Article

Thermal and Energy Performance Assessment of the Prefab Electric Ondol System for Floor Heating in a Residential Building

1
Department of Architectural Engineering, Seoil University, Seoul 02192, Korea
2
Department of Architectural Engineering, King Fahd University of Petroleum and Minerals (KFUPM), Dhahran 31261, Saudi Arabia
*
Authors to whom correspondence should be addressed.
Energies 2020, 13(21), 5723; https://doi.org/10.3390/en13215723
Submission received: 1 September 2020 / Revised: 24 September 2020 / Accepted: 9 October 2020 / Published: 2 November 2020
(This article belongs to the Special Issue Buildings Energy Efficiency and Innovative Energy Systems)

Abstract

:
In South Korea, radiant floor heating has been used from old housing to the recently constructed residential buildings, which is called “Ondol”. The Ondol system is generally a water-based system and it uses hot water as a heat medium provided by boilers fueled by natural gas. With great effort to reduce greenhouse gas emissions, electric Ondol panels have been increasingly applied to the recent residential buildings for floor heating. While the prefab electric Ondol panels were developed with the demand for dry construction method, the information about the prefab electric Ondol system is not sufficient. For the present study, the thermal performance of the prefab electric Ondol panels was investigated through field measurement. In addition, the heating energy and economic performance of the electric panel were compared with the conventional Ondol system. As a result, a significant surface temperature difference was observed. Moreover, the heating cost for the prefab electric Ondol system was more expensive than the conventional system, even though a heat loss was observed by the operation of the conventional system.

1. Introduction

As one of the main contributors to building energy consumption in South Korea, a residential building sector has accounted for more than 65% of total buildings in 2017 [1]. According to the report provided by the Korea Energy Economics, about 10% of the total energy was used for residential buildings [2]. Specifically, natural gas and electricity accounted for 46% and 28% of household end-use energy consumption in 2015, respectively, which were the most-used energy sources for residential buildings [2]. In addition, more than half of the annual energy consumption for residential buildings was used for space heating and cooling, and others were used for water heating, lighting, and miscellaneous equipment [3,4].
While the energy consumption for cooling has been recently increased, a significant amount of energy still has used for heating in residential buildings [5,6]. Accordingly, there are several types of heating methods available including central gas heating, district heating, and individual gas heating. As an individual gas boiler has become available with the development of infrastructures since 2000, the individual gas heating method has been dominantly used for residential buildings [7]. Traditionally, most residential buildings in South Korea have preferred to use radiant floor heating. According to the sample data of housing units in the study of Park et al., all housing units have equipped a hydronic radiant floor heating system [8]. For a radiant heating method, it is imperative to use fossil fuels for a domestic boiler, district, or central heating in South Korea in that the greenhouse gas emissions are still increased. Therefore, it is necessary to find alternative heat sources for radiant heating in residential buildings for the goal of reducing greenhouse gas emissions [9].
The use of radiant heating enables to provide more thermal comfort to occupants in houses as well as an opportunity for the energy-saving more than the conventional air heating systems [10,11]. Many studies have performed investigations for the performance of the radiant heating method. According to the study of Lin et al., the thermal performance of a water-based radiant heating system was compared with a convective heating system in residential buildings. Even though there was little difference between the two systems, the convective heating system might cause local discomfort based on the occupants’ surveys [12]. Sun et al. also investigated the thermal performance of a radiant heating system using a heat pipe [13]. In addition, the capillary tube was employed for the radiant floor heating system [14]. While water has been generally used for radiant heating systems as a heat source, radiant heating systems using electric cables have been recently adapted. Lodi et al. analyzed the efficiency of electric radiant heating systems regarding thermal comfort in old buildings [15]. As another type of electric panel, thermoelectric heating panels are used consisting of a radiant plate and several thermoelectric modules [16]. In the case of the study of Fang et al., phase change materials as a thermal storage medium were used for the electric radiant floor heating [17].
For the present study, the energy and economic performance of the electric radiant floor heating system in a residential building were assessed through the measurement and energy simulation. According to the Act on the Promotion of the Development, Use, and Diffusion of New and Renewable Energy, Korea Ministry of Trade, renewable energy systems should be designed for newly constructed residential buildings in South Korea [18]. Therefore, the electricity consumption for electric radiant floor heating systems can be offset by renewable energy systems such as electricity generated by solar PV panels. Moreover, this electric-based radiant heating system can contribute to reducing greenhouse gas emissions. However, there were a few studies for the investigation of the performance of the electric Ondol panels. Thus, this study will evaluate the thermal performance and the economic impact of the electric Ondol systems and discuss the results obtained through the measurement and the simulation. Moreover, the outcomes of the present study will be used to develop more energy and thermally efficient electric Ondol panels.

2. Prefab Electric Ondol System

Traditionally, Ondol has been used for an underfloor heating system in residential buildings, which meant a warm stone [19,20]. From the early nineteenth century to the recent construction, the Ondol system has been used in residential buildings as a representative floor heating method because of the advantage of the radiant heating [19,21,22]. By using hot water as a heating medium, hot water provided by a boiler system circulates pipes embedded in the concrete slab in that the circulation of hot water within the Ondol system can provide radiant heating. Comparing with the conventional air heating method, the Ondol system is more environmentally sustainable and cheaper regarding the life cycle cost [23,24,25].
In general, the Ondol system was constructed by the wet construction method on site. Nowadays, the modular construction method with prefab Ondol panels is increasingly adapted in residential buildings to enhance the construction quality and shorten the construction period [26]. The use of prefab Ondol panels can make buildings lighter than those made by the wet construction method as well as provide an opportunity to reduce construction waste [27]. While most prefab Ondol panels have used hot water from boilers fueled by natural gas or oil, another type of Ondol panel system using electricity was proposed as shown in Figure 1. According to the study of Jeong, about 10% of total energy-saving was achieved by using the prefab electric Ondol system [28]. However, there are a few studies about the performance of the prefab electric Ondol panels. To assess the performance of the prefab electric Ondol panels more accurately, the present study compared the performance of the prefab electric Ondol panels with the conventional Ondol systems in residential buildings.

3. Methodology

To assess the thermal performance of the prefab electric Ondol panels, thermal performance measurement was conducted in a residential building. In addition, energy performance, especially heating was analyzed by using energy simulation.

3.1. Building Description

For the present study, an apartment building located in Seoul in South Korea was selected. The apartment building has 56 units with 16 floors. On the 8th floor of the apartment building, the unit was selected with a total area of 125 m2. The measurement was conducted in the living room of the unit facing the southeast. The specification of the building envelops of the unit was presented in Table 1.

3.2. Thermal Measurement

As shown in Figure 2, 9 K-type thermocouples were located on the floor with 50 cm intervals to figure out the surface temperature of the floor heated by using the prefab electric Ondol panels. To monitor the indoor air temperature, a thermocouple was located at 1.5 m from the floor. In addition, a thermocouple was also located outdoor. The measurement was conducted from April 27th to May 4th in 2018 and the temperature data were recorded with 10 min intervals by the datalogger. Moreover, a surface temperature on the floor was visualized by using a thermal imaging camera. The energy consumption was also monitored to compare with the energy simulation. The equipment used for the measurement was presented in Table 2.

3.3. Energy Simulation

To assess the energy performance of the prefab electric Ondol panels, the energy simulation was performed by using eQuest 3.61, which is the comprehensive energy simulation tool to evaluate design parameters of energy conservation measures as well as provide detailed information of building energy use [29]. Using this software, the reference apartment building was modeled as shown in Figure 3. In addition, the energy simulation was performed by using the specification of the reference building in Table 1. The residential building was operated for 24 hours and the HVAC system ran between 5 pm to 7 am. Moreover, the design temperatures for heating and cooling were set at 20 °C and 26 °C, respectively. For the conventional Ondol system, a central water-to-water heat pump system was modeled for providing hot water, while the data obtained from the measurement were used for the prefab electric ondol model. The annual energy consumption of the unit by using the conventional Ondol system fueled by natural gas was compared with that operated by the prefab electric Ondol panels. For the simulation, the TMY weather data of Seoul in South Korea was utilized. The mean air temperature in Seoul was about 13 °C. The lowest and highest air temperatures were −12.6 °C and 35.4 °C, respectively. The mean wind speed was 2.2 m/s.
By using the coefficient of variation of the root mean squared error (CV(RMSE)) provided by ASHRAE Guideline 14, the monthly energy consumption of the reference residential building with the conventional Ondol system was compared with the energy simulation [30]. The models will be declared to be calibrated if they produce CV(RMSE)s within ±15% with monthly energy data.
R M S E = i = 1 n ( M i S i ) 2 n
C V R M S E = R M S E M a v g × 100
where Mi is the energy consumption of the residential building, while Si is the monthly energy consumption by energy simulation. n is the period and Mavg is the average for the energy consumption of the residential building.

4. Result

4.1. Thermal Performance of the Prefab Electric Ondol Panels

Figure 4 shows the air temperature distributions of the surface on the floor and the indoor and outdoor on May 2nd and 3rd. From 0 to 19:30 h on May 2nd, the heating was off and the indoor air temperature and the surface temperature on the floor were maintained at about 19.5 °C because of the thermal capacity of the building envelopes. From 19:30 h on May 2nd to 24 h on May 3rd, heating was provided by using the prefab electric Ondol panels. While the setpoint temperature for the Ondol panels was set at 60 °C at full-load, the maximum surface temperature on the floor was maintained at about 50 °C. In addition, the minimum surface temperature on the floor was about 28 °C. Even though the surface temperature on the floor was increased about 7 °C by the operation of the Ondol panels, the increase in the indoor air temperature was only about 4 °C with/without the Ondol panels. Thus, the indoor air temperature was about 24 °C. The operation of the Ondol panels took 1.4 kWh of electricity. Moreover, the surface temperature on the floor was visualized by using the thermal imaging camera (Figure 5). As shown in Figure 4, the maximum and minimum surface temperature difference was more than 20 °C and the surface temperature was higher than the indoor air temperature. It can be seen that water from conventional Ondol systems can transfer radiant and convective heat into the indoor fully because of higher heat capacity of water than that of air, while the electric Ondol panels only heated the floor directly. This caused the lower indoor air temperature than the surface temperature on the floor.

4.2. The Analysis of the Energy Consumption

4.2.1. The Comparison between Energy Simulation and the Monthly Energy Consumption

To confirm the validity of the energy model, the monthly energy consumption of the selected unit of the apartment building was compared with the energy consumption prediction. The energy simulation modeled the conventional Ondol system fueled by natural gas. As can be shown in Table 3, the total energy consumption of the selected unit and the energy simulation were 7862 kWh and 8611 kWh, respectively. In addition, the root mean squared errors (CV(RMSEs) ranged from 0.18 to 7.77. Even though there was much difference between the data and the prediction in December, all the values were within the acceptable range, the predicted results by the simulation met the requirement by ASHRAE Guideline 14 [30].

4.2.2. The Heating Cost Analysis

Considering the heating energy consumption, the annual heating cost for the conventional Ondol system and the prefab electric Ondol panel system was analyzed for 8 months (October to May) (Figure 6). Table 4 and Table 5 show the heating energy consumption and the cost of these two heating methods. The total heating cost for the conventional Ondol system and the prefab electric Ondol system were $140.5 (US dollar) and $313.2 (US dollar), respectively. As a result, the prefab electric Ondol system requires about 53% of the additional heating cost.

5. Discussion

The present study assessed the thermal and energy performance of the prefab electric Ondol panel comparing with the conventional Ondol system. Considering the result of the thermal measurement, a notable surface temperature difference was observed when the prefab electric Ondol system was applied. In addition, the increase in the surface temperature on the floor was about 30 °C, while about a 4 °C increase in the indoor air temperature was observed. This can cause thermal stratification, as well as occupants, can be dissatisfied thermally. Finally, it may require a significant amount of energy for thermal comfort. Considering the balance point temperature and the heat gain/loss by building envelopes. Thus, it is also necessary to conduct thermal measurement in a chamber by varying climate conditions.
As shown in Figure 7, the use of the prefab electric Ondol panels cost 50% more than that of the conventional Ondol system, while the heating energy consumption of the prefab electric Ondol system was about 8.6% lower than that of the conventional Ondol system. This was caused by the progressive electricity billing during the winter period (December to February) in South Korea, while the price of natural gas was the flat rate. Therefore, it requires to find out the criteria for assessing the performance of the prefab electric Ondol panel system more accurately.
Another important design consideration for the use of the electric Ondol panel system is electromagnetic waves. According to the National Radio Research Agency in South Korea, the permissible exposure limit is 833 mG, which is quite bigger than the permissible limit of the United States (2 mG) and Swiss (10 mG) [31,32]. Even though the electromagnetic wave of the prefab electric Ondol panel system ranges generally 0.4–0.5 mG, it requires further investigation for the electromagnetic waves from this electric Ondol panels and re-assessment with the permissible limit of other countries.

6. Conclusions

With an increasing demand for the dry construction method, the use of prefab Ondol panels has simplified building construction methods and shortened construction periods, where Ondol floor systems have been dominant. In addition, the electric Ondol panel system has become attractive due to its simplicity and electricity provided by the solar PV panels. The newly constructed residential buildings in South Korea should equip renewable energy systems. Even though the use of the prefab electric Ondol panel system has been rapidly increased, there were a few studies about the performance of this panel system.
For the present study, the thermal performance of the prefab electric Ondol system was investigated through the on-site measurement. In a unit of an apartment building, the surface temperature on the floor and the indoor and outdoor air temperatures were measured. As a result, a significant surface temperature difference was observed. In addition, the use of the prefab electric Ondol system rarely influenced indoor air temperature. The increase in the indoor air temperatures was quite lower than the increase in surface temperature on the floor with/without the use of the electric panels. This was also visualized by using a thermal imaging camera. Moreover, the heating cost for these two systems were evaluated by using energy simulation. The heating energy consumption in the unit with the prefab electric Ondol panel was about 10% lower than that by the conventional Ondol system fueled by natural gas. However, more than 50% of the heating cost was required for the electric Ondol system than the conventional one. It was caused by different energy sources.
Regarding the views of thermal and heating cost performance, the advantage for the use of the prefab electric Ondol panel system is not clear, even though this system has several advantages in terms of construction. For further study, it is necessary to investigate electromagnetic waves from the electric Ondol panels for occupants’ safety in buildings. In addition, it requires to conduct measurements with various types of Ondol panels during the winter. To figure out the surface temperature distribution, it is also necessary to employ computational fluid dynamics simulation. Moreover, the life cycle cost analysis is required for the complete investigation of the economic impact of the electric Ondol system.

Author Contributions

Data curation, W.L. and T.L.; formal analysis, W.L. and T.L.; investigation, W.L. and T.L.; software, D.D.K.; validation, D.D.K.; writing—original draft, D.D.K. All authors have read and agreed to the published version of the manuscript.

Funding

The present research has been conducted by the Research Grant of Seoil University in 2020.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. The Annual Energy Consumption in 2017. Korea Energy Agency. Available online: http://www.Energy.Or.Kr/renew_eng/main/main.Aspx (accessed on 15 August 2018).
  2. A Report for the Energy Consumption in 2017. Korea Energy Economics Institute. Available online: http://www.Keei.Re.Kr/main.Nsf/index.Html (accessed on 15 August 2018).
  3. Song, D.; Choi, Y.-J. Effect of building regulation on energy consumption in residential buildings in korea. Renew. Sustain. Energy Rev. 2012, 16, 1074–1081. [Google Scholar] [CrossRef]
  4. Choi, I.Y.; Cho, S.H.; Kim, J.T. Energy consumption characteristics of high-rise apartment buildings according to building shape and mixed-use development. Energy Build. 2012, 46, 123–131. [Google Scholar] [CrossRef]
  5. Jeong, Y.-S.; Lee, S.-E.; Huh, J.-H. Estimation of CO2 emission of apartment buildings due to major construction materials in the republic of korea. Energy Build. 2012, 49, 437–442. [Google Scholar] [CrossRef]
  6. Kim, M.J.; Cho, M.E.; Kim, J.T. Energy use of households in apartment complexes with different service life. Energy Build. 2013, 66, 591–598. [Google Scholar] [CrossRef]
  7. Jang, H.; Jones, L.; Kang, J. Prioritisation of old apartment buildings for energy-efficient refurbishment based on the effects of building features on energy consumption in south korea. Energy Build. 2015, 96, 319–328. [Google Scholar] [CrossRef] [Green Version]
  8. Park, J.S.; Lee, S.J.; Kim, K.H.; Kwon, K.W.; Jeong, J.-W. Estimating thermal performance and energy saving potential of residential buildings using utility bills. Energy Build. 2016, 110, 23–30. [Google Scholar] [CrossRef]
  9. Sim, J.; Sim, J. The effect of new carbon emission reduction targets on an apartment building in south korea. Energy Build. 2016, 127, 637–647. [Google Scholar] [CrossRef]
  10. Laouadi, A. Development of a radiant heating and cooling model for building energy simulation software. Build. Environ. 2004, 39, 421–431. [Google Scholar] [CrossRef] [Green Version]
  11. Karakoyun, Y.; Acikgoz, O.; Yumurtacı, Z.; Dalkilic, A.S. An experimental investigation on heat transfer characteristics arising over an underfloor cooling system exposed to different radiant heating loads through walls. Appl. Therm. Eng. 2020, 164, 114517. [Google Scholar] [CrossRef]
  12. Lin, B.; Wang, Z.; Sun, H.; Zhu, Y.; Ouyang, Q. Evaluation and comparison of thermal comfort of convective and radiant heating terminals in office buildings. Build. Environ. 2016, 106, 91–102. [Google Scholar] [CrossRef]
  13. Sun, H.; Wu, Y.; Lin, B.; Duan, M.; Lin, Z.; Li, H. Experimental investigation on the thermal performance of a novel radiant heating and cooling terminal integrated with a flat heat pipe. Energy Build. 2020, 208, 109646. [Google Scholar] [CrossRef]
  14. Cho, J.; Park, B.; Lim, T. Experimental and numerical study on the application of low-temperature radiant floor heating system with capillary tube: Thermal performance analysis. Appl. Therm. Eng. 2019, 163, 114360. [Google Scholar] [CrossRef]
  15. Lodi, C.; Magli, S.; Contini, F.M.; Muscio, A.; Tartarini, P. Improvement of thermal comfort and energy efficiency in historical and monumental buildings by means of localized heating based on non-invasive electric radiant panels. Appl. Therm. Eng. 2017, 126, 276–289. [Google Scholar] [CrossRef]
  16. Shen, L.; Tu, Z.; Hu, Q.; Tao, C.; Chen, H. The optimization design and parametric study of thermoelectric radiant cooling and heating panel. Appl. Therm. Eng. 2017, 112, 688–697. [Google Scholar] [CrossRef]
  17. Fang, Y.; Ding, Y.; Tang, Y.; Liang, X.; Jin, C.; Wang, S.; Gao, X.; Zhang, Z. Thermal properties enhancement and application of a novel sodium acetate trihydrate-formamide/expanded graphite shape-stabilized composite phase change material for electric radiant floor heating. Appl. Therm. Eng. 2019, 150, 1177–1185. [Google Scholar] [CrossRef]
  18. Berger, J.; Gasparin, S.; Dutykh, D.; Mendes, N. Accurate numerical simulation of moisture front in porous material. Build. Environ. 2017, 118, 211–224. [Google Scholar] [CrossRef] [Green Version]
  19. Yeo, M.-S.; Yang, I.-H.; Kim, K.-W. Historical changes and recent energy saving potential of residential heating in korea. Energy Build. 2003, 35, 715–727. [Google Scholar] [CrossRef]
  20. Kim, D.-K. The natural environment control system of korean traditional architecture: Comparison with korean contemporary architecture. Build. Environ. 2006, 41, 1905–1912. [Google Scholar] [CrossRef]
  21. Lee, J.; McCuskey Shepley, M.; Choi, J. Exploring the localization process of low energy residential buildings: A case study of korean passive houses. J. Build. Eng. 2020, 30, 101290. [Google Scholar] [CrossRef]
  22. Song, G.-S. Buttock responses to contact with finishing materials over the ondol floor heating system in korea. Energy Build. 2005, 37, 65–75. [Google Scholar] [CrossRef]
  23. Chu, W.-S.; Kim, M.-S.; Lee, K.-T.; Bhandari, B.; Lee, G.-Y.; Yoon, H.-S.; Kim, H.-S.; Park, J.-I.; Bilegt, E.; Lee, J.-Y.; et al. Design and performance evaluation of korean traditional heating system—Ondol: Case study of nepal. Energy Build. 2017, 138, 406–414. [Google Scholar] [CrossRef]
  24. Chung, M.; Park, C.; Lee, S.; Park, H.-C.; Im, Y.-H.; Chang, Y. A decision support assessment of cogeneration plant for a community energy system in korea. Energy Policy 2012, 47, 365–383. [Google Scholar] [CrossRef]
  25. Bae, C.; Chun, C. Research on seasonal indoor thermal environment and residents’ control behavior of cooling and heating systems in korea. Build. Environ. 2009, 44, 2300–2307. [Google Scholar] [CrossRef]
  26. Lee, W.-h.; Kim, K.-w.; Lim, S.-h. Improvement of floor impact sound on modular housing for sustainable building. Renew. Sustain. Energy Rev. 2014, 29, 263–275. [Google Scholar] [CrossRef]
  27. Kim, Y.K.; Lee, T.W. A study on the heating characteristics of radiant floor panel using heat pipes with the double wick. Soc. Air-Cond. Refrig. Eng. Korea 2012, 24, 183–189. [Google Scholar]
  28. Yong-ho, J. The performance evaluation of electric ondol system with the ptc thermistor function. Korean Inst. Archit. Sustain. Environ. Build. Syst. 2011, 5, 153–160. [Google Scholar]
  29. Equest. Available online: http://www.Doe2.Com/equest/ (accessed on 15 August 2018).
  30. American Society of Heating, Refrigerating and Air Conditioning Engineers. Ashrae Guideline 14-2002, Measurement of Energy and Demand Savings—Measurement of Energy, Demand and Water Savings. American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.: Atlanta, CA, USA, 2002. [Google Scholar]
  31. National Radio Research Agency, South Korea. Available online: https://rra.Go.Kr/ko/index.Do (accessed on 1 November 2018).
  32. Radio Frequency Safety, Federal Communications Commission. Available online: https://www.Fcc.Gov/ (accessed on 1 November 2018).
Figure 1. Prefab electric Ondol panel.
Figure 1. Prefab electric Ondol panel.
Energies 13 05723 g001
Figure 2. Thermal measurement: (a) The locations of thermocouples, (b) monitoring electricity consumption.
Figure 2. Thermal measurement: (a) The locations of thermocouples, (b) monitoring electricity consumption.
Energies 13 05723 g002
Figure 3. Computational model of the apartment building.
Figure 3. Computational model of the apartment building.
Energies 13 05723 g003
Figure 4. Temperature distribution and the electricity consumption.
Figure 4. Temperature distribution and the electricity consumption.
Energies 13 05723 g004
Figure 5. Temperature distribution by the thermal imaging camera.
Figure 5. Temperature distribution by the thermal imaging camera.
Energies 13 05723 g005
Figure 6. The heating cost comparison between the conventional Ondol system and the prefab electric Ondol system.
Figure 6. The heating cost comparison between the conventional Ondol system and the prefab electric Ondol system.
Energies 13 05723 g006
Figure 7. The heating energy and cost comparison.
Figure 7. The heating energy and cost comparison.
Energies 13 05723 g007
Table 1. The specification of the envelope systems of the reference building.
Table 1. The specification of the envelope systems of the reference building.
U-value of walls0.62 W/m2K
U-value of ceiling 0.69 W/m2K
U-value of window systems2.8 W/m2K
Shading coefficient0.6
Air infiltration 2.1 cm2/m2
Internal heat gain3 occupants
Lighting: 5.4 W/m2
Equipment: 7.0 W/m2
Design temperature26 °C for cooling and 20 °C for heating
Table 2. Specifications of the equipment.
Table 2. Specifications of the equipment.
Power meter
(3166 Clamp on Power HiTESTER, US)
-
Voltage: 150 V to 600 V
-
Frequency range: 45 Hz to 66 Hz
-
Accuracy: AC Voltage: ±0.2% reading. ±0.1% full scale
AC Current: ±0.2% reading. ±0.1% full scale
Datalogger
(1250 series Remote Squirrel meter/logger, UK)
-
Operation range: Temperature −40 °C to +85 °C
-
Accuracy: Temperature: ±0.3 °C
-
Response time: <0.7 s (start-up 3 s)
Thermal imaging camera
(testo 865, Germany)
-
IR resolution of 160 x 120 pixels
-
Measuring range: −20 °C to 280 °C
-
Accuracy of ±2 °C
-
Emissivity: 0.01 to 1
Table 3. The monthly energy consumption comparison.
Table 3. The monthly energy consumption comparison.
MonthEnergy Consumption (kWh)CV(RMSE) (%)
The Selected Unit of the Apartment BuildingEnergy SimulationDifference
January769.3860.0−90.74.00
February664.5779.0−114.55.04
March640.2745.0−104.84.62
April576.0580.0−4.00.18
May589.2512.077.23.40
June607.7648.0−40.31.78
July748.4799.0−50.62.23
August792.5823.0−30.51.34
September612.2786.0−173.87.66
October564.4644.0−79.63.51
November578.5680.0−101.54.47
December719.3755.0−35.71.57
Table 4. The conventional Ondol system.
Table 4. The conventional Ondol system.
MonthJanFebMarAprMayJunJulyAugSepOctNovDecTotal
Heating energy consumption (kWh)624.7488374.4175.866.30000119348.6559.42756
Heating costDemand charge
($US dollar)
1.131.131.131.131.1300001.131.131.13-
Energy charge
($US dollar)
3225188.63.200005.81728.6-
Monthly total heating cost
($US dollar)
3319.419.49.74.400006.91829.7$140.5/year
Table 5. The prefab electric Ondol panel system.
Table 5. The prefab electric Ondol panel system.
MonthJanFebMarAprMayJunJulyAugSepOctNovDecTotal
Heating energy consumption (kWh)5714463421616100001093195112520
Heating costDemand charge
($US dollar)
8.24.52.40.60.0300000.62.48.2-
Energy charge
($US dollar)
9550.33092.700005.12668.4-
Monthly total heating cost
($, US dollar)
10355329.52.700005.628.477$313.2/year
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Lee, W.; Lim, T.; Kim, D.D. Thermal and Energy Performance Assessment of the Prefab Electric Ondol System for Floor Heating in a Residential Building. Energies 2020, 13, 5723. https://doi.org/10.3390/en13215723

AMA Style

Lee W, Lim T, Kim DD. Thermal and Energy Performance Assessment of the Prefab Electric Ondol System for Floor Heating in a Residential Building. Energies. 2020; 13(21):5723. https://doi.org/10.3390/en13215723

Chicago/Turabian Style

Lee, Wongeun, Taesub Lim, and Daeung Danny Kim. 2020. "Thermal and Energy Performance Assessment of the Prefab Electric Ondol System for Floor Heating in a Residential Building" Energies 13, no. 21: 5723. https://doi.org/10.3390/en13215723

APA Style

Lee, W., Lim, T., & Kim, D. D. (2020). Thermal and Energy Performance Assessment of the Prefab Electric Ondol System for Floor Heating in a Residential Building. Energies, 13(21), 5723. https://doi.org/10.3390/en13215723

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop