The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Overcurrent Protection and an Improved Protection with the Second Harmonic Restraint
Abstract
:1. Introduction
2. Analytical Model of Zero-Mode Inrush Current of Y0/Δ Transformer
2.1. Derivation of Single Transformer Magnetizing Inrush Current
2.2. Derivation of Zero-Mode Inrush Current
3. The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Protection
3.1. The Parameter Differences of T-Hin and Its Impact on Zero-Sequence Protection
3.2. Comparation of Mathematical Waveforms and Recorded Waveforms
3.2.1. Parameter Determination for Mathematical Expression
3.2.2. The Graphical Representation
4. Improved Method for Zero-Sequence Overcurrent Protection Based on Second Harmonic Ratio of Zero-Mode Inrush Current
4.1. Distribution of Second Harmonic Ratio
4.1.1. No Remanence in the Three-Phase Iron Core
4.1.2. Symmetric Remanence in the Three-Phase Core
- (1)
- The angle difference between opening angle and closing angle are 180°, that is, the relative closing angle is 180°, and the remanence and bias directions of each phase are opposite;
- (2)
- There is always one phase whose remanence and bias are both zero. For example, in the combination of (330°, 150°), the remanence and bias of phase C are zero; in the combination of (270°, 90°), the remanence and bias of phase A are zero; in the combination of (210°, 30°), the remanence and bias of phase B are zero.
4.1.3. Random Remanence in Three-Phase Iron Core
4.2. Improved Criteria
4.3. Setting Method in Engineering Application
5. Application of the Improved Method
- (1)
- The recorded waveform Number One did not satisfy the setting value of zero-sequence overcurrent protection zone-I and zone-II, and the protection did not operate;
- (2)
- The recorded waveform Number Two satisfied the setting value of zero-sequence overcurrent protection zone-I and zone-II, and the protection misoperated when reaching the delay of the zone-I;
- (3)
- The recorded waveform Number Three satisfied the setting value of zero-sequence overcurrent protection zone-I and zone-II, but does not satisfy the delay of zone-I. The protection misoperated when reaching the delay of the zone-II;
6. Conclusions
- (1)
- Based on the derivation of single-phase and three-phase magnetizing inrush current, the mathematical expression of the zero-mode inrush current of transformer is derived;
- (2)
- According to the mathematical expression and parameter differences between the T-Hin and T-Ord, the zero-mode inrush current of T-Hin is larger, which tends to cause the misoperation of zero-sequence overcurrent protection;
- (3)
- The zero-mode inrush current recorded waveforms are reconstructed through mathematical expression and it is found that their second harmonic ratio is high, which is verified by mathematical analysis under various conditions;
- (4)
- An identification method based on the second harmonic ratio of zero-mode inrush current is proposed. Then the theoretical setting value of the method and the practical engineering method for determining the setting value are obtained.
Author Contributions
Funding
Conflicts of Interest
Appendix A
Appendix B
H | magnetic field intensity. |
B | magnetic density |
μ0 | permeability of vacuum |
ψ | flux linkage |
W | the number of winding turns |
S | the cross-sectional area |
JSat | the saturation magnetization |
uA, uB, uC | three-phase voltage of the system |
Ls | positive-sequence inductance |
Ls0 | zero-sequence inductance |
Lσ | leakage inductance of primary winding |
LσD | leakage inductance of secondary winding |
ea, eb, ec | induced electromotive force |
iD | circulation current of delta winding |
Mair | saturated mutual inductance |
References
- Sharp, R.L.; Glassburn, W.E. A Transformer Differential Relay with Second-Harmonic Restraint. IEEE Trans. Power Appar. Syst. 1958, 3, 913–918. [Google Scholar] [CrossRef]
- Hayward, C.D. Prolonged inrush currents with parallel transformers affect differential relaying. Electr. Eng. 1941, 12, 1096–1101. [Google Scholar] [CrossRef]
- Bi, D.Q.; Wang, X.H.; Li, D.J.; Yu, G.W.; Wang, Z.J.; Wang, W.J. Theory Analysis of the Sympathetic Inrush in Operating Transformers. Autom. Electr. Power Syst. 2005, 6, 1–8. [Google Scholar]
- Zhang, A.Q.; Ji, T.Y.; Li, M.S.; Wu, Q.H.; Zhang, L.L. An Identification Method Based on Mathematical Morphology for Sympathetic Inrush. IEEE Trans. Power Deliv. 2018, 1, 12–21. [Google Scholar] [CrossRef]
- Qi, X.W.; Yin, X.G.; Zhang, Z.; Chen, D.; Wang, Y.; Cai, F. Study on the Unusual Misoperation of Differential Protection During Transformer Energization and its Countermeasure. IEEE Trans. Power Deliv. 2016, 5, 1998–2007. [Google Scholar] [CrossRef]
- Peng, F.; Gao, H.L.; Liu, Y.Q. Transformer Sympathetic Inrush Characteristics and Identification based on Substation–Area Information. IEEE Trans. Power Deliv. 2018, 1, 218–228. [Google Scholar] [CrossRef]
- Brunke, J.H.; Frohlich, K.J. Elimination of Transformer Inrush Currents by Controlled Switching–Part I: Theoretical Considerations. IEEE Trans. Power Deliv. 2001, 2, 276–280. [Google Scholar] [CrossRef]
- Brunke, J.H.; Frohlich, K.J. Elimination of Transformer Inrush Currents by Controlled Switching–Part II: Application and Performance Considerations. IEEE Trans. Power Deliv. 2001, 2, 281–285. [Google Scholar] [CrossRef]
- Liu, J.; Hao, X.D.; Wang, X.; Chen, Y.F.; Fang, W.L.; Niu, S.B. Application of thyristor controlled phase shifting transformer excitation impedance switching control to suppress short-circuit fault current level. J. Mod. Power Syst. Clean Energy 2018, 4, 821–832. [Google Scholar] [CrossRef]
- Li, Y.; Su, Z.H.; Wang, R.F.; Xu, Z.F.; Lin, Y.T.; Zhan, X.B. Calculation and Analysis of Magnetizing Inrush Current of High Impedance Transformer with Built-In High Voltage Winding. Transformer 2017, 8, 1–5. [Google Scholar]
- Li, X.H.; Luo, L.L.; Xie, J.Q.; Li, Y.Q.; Li, Y. Impact of Inrush Current Characteristics of High-Voltage Built-in High-impedance Transformer on Relay. Autom. Electr. Power Syst. 2016, 11, 108–114. [Google Scholar]
- Li, C.; Li, B.; Guo, F.; Geng, J.; Zhang, X.; Coombs, T. Studies on the active SISFCL and its impact on the distance protection of the EHV transmission line. Prot. Control Mod. Power Syst. 2016, 1, 1–18. [Google Scholar] [CrossRef]
- Xu, C.H. Analysis of the zero-sequence Inrush Current Waveform for 500kV Transformer. Relay 1983, 3, 13–21. [Google Scholar]
- Tan, J.; Xiao, H.; Li, Y.; Zhang, A.L.; Li, Y.H. Study on impact of transformer magnetizing inrush current on the line zero sequence overcurrent protection by transient simulation. Power Syst. Prot. Control 2015, 19, 149–153. [Google Scholar]
- Du, J.W.; Liu, S.Z.; Wang, B. Study on Principle of Zero-Sequence Component Caused by transformer Inrush Phenomenon. Electr. Appl. 2007, 1, 27–31. [Google Scholar]
- Du, J.W.; Zhang, J.T.; Peng, H. Analysis of Impact of Transformer and Inrush Current on Zero-sequence Protection. Electr. Appl. 2009, 1, 42–46. [Google Scholar]
- Fang, Y.D.; Xu, X.D.; Zhu, B.Q. Impact of transformer inrush on zero-sequence current protection. Electr. Power Autom. Equip. 2008, 9, 115–118. [Google Scholar]
- Guo, Q.W.; Mo, W.X.; Zheng, F.Q.; Xiong, J. Analysis and measures of zero sequence current protection malfunction caused by no-load high-voltage built-in transformer. Power Syst. Prot. Control 2018, 22, 164–170. [Google Scholar]
- Weng, H.L.; Liu, W.; Lin, X.N.; Jin, N.; Li, Z.X.; Huang, J.G. Mechanism and Countermeasures of Mal-operation of Converter Transformer Zero-sequence Overcurrent Protection Caused by Inrush Currents. Autom. Electr. Power Syst. 2019, 9, 171–182. [Google Scholar]
- Wang, Y.X.; Cao, W.B.; Huang, M.H.; Yin, X.G.; Zeng, G.H.; Li, Y.Q.; Liu, W.; Chen, Q.P.; Wang, Z.C.; Liu, K. Mathematical Analysis for Zero-Mode Inrush Current of Transformer and Its Equivalent Circuit. Power Syst. Technol. 2018, 12, 3960–3968. [Google Scholar]
- Suonan, J.L.; Jiao, Z.B.; Kang, X.N.; Zhang, Y.N.; Song, G.B.; Liu, K. Algorithm to Identify Leakage Inductances of Power Transformer With Y-Delta Connection. Proc. CSEE 2008, 13, 84–90. [Google Scholar]
- Shi, S.W. Large Generator and Transformer Relay Protection; China WaterPower Pressfigure: Beijing, China, 1987. [Google Scholar]
- Yin, X.G.; Cao, W.B.; Pan, Y.L.; Wang, Y.X.; Guo, Q.; Liu, W. Inrush current characteristic of high-impedance transformers and its impact on protective relays. Power Syst. Prot. Control 2018, 20, 1–11. [Google Scholar]
- Jiao, Z.B.; Xing, W.; Wang, Z.; Jin, J.L. Features and Mechanism of Negative-sequence Second Harmonics of Magnetizing Inrush Current in Transformers. Autom. Electr. Power Syst. 2015, 11, 146–151. [Google Scholar]
- Jia, N.; Ma, S.M.; Li, Z.D.; Chen, Y.W.; Mao, J.; Zhou, L. Research on Initial Remanence Coefficient and Stable Remanence Coefficient of Current Transformer. Water Res. Power 2017, 11, 194–197. [Google Scholar]
- Qian, K.M.; Dai, D.S. Ferromagnetics; Science Press: Beijing, China, 1998. [Google Scholar]
- Shao, W.Q.; Qiao, N.; Wang, J.B. A novel algorithm of identifying inrush current based on waveform cross-correlation coefficient. Power Syst. Prot. Control 2015, 23, 14–20. [Google Scholar]
- He, J.H.; Li, J.Z.; Yao, B.; Ou, Z.J.; Fan, Y. A New Approach of Transformer Inrush Detected Based on the Sine Degree Principle of Current Waveforms. Proc. CSEE 2007, 4, 54–59. [Google Scholar]
- Bi, D.Q.; Zhang, X.A.; Yang, H.H.; Yu, G.W.; Wang, X.H.; Wang, W.J. Correlation Analysis of Waveforms in Nonsaturation Zone-Based Method to Identify the Magnetizing Inrush in Transformer. IEEE Trans. Power Deliv. 2007, 3, 1380–1385. [Google Scholar] [CrossRef]
Parameters | Lσ | LσD | Mair |
---|---|---|---|
T-Hin | 0.14 pu | 0.22 pu | 0.07 pu |
T-Ord | 0.14 pu | 0.09 pu | 0.2 pu |
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Cao, W.; Yin, X.; Chen, Y.; Pan, Y.; Yin, X.; Wang, Y. The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Overcurrent Protection and an Improved Protection with the Second Harmonic Restraint. Energies 2019, 12, 2911. https://doi.org/10.3390/en12152911
Cao W, Yin X, Chen Y, Pan Y, Yin X, Wang Y. The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Overcurrent Protection and an Improved Protection with the Second Harmonic Restraint. Energies. 2019; 12(15):2911. https://doi.org/10.3390/en12152911
Chicago/Turabian StyleCao, Wenbin, Xianggen Yin, Yongxin Chen, Yuanlin Pan, Xiangyuan Yin, and Yuxue Wang. 2019. "The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Overcurrent Protection and an Improved Protection with the Second Harmonic Restraint" Energies 12, no. 15: 2911. https://doi.org/10.3390/en12152911
APA StyleCao, W., Yin, X., Chen, Y., Pan, Y., Yin, X., & Wang, Y. (2019). The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Overcurrent Protection and an Improved Protection with the Second Harmonic Restraint. Energies, 12(15), 2911. https://doi.org/10.3390/en12152911