Figure 1.
Schematic of heat pump unit.
Figure 1.
Schematic of heat pump unit.
Figure 2.
Cooling capacity with variation of refrigerant charge amount and
Figure 2.
Cooling capacity with variation of refrigerant charge amount and
Figure 3.
Evaporating temperature with variation of refrigerant charge amount and
Figure 3.
Evaporating temperature with variation of refrigerant charge amount and
Figure 4.
Refrigerant charge flow rate with variation of refrigerant charge amount and
Figure 4.
Refrigerant charge flow rate with variation of refrigerant charge amount and
Figure 5.
Variation of COP with and refrigerant charge amount.
Figure 5.
Variation of COP with and refrigerant charge amount.
Figure 6.
Power consumption with variation of refrigerant charge amount and
Figure 6.
Power consumption with variation of refrigerant charge amount and
Figure 7.
Pressure ratio with variation of refrigerant charge amount and
Figure 7.
Pressure ratio with variation of refrigerant charge amount and
Figure 8.
Variation of cooling capacity with in cooling mode.
Figure 8.
Variation of cooling capacity with in cooling mode.
Figure 9.
Variation of condensing temperature with in cooling mode.
Figure 9.
Variation of condensing temperature with in cooling mode.
Figure 10.
Variation of evaporating temperature with in cooling mode.
Figure 10.
Variation of evaporating temperature with in cooling mode.
Figure 11.
Variation of COP with in cooling mode.
Figure 11.
Variation of COP with in cooling mode.
Figure 12.
Variation of power consumption with in cooling mode.
Figure 12.
Variation of power consumption with in cooling mode.
Figure 13.
Variation of heating capacity with refrigerant charge ratio and
Figure 13.
Variation of heating capacity with refrigerant charge ratio and
Figure 14.
Variation of evaporating temperature with refrigerant charge ratio and
Figure 14.
Variation of evaporating temperature with refrigerant charge ratio and
Figure 15.
Variation of refrigerant mass flow rate with refrigerant charge ratio and
Figure 15.
Variation of refrigerant mass flow rate with refrigerant charge ratio and
Figure 16.
Variation of COP with refrigerant charge ratio and
Figure 16.
Variation of COP with refrigerant charge ratio and
Figure 17.
Variation of power consumption with refrigerant charge ratio and
Figure 17.
Variation of power consumption with refrigerant charge ratio and
Figure 18.
Heating capacity with variation of in heating mode.
Figure 18.
Heating capacity with variation of in heating mode.
Figure 19.
COP with variation of in heating mode.
Figure 19.
COP with variation of in heating mode.
Figure 20.
Degree of subcooling with variation of refrigerant charge ratio and
Figure 20.
Degree of subcooling with variation of refrigerant charge ratio and
Figure 21.
Relationship between refrigerant charge ratio and condensing temperature in cooling mode.
Figure 21.
Relationship between refrigerant charge ratio and condensing temperature in cooling mode.
Figure 22.
Relationship between the refrigerant charge ratio and compressor discharge temperature in cooling mode.
Figure 22.
Relationship between the refrigerant charge ratio and compressor discharge temperature in cooling mode.
Figure 23.
Relationship between the refrigerant charge ratio and degree of subcooling in cooling mode.
Figure 23.
Relationship between the refrigerant charge ratio and degree of subcooling in cooling mode.
Figure 24.
Relationship between the refrigerant charge ratio and evaporating temperature in cooling mode.
Figure 24.
Relationship between the refrigerant charge ratio and evaporating temperature in cooling mode.
Figure 25.
Condensing temperature with variation of in cooling mode.
Figure 25.
Condensing temperature with variation of in cooling mode.
Figure 26.
Compressor discharge temperature with variation of in cooling mode.
Figure 26.
Compressor discharge temperature with variation of in cooling mode.
Figure 27.
Relationship between refrigerant charge ratio and condensing temperature in heating mode.
Figure 27.
Relationship between refrigerant charge ratio and condensing temperature in heating mode.
Figure 28.
Relationship between refrigerant charge ratio and degree of subcooling in heating mode.
Figure 28.
Relationship between refrigerant charge ratio and degree of subcooling in heating mode.
Figure 29.
Relationship between refrigerant charge ratio and evaporating temperature in heating mode.
Figure 29.
Relationship between refrigerant charge ratio and evaporating temperature in heating mode.
Figure 30.
Compressor discharge temperature with variation of refrigerant charge ratio in heating mode.
Figure 30.
Compressor discharge temperature with variation of refrigerant charge ratio in heating mode.
Figure 31.
Comparison between experimental and predicted RCR in cooling mode at of (a) 20 °C, (b) 25 °C, (c) 30 °C and (d) 35 °C.
Figure 31.
Comparison between experimental and predicted RCR in cooling mode at of (a) 20 °C, (b) 25 °C, (c) 30 °C and (d) 35 °C.
Figure 32.
Comparison between experimental and predicted RCR in heating mode at of (a) −5 °C, (b) 0 °C, (c) 5 °C and (d) 10 °C.
Figure 32.
Comparison between experimental and predicted RCR in heating mode at of (a) −5 °C, (b) 0 °C, (c) 5 °C and (d) 10 °C.
Figure 33.
Refrigerant FDD algorithm for water-to-water heat pump unit.
Figure 33.
Refrigerant FDD algorithm for water-to-water heat pump unit.
Table 1.
Test Conditions.
Table 1.
Test Conditions.
Parameter | Unit | Cooling Mode | Heating Mode |
---|
| | Reference condition | Experimented condition | Reference condition | Experimented condition |
Refrigerant | ** | R410A | R410A | R410A | R410A |
Optimum charge amount | (kg) | 4.7 | 4.7 | 4.7 | 4.7 |
Refrigerant charge ratio | (%) | 100 | 70, 80, 90, 100, 110, 120 | 100 | 70, 80, 90, 100, 110, 120 |
| (°C) | 12 | 12 | 40 | 40 |
| (°C) | 25 | 20, 25, 30, 35 | 5 | −5, 0, 5, 10 |
OD/ID HX secondary fluid flow rate | (LPM) | 8/8 | 8/8 | 8/8 | 8/8 |
EEV opening | % | Adjusted | Adjusted | Adjusted | Adjusted |
Table 2.
Parameter trend and characteristics of the water-to-water heat pump in cooling mode.
Table 2.
Parameter trend and characteristics of the water-to-water heat pump in cooling mode.
Parameter | Refrigerant Reduction | TOD Increase
|
---|
Degree of subcooling | ↓ | ≈ |
Condensing temperature | ↓ | ↑ |
Evaporating temperature | ↑ | ↑ |
Compressor discharge pressure | ↓ | ↑ |
Compressor discharge temperature | ↓ | ↑ |
Secondary fluid temperature difference across ID HX | ↓ | ↓ |
Secondary fluid temperature difference across OD HX | ↓ | ↓ |
Table 3.
Parameter trend and characteristics of the water-to-water heat pump in heating mode.
Table 3.
Parameter trend and characteristics of the water-to-water heat pump in heating mode.
Parameter | Refrigerant Reduction | TOD Increase |
---|
Degree of subcooling | ↓ | ≈ |
Condensing temperature | ↓ | ↓ |
Evaporating temperature | ↑ | ↓ |
Compressor discharge pressure | ↓ | ↓ |
Compressor discharge temperature | ↓ | ↓ |
Secondary fluid temperature difference across ID HX | ↓ | ↑ |
Secondary fluid temperature difference across OD HX | ↓ | ↑ |
Table 4.
Coefficients of refrigerant charge correlations in cooling mode.
Table 4.
Coefficients of refrigerant charge correlations in cooling mode.
Correlation Type | a | b | c | d | e | f | g | h | i | j | k |
---|
Compressor discharge temperature | 23.79 | −4.947 | 0.06051 | 2.4861524 | −0.00491 | −0.006853 | ** | ** | ** | ** | ** |
Degree of subcooling | 78.7 | 0 | 0 | 2.889 | −0.052 | 0 | ** | ** | ** | ** | ** |
Condensing temperature | −4.778 | −7.7740471 | 0.038358778 | 6.5626564 | −0.04537 | 0.05732 | ** | ** | ** | ** | ** |
Evaporating temperature | −341.8 | 49.38 | −1.931 | 0.02526 | −295.7 | −57.66 | −4.667 | 23.52 | 1.999 | −0.4669 | 0.01102 |
Table 5.
Coefficients of refrigerant charge correlations in heating mode.
Table 5.
Coefficients of refrigerant charge correlations in heating mode.
Correlation Type | a | b | c | d | e | f | g | h | i | j | k |
---|
Compressor discharge temperature | −365.2 | −6.132 | 0.1011 | 0.00003 | 12.55 | −0.1202 | 0.0004 | 0.1211 | −0.0006 | −0.0021 | 0.00001 |
Degree of subcooling | 77.11 | 0 | 0 | 4.894 | −0.1422 | 0 | ** | ** | ** | ** | ** |
Condensing temperature | 292.5 | 4.659 | 0.005569 | −12.31 | 0.1669 | −0.1303 | ** | ** | ** | ** | ** |
Evaporating temperature | 65.81 | 1.867 | 0.1232 | −3.6727125 | 0.09042 | −0.2262 | ** | ** | ** | ** | ** |
Table 6.
Error thresholds.
Table 6.
Error thresholds.
Correlation | Percentage Error (%) |
---|
Cooling Mode | Heating |
---|
Evaporating temperature | ±7.9 | ±4.3 |
Condensing temperature | ±4.1 | ±2.9 |
Degree of subcooling | ±11.5 | ±10.7 |
Compressor discharge temperature | ±4.5 | ±1.1 |