The Effect of High Occupancy Density on IAQ, Moisture Conditions and Energy Use in Apartments
Abstract
:1. Introduction
1.1. Housing Shortage Results in Overcrowded Apartments
1.2. Effects of High Occupancy Density on Indoor Quality and Demand for Ventilation
1.3. Effects of High Occupancy Density on General Wellbeing
1.4. The Effect of Occupancy Density on Energy Use
1.5. The Effect of Occupancy Density on Indoor Environment and Moisture supply
1.6. Aim of the Study
2. Materials and Methods
2.1. General Outline of the Methods Used
2.2. Measurements of Carbon Dioxide, Temperature and Moisture Supply
2.3. Calculations of Occupancy Level based on CO2 Measurements
2.4. Relation between Occupancy and Moisture Supply
2.5. Calculations of Energy Demand for Heating and Ventilation
3. Results
4. Discussion
5. Conclusions
Author Contributions
Funding
Conflicts of Interest
References
- Boverket, Swedish Board of Housing Building and Planning. Calculation of the Need of Housing Until 2025; Swedish Board of Housing Building and Planning: Karlskrona, Sweden, 2017. [Google Scholar]
- Boverket. Trångboddheten i Storstadsregionerna; Report 2016:28; Boverket: Karlskrona, Sweden, 2016; ISBN 978-91-7563-419-7. [Google Scholar]
- SCB Statistics. Undersökningarna av Levnadsförhållanden (ULF), Statistics Sweden, Stockholm. Available online: http://www.scb.se (accessed on 13 September 2019).
- Swedish Tenant Association. 2018. Available online: https://hurvibor.se/hur-vi-bor/bostadsyta/ (accessed on 21 November 2019).
- Boverket. BETSI Study—Buildings’ Energy Use, Technical Status and Indoor Environment; Boverket: Karlskrona, Sweden, 2009. [Google Scholar]
- Dovjak, M.; Slobodnik, J.; Krainer, A. Deteriorated Indoor Environmental Quality as a Collateral Damage of Present Day Extensive Renovations. Strojniški vestnik. J. Mech. Eng. 2019, 65, 31–40. [Google Scholar] [CrossRef]
- Bagge, H. Building Performance—Methods for Improved Prediction and Verification of Energy Use and Indoor Climate, Building Physics LTH; Lund University: Lund, Sweden, 2011. [Google Scholar]
- Bagge, H.; Johansson, D.; Lindstrii, L. Measured indoor hygrothermal conditions and occupancy levels in an arctic Swedish multi-family building. HVAC R Res. J. 2014, 20, 376–383. [Google Scholar] [CrossRef]
- Fransson, V.; Bagge, H.; Johansson, D. Impact of variations in residential use of household electricity on the energy and power demand for space heating—Variations from measurements in 1000 apartment. Appl. Energy 2019, 254, 113599. [Google Scholar] [CrossRef]
- Boverket. Boverket’s Building Regulations. Available online: https://www.boverket.se/en/start/building-in-sweden/swedish-market/laws-and-regulations/national-regulations/building-regulations/ (accessed on 17 November 2019).
- Boverket. OVK Obligatory Ventilation Control. Available online: https://www.boverket.se/en/start/building-in-sweden/swedish-market/laws-and-regulations/national-regulations/obligatory-ventilation-control/ (accessed on 17 November 2019).
- SCB Statistics. Available online: https://www.scb.se/hitta-statistik/artiklar/var-femte-person-fodd-utanfor-europa-ar-trangbodd/ (accessed on 13 September 2019).
- Krieger, J.; Higgings, D.L. Housing and Health: Time Again for Public Health Action. Am. J. Public Health 2002, 92, 758–768. [Google Scholar] [CrossRef] [PubMed]
- Bornehag, C.G.; Blomquist, G.; Gyntelberg, F.; Järvholm, B.; Malmberg, P.; Nordvall, L.; Sundell, J.; Pershagen, G.; Nielsen, A. Dampness in buildings and Health. Nordic interdisciplinary review of te scientific evidence on associations between exposure to “dampness” and health effects. Indoor Air 2001, 11, 72–86. [Google Scholar] [CrossRef] [PubMed]
- Evidens. Trångboddhet i Sverige—Beskrivning av Nuläget och Diskussion om Effekter, Stockholm i december 2016. Available online: http://www.mynewsdesk.com/se/hsb_riksforbund/documents/traangboddhet-i-sverige-beskrivning-av-nulaeget-och-diskussion-om-effekter-64435 (accessed on 21 November 2019).
- Johansson, T. Performance Visualization of Urban Systems. Ph.D. Thesis, Luleå University of Technology, Luleå, Sweden, 2017. [Google Scholar]
- Sekki, T. Evaluation of Energy Efficiency in Educational Buildings. Ph.D. Thesis, Aalto University, Helsinki, Finland, 2017. [Google Scholar]
- Markus, T.A. Cold, condensation and housing poverty. In Unhealthy Housing Research Remedies and Reform; Burrage, R., Ormandy, D., Eds.; Spon Press: New York, NY, USA, 1993; pp. 141–167. [Google Scholar]
- Møller, E.B.; de Place Hansen, E. Moisture Supply in Danish single-family houses—The influence of occupant behavior and type of room. Proceeding of the 11th Nordic Symposium on Building Physics, NSB2017, Trondheim, Norway, 11–14 June 2017. [Google Scholar]
- Swegon. Technical Documentation on Ventilation Systems; Swegon: Tomelilla, Sweden, 2006. [Google Scholar]
- Coley, D.A.; Beisteiner, A. Carbon dioxide levels and Ventilation Rates in Schools. Int. J. Vent. 2003, 1, 45–52. [Google Scholar] [CrossRef]
- Ruch, T.C.; Patton, H.D. Physiology and Biophysics; W B Saunders Company: Philadelphia, PA, USA, 1965. [Google Scholar]
- Levin, P. Anvisningar för val av Brukarindata för Beräkningar av specifik Energianvändning i Bostäder, Final Report 2009-01-20. Available online: http://www.sbuf.se (accessed on 21 November 2019).
- Bagge, H.; Lindstrii, L.; Johansson, D. Brukarrelaterad Energianvändning. Resultat från Mätningar i 1300 Lägenheter; FoU-Väst Rapport 1240; Sveriges Byggindustrier: Stockholm, Sweden, 2012. [Google Scholar]
- Kristoffersson, J.; Bagge, H.; Abdul Hamid, A.; Johansson, D.; Almgren, M.; Persson, M.-L. Användning av Värmeåtervinning i Miljonprogrammet; Report 2017:17; Swedish Energy Agency: Frösön, Sweden, 2017. [Google Scholar]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Mjörnell, K.; Johansson, D.; Bagge, H. The Effect of High Occupancy Density on IAQ, Moisture Conditions and Energy Use in Apartments. Energies 2019, 12, 4454. https://doi.org/10.3390/en12234454
Mjörnell K, Johansson D, Bagge H. The Effect of High Occupancy Density on IAQ, Moisture Conditions and Energy Use in Apartments. Energies. 2019; 12(23):4454. https://doi.org/10.3390/en12234454
Chicago/Turabian StyleMjörnell, Kristina, Dennis Johansson, and Hans Bagge. 2019. "The Effect of High Occupancy Density on IAQ, Moisture Conditions and Energy Use in Apartments" Energies 12, no. 23: 4454. https://doi.org/10.3390/en12234454
APA StyleMjörnell, K., Johansson, D., & Bagge, H. (2019). The Effect of High Occupancy Density on IAQ, Moisture Conditions and Energy Use in Apartments. Energies, 12(23), 4454. https://doi.org/10.3390/en12234454