation air flows (L/s.m2)0.4 in, 0.42 out0.4 in, 0.42 out 0.4 in, 0.42 out0.4 in, 0.42 out 0.4 in, 0.42 out0.4 in, 0.42 out
Domestic hot water use (L/m2.year)345345 345345 345345
Airing4 kWh/m2∙Year Tenant-specific 4 kWh/m2∙YearTenant-specific 4 kWh/m2∙yearTenant-specific
Table 8. Transcribed time diary from tenant in apartment 5, second floor, on 19 November. The effects of entries on the gray background are clearly visible in the logged measurements in Figure 2.
Table 8. Transcribed time diary from tenant in apartment 5, second floor, on 19 November. The effects of entries on the gray background are clearly visible in the logged measurements in Figure 2.
TimeActivityPlaceWith WhomElectrical AppliancesComments
07:30 a.m.Wakes up, turns on radioBedroomAloneRadio
08:15 a.m.Turns off radio, gets out of bedBedroomAloneRadio
08:16 a.m.Turns on radio, feeds the cats, makes teaKitchenAloneWater boiler 4 min, radio
08:22 a.m.Showers and gets dressedBathroomAlone
08:30 a.m.Hangs out linens on the balcony Balcony/living roomAlone
08:30‒08:50 a.m.Opens balcony door Cats wanted to be out
08:40 a.m.Empties litter boxBathroomAloneLamp
08:45 a.m.Makes breakfast, eats breakfastKitchenAloneLamp, microwave (4 min)
09:20 a.m.Brushes teethBathroomAloneElectrical toothbrush
09:30 a.m.Takes in the linens and makes the bedBalcony/bedroomAlone
09:35 a.m.Turns off the radioKitchen Radio
09:35 a.m.‒12:00 p.m.Not at homeOut
12:00 p.m. Home again, turns on radio, washes hands, puts groceries in fridgeKitchenAloneRadio
12:10 p.m.Makes copies and laminatesBedroom/kitchenAloneCopying machine, laminator
12:20 p.m.At computer, talks on the phoneBedroomAloneComputer, cell phone
12:40 p.m.ToiletBathroomAlone
12:42 p.m.Heats and eats food, does dishesKitchenAloneMicrowave (3 min)
1:05 p.m.Empties litter box, vacuumsBathroomAloneLamp, vacuum cleaner
1:10 p.m.VacuumsKitchen, living room, bedroomAloneVacuum cleaner
1:20 p.m.Talks on the phoneKitchenAloneCell phone
1:25 p.m.Turns on lamps in windowsKitchen, living roomAloneLamps
1:26‒1:40 p.m.Lights lanternBalconyAlone Balcony door open; cats outside
1:40 p.m.Calls hair salonKitchenAloneCell phone
1:45 p.m.Has a guest at home, has coffee, talks, gets help with computer FriendComputer, water boiler (4 min)Very nice with good company
4:05 p.m.ToiletBathroomAlone
4:10 p.m.Turns off radio and kitchen lampKitchenAlone
4:10 p.m.Goes for a walkOut Nice with a walk
5:00 p.m.Turns on radio, starts to make dinnerKitchenAloneRadio, stove (17–19 min)
5:15 p.m.CopiesBedroomAloneCopying machine
5:25 p.m.Does the dishesKitchenAloneLamp
5:40 p.m.Goes through the mailKitchenAloneLamp
5:50 p.m.Cleans toiletBathroomAlone
6:00 p.m.Turns off radio, turns on floor lamp, watches television (TV)Living roomAloneTV, radio, lamp
7:00 p.m.Eats, does dishes, cleans stoveKitchenAlone
7:00–7:45 p.m.Charges cell phone Cell phone
8:05 p.m.Watches TVLiving roomAloneTV
8:10 p.m.Answers an e-mailBedroomAloneComputer
8:15–10:00 p.m.Watches TVLiving roomAloneTVPuts on thick socks
8:40–8:46 p.m.Opens balcony door Cats wanted to be out
10:00 p.m.Empties litter box, washes handsBathroomAlone
10:03 p.m.Puts out lanternBalconyAlone Balcony door open 10:03–10:09
10:04 p.m.Makes the bedBedroomAlone
10:10 p.m.Cuddles with catKitchenAlone
10:20 p.m.Brushes teethBathroomAloneElectrical toothbrush
10:25 p.m.Goes through some papersKitchenAlone
10:59 p.m.Gets ready for bedBathroomAlone
11:15 p.m.Turns off all lights and goes to bed Alone Finally in bed
Table 9. This table describes which parameters were compared between reference BES (BES-ref) and BES version 2 (BES-v.2) at each level.
Table 9. This table describes which parameters were compared between reference BES (BES-ref) and BES version 2 (BES-v.2) at each level.
ParameterLevel 1 BuildingLevel 2 ApartmentLevel 3 Room
Energy supplied by water radiators (District Heating)XXX
Air Handling Unit heating (electrical)XXX
Energy losses due to airingXXX
Indoor temperature XX
CO2 level XX
PPD (Predicted Percentage Dissatisfied) X
Simulation Period
Full-year simulationXXX
Simulation of measuring period XX
X: Parameter that is compared between the models.
Table 10. Simulated values for a whole-year simulation at building level from BES-ref and BES v.2, and difference in percentage between them (unit KWh).
Table 10. Simulated values for a whole-year simulation at building level from BES-ref and BES v.2, and difference in percentage between them (unit KWh).
ParameterBES-refBES-v.2Difference BES-ref to BES-v.2
Energy supplied by water radiators (DH)48,54558,34520%
AHU heating (electrical)3432635785%
Total energy use for space heating51,97664,70224%
Energy loss due to airing546410,86599%
Household electricity (input)34,09220,659−39%
Table 11. Results at the apartment level from simulations using the two models (BES-ref and BES-v.2). The simulations were done for the same period as the logged measurements, and the time diaries were done for each apartment.
Table 11. Results at the apartment level from simulations using the two models (BES-ref and BES-v.2). The simulations were done for the same period as the logged measurements, and the time diaries were done for each apartment.
ParametersFloor 1Floor 2Floor 3
BES-refBES-v.2DifferenceBES-refBES-v.2DifferenceBES-refBES-v.2Difference
Apartment 1Simulation period 10 to 14 December 2014Simulation period 14 to 18 January 2015Simulation period 10 to 14 December 2014
Energy supplied by water radiators (DH) (kWh)127.5137.48%8390.39%101.3115.814%
AHU heating (electrical) (kWh)3.43.66%4.911.4133%4.24.20%
Total energy use for space heating (kWh)130.91418%87.9101.716%105.512014%
Energy loss due to airing (kWh)4.64−13%5.55.97%5.51.4−75%
Indoor temperature (°C)22.0–22.121.8–22.1-21.8–22.021.0–22.0-21.9–22.021.9–22.1-
Maximum CO2 (ppm)670.7672.72.0512.5594.982.4626.3627.41.1
Maximum PPD (%)13.513.90.413.314.61.312.312.30.0
Apartment 2Simulation period 21 to 25 January 2015Simulation period 21 to 25 January 2015Simulation period 10 to 14 December 2014
Energy supplied by water radiators (DH) (kWh)83.6123.748%40.877.590%82.694.615%
AHU heating (electrical) (kWh)1419.741%14.319.134%4.113217%
Total energy use for space heating (kWh)97.6143.447%55.196.675%86.7107.624%
Energy loss due to airing (kWh)4.346.9991%4.338.3791%4.312.8198%
Indoor temperature (°C)20.4–20.519.9–21.9-20.3–20.519.9–22.5-21.6–21.721.2–21.8-
Maximum CO2 (ppm)545.3686.5141.269.7686.4616.7692.1692.40.3
Maximum PPD (%)23.525.52.021.523.01.513.714.40.7
Apartment 3Simulation period 3 to 7 December 2014Simulation period 19 to 23 November 2014Simulation period 28 January to 1 February 2015
Energy supplied by water radiators (DH) (kWh)74774%45.469.252%105.8136.429%
AHU heating (electrical) (kWh)9.122142%4.14.35%6.56.4−2%
Total energy use for space heating (kWh)83.19919%49.573.548%112.3142.827%
Energy loss due to airing (kWh)4.34.2−2%4.315249%4.325481%
Indoor temperature (°C)20.2–20.420.1–20.6-20.9–21.220.8–21.5-22.0–22.222.0–22.3-
Maximum CO2 (ppm)545.1689143.9691.3689.6−1.7546579.133.1
Maximum PPD (%)23.824.81.015.616.81.213.313.0−0.3
Apartment 4Simulation period 21 to 25 January 2015Simulation period 10 to 14 December 2014Simulation period 14 to 18 January 2015
Energy supplied by water radiators (DH) (kWh)105138.932%48.457.819%46.276.566%
AHU heating (electrical) (kWh)8.48.51%3.511.1217%5.15.10%
Total energy use for space heating (kWh)113.4147.430%51.968.933%51.381.659%
Energy loss due to airing (kWh)3.627.5664%3.610.2183%3.614.7308%
Indoor temperature (°C)22.0–22.121.8–22.1-21.6–21.821.2–21.9-20.9–21.120.8–21.1-
Maximum CO2 (ppm)570.9606.335.4737.6742.14.5570.6570.70.1
Maximum PPD (%)14.415.00.612.713.71.016.216.60.4
Apartment 5Simulation period 28 January to 1 February 2015Simulation period 19 to 23 November 2014Simulation period 3 to 7 December 2014
Energy supplied by water radiators (DH) (kWh)7.620.8174%6.628.3329%48.589.484%
AHU heating (electrical) (kWh)93.1−66%6.16−2%714.6109%
Total energy use for space heating (kWh)16.623.944%12.734.3170%55.510487%
Energy loss due to airing (kWh)2.913.5366%3.611.6222%3.624.4578%
Indoor temperature (°C)19.3–20.219.3–19.9-19.5–20.619.4–20.4-20.6–20.820.5–20.8-
Maximum CO2 (ppm)61322521639.0566.3714.3148.0566.6566.80.2
Maximum PPD (%)27.726.9−0.922.722.3−0.418.619.50.9
Table 12. Results from yearly simulations at the apartment level for both models (BES-ref and BES-v.2).
Table 12. Results from yearly simulations at the apartment level for both models (BES-ref and BES-v.2).
ParametersFloor 1Floor 2Floor 3
Apartment 1BES-refBES-v.2DifferenceBES-refBES-v.2DifferenceBES-refBES-v.2Difference
Energy supplied by water radiators (DH) (kWh)4856.85386.611%3177.53279.13%3417.33993.817%
AHU heating (electrical) (kWh)188.7194.73%240.81695.4604%227.9230.11%
Total energy use for space heating (kWh)5045.55581.311%3418.34974.546%3645.24223.916%
Energy loss due to airing (kWh)332188.9−43%400217.3−46%40060.2−85%
Indoor temperature (°C)21.9–31.021.6–29.5N/A21.6–33.018.4–31.2N/A21.8–33.721.8–31.9N/A
Maximum CO2 (ppm)682.4682.30%517.8610.118%637.8637.70%
Apartment 2
Energy supplied by water radiators (DH) (kWh)28964158.644%1055.11952.485%2859.33119.79%
AHU heating (electrical) (kWh)289.9442.353%282.3432.553%197.4490.6149%
Total energy use for space heating (kWh)3185.94600.944%1337.42384.978%3056.73610.318%
Energy loss due to airing (kWh)3101842.6494%310798.9158%310498.761%
Indoor temperature (°C)20.3–30.517.7–30.6N/A20.2–32.518.8–32.7N/A21.5–33.020.8–31.9N/A
Maximum CO2 (ppm)551.3696.326%704.9698.2−1%705.67050%
Apartment 3
Energy supplied by water radiators (DH) (kWh)28453129.310%1786.62667.549%3668.44557.824%
AHU heating (electrical) (kWh)307.6780.7154%242.4253.55%169.2167.5−1%
Total energy use for space heating (kWh)3152.6391024%2029292144%3837.64725.323%
Energy loss due to airing (kWh)310441.943%310797157%310782.7152%
Indoor temperature (°C)20.1–30.719.9–30.1N/A20.8–32.720.6–31.2N/A21.9–33.321.5–31.7N/A
Maximum CO2 (ppm)551.1702.327%704.6702.90%552.564917%
Apartment 4
Energy supplied by water radiators (DH) (kWh)4068.74981.822%1741.41893.59%1692.13006.378%
AHU heating (electrical) (kWh)150.1151.51%169.7418.6147%208.32143%
Total energy use for space heating (kWh)4218.85133.322%1911.12312.121%1900.43220.369%
Energy loss due to airing (kWh)264734178%264403.653%2641154337%
Indoor temperature (°C)21.8–30.621.4–29.4N/A21.5–32.720.9–31.6N/A20.8–33.020.5–30.9N/A
Maximum CO2 (ppm)577.1614.66%753756.91%578.8577.80%
Apartment 5
Energy supplied by water radiators (DH) (kWh)457.5641.440%425.958738%1492.33009.6102%
AHU heating (electrical) (kWh)244.468.86−72%277.7317.17%229.1499.3118%
Total energy use for space heating (kWh)701.9710.261%703.6904.128%1721.43508.9104%
Energy loss due to airing (kWh)212404.291%264771.9192%2641269.3381%
Indoor temperature (°C)19.2–30.618.9–29.6N/A19.3–33.116.3–31.2N/A20.5–33.520.1–31.4N/A
Maximum CO2 (ppm)622.73120401%574.8791.738%575.1573.30%
Table 13. Mean bias error (MBE), normalized mean bias error (NMBE), and coefficient of variation (CV) of the root-mean-square error (RMSE) for logged measurements of temperature and the simulated results for BES-ref and BES-v.2.
Table 13. Mean bias error (MBE), normalized mean bias error (NMBE), and coefficient of variation (CV) of the root-mean-square error (RMSE) for logged measurements of temperature and the simulated results for BES-ref and BES-v.2.
Apartment and FloorLogged vs. BES-refLogged vs. BES-v2
Floor 1MBENMBECV (RMSE) (%)MBENMBECV (RMSE) (%)
Apartment 1−0.068−0.3111.7−0.0077−0.0351.33
Apartment 20.0280.145.190.0120.0592.26
Apartment 30.0760.3814.30.0710.3513.2
Apartment 40.0510.238.75−0.015−0.0672.55
Apartment 50.0780.4015.2−0.054−0.2810.49
Floor 2
Apartment 10.0320.155.540.0210.0983.71
Apartment 20.0280.145.19−0.0099−0.0481.84
Apartment 3−0.079−0.3814.2−0.008−0.0381.46
Apartment 40.00840.0391.480.00610.0281.07
Apartment 5−0.056−0.2810.8−0.023−0.114.36
Floor 3
Apartment 1−0.068−0.3111.7−0.0077−0.0351.33
Apartment 20.00840.0391.480.00670.311.18
Apartment 3−0.065−0.3011.2−0.012−0.0552.11
Apartment 4−0.059−0.2810.60.0210.103.80
Apartment 5−0.14−0.6825.70.0400.207.53
Table 14. Comparison of apartment 5, second floor, at the room level between BES-ref and BES-v.2 for the validation period and for a full-year simulation.
Table 14. Comparison of apartment 5, second floor, at the room level between BES-ref and BES-v.2 for the validation period and for a full-year simulation.
Apartment 5, Floor 2Simulation Period 19/11-23/11Full Year Simulation
Living roomBES-refBES-v.2DifferenceBES-refBES-v.2Difference
Energy supplied by water radiators (DH) (kWh)2.415.9563%190.7564.8196%
Energy loss due to airing (kWh)1.72.653%122242.999%
Indoor temperature (°C)19.6‒20.119.6‒20.2-19.4‒32.118.7‒30.9-
Maximum CO2 (ppm)579.6846.8267.2597.5883.6286.1
Maximum PPD (%)21.721.6−0.1087.866.7−21.06
Kitchen
Energy supplied by water radiators (DH) (kWh)1.440−100%100.60−100%
Energy loss due to airing (kWh)0.840.2−76%61.145.1−26%
Indoor temperature (°C)19.6‒20.119.6‒21.1-19.4‒32.619.0‒32.0-
Maximum CO2 (ppm)559821.5821.5569.6912.8343.2
Maximum PPD (%)N/A22.4-N/A79.5-
Bedroom
Energy supplied by water radiators (DH) (kWh)5.418.761%215.7265.823%
Energy loss due to airing (kWh)0.814.5456%59.4172.3190%
Indoor temperature (°C)19.5–19.818.9–19.9-19.4‒32.217.6‒31.2-
Maximum CO2 (ppm)546.8793.1246.3557.4807.6250.2
Maximum PPD (%)N/A25.7-N/A72.7-
Bathroom
Energy supplied by water radiators (DH) (kWh)0.550−100%403.4−92%
Energy loss due to airing (kWh)0.550.1−82%39.927.1−32%
Indoor temperature (°C)20.0‒20.520.1‒20.2-19.7‒31.919.7‒30.3-
Maximum CO2 (ppm)579.5834.1254.6596.4881.7285.3
Maximum PPD (%)N/A18.5-N/A60.6-
Apartment total
Energy supplied by water radiators (DH) (kWh)9.824.6151%54783452%
AHU heating (electrical) (kWh)7.57.73%332.6345.34%
Total energy use for space heating (kWh)13.432.387%879.61179.334%
Energy loss due to airing (kWh)3.97.490%282.4487.473%
Indoor temperature (°C)19.5‒20.518.9‒21.1-19.4‒32.617.6‒32.0-
Maximum CO2 (ppm)579.6846.8267.2597.5912.8315.3
Maximum PPD (%)21.725.74.0287.879.5−8.32

Share and Cite

MDPI and ACS Style

Carlander, J.; Trygg, K.; Moshfegh, B. Integration of Measurements and Time Diaries as Complementary Measures to Improve Resolution of BES. Energies 2019, 12, 2072. https://doi.org/10.3390/en12112072

AMA Style

Carlander J, Trygg K, Moshfegh B. Integration of Measurements and Time Diaries as Complementary Measures to Improve Resolution of BES. Energies. 2019; 12(11):2072. https://doi.org/10.3390/en12112072

Chicago/Turabian Style

Carlander, Jakob, Kristina Trygg, and Bahram Moshfegh. 2019. "Integration of Measurements and Time Diaries as Complementary Measures to Improve Resolution of BES" Energies 12, no. 11: 2072. https://doi.org/10.3390/en12112072

APA Style

Carlander, J., Trygg, K., & Moshfegh, B. (2019). Integration of Measurements and Time Diaries as Complementary Measures to Improve Resolution of BES. Energies, 12(11), 2072. https://doi.org/10.3390/en12112072

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop