1. Introduction
The European Union (EU) has set an objective to be climate neutral by 2050. This implies that 80–95% reduction in greenhouse gas (GHG) emissions, compared to the 1990 levels, needs to be achieved through pursuing the most energy efficient and economically feasible measures. It is estimated that the EU building sector accounts for about 36% of CO
2 emissions and 40% of used energy [
1] and over 25% of buildings are historic [
2]. Therefore, one of the main measures to achieve these goals is to focus on improving energy efficiency in the building sector, including historic buildings.
One part of energy use in buildings, especially for office and commercial buildings, is cooling demand. Night ventilation (NV) is one of the promising techniques which has shown to significantly reduce buildings’ cooling demand and improve thermal comfort [
3], specifically when applied to massive/heavy buildings [
4]. This is an indirect way of cooling in which the building is ventilated with colder ambient air during nighttime to cool down its structural elements. The cool fabric can then absorb the heat flows the following day and provide comfort by reducing both the indoor air and wall temperature rises.
The efficiency of NV is strongly dependent on some main parameters: (1) daily amplitude of the ambient temperature (higher effectiveness with higher amplitude; specifically with lower minimum ambient temperature), (2) the difference between indoor and ambient temperatures mainly during night period, (3) the NV rate, (4) the NV operation period and duration, (5) the thermal capacity of the building, and (6) efficient coupling of air flow and thermal mass (an example of inefficient coupling is short circuit air flow through the windows) [
5].
Some studies have evaluated the effect of climatic situations (including the ambient temperature) on the potential of NV strategy. Artman et al. [
6] showed that Northern European climates (including the British Isles) offer a significant potential for cooling by NV, while in Central, Eastern and even some regions of Southern Europe, additional cooling systems are required to fulfill thermal comfort during a series of warmer nights at some locations. It was depicted that in southern Spain, Italy and Greece, NV might be promising for hybrid systems. Another study by Artmann et al. [
7] assessed the influence of the future climate warming on NV potential and showed that by 2071–2100, the decrease in mean cooling potential will be in the range of 12.5–37.5 W/m
2, depending on season, location and the emission scenarios. Jimenez-Bescos [
8] simulated the effect of the future climate scenarios on the required NV rates with the help of thermal mass for reducing overheating in the buildings located in London Islington. It was shown that while NV rates over eight air changes per hour (ACH) could provide significant overheating reductions in the short term, in the long term, the 2080s, NV rates less than 10 ACH have very low influence for this purpose, less than 3% and 8% for high and medium emissions scenarios, respectively. Kolokotroni et al. [
9] simulated how urban heat island phenomenon can increase the building summer cooling demand and deplete the NV potential. They showed that, during a typical hot week and in the same location, the rural reference office has 84% of the cooling demand of the urban one. It also depicted that a rural optimized office, unlike an urban one, could maintain temperatures below 24 °C without artificial cooling and would need 42% of the cooling required for an urban optimized office.
Several parametric studies using Building Energy Simulation (BES), pointed out the important influence of different building design and operational parameters including thermal mass of the building [
10], NV rate [
11,
12] and NV period and duration [
12] on the effectiveness of NV strategy in different climatic conditions. The results of some studies have shown more than 60% cooling load reduction by increasing building time constant between 400–1000 h [
13], up to 3 °C reduction in peak indoor air temperature for high thermal mass [
5,
14], 2–3 °C reduction in indoor temperatures by doubling the building mass (800 kg/m
3 to 1600 kg/m
3) [
15], and 3–6 °C indoor temperature decrease depending on the amount of thermal mass, the rate of NV, and the temperature swing of the site between day and night [
16].
The higher the NV rate, the higher the effectiveness of the strategy; there may exist some thresholds, however. The results of some parametric studies using BES have depicted the achievable reduction of the peak indoor temperature up to 1 °C as well as attained comfort criteria with NV rates lower than 10 ACH for Spanish climates (further increases produced marginal improvements) [
17] and for maritime Irish climate [
15]. Some studies have shown reduction in the mean radiant temperature of building’s indoor surface up to 3.9 °C at 8:00 am with NV rate of 10 ACH for the Northern Chinese climate [
4], and a 39–96% decrease in the overheating hours (with natural NV) and 48–94% energy reduction (with air conditioning systems) with the NV rates of 10–30 ACH for the Greek climate (Athens) [
5].
Different suggestions have been proposed regarding the influence of NV runtime (including the start point and the duration) on the effectiveness of NV strategy. They include, among others, NV duration with 5 a.m. in the middle of the period (such as 4 a.m. to 6 a.m.) [
18] and longer NV duration and closer NV period to the active cooling period [
4,
12,
19,
20].
Many parametric studies, using BES, investigated the influence of NV strategy on both improvement of thermal comfort and reduction of energy use for active cooling in office buildings. Some studies have shown the potential of NV in the form of determining the optimal NV flow rate over which further increase in ventilation rate, produces marginal improvements in thermal comfort in the building; dependent on the thermal mass capacity of the building [
4,
5,
17]. These studies, afterward, calculated the amount of saved energy for active cooling based on this maximum beneficial ventilation rate. However, for mechanically driven NV, the electricity use in ventilation unit’s fans needs also to be taken into account. In other words, the maximum beneficial NV rate is the ventilation rate which results in the minimum total energy use which consists of energy use for active cooling plus electricity use in ventilation unit’s fans. For NV rates above this maximum limit, the amount of increase in electricity use in fans outweighs the amount of decrease in energy use for active cooling and, therefore, the total energy use starts increasing.
Lain and Hensen [
21] performed a parametric study on the optimization of mechanical NV system in an office building, including two NV rates and the mechanical cooling system’s coefficient of performance (COP) 2.5. They illustrated that due to the relatively high COP value, the electrical energy use in the fans can outweigh even the large cooling energy savings by NV. However, they did not evaluate the potential of NV for other COP values. In fact, cooling systems with lower performance, lower COP values, might result in higher potential of NV for cooling energy savings. The evaluation of NV potential for cooling energy savings for various cooling system’s COP values has not been widely covered in the literature and a research gap is recognized in this area.
Guo et al. [
22] evaluated the influence of the key design parameters on NV performance indicators using a holistic approach integrating sensitivity and parametric simulation analyses. They concluded that the window-wall ratio, internal convective heat transfer coefficient, internal thermal mass level, and NV rate are the most important parameters. Percentage outside the range (POR), from the thermal comfort improvement category, ventilative cooling advantage (ADV), from the energy efficiency category, and cooling requirements reduction (CRR), from the ability to reduce cooling energy use category, were recommended to evaluate the NV performance.
In the present study, the effect of mechanical NV strategy on both thermal comfort and electricity use for cooling of a typical historic office building in north-central Sweden was assessed. The NV performance indicators from thermal comfort improvement and energy efficiency categories were used in the assessment. In the former, POR was applied and, in the latter, the total electricity use for cooling, comprising the electricity use in cooling machine plus the electricity use in ventilation system, was compared in different cases. The IDA indoor climate and energy (IDA-ICE) simulation program was used to model the potential for improving thermal comfort and electricity savings by applying NV cooling. The parametric study comprised different outdoor climate conditions, flow rates, cooling machine´s COP and ventilation unit’s specific fan power (SFP) values. In addition, the effect of different door schemes (i.e., open doors or closed doors) on thermal comfort in the offices was investigated.
3. Materials and Methods
Methods used in this study include on-site measurements, including logging on the building management system (BMS), and applying a BES tool. An overview of the methods is shown in
Figure 2, and it can be divided into five main steps. In the first step, the input and calibration data were collected from on-site measurements and BMS logging, and the initial BES model of a non-occupied zone was created. In the second step, the BES model of the zone was calibrated. The final calibrated BES model included the construction materials normally used at the time the City Hall was constructed [
24]. In the third step, the BES model of a representative floor level was created with the same construction materials as the second step. In the fourth and fifth steps, using the floor-level BES model, the thermal comfort and energy use analyses were carried out.
3.1. Calibration
The numerical analyses were carried out using the dynamic simulation software IDA-ICE version 4.8. IDA-ICE has been tested and validated according to various international and standard tests [
25,
26,
27,
28,
29].
The aim was to simulate a floor plan of the building for the parametric study. In order to get the materials and the thermal performance of the structures reasonably accurate, a simulation model of a non-occupied office room was calibrated. The IDA-ICE simulation program supports only one-dimensional heat transfer, while the windows have niches which are two-dimensional thermal bridges. The niches were modelled as equivalent walls with one-dimensional heat transfers and the equivalent thicknesses were calculated using COMSOL Multiphysics (CM) simulation program version 5.3.
The modeled building in IDA-ICE is oriented with 40° clockwise from north which was measured on site. The shading effects of neighboring buildings were modelled by non-transparent bars (shading building) based on estimated heights and distances to the building of the City Hall using on-site observation.
3.2. Calibration of One Zone
In order for BES models to be used with any degree of confidence, it is necessary that the model closely characterizes the actual behavior of the building. The purpose of model calibration is to decrease the discrepancies between BES and measured building performance.
With the aim of calibrating the BES model, a set of detailed measurements were done in a non-occupied office room in the building, with mechanical ventilation turned off. The room was situated on the last floor facing northwest with the minimum solar radiation during the day. The room size was 4 × 3.2 m and the floor–ceiling height was 2.9 m. The window size was 1.3 (width) × 2.6 m (height) and without internal shading.
The calibration of the office’s BES model was done based on the heating demand of the office during the measurement period. An electrical radiator in which the operative temperature was controlled by the thermostat was applied in the model.
A manually tuned iterative process of simulation runs aiming at reducing discrepancies between simulated and measured data was used for calibrating the model of the selected office room. The iterative process was performed by calculating two principal uncertainty indices at each runtime including Normalized Mean Bias Error (NMBE) and Coefficient of Variation of the Root Mean Square Error (CV(RMSE)) [
30].
The calibration indices were calculated as follows:
where
is the measured value,
is the simulated value,
is the number of measured data points, and
is the mean of the measured values. P is the number of adjustable model parameters which, for calibration purpose, is suggested to be zero in Equation (1) and to be one in Equation (2) [
31,
32].
Table 1 shows the calibration criteria proposed by ASHRAE Guideline 14 [
33].
After the first set of simulation runs, the heat transmission through the internal walls as well as the construction materials were identified as the influencing parameters on the difference between the simulated and measured data. In the final calibrated model, the temperature profiles of the adjacent zones (based on BMS logged data) as well as the typical constructions used in buildings at the time when City Hall was built [
24] were taken into account. Thermal bridges along different joints were also implemented.
3.3. Measurements Used for Calibration
An electrical radiator, on/off controlled by thermostat, was used to heat up the room during the period 12th–17th May 2018. During this period, the hydronic radiator was shut off, the ventilation supply and return devices were completely sealed, and the room’s closed door was taped to ensure that only the electrical radiator heated up the room.
The electrical power measurements were done at one-minute intervals using an energy logger. Room air and surface temperatures were measured at five-minute intervals using thermistor sensors for temperature which were connected to a data logger. A vertical rod with attached thermistor sensors for temperatures at four different heights was placed in the middle of the room to measure room air temperature. Room air temperature was calculated as the average of measured values at the four different heights. Temperatures of all available internal surfaces in the room were measured, including the surface of internal walls, external wall, floor, ceiling, door and window. A weather station installed on the roof of a nearby building was used to measure ambient air temperature, relative humidity, and wind direction. The climate file used for the simulation part of the calibration process was created based on the measured data on the weather station plus the solar radiation data from the Swedish meteoroidal institute [
34]. The measurement tools and equipment are illustrated in
Figure 3. The technical data of measurement equipment are presented in
Table 2.
3.4. Model Calibration
Table 3 illustrates the construction materials and infiltration rate used in the IDA-ICE model of the selected room for the calibration purpose.
Table 4 shows the calculated linear heat loss coefficients for thermal bridges for different types of joints.
The calibration indices were calculated on an hourly basis for office room’s air temperature and different surface temperatures. Since the electrical radiator was an on/off radiator and due to low seasonal heating demand, it turned on during very short periods (maximum ten-minute periods). The thermostat of the modelled radiator could not model the on/off performance, rather than on P-control. Therefore, the use of hourly calibration indices for the power of the electrical radiator did not give the possibility for correct comparison between measured and simulated data for this parameter. Thus, the calibration indices for this parameter were calculated based on a daily basis. The calculated indices are shown in
Table 5.
As
Table 5 illustrates, the hourly calibration indices for the office room’s air temperature and different surface temperatures are in the acceptable range based on ASHRAE Guideline 14 according to
Table 1. This guideline does not present any daily criteria. However, considering the daily criteria as an average between hourly and monthly criteria, the acceptable daily criteria for NMBE and CV (RMSE) could be proposed as ±7.5% and 22.5%, respectively. Considering these daily criteria, the daily calibration indices for the power of the electrical radiator are in the acceptable range base on ASHRAE Guideline 14.
Figure 4 shows the office room’s air temperature and the power of the electrical radiator during the measurement period based on both measurement and simulation results. Note the influence of late afternoon sun on the increase in room temperature. Simulations tend to over-estimate the air temperature during insolation (which could be due to window niches which are not possible to fully model in IDA-ICE).
3.5. Simulation of NV
In thermal comfort analysis, in the first step, the influence of totally eight different cases on the operative temperatures of office rooms was assessed and the optimum case was determined. The cases included with and without NV strategy as well as different schemes of offices’ doors (i.e., closed or open doors). The cases are presented in
Table 6.
Next, the effect of four different improving measures was evaluated on the optimum case determined in the previous step. In the building’s energy use analysis section, the variation of total electricity use for cooling (i.e., electricity use in cooling machine plus electricity use in fans) was evaluated for different cooling machine’s COP values and various SFP models for ventilation unit’s fans.
The corridors and the entrance hall on the representative floor level were modelled as integrated zones and the existing internal walls located inside them were defined as internal masses in these zones. The model of the representative floor level on IDA-ICE is shown in
Figure 5.
Internal gains from equipment and lighting were defined according to common assumptions for office buildings [
37]. The default value of 0.1 m/s was specified for the air velocity in offices during summer. The occupants’ clothing insulation was defined as 0.8 ± 0.2 clo for summer in order to represent normal office clothing plus, when needed, an extra sweater [
38]. The activity level was specified to be 1.1 met to represent the average of common office activities including seated quiet resting, seated reading, typing as well as standing relaxed rest [
38]. It was assumed that only one person worked in each single office with their desk placed in the middle of the office. The period 08:00–17:00 (normal working hours) was defined as the schedule for all internal gains. The defined internal gains in different zones on the floor are shown in
Table 7.
Predefined supply and return air ventilation unit with a constant air volume (CAV) type was applied. The unit included a predefined control macro for NV strategy which also included the schedule of the daytime ventilation. The ventilation rate was measured as 1.66 ACH in one of the offices in the building which corresponded to the design ventilation rate. Considering the same design ventilation rate in all offices, the ventilation unit’s total design ventilation rate was defined as 1.66 ACH of the total volume of the connected office rooms. The schedule for daytime ventilation and NV were defined as 06:00–18:00 and 20:00–06:00, respectively. For improving measures on NV by doubled and tripled NV rates (see thermal comfort analysis section), the NV schedule was shortened to 20:00–04:00.
For thermal comfort analysis, without active cooling (AC) during day, the total design ventilation rate was set for both daytime- and NV rates. For energy use analysis, when local ideal coolers were applied in offices as active cooling, the minimum required ventilation rate (corresponding to 0.35 l/s·m
2 + 7 l/s·person) [
39] was set for the daytime ventilation keeping the night ventilation rate at the total design value. This means that the ventilation unit acted as a CAV system with two different constant ventilation rates with different working schedules (daytime ventilation and NV) plus the off mode. The proportional controller with the P-band corresponding to 1 °C (i.e., set point temperature ±0.5 °C) was defined for each local ideal cooler.
For NV strategy, the ventilation unit’s return air and ambient temperature limit were set to 18 and 10 °C, respectively, and the benefit limit (i.e., the difference between ambient and return air temperatures) was defined as +2 °C. It means that the NV starts if all the following conditions are fulfilled and stops if any of them is missed:
- (1)
The time is during the period defined for NV schedule;
- (2)
The ventilation unit’s return air temperature is over 18 °C;
- (3)
The ambient temperature is over 10 °C;
- (4)
The ambient temperature is at least 2 °C lower than the return air temperature.
3.6. Thermal Comfort Analysis
In order to evaluate thermal comfort in this study through comparing with standards’ recommendations, operative temperature (T
op) was used as an indicator. The maximum acceptable T
op during summer for activity level around 1.2 met and clothing insulation around 0.5 clo in single (cellular) offices is 26 °C [
40]. T
op of office rooms with different orientations were compared with each other for the eight different cases presented in
Table 6. Simulations were carried out for two summer climates for the city of Gävle in Sweden: (1) Typical summer (representative of the average climate condition for a 30-year period of 1981–2010), and (2) the unusually hot summer of 2018. The cases which resulted in the lowest possible T
op in the offices were determined. The mean and average diurnal variation of ambient temperature for both typical and hot summer are presented in
Table 8.
In order to further decrease the Top in offices for the determined cases, four improving measures were proposed:
- (1)
Decreasing the minimum ambient temperature limit (ATL) of NV strategy from 10 to 5 °C;
- (2)
Doubling the daytime ventilation rate (DVR);
- (3)
Doubling the NV rate (NVR) while decreasing the NV period (NVP) from 20:00–06:00 to 20:00–04:00;
- (4)
Tripling the NV rate (NVR) while decreasing the NV period (NVP) from 20:00–06:00 to 20:00–04:00.
3.7. Energy Use Analysis
In the first step, the active cooling was added to four different cases with NV in the “Thermal comfort analysis” section (i.e., cases 3, 4, 6, and 8 in
Table 6) and simulations were run for both typical and hot summers in order to show the difference in building’s total electricity use for cooling between these cases.
In the second step, the parametric study was carried out on the effect of different NV rates on the building’s total electricity use for cooling during the hot summer conditions of 2018. The total electricity use for cooling in the building consisted of (1) electricity use in cooling machine plus (2) the electricity use in ventilation unit’s fans. Considering the former, three cooling machines with COP values of 1, 2 and 3 as well as two cooling set points for T
op including 26 and 24 °C were taken into account in the parametric study. COP = 1 represents a cooling machine in which the amount of electricity use equals the amount of heat extracted equivalent to the cooling demand. Considering the latter part, five different NV rates including 0 ACH (i.e., without NV) and four multiples of 1.66 ACH as well as three various SFP models were considered. The VR during daytime was the minimum required value. In the first model, a constant SFP was defined for all NV rates. In the second and third models, the NV rates of 1.66 ACH and 3 × 1.66 ACH were considered as the design ventilation rates, respectively, and the SFP value was defined at these design ventilation rates. The SFP = 1.5 kW/(m
3/s) was applied as a common value for each design flow rate, which is recommended for new air-handling systems for the supply and return fans in ventilation units with heat recovery [
39]. SFP values for ventilation rates below the design flow rate were calculated based on data of part-load performance for VAV fan systems according to ASHRAE standard 90.1 [
41].
Table 9 shows the SFP values in different NV rates in the three mentioned models.