1. Introduction
Harmonic distortion of voltages and currents in power systems is an inevitable phenomenon, due to the nonlinear nature of loads and elements constantly present across different voltage levels. In particular, this applies to industrial networks that have witnessed a large increase in the number of connected power converters, supplying various loads [
1]. Excessive levels of harmonic distortion may be detrimental to the network and connected devices, as it can disrupt their operation and, in extreme cases, even cause their failure. In order to limit these negative effects, recommended guidelines determine the levels of permitted harmonic distortion in the supply voltage [
2].
Under normal operating conditions, harmonic distortion does not generally exceed limits set by the standards [
3]. However, with harmonic resonance conditions present in the network, voltages and/or currents can get amplified significantly. Resonance has been reported as one of the main harmonic-related causes for problems with electrical equipment [
4]. To prevent equipment failure, appropriate methods for harmonic resonance identification and mitigation are essential. Having said that, these methods need to be used in both existing networks when topology is changing or new equipment is being connected to the system, as well as in the network planning procedure.
The most frequently used harmonic resonance analysis method is an impedance frequency scan [
5,
6]. It is a relatively straightforward analysis technique, where the impedance seen from a certain bus is calculated as a function of frequency. This technique shows if parallel and/or series resonance exist in a system. However, it does not give any answers as to which network components are involved in the resonance, which network nodes are most affected, where is the best location, and what is the best approach to mitigate the problem [
7].
These questions have been addressed partially in the literature by several authors. The idea of the harmonic resonance mode analysis (HRMA) has been introduced by Xu et al. [
7] as a tool for parallel harmonic resonance analysis. Compared to the conventional impedance frequency scan analysis method, the harmonic resonance mode analysis enables individual analysis of resonance phenomena. The method is based on admittance matrix eigen-decomposition, which yields eigenvalues and eigenvectors used to determine bus participation in a particular resonance phenomenon. Obtained results can be further used to determine the modal sensitivity. The concept of the modal impedance magnitude sensitivity was presented by Huang et al. [
8]. Furthermore, modal impedance resonance frequency can also be calculated using the method presented by Cui and Wang [
9] and altered for use with the complex admittance matrix by Hu et al. [
10]. All of the aforementioned calculations can be performed for series harmonic resonance analysis with modifications presented by Zhou et al. [
11]. With all mentioned calculations, parameters of the specific network elements with the highest influence on the resonance frequencies can be selected. Using the Newton–Rhapson method presented by Hu et al. for use with the HRMA method in [
10], the values of parameters can be altered in such a way that resonance frequencies are shifted to the values, at which the harmonic voltage amplification is minimized.
While the principles of the harmonic resonance mode analysis were thoroughly described in the aforementioned literature, it was noted that there is a lack of systematic approach to performing the analysis comprehensively. Additionally, two more issues, that were not addressed in the literature, were encountered during the implementation of the method. The first issue was the dependence of the modal sensitivity on the selected frequency calculation step. Specifically, by decreasing the calculation step the sensitivity indices converge to the actual values. The second issue was noticed during the modal resonance frequency shift. It was observed, that the numbering of the modal impedances may change after the new value of the adjusted parameter is calculated during a Newton–Rhapson method iteration. This makes it difficult to keep track of the adjusted modal impedance resonance frequency properly without any further measures.
The main objective of this paper is therefore to propose a systematic approach to harmonic resonance (parallel and series) analysis and mitigation utilizing the HRMA method. Additionally, the algorithm for calculation of more accurate resonance frequency values of the resonance modes is presented to address the issues with calculation step dependence of modal sensitivity indices. The final proposed improvement is the algorithm for tracking the adjusted modal impedance resonance frequency. In described approach, the harmonic resonance mode analysis through admittance matrix eigen-decomposition is first presented. Modal sensitivity analyses of impedance magnitude and resonance frequency are performed next to determine the influence of network parameters on both quantities. To improve the accuracy of the modal resonance frequencies calculation, an accurate resonance frequency calculation procedure is proposed. Based on the results of all the previous calculations, the harmonic resonance mitigation method is presented next, to adjust the resonance frequencies of the modal impedances. Parameters with the highest influence on resonance frequencies were selected and, using the Newton method, the values of selected parameters at which resonance frequencies reach the desired values were determined.
In the last part of the paper, the proposed approach to harmonic resonance analysis is tested by means of simulations on an actual industrial network model.
2. Harmonic Resonance Identification
The presented resonance mode analysis method consists of several steps summarized in
Figure 1. The most important are network admittance matrix calculation, admittance matrix eigen-decomposition, modal sensitivity indices calculation and modal resonance frequency shift. In order to perform the series resonance analysis, the admittance matrix needs to be modified as it is presented in
Figure 1. The modification is comprised of identification of the network bus, for which the series resonance analysis is performed, and elimination of the row and the column related to the analyzed network bus. The steps presented in
Figure 1 are explained in the next subsections as follows. The basic theory of modal analysis and the meaning of transformation of the network is explained in
Section 2.1. Next, the modal and the resonance frequency indices are presented in
Section 2.2. Together with the sensitivity indices, the algorithm for calculation of the accurate value of the resonance frequency is presented in the subsection. Finally, modifications needed for series resonance analysis are presented in
Section 2.3. The resonance frequency shift is addressed later, in
Section 3.
2.1. Resonance Mode Analysis
The power network can be represented using the admittance matrix
. In this case, the nodal voltage vector
is equal to
where
denotes the nodal current injections vector. The admittance matrix representation of the network is chosen because of the simplicity of its construction. Moreover, the parallel resonance’s relation with admittance matrix
being close to singularity has been discovered by Xu et al. [
7]. It has also been noted by the authors that one of the eigenvalues of the singular matrix is equal to zero. That is why the admittance matrix eigen-decomposition needs to be performed in order to do a more detailed study of the resonances.
Admittance Matrix Eigen-Decomposition
The harmonic resonance mode analysis is based on presentation of electrical network with the admittance matrix
, which can be decomposed into [
7]:
where
and
are the left and the right eigenvectors matrix, respectively, and
is the eigenvalues matrix, which is diagonal. The elements of the eigenvalue matrix are eigenvalues
, also named modes, where subscript
denotes mode number, and its dimension is equal to the dimension of the admittance matrix.
Calculation of the inverse value of the eigenvalue matrix yields the modal impedances matrix
. Since the eigenvalue matrix is diagonal, the elements of the
matrix are equal to
. They are named modal impedances. Each modal impedance resonance determines one nodal impedance parallel frequency. The voltage equation of the network presented in the modal domain can be written as
where
and
are modal voltages vector and modal current injections vector, respectively.
The corresponding eigenvectors matrices determine the parallel resonance effect on the network nodes. The
matrix can be used to determine modal current injection vector
as
where
denotes the nodal current injections vector. The influence of the right eigenvector matrix on the degree of effect of a current injection into a certain network bus to the particular modal current can be seen from Equation (4). The right eigenvectors are the rows of the right eigenvector matrix. That is why the right eigenvectors give information on modal excitability [
7]. The
matrix determines the modal voltage effect on the nodal voltages
as
Equation (5) describes the influence of the left eigenvector matrix to the degree of effect of a certain modal voltage expressed in the bus voltages. Namely, it gives information on modal observability [
7]. The left eigenvectors are the columns of the left eigenvector matrix.
As the admittance matrix
is symmetrical, the relationship between the right and left eigenvalue matrix is
and
, where the operator
T indicates matrix transposition. This means that the bus with the highest observability level also has the highest excitability level. Thus only one of the two eigenvectors gives enough information for the harmonic resonance analysis [
7].
Since the right and left eigenvectors essentially give the same information, they can be combined into the participation factors [
7]. They are calculated using the equation
where the subscripts
and
denote mode number and bus number, respectively.
2.2. Modal Sensitivity Analysis
To shift the modal resonance frequency as effectively as possible, the effect of each network parameter on the modal impedance needs to be evaluated. The general parameter is marked with the letter
and represents either the inductance, capacitance or resistance of a network element.
Figure 2 presents the effect of changing the parameter
on the modal impedance characteristic. The full red line represents a modal impedance characteristic before the parameter change and the dotted red line represents a modal impedance characteristic after the change. It can be observed that the modal impedance magnitude and the modal resonance frequency may change.
To fully understand the particular parameter effect, both, the modal impedance magnitude and the resonance frequency sensitivity need to be calculated.
2.2.1. Modal Impedance Magnitude Sensitivity
The modal impedance magnitude together with the participation factor determines the effect of a nodal harmonic current injection on the network nodal voltages magnitude. That means, in order to mitigate a harmonic voltage magnitude, the modal impedance magnitude needs to be minimized. The modal impedance magnitude sensitivity is calculated through the eigenvalue magnitude sensitivity using the process thoroughly described in [
8].
In summary, the eigenvalue sensitivity is calculated using the equation
where
and
represent the real and imaginary parts of the network branch admittance, respectively. In Equation (7),
and
are derivatives of the series RLC branch admittance with respect to one of the parameters
(
,
or
). The derivatives
and
are equal to
And
where
denotes sensitivity coefficient for analyzed element. The sensitivity coefficients for the
-th mode are calculated from entries of the sensitivity matrix,
where the operator
and
are left and right eigenvector of
-th mode, respectively. The calculation of
for the element to which the analyzed parameter relates is performed depending on how the element is connected. In case it is connected as a shunt element,
is equal to
, where
is the node that the element is connected to. If the element is connected in series between nodes
and
, then the sensitivity coefficient is equal to
.
The modal impedance magnitude sensitivity is equal to
In order to achieve the comparability between parameter changes done with different kinds of elements, the result from Equation (11) is normalized using equation
During the calculation process, it was observed that the value of the modal impedance magnitude sensitivity depends on the calculation step . The smaller the calculation step, the better the sensitivity coefficient approximation is. This is because the density of the calculation points on the observed frequency interval increases, and the identified resonance frequency converges to the real resonance frequency. To avoid the dependence on the calculation step size, an accurate resonance frequency calculation procedure is proposed. The calculation is performed using the modified idea of bisection, which is an iterative numerical method for calculation of zeros of a function. The algorithm is based on the assumption that the modal impedance function is continuous and concave in the surroundings of the resonance frequency. The difference between the bisection and the proposed method is the latter being used to determine the frequency at which the maximum of the modal impedance characteristic is located.
The calculation can be summarized in the following steps.
Import -th mode data, identify the resonance frequency , and set the counter to .
Set , and , then calculate , , and modal impedance amplitudes and .
Find at which frequency the modal impedance magnitude is higher (point or point ) and set it as . If , set and , else and .
Set the new resonance frequency approximation for -th iteration .
If , where is the stopping criterion, continue to step 2, else construct an array with elements , where is the diminished calculation interval, and finish the calculation.
2.2.2. Resonance Frequency Sensitivity
To obtain full information on the system parameter effect on modal impedance, the modal resonance frequency sensitivity also needs to be calculated. Namely, the example with a parallel RLC circuit has shown, that the inductor and the capacitor do not have any effect on the modal impedance magnitude. However, they have an effect on its resonance frequency [
9].
The resonance frequency sensitivity has been calculated using the method described in [
9,
10]. It is calculated using the equation
The first part of the Equation (13),
, is equal to
where
is evaluated in Equation (8) and
in Equation (9). The derivatives of
and
are
and
The expressions , , and from the Equation (14) are derivatives of the series RLC branch impedance with respect to parameter and to frequency .
The second part of the Equation (13),
, is equal to
The resonance frequency sensitivity, evaluated with the Equation (13) is further normalized [
9,
10] using the equation
2.3. Series Resonance Modal Analysis
It has been shown that applying the resonance mode analysis method to the inverse nodal admittance matrix
is not appropriate for the series resonance analysis [
7,
11]. Since series resonance relates to high loop current values, a loop impedance matrix
should be constructed and analyzed. As harmonic voltage is applied between a network node and the reference node to excite a harmonic current, the observed node should be connected to the reference node through the dummy branch (a short circuit connection) [
11]. Such connection is necessary because the impedance of an ideal voltage source is equal to zero.
The main drawback of the loop impedance matrix is the complexity of its construction, which is more complex in comparison with the construction of the nodal admittance matrix. Because of that, Neufeld et al. [
12] proposed the representation of the network, whose topology is changed with the dummy branch method, using the nodal admittance matrix.
The implemented network nodal admittance matrix modification for series resonance modal analysis was performed by deleting the row and the column referring to the analyzed node. Because of that, the original node numbers were saved for the later analysis of the results. The network modification algorithm is summarized in
Figure 3.
5. Conclusions
The main objective of this paper is to propose a systematic approach to harmonic resonance identification and mitigation in power system using modal analysis. The main steps in the proposed calculation procedure are as follows. First, the network is transformed into the modal domain. In this way, individual resonance phenomena are separated and represented with modal impedances, enabling their individual analysis. The influence of elements and their parameters at the nominal frequency was included in the analysis. This was achieved by calculating the sensitivity of the amplitude of modal impedances and resonant frequencies of modal impedances to changes in parameters. The analysis of series resonances was included in the analysis with appropriate adjustments of the admittance matrix, thus enabling the use of the same computational procedures as for parallel resonances. Finally, with the help of sensitivity coefficients, the parameter values of network elements at which the adjusted resonance frequency of the modal impedance reaches the desired value were determined using the Newton method. The effectiveness of the proposed method was evaluated on a real industrial network model.
As highlighted in the paper, the following solutions are presented.
When calculating the sensitivity coefficients, it was observed that sensitivity coefficients of modal impedances are dependent on the size of a calculation step Δf. The problem was solved by proposing an additional calculation of a more accurate value of the resonance frequency.
Another problem, that was encountered, was the question of how to follow the shifted mode when changing the resonance frequency. Namely, it was observed that the frequency characteristic of one modal impedance can have several resonant frequencies, and the fact that the labels of some resonant modes changed in a way that was not exactly consistent when the parameters were changed made it even more difficult. This obstacle was solved by estimation of expected resonance frequency and modal impedance magnitude in every iteration of the resonance frequency shift calculation, so that after changing the parameters in the new iteration of the calculation, we chose the resonance mode that was closest to the estimated value.
Overall, the results show that the transformation of a network, presented with the admittance matrix, into modal domain is a useful tool for individual analysis of each individual resonance phenomenon. In relation to the modal sensitivity indices, it has been noted that together with the enhanced resonance frequency calculation, the proposed approach reliably determines the degree of effect that every individual parameter has on modal impedance characteristics. Finally, it can be seen from the results, that using the proposed resonance frequency shift method, the bus impedances were successfully lowered at the frequency in question (the 7th harmonic). Consequently, the degree of bus voltage harmonic distortion, caused by nodal harmonic current injections, is successfully mitigated.