1. Introduction
Research on modern technologies that focus on lowering the emission of harmful substances from solid fuel heating boilers is still a widely discussed scientific topic [
1]. The great number of papers implements a very similar scientific approach of examining the solid fuel heating boiler system as a technical object affecting human beings and the environment [
2]. Scientific publications [
3,
4,
5] propose that, in terms of thermodynamics, a solid fuel heating boiler is considered a closed heterogeneous system with a strong impact on the external environment, depending on the physical and chemical properties of the fuel used. Moreover, those parameters have a significant impact on the change in emission parameters of the boiler.
The approach adopted by the researchers examines the problem solely with regard to the emission of harmful substances, and not in terms of chemical parameters of the combustion process. While analyzing the most renowned publications on the emission of harmful substances from heating boilers, it’s possible to ascertain that the research problem related to the analysis of the chemism of the solid fuel combustion process is not a frequently taken up topic [
6,
7]. The previously published publications [
8,
9] have discussed the impact of the chemical composition of the burnt fuels on the emission of harmful substances from boilers. In addition to that, the earlier research used to focus on the effect of heating devices’ construction methods on the emission of harmful substances and the combustion process occurring inside them [
10]. The publications [
11,
12] conclude that the emission level of harmful substances is directly connected with the technical parameters of the devices as well as the technical parameters of the burnt fuel.
The publication [
13] revolves around harmful substances emitted from heating devices that are not subject to the environmental register. It concludes that the location of heat distribution buildings has a significant impact on the amount of harmful substances emitted in that area.
The researchers calculated that the dust concentration in exhaust gases emitted from boilers greatly exceeds values indicated in standards and directives. It is worth pointing out the scale of the problem in terms of air quality in Poland; that is, dust particles, in particular solid particles characterized mostly as PM 2.5 and PM 10, are very harmful to humans because they demonstrate strong cancerogenic properties. What’s more, the statistical data [
14] indicates that 84% of the total particle emission of PM 2.5 originates from fuel combustion, whereas as much as 49% can be attributed to the combustion of solid fuels in households. The total amount was assessed to be at the level of 59,850 tons in 2019 for PM 2.5 and 89,620 tons in 2019 for PM 10.
The obtained results motivate scientists to deepen their research on the reduction of dust and black carbon emissions from household heating sources. The scale of the problem related to the emission of harmful substances in Poland, resulting from the use of solid fuel heating boilers, shows the dire need of implementing modern technologies which will significantly reduce the amount of dust emitted to the environment. Currently, research is also being conducted on the factual operation of heating boilers, with special attention paid to the problem of lowering the amount of the emitted harmful substances. The implementation of the suggested solutions may contribute to reduced emissions [
15].
The previously conducted research proves that the technical parameters of fuel bear a strong effect on the variability of mass concentration of PM, CM and NOx in exhaust gases. Moreover, research on co-combustion of coal-derived fuels with the use of woody and non-woody biomass shows convergent processes regarding the emitted harmful substances. It allows for analogous research methods to be implemented in order to examine heating devices that use such fuels [
16].
Further research on changes in the quality of the combustion process of low-power heating boilers after the introduction of water steam is the continuation of the previous research [
17]. So far, there have been satisfactory grounds that prove the reduced emission of harmful substances generated by solid fuel heating boilers fueled with hard coal. On the grounds of the previous research [
18], it was concluded that such parameters have the greatest effect on physical and chemical aspects of combustion. Heat and emission of the boiler were analyzed during its operation at nominal power without water steam and with water steam in the amount of 0.71 kg/h, with 3.60 kg/h being introduced to the combustion and afterburning chamber of two different boilers.
The obtained results were presented in collective tables and in drawings, which demonstrate the course of emission in time and mass distribution with reference to the oxygen concentration in exhaust gases.
On the basis of the previously conducted research, a significant reduction in PM emission and a slight reduction in NOx were observed, with simultaneous and rapid increase in the mass concentration of the emitted CO. The high level of the CO emission and detection of hydrogen (H
2) in exhaust gases may be evidence of coal gasification after the introduction of water steam. Carbon monoxide is formed in the first stage of the Bosch reaction, i.e., the reaction of elemental carbon (e.g., incandescent coke) with water steam (hydrogen is also formed in the above reaction). The following chemical reaction reflects this mechanism:
On its basis, it is possible to conclude that, following the introduction of water steam to the combustion chamber, CO is created from carbon (e.g., originating from soot) affected by steam water, and that this results in the reduction in the emitted PM with a simultaneous increase in the emission of CO. It means that the introduction of an additional thermodynamic factor to the combustion chamber causes the reorganization of the combustion process. A visible reduction in the oxygen content in exhaust gases would then be one of the effects of a worse quality of the combustion process, however, in the case of the research conducted, changes in the amount of oxygen created from the combustion process were not observed. It may prove that water steam introduced to the combustion chamber did not replace oxygen, but it only became an additional reactive factor in the combustion process. Other possible chemical reactions, which may occur during the introduction of water steam to the combustion chamber, are as follows:
It may prove a significant increase in the amount of the emitted carbon dioxide (CO
2) and CO, which emission, when compared to the normal operation of the boiler, increases by as much as 200% in comparison to the standard operation of the burner, and the detection of a significantly higher content of hydrogen in exhaust gases in comparison to the standard operation of the boiler. On the basis of the obtained results, it was concluded that many chemical reactions occur during the coal combustion process in heating boilers while feeding water steam to the combustion chamber, and their joint effect is an obvious reduction in the amount of the emitted PM and the simultaneous increase in the CO emission [
19].
It should be mentioned that in the energetics aspect, adding water steam to the combustion process may contribute to efficiency reduction, because it makes a ballast and consumes energy from the combustion process. Although the tests were carried out for a system without heating recovery, the main type of heating boiler on the market is condensing boilers, which recover a significant amount of thermal energy from the water steam contained in exhaust gases, and the efficiency impact is negligibly small.
An alternative to the research conducted can be the carbon oxide conversion process, during which its emission significantly decreases due to the oxidation of CO to CO
2. It is possible to obtain better parameters of heat exchange between exhaust gases and the work factor because of the reduction in the CO level, and that can bear a positive effect on the efficiency of a given heating device. It was also observed that the introduction of additional chemical substances to the flame area resulted in the nullification of part of its energy, as well as the reduction (by as much as approximately 250 °C) of the temperature inside the combustion chamber [
20]. A lower flame temperature causes changes in emission parameters and it results in, for instance, a lower amount of the emitted PM and a slight reduction in the emitted NOx. Moreover, a significant increase in the H
2 emission is detected during the combustion process in comparison to the combustion process without the introduction of water steam. The transmission of heat, created during the combustion process, from the flame to the water steam introduced to the combustion chamber limits the participation of the thermal mechanism of nitric oxide creation, thus causing slight decrease in the NOx emission. Such a mechanism, in terms of low-temperature solid fuel boilers, has an insignificant effect on the amount of nitric oxides created during the combustion process because it is the fuel mechanism that has the greatest percentage of participation [
21,
22,
23].
The latest research works related to the reduction of harmful substance emissions from the combustion processes tend to focus on the modification of combustion processes in terms of their reorganization and secondary air supply, as well as the insertion of additives that may generate chemical reactions in the area of high temperatures, resulting in the reduction of exhaust gas compounds [
24,
25,
26]. Research associated with the techniques of harmful substance reduction from the combustion processes carried out in real time gives genuine evidence of assumption correctness [
27], however, the modern development of numerical technology provides possibilities for highly precise simulation, taking into account many input data and factors for the purpose of estimating emissions from fuel combustion processes in many heating boiler types [
28,
29,
30].
The research primarily aimed to analyze the thermodynamic parameters in the case of boilers operating without water steam, and with water steam added to the combustion and afterburning chamber. The use of water steam in the energy industry has recently taken on a unique importance. Thanks to the ease of obtaining H
2O
(g), water steam can be used in energy processes in an optimal and economic way as a widely available waste agent (low-energy, low temperature and pressure), and not only in combustion [
31], but also torrefaction, for which the end product is biochar. In turn, it can be used further, for instance, as a substitute for fossil fuels [
32].
3. Results and Discussion
The first and second cycle of tests showed that the CO emission didn’t exceed the average range from 100 mg/m
3 to 946 mg/m
3, the average range of NOx emission was from 295 mg/m
3 to 443 mg/m
3 and the average PM emission was from 90 mg/m
3 to 103 mg/m
3. There were traces of the H
2 emission (from 0.68 mg/m
3 to approximately 1.12 mg/m
3 on average), which could result from the content of the substance in the fuel. The average exhaust gas temperature was from approximately 153 °C to approximately 230 °C. The average temperature inside the combustion chamber for the minimal power was 730 °C, while for the boiler operating at nominal power the average temperature was 880 °C. The average efficiency range of the combustion process was from approximately 87% to approximately 91%. The results obtained clearly show that the boiler meets the class 3 requirements of the standard, which defines the border values for the CO and PM emissions from burning fossil fuels related to boilers operating at nominal power of ≤50 kW with automatic fuel supply, which comes to 3000 mg/m
3 for CO and 150 mg/m
3 for PM, respectively [
33].
Figure 5 shows mass distribution of basic harmful substances emitted during the Q EKO 15 boiler operation at minimum and nominal power. The following charts show estimated equations for trend lines depicting the approximate emission distribution of harmful substances with reference to the oxygen content in exhaust gases.
In the case of the third and fourth cycle of tests, it was observed that the introduction of water steam to the combustion chamber at the flow rate of 0.71 mg/m
3 resulted in the CO emission lowering by approximately 17% for the boiler operating at minimum power, but for the boiler operating at nominal power it resulted in an increase in the amount of the emitted CO by approximately 156%. Dust emission was lower in relation to the normal boiler operation by approximately 13% to 19%, regardless of the boiler power. The NO
x emission decreased by approximately 4% to 27% regardless of the boiler power. Hydrogen was detected in exhaust gases in the average amount of approximately 5.62 mg/m
3 to 8.87 mg/m
3. The efficiency of the combustion process decreased by the maximum amount of approximately 4%. The average exhaust gas temperature was from the approximately 149 °C to approximately 215 °C. While feeding the water steam to the combustion chamber, the temperature inside the combustion chamber dropped by approximately 14 °C (the temperature was approximately 716 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the combustion chamber dropped by approximately 46 °C (the temperature was approximately 834 °C). Decreased temperature inside the combustion chamber had a positive effect on the lowering of the NOx content created during thermal processes.
Figure 6 shows the mass distribution of basic harmful substances emitted during boiler operation at minimum and nominal power. The following charts show estimated equations for trend lines depicting the approximate emission distribution of harmful substances with reference to the oxygen content in exhaust gases.
In the case of the fifth and sixth cycle of tests, it was observed that the amount of the emitted CO, in comparison to the standard combustion process, increased by approximately 80% to 268%, on average. The introduction of water steam to the combustion process resulted in a lower PM emission by approximately 20% to 25%, on average. The NOx emission, in comparison to emission from the unmodified combustion process, increased to a maximum amount of approximately 5%. The increase in the emitted nitric oxides could be the result of an additional amount of energy introduced along with the maximum amount of water steam fed to the combustion chamber. The efficiency of the combustion process decreased by an average amount of approximately 3%. H
2 was detected in exhaust gases in amounts from 5.25 mg/m
3 to approximately 18.38 mg/m
3. The average exhaust gas temperature was from approximately 145 °C to approximately 194 °C. The temperature inside the combustion chamber decreased by approximately 26 °C (the temperature was approximately 704 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the combustion chamber dropped by approximately 86 °C (the temperature was approximately 794 °C).
Figure 7 shows the mass distribution of basic harmful substances emitted during boiler operation at minimum and nominal power. The following charts show estimated equations for trend lines depicting the approximate emission distribution of harmful substances with reference to the oxygen content in exhaust gases.
The following
Table 4 shows the results of individual test cycles for the first stage of research.
Figure 8 shows graphical changes in the emission of harmful substances as well as the efficiency of the combustion process after supplying water steam to the combustion chamber at different flow rates. The values were obtained on the basis of a comparison of the average emission parameters of individual harmful exhaust gas components with the values obtained for the standard boiler operation at minimal and nominal power (cycle 1 and 2).
In the case of the seventh and eighth cycle of tests, it was observed that the CO emission was within the average range of 58 mg/m
3 to 516 mg/m
3, however, the NO
x emission was within the average range of 285 mg/m
3 to 479 mg/m
3. The PM emission was within the average range of 93 mg/m
3 to 112 mg/m
3. The H
2 emission was within the average range of up to 8 mg/m
3. The average exhaust gas temperature was from approximately 114 °C to approximately 130 °C. The average temperature inside the combustion chamber for the minimal power was 820 °C, while for the boiler operating at nominal power the average temperature was 910 °C. The average temperature inside the afterburning chamber was 690 °C at minimal and 757 °C at nominal power conditions. The efficiency of the combustion process was within the average range, from 90% to 95%.
Figure 9 shows the mass distribution of basic harmful substances emitted during the KN-20 boiler operation at minimum and nominal power. The following charts show estimated equations for trend lines depicting the approximate emission distribution of harmful substances with reference to the oxygen content in exhaust gases.
In the case of the ninth and tenth cycle of tests, it was observed that the introduction of water steam to the combustion chamber at the flow rate of 0.71 kg/h resulted in the increase in the emitted CO by approximately 58% for the boiler operating at nominal power, however, only a slight increase was observed in the case of the boiler operating at minimum power. Dust emission was lower in comparison to the nominal power of the boiler by approximately 17% for operation at minimum power, and by approximately 19% for operation at nominal power. Hydrogen was detected in exhaust gases in the average amount of approximately 3.46 mg/m
3. The efficiency of the combustion process increased by the maximum amount of approximately 2%. The average exhaust gas temperature was from approximately 120 °C to approximately 138 °C. The temperature inside the combustion chamber increased by approximately 8 °C (the temperature was approximately 828 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the combustion chamber dropped by approximately 26 °C (the temperature was approximately 936 °C). The temperature in the afterburning chamber increased by approximately 2 °C (the temperature was approximately 692 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the afterburning chamber dropped by approximately 5 °C (the temperature was approximately 762 °C).
Figure 10 shows the mass distribution obtained for the emission of harmful substances with reference to the oxygen content in the exhaust gases and the approximate equations for trend lines.
In the case of the eleventh and twelfth cycle of tests, it was observed that the introduction of water steam to the combustion chamber at the flow rate of 3.60 kg/h resulted in an increase in the emitted CO, from approximately 61% to approximately 243%. Dust emission was lower in comparison to the normal operation of the boiler by approximately 18%, regardless of the boiler power. The NO
x emission decreased by approximately 4% to 16%. There was hydrogen detected in exhaust gases in the average amount of approximately 8.02 mg/m
3 to 9.17 mg/m
3. The efficiency of the combustion process in the case of the boiler operating at nominal power decreased by approximately 3%, and it didn’t change for the boiler operating at minimum power. The average exhaust gas temperature was from approximately 124 °C to approximately 160 °C. The temperature inside the combustion chamber increased by approximately 14 °C (the temperature was approximately 834 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the combustion chamber dropped by approximately 48 °C (the temperature was approximately 958 °C). The temperature in the afterburning chamber increased by approximately 10 °C (the temperature was approximately 700 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the afterburning chamber dropped by approximately 32 °C (the temperature was approximately 789 °C).
Figure 11 shows the mass distribution obtained for the emission of harmful substances with reference to the oxygen content in the exhaust gases and the estimated equations for trend lines.
The thirteenth and fourteenth cycle of tests showed that the supply of water steam to the afterburning chamber at the flow rate of 0.71 kg/h resulted in a decrease in the emitted CO by approximately 6%, and for the boiler operating at nominal power, the CO emission increased by approximately 142%. Dust emission was lower by approximately 26%, in comparison to the normal operation of the boiler, for the boiler operating at minimum power, and by approximately 10% for the boiler operating at nominal power. The NO
x emission decreased by approximately 16%. Hydrogen was detected in exhaust gases in the average amount of approximately 5.34 mg/m
3 to 8.02 mg/m
3. The efficiency of the combustion process in the case of the boiler operating at nominal power increased by approximately 2%, and it decreased for the boiler operating at minimum power by approximately 3%. The average exhaust gas temperature was from approximately 128 °C to approximately 155 °C. The temperature inside the combustion chamber increased by approximately 6 °C (the temperature was approximately 826 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the combustion chamber dropped by approximately 20 °C (the temperature was approximately 930 °C). The temperature in the afterburning chamber increased by approximately 8 °C (the temperature was approximately 698 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the afterburning chamber dropped by approximately 28 °C (the temperature was approximately 785 °C).
Figure 12 shows the mass distribution obtained for the emission of harmful substances with reference to the oxygen content in the exhaust gases and the approximate equations for trend lines.
In the case of the fifteenth and sixteenth cycle of tests, it was observed that the introduction of water steam to the afterburning chamber at the flow rate of 3.60 kg/h resulted in an increase in the emitted CO by approximately 119% for the boiler operating at nominal power, however, for the boiler operating at minimum power, the CO emission decreased by approximately 6%. Dust emission was lower in comparison to the normal operation of the boiler by approximately 18%, regardless of the boiler power. The NO
x emission decreased by approximately 17%. Hydrogen was detected in exhaust gases in the average amount of approximately 7.06 mg/m
3 to 9.75 mg/m
3. The efficiency of the combustion process in the case of the boiler operating at nominal power decreased by approximately 3%, and in the case of the boiler operating at minimum power it increased by approximately 2%. The average exhaust gas temperature was from approximately 139 °C to approximately 175 °C. The temperature inside the combustion chamber increased by approximately 16 °C (the temperature was approximately 836 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the combustion chamber dropped by approximately 52 °C (the temperature was approximately 962 °C). The temperature in the afterburning chamber increased by approximately 8 °C (the temperature was approximately 705 °C) for the minimal power, while for the boiler operating at nominal power the temperature inside the afterburning chamber dropped by approximately 50 °C (the temperature was approximately 807 °C).
Figure 13 shows the mass distribution obtained for the emission of harmful substances with reference to the oxygen content in the exhaust gases and the approximate equations for trend lines.
The following
Table 5 shows the results obtained for individual test cycles for the second stage of research.
Figure 14 shows graphical changes in the emission of harmful substances as well as the efficiency of the combustion process after supplying water steam to the combustion and afterburning chambers at different flow rates. The values were obtained on the basis of a comparison of the average emission parameters of individual harmful exhaust gas components with the values obtained for the standard boiler operation at minimal and nominal power (cycles seven and eight).
By analyzing the results obtained for all test cycles (in relation to the tests without water steam supplied to the boiler), it can be observed that in the case of a boiler without an afterburning chamber (Q EKO 15), the exhaust gas temperature and the combustion chamber temperature with the water steam addition (regardless of steam water stream) decreases. At the same time, it can be seen that the higher the temperature drop in the combustion chamber, the higher the emissions of CO: for a 46 °C reduction in temperature in the combustion chamber, CO increased by 155%, and for a 86 °C reduction in temperature in the combustion chamber, CO increased by 267%, compared to standard work.
It should be emphasized that the feed of steam, in terms of energy, is ballast (heat absorption), which may transform into an efficiency reduction in the system. Nevertheless, the tested solution can ultimately be used in condensing boilers, which will make the energy contained in the water steam in the exhaust gas recoverable, and this will make the change in the energy system’s efficiency unnoticeable.
Lowering the temperature (as mentioned above) consequently makes the process of oxidation of the carbon element to carbon dioxide impossible to complete; the process is interrupted, which contributes to the increase in CO emissions. This issue was not analyzed in detail, due to the fact that the main issue was the reduction of PM emissions, while the reduction of carbon monoxide emissions will be possible with the use of afterburning chambers or systems.
At the same time, constant parameters in relation to NOx emission can be observed, which can be confirmed by the slight influence of the thermal mechanism on the emission of nitrogen oxides from low-power heating boilers. The steam water supply in both cycles (cycles four and six) was respectively 0.71 kg/h and 3.60 kg/h, while the reduction in PM emissions based on the results obtained is the same, and is associated with a change in the stoichiometry of the combustion process and its reorganization from the incomplete combustion process, with significant soot release to the combustion process with significant CO emission. The addition of steam in the amount of 0.71 kg/h resulted in a complete reduction of soot, therefore, the further increase in the amount of steam water did not bring any measurable effect, and thus the PM emission did not decrease.
Analyzing the results obtained for the boiler with an additional afterburning chamber (KN-20), it can be seen that the temperature of the exhaust gases and the temperature inside the combustion and afterburning chamber increase with the increasing amount of steam supplied for combustion (regardless of the place of steam injection). The temperature increase is higher in the case of boiler operation at nominal power compared to operation at minimum power, which is associated with a greater stream of fuel feeding. Similar to boilers not equipped with an additional afterburning chamber, a mechanism can be observed where the additional thermodynamic medium (water steam) absorbs a part of the heat, which in turn deteriorates the process of carbon oxidation to carbon dioxide and detects increased CO emissions. In both configurations (steam injection into the combustion chamber or the afterburning chamber), intensification of heat in the system and the problem with its removal by the boiler are visible (exhaust gas temperature increase). However, in the case of both configurations, a reduction in the NOx emission can be observed (from approximately 3% to approximately 17%) as well as for PM (from approximately 9% to approximately 25%).
These results may indicate the occurrence of reducing reactions on these substances in the combustion chamber, where the temperature during the tests with the water steam supply fluctuated in the range of 826 °C to 962 °C. High temperatures could deepen the reduction in PM by exceeding the ash softening temperature and keeping it within the boiler (PM reduction above 20%). In the case of NOx emissions, an increase in the exhaust gas temperature inside the combustion chamber (by supplying water steam) resulted in a decreasing emission. This process is associated with an increased share of radiation on the exhaust gas side, which deepened the redox reactions on nitrogen oxides.
The most favorable emission results (reduction) were obtained for cycles three and thirteen, with an average decrease in CO by approximately 5% to approximately 16%, an average decrease in NOx by approximately 15% to approximately 27% and an average decrease in PM by approximately 12% to approximately 25%. In both of these research cycles, water steam was added to the combustion process with an expenditure of 0.71 kg/h. In the case of cycle three, a decrease in exhaust gas temperature and temperature inside the combustion chamber was observed. In the case of cycle thirteen, an increase in exhaust gas temperature and temperature inside the combustion and afterburning chamber was observed. The increased temperature could transform into a stronger afterburning of soot (PM), while in the case of a boiler equipped with an afterburning chamber, a greater amount of NOx in relation to the boiler without an afterburning chamber was observed.
The injection of water steam to the combustion process may contribute to the occurrence of pyrolysis in certain areas and, consequently, the formation of hydrocarbon compounds which were not analyzed by the authors as a component of the resulting exhaust gases. This results from the fact that at the prevailing temperature in the system (above 750 °C), combined with the appropriate residence time of the particles (min. 2 s) the hydrocarbons’ oxidation to water steam and carbon dioxide is guaranteed. In addition, in commercial applications, the introduction of a possible afterburning system (as mentioned earlier) will multiply the above phenomena of hydrocarbon oxidation.
The results obtained on the basis of the research showed that the most favorable reduction in harmful substances was obtained for the boiler operation at minimal power with a water steam supply output of 0.71 kg/h. These results provide a proper premise for an application approach to the implementation of this technology in mass-produced heating boilers. On the basis of previously carried out studies [
13,
14,
15], solid fuel heating boilers in Poland operate with an average annual power under 30% of the rated power, which results in poor air quality in Poland during the heating period, and at the same time provides a basis for implementation of the tested technology. For such operating parameters (the most common ones), an algorithm was made to supply water vapor to reduce the emission of harmful substances. The algorithm was based on the research and information on the highest reduction in harmful substances (
Figure 8 and
Figure 14).
The proposed algorithm meets the conditions for reducing harmful substances in the boilers unequipped with an additional afterburning chamber. The combustion chamber is understood as a chamber where the fuel is burnt. The afterburning chamber is understood to mean an exhaust gas chamber where hot exhaust gases and a flame freely penetrate. The proposed algorithm of the procedure may help to create a preliminary algorithm or machine learning algorithm for the purpose of creating an automatic control system and water steam dosing for the combustion process. Such an algorithm could be based on information about the exhaust gas temperature and the temperature inside the combustion/afterburning chamber. A similar control system based on the analysis of exhaust gas temperature and oxygen content in the exhaust gas to reduce harmful substances and minimize the amount of fuel burned has been researched in the articles [
13,
14,
15].
An action algorithm was developed on the basis of the analysis for introducing wet steam to the hard coal combustion process in low power heating boilers fitted with an afterburning chamber. It was observed that the greater the stream of water steam introduced to the combustion process, the greater the CO emission (31–90%) in comparison to the normal operation of the boiler. In the case of PM, there was a sharp decrease in emission (12–25%). In turn, the NOx emission slightly decreased (2–5%) in comparison to the normal operation of the boiler. The effect can be the result of the occurrence of chemical reactions mentioned in the introduction. The evidence supporting the hypothesis is the rapid increase in the emission of CO and H2. In the case of steam water fed to the afterburning chamber, no significant increases in the CO emission were observed, and there was a positive decrease in the PM (approximately 20%) and NOx (approximately 7%) emissions in comparison to the normal operation of the boiler.
The action algorithm developed for introducing steam water to the coal-derived fuel combustion process occurring inside a low power boiler is depicted in the following
Figure 15.