1. Introduction
Studies and analyses have shown that obtaining up to a good operating thermal characteristics of the radiators currently tested according to the “
-2
.
” is not possible. Analyses of the conducted measurement results have shown that the current description of the heat transfer process in convection radiator according to
442 [
1,
2] equation is practically correct only for radiators with a low degree of ribbings and mass flow rate close to the
nominal value. In the case of smaller radiators mass flows, according to conducted analysis, the discrepancies are up to a
dozen percent depending on the
type of radiators and the water
mass flow rate. The need to correctly determine the influence of the water mass flow on the heat output of the radiators was felt and signalled in some way, and various attempts were made to solve this problem. For example, Calisir et al. [
3], for various connection configurations of the tested radiators, provided formulas determining the radiator heat output depending on the
mass flow rate and the temperature difference of the
supply and
return water the form of exponential equations. After the measurements in accordance with
EN 442-2 [
2], the general formula for the radiator heat output was given in the form:
where:
For example, for the TBSE
(Top-Bottom-Same-Ends) radiator connection system
for the TBOE
(Top-Bottom-Opposite-Ends) radiator connection system
When it is well known from the
“Physics Laws” that if the water temperature drops in the radiator
and the radiator mass flow rate
are known—the
radiator heat output is determined only by the equation:
The comparison of the
radiator heat output in the
TBSE system obtained from the formula above and according to the
“Laws of Physics” in this case is shown in
Figure 1.
Some
researchers try to attribute the influence of heat transfer conditions in the radiator from the water side only to the
phenomenon of convection from the heated room side—which leads to
mathematically correct relationships to a very limited extent, but at the same time contradicting the
source research of this phenomenon carried out by Nusselt [
4].
According to pioneering research performed by Nusselt on the of the heat transfer process in the free convection conditions the exponent of the power taking into account the influence of the temperature difference between the wall and the surrounding air in the case of laminar air flows does not exceed the value 0.25 while in the conditions of turbulent air flows it does not exceed the value 0.33.
For example, A. B. Erdogamus [
5] in order to obtain acceptable accuracy for the various types of radiators tested with different water mass flow rate, suggested the following dependence for the
radiator 1-row type:
for the
radiator 3-row type:
Ássessing the results from the
“mathematical” point of view, they may seem correct, but looking from the
side of the convection phenomenon, we cannot forget about the pioneering source studies by Nusselt [
4]—that in
convection conditions the exponent
“m” must not exceed the value of
.
In the publication [
6] by Marchesi, R., at al., it was emphasized that the actual
operating conditions of the radiators differ significantly from the conditions in the chamber test according to
EN 442, among others—curtains, water mass flow rate, supply temperature and the connection method of the radiator. After the
, it was found that the radiators heat output decreased to
15% due to hydraulic connections and due to changes in the water mass flow from 10% to 20%. It should be clearly stated that according to the regulations of the currently binding [
2]
EN 442 standard, it is not possible to determine in accordance with the
“Physics Laws”, neither the actual thermal performance nor the energy efficiency of radiators. In principle, according to current practice, only the thermal heat output obtained by the radiator is tested in the assumed
and reconstructed design parameters in the radiator
test chamber: water temperature drop in the radiator
= 20 K or 10 K air temperature in the room
= +20
C and the difference between the average water temperature and the air temperature in the room
= 50 K. Even if at the request of the
, tests were carried out on the heat output of radiators with a variable water mass flow
-the equations predicted for this case in the currently valid
-2
[
2] led to results that are inconsistent with the
“Physics Laws”. According to the proposed Equations (7)–(9) with a constant value of the
exponent “c” it follows, that there is a
continuous increase in the radiators heat output only due to the increasing of the water mass flow rate through the radiator
.
In addition, it is very difficult to measure accurately the actual average temperature of the radiator—while measuring the temperature difference between the water supplying the radiator and the air temperature in the room—is indisputable and simple.
It is also known that the radiators will not work in heated rooms at the design air temperature equal to = +20 C, but at the operating air temperature which in case of using Individual billing for heating costs, may be for example = +18 C, while in case of oversized radiators and dysregulated central heating system or because of the individual thermal comfort requirements of the inhabitants may achieved = +24 C.
There is also a fundamental question about the and sense of obtaining and maintaining during the currently conducted approval tests of radiators—air temperature exactly equal to = +20 C with acceptable small deviations while cooling the walls of the chamber and looking for such a radiator water mass flow rate with a yet unknown radiator thermal power to obtain the nominal radiator return water temperature—waiting for the stabilization of the heat transfer conditions, depending on the type of the tested radiator several dozen hours—when we know that obtained are useless in terms of the operation?
In addition at present a lot of emphasis is placed on activities related to the reduction of the air pollutant emissions e.g., by introducing high efficiency, low—temperature heating installations and low—temperature district heating systems—without changing the current standard 442 it will be very difficult to achieve.
Tests for the actual thermal characteristics of different types of radiators were carried out: iron 10-elements radiator, plate radiator, convectors in different connection configurations and operating conditions—temperature and water mass flow rates generally changes from to of the nominal value. The iron elements T1-type radiator constitute the vast majority of the existing central heating installations in Poland. Of course, in currently designed central heating installations, plate radiators and convector radiators are most often used.
On the basis of the and carried out the has been developed and verified. The properly describes the heat transfer processes taking place in radiators used in heating systems over a wide range of operating conditions and not only under conditions close to the nominal.
This issue is particularly important in the case of
existing buildings after their
refurbished, where central heating installations with
substantial oversized radiators and with too high
supply temperature operate during the
heating season practically at a mass flow rate of 2 times to 4 times smaller than the
nominal value [
7,
8].
Conducted analyses of the
actual heat consumption in more than
600 refurbished buildings showed that the vast majority did not achieve the
expected reduction in actual heat consumption (and in some cases actual consumption
) [
7], due to unproperly operating conditions of radiators with very high
supply temperature,
low mass flow rate and the associated low energy
efficiency of the heating systems (Most of which use the
Iron Element Radiator T1-type).
In such facilities there is an urgent need to develop “Individual projects” for the thermal and hydraulic adaptation of existing oversized central heating systems to new actual heat demand of the rooms, which is not possible without knowledge of a good model describing the heat transfer in radiators under these conditions.
In addition in such buildings the
individual heat cost allocator is commonly used and the
current heat transfer model in radiators according to
442 [
2] is used for their
. As the
and
carried out have shown, errors due to differing significantly from the
nominal of the radiators and the
incorrect installation point the heat allocators reach up to
40%.
The developed model is essential for: directly assessing the actual energy efficiency of the heating system in the heating season and in the Individual Heating Costs Allocation System, while established the suitable conditions for operational regulation of the Central heating installations and district heating systems.
In addition it will also allow for an appropriate modification of the EU Standards regarding the scope and test conditions of the radiators.
3. NEHTMiR—New Extended Model of the Heat Transfer in Radiators
Studies and analyses have shown that the best current model of description of the
process in the
proposed by by W. Wasilewski [
9,
10] and by R. Rabjasz [
11,
12] described by the Equation (10) is correct for water flows through the radiators not less than around
of the
value. Below these mass water flow values differences between
and
radiator heat outpu are unacceptable and the problem is bigger in the case of ribbed radiators with larger quotient of the outer surface transmitting heat to the
in the room and the surface contacting the
.
The main assumption in the verified
is the
of the radiator heat transfer coefficient depending on the water mass flow rate and temperature difference described in the equation:
In operating conditions the heat transfer process in
takes place at a
value of the heat transfer coefficient due to temperature and water mass flow rate changes described by Equation (11). The
,
is presented in
Figure 2.
For the elementary surface of the radiator
the heat flux transferring to the
in the room describes the equation:
Taking into account Equation (11) we will get:
An elementary change in the temperature difference between
and
along element dAx describes the equation:
On the basis of the above relationship substitute the Equation (13) we will receive:
After conversion Equation (
15) we will get:
Integrating in the boundaries for:
,
=
and for
,
after the transformation we will get the equation describing the energy efficiency of the radiators in the form of:
and radiator heat output:
Equation describing the temperature of the return water from the radiator:
The exponent
is
and its value depends on the radiator water mass flow rate and the radiator type. In the case of the plate, multi-row radiator with a
level up to
= 8.0 good result can be achieved using Equation (21):
For the convectors with a higher degree of
, especially in forced airflow conditions, a better result can be achieved by describing the exponent
as a power function in the form of Equation (22):
Generally, in the case of radiators optimalization of the temperature distribution on the surface of the heater in terms of obtaining the greatest possible radiator heat output —it is important but solved only once at the stage of () of the radiator. However, during the —only the actual thermal characteristics of the radiator used are important. That means, how the actual radiator heat output is changing at the set temperature of the in the heated room—when changing the parameters over which we are influenced i.e., the temperature and the radiator water mass flow . And also whether the radiator heat output corresponds to the actual thermal needs of the room.
During the radiators thermal characteristics
tests the actual
can be directly determined in a very wide range of parameter changes by measuring for the specified ater mass flow rates
and the set supply temperature
and air in room
—two standard radiator response parameters: the heat output
and return water temperature
.
5. Result and Analysis
The comparison between the
and
simulation calculations result of radiator heat output, radiator
and
water temperature according to the
for 10-elements iron radiator T1 with no extended external surface (ribbed degree around 1.0) at
C is presented in the
Table 1 and
Table 2.
Across a wide range of tests and measurements carried out, the discrepancy between the results obtained from simulation calculations based on the and the actual values obtain from measurement’s had not exceed 2.5%.
On the other hand, using the 442 model, discrepancies in the radiator heat output under low water mass flow conditions reach up to −22.3%.
On
Figure 11 and
Figure 12 for example a comparison between the result of the simulation calculations based on developed
and measurements the temperature distribution of the water flowing through the radiator and radiator surface temperature distribution along its height obtain from thermography measurements are provided
(measurement 1 and 4).In the drawings above the radiator heat demand output means the heat transmitted to a given point at the height of the heater measured from the top. For example, if the water flow = 0.0051 kg/s, measurement 4 and = 0.6 m, = 602 W—heat output transferred by the entire radiator, if = 0.3 m, W—heat output of the upper half of the radiator, if = 0.4 m, = 467 W—heat output transferred by the upper of the radiator surface.
For the entire range carried out of the
measurement from 1 to 5 the result of simulation calculations according the
of the water and radiator surface temperature distribution along its height at
C and mass flow rate
from 39% to 356% of the
nominal value are presented on
Figure 13 and
Figure 14.
Profile of the radiator T1 surface temperature change, at
=
C, and mass flow rate
from
to
nominal flow rate is presented in
Figure 14.
As it can be seen in
Figure 13 under the high radiator water mass flow rate conditions, the
of temperature changes and changes in radiator heat output along the heat transfer surface is close to
. However, in the case of a mall mass water flow rate (
Figure 13—measurement 4)—the profile of the temperature distribution and radiator heat output changes are clearly different from the
linear. In addition
Figure 14 shows, that for a small water mass flow in the upper zone of the radiator there is the largest difference between the temperature of the water and the radiator wall of about 6.0 K. From the level less than half of the heater in this case, the temperature difference between the flowing water and the radiator wall
does not exceed 0.9 K.
Along the entire heat transfer area of the radiator the difference between the surface temperature determined from the thermography measurements and simulation calculations according to for Elements Iron Radiator T1-type does not exceed 2%.
The developed with high accuracy describes heat transfer processes under significant changes of the radiator water mass flow rate and temperature supply. It is highly recommended and useful for determination of seasonal operating conditions and actual of the radiators and the whole central heating installations.
On
Figure 15 and
Figure 16 for example, the radiator T-1 surface temperature distribution according the thermography measurements at
=
C and mass flow rate
=
kg/s and
=
kg/s are presented.
On
Figure 17 and
Figure 18 the profile of the water and radiator T1 surface temperature change according simulation calculations by
for mass flow rate from 24% to 153% of the
nominal value are presented.
The comparison between the
and
simulation calculations result of radiator heat output, radiator
and return water temperature according to the
for 2-row plate radiator Delonghi 22 with extended external surface (ribbed degree around 4.76) at
C and radiator water mass flow rate from 0.0059 kg/s, 24%
(nominal value) to 0.0379 kg/s, 153%
(nominal value) are presented in the
Table 3 and
Table 4.
Across a wide range of and carried out for ribbed radiator Delonghi type 22, the discrepancy between the results obtained from based on the and the actual values obtain from measurement’s had not exceed 2.0%.
On the other hand, using the 442 model, discrepancies in the radiator heat output under low water mass flow conditions reach up to −9.2%.
On
Figure 19 and
Figure 20 for example, the radiator Delonghi type 22, surface temperature distribution according the thermography measurements at
= 89.6
C and mass flow rate
= 0.0247 kg/s,
(measurement 2) and
= 0.0012 kg/s,
(measurement 3) are presented.
The comparison radiator Delonghi type 22
effectiveness according the
and
calculations based on the
(measurements from 1 to 4) for radiator water mass flow rate from 22% to 100% of the
nominal value are presented are presented on
Figure 21.
The radiator Delonghi type 22,
effectiveness according
calculations based on the
as a function of the radiator surface area for radiator water mass flow rate from 22% to 100% of the
nominal value are presented on
Figure 22.
The developed “New Extended Heat Transfer Model in Radiators” describes very well heat transfer processes under wide changes of the seasonal operating conditions also in the types of radiators.
On
Figure 23 and
Figure 24 for example, comparison between the result of the
calculations based on developed
and
the temperature distribution of the water flowing through the radiator Delonghi type 22 and radiator surface temperature distribution along its height obtain from thermography measurements are provided
(measurement 1 and 4).
Along the entire heat transfer area of the radiator Delonghi-22, the differences between the temperature determined from the thermal measurements on the radiator Delonghi-22 surface and the results of the calculations based on developed does not exceed 2.0%.
The results of the
calculations based on the
of the water and surface temperature profile for ribbed radiator Delonghi type 22, at water supply temperature
=
C and
=
C in the extended range of changes in the radiator water mass flow rate from 0.0009 kg/s (10%
value) to 0.0178 kg/s (203%
value)
, are presented on
Figure 25 and
Figure 26.
As can be seen on
Figure 26, under conditions of high water mass flowing through the Delonghi-22 (ribbed degree 4.76), the profile of radiator temperature and heat output changes along the heat transfer surface is practically linear. In the case of a small mass water flow rate
= 0.0059 kg/s, 24% nominal
, see
Figure 24—
4—the profile of temperature and radiator heat output changes are more
non-linear compared to the non-ribbed radiator
.
In order to carry out a complete verification of the , an additional test cycle of convector type radiators with a very high degree of ribbing (from 22.1 to 36.9) also with forced airflow was carried out using a 3-steped drum fan.
The radiators were made up of 8 copper tubes dimeter 18 × 0.5 mm, on which aluminum ribs of 0.15 mm thickness, diameter 125 × 200 mm, and spacing 5 mm were mounted. Tubes arranged in two rows in a combination 2 tubes of
parallel or in a
serial connection. The convector radiator housing is made of steel sheet. The view of the convector radiators are showed on
Figure 27 and
Figure 28.
A number of measuring series were carried out over a wide range of changes in the water mass flow rate through the convector radiators from approximately from 26% to 216% of the mas flow rate.
The comparison between the
and
simulation calculations result of radiator heat output, radiator efficiency and return water temperature according to the
for Convector Radiator type-8RR and type-8RS with extended external surface (ribbed degree around 22.1) at
C and radiator water mass flow rate from 0.0047 kg/s (
nominal) value to 0.0303 kg/s (
nominal) value are presented in the
Table 5.
The comparison between the
and
simulation calculations result of radiator
, radiator
and
water temperature according to the
for Convector Radiator type-8RS with extended external surface (ribbed degree around 22.1) at
C and radiator water mass flow rate from 0.0047 kg/s, 26%
(nominal) value to 0.0303 kg/s 168%
(nominal) value are presented in the
Table 6 and
Table 7.
The comparison between the
and
simulation calculations result of the Convector Radiator type-8RR heat output, with extended external surface (ribbed degree around 22.1) according to the
at
C and radiator water mass flow rate from 0.0047 kg/s, 34%
(nominal) value to 0.0303 kg/s, 216%
(nominal) value are presented on the
Figure 29.
The comparison between the
and simulation calculations result of the convector radiator type-8RS heat output, with extended external surface (ribbed degree around 22.1) according to the
at
C and radiator water mass flow rate from 0.0035 kg/s, 26%
(nominal) value to 0.0226 kg/s, 168%
(nominal) value are presented on the
Figure 30.
The difference between the heat output of the convector radiators with extended external surface (ribbed degree around 22.1) and according to the do not exceed 4.3%.
6. Calculations Examples
6.1. Implementation of the “NEHTMiR”—Iron Elements Radiator T-1
Data input: , m, ,
The result of the
from
1 to 4 and simulation calculations of the
T-1
are presented on the
Figure 31.
Example 1. = 0.0307 kg/s, = 70.6C, = 21.1C, = 70.6 − 21.1 = 49.5 K ( = 924 W, = 63.4C).
The radiator energy efficiency according :
=
= =
Actual radiator heat output: W
Heat output according to radiator effectiveness:
W, W
Actual radiator return temperature = C
The return water temperature according to radiator effectiveness:
= 0.143 = 63.5 C, =
Example 2. = 0.0155 kg/s, = 70.6C, = 20.9C, = 70.6 − 20.9 = 49.7 K ( = 832 W, = 57.8C).
The radiator energy efficiency according :
=
= =
Actual radiator heat output:
W Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature = C
The return water temperature according to radiator effectiveness:
= = C, =
Example 3. = 0.0086 kg/s, = 70.5C, = 20.7C, = 70.5 − 20.7 = 49.8 K ( = 737 W, = 50.1C).
The radiator energy efficiency according :
=
= =
Actual radiator heat output:
W Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature = C
The return water temperature according to radiator effectiveness:
= = C, =
Example 4. = 0.0051 kg/s, = 69.7C, = 20.3C, = 69.7 − 20.3 = 49.4 K ( = 588 W, = 42.2C).
The radiator energy efficiency according :
=
= =
Actual radiator heat output:
W Heat output according to radiator effectiveness:
W, W,
= C
The return water temperature according to radiator effectiveness:
= = C, =
Example 5. = 0.0034 kg/s, = 69.4C, = 19.9C, = 69.4 − 19.9 = 49.5 K ( = 481 W, = 35.3C).
The radiator energy efficiency according :
=
= =
Actual radiator heat output:
W Heat output according to radiator effectiveness:
W, W,
= C
Actual radiator return temperature: = C
The return water temperature according to radiator effectiveness:
= = C, =
The Discrepancy
The discrepancy in the results of and calculations of the radiator efficiency, radiator heat output and return temperature in terms of mass flow rate changes from 39% to 179% of the radiator nominal mass flow rate does not exceed .
6.2. Implementation of the “NEHTMiR” for 2-Row Delonghi-22 Ribbed Radiator
Data input: , m, , ribbing level , , .
The result of the
from
1 to 5 and simulation calculations of the
-22
are presented on the
Figure 32.
Example 6. = 0.0379 kg/s, = 89.8C, = 19.9C, = 89.8 − 19.9 = 69.9 K, 0.0199, 0.0721. ( = 2215 W, = 75.9C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output:
W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The return water temperature according to radiator effectiveness:
= = C, =
Example 7. = 0.0247 kg/s, = 89.6C, = 19.5C, = 89.6 − 19.5 = 70.1 K, 0.0199, 0.0721. ( = 2103 W, = 69.3C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output according to “”:
W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “”: radiator effectiveness:
= = C, =
Example 8. = 0.0120 kg/s, = 89.8C, = 19.7C, = 89.8 − 19.5 = 70.1 K, 0.0199. 0.0721. ( = 2103 W, = 69.3C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output according to “”: W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “” radiator effectiveness:
= = C, =
Example 9. = 0.0059 kg/s, = 89.7C, = 19.7C, = 89.7 − 19.7 = 70.0 K, 0.0199. 0.0721. ( = 1289 W, = 37.1C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output according to “”: W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “” radiator effectiveness:
= = C, =
The Discrepancy
The discrepancy in the results of and calculations of the Radiator -22 efficiency, radiator heatoutput and return temperature in terms of mass flow changes from 23% to 151% of the radiator nominal mass flow rate does not exceed .
6.3. Implementation of the “” for High Ribbed Convective Radiator type-8RR
Data input:
, m, , ribbing level , ,
.
The result of the
from
1 to 5 and simulation calculations of the High Ribbed
-
are presented on the
Figure 33.
Example 10. = 0.0303 kg/s, = 51.2C, = 21.0C, = 51.2 − 21.0 = 30.2 K, 0.01124, 0.0721. ( = 1289 W, = 37.1C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output according to “”:
W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “” radiator effectiveness:
= = C, =
Example 11. = 0.0047 kg/s, = 51.1C, = 21.0C, = 51.1 − 21.0 = 30.1 K, 0.01124, 0.0721, ( = 352 W, = 33.3C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output according to “”:
W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “” radiator effectiveness:
= = C, =
Example 12. = 0.0226 kg/s, = 59.0C, = 22.0C, = 59.8 − 22.0 = 37.0 K, 0.01124, 0.0721, ( = 709 W, = 51.5C).
The radiator energy efficiency according :
=
= =
Actual radiator heat output according to “”: W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “” radiator effectiveness:
= = C, =
Example 13. = 0.0035 kg/s, = 58.6C, = 20.8C, = 58.6 − 20.8 = 37.8 K, 0.01124, 0.3952, ( = 388 W, = 32.1C).
The radiator energy efficiency according “”:
=
= =
Actual radiator heat output according to “”: W
Heat output according to radiator effectiveness:
W, W,
Actual radiator return temperature: = C
The radiator return temperature according the “” radiator effectiveness:
= = C, =
The Discrepancy
The discrepancy in the results of and calculations of the high ribbed convective - efficiency, radiator heat output and return temperature in terms of mass flow changes from 26% to 202% of the radiator nominal mass flow rate does not exceed .
7. Conclusions
A revised is general and suitable for all types of radiators, both new radiators and existing radiators after a certain period of operation. It describes the heat transfer processes with very high accuracy in panel radiators (medium ribbed), iron elements radiators (not ribbed), convectors (high ribbed) not only in the conditions - in which the radiators are designed, but what is particularly important also in the parameters when the radiators water mass flow rate changes from to of the nominal value and at the same time the supply temperature changes whole range of radiators operation during the heating season (in all tests range inaccuracies are below ).
In order to prove the general nature of the the comparison of the calculations and measurements results for older iron elements radiators previously commonly used in central heating installations, new plate radiators and convectors currently designed are presented.
Across a wide range of and carried out for ribbed radiator Delonghi type 22, the discrepancy between the results obtained from calculations based on the and the actual values obtain from measurement’s in terms of mass flow changes from 23% to 151% of the nominal value—do not exceed 2.0%.
The discrepancy in the results of the and based on the calculations for the Iron Elements Radiator T-1 in terms of mass flow changes from 39% to 179% of the radiator mass flow rate—not exceed .
In case of the tests and measurements carried out for High Ribbed Convective Radiator - across a very wide range of change: supply temperature from = C to = C and water mass flow from to of the flow rate, maximum discrepancy between the and obtain from calculations result according —do not exceed 4.3%.
The additional thermography of the temperature distribution on the radiators surface, in the entire range fully confirmed the results obtained from the calculations based on the .
This issue is particularly important in the case of the existing buildings after their
refurbished, where central heating installations with substantial oversized radiators and with too high
supply temperature operate during the
heating season practically at a mass flow rate of
2-times to
4-times smaller than the
value [
7,
8,
13].
Conducted analyses of the actual heat consumption in more than
600 refurbished buildings showed that the vast majority did not achieve the expected reduction in actual heat consumption (and in some cases actual consumption
) [
7] due to unproper operating conditions of radiators with to high
supply temperature, low mass flow rate and the associated low
energy efficiency of the heating systems. In such facilities there is an urgent need to develop
“Individual projects” for the thermal and hydraulic adaptation of existing oversized central heating systems to new actual heat demand of the rooms, which is not possible without knowledge of the
“good model” describing the heat transfer proces in radiators under these conditions.
In addition, in such building the individual
heat cost allocators are commonly used and the current heat transfer model in radiators according to
442 is used for their
. As the
and
carried out have shown, errors due to differing significantly from the
nominal radiators operating conditions and the incorrect
installation point of the heat cost allocators reach up to
40%, [
13].
Achieved the high compatibility of the results of the calculations with the results for different types of radiators: Iron Elements, Plate Radiators, Convectors in a very wide range of changes in the water rates and the temperature indicates that the developed model is also essential for:
directly assessing the actual energy efficiency of the heating system in the heating season.
improve the indications of the heat allocator due their proper
programming in the Individual Heating Costs Allocation Systems [
14].
to establish the suitable conditions for regulation of the Central Heating Installations especially in existing buildings after their refurbishment as well as for the District Heating Systems with oversized heat exchangers.
Verified can also be used in: and calculations of the central heating installations, for the rational conversion of the existing installations and district heating systems into energy efficient systems.
In addition, it may form the basis for an modification of the EU Standards regarding the scope and test conditions of the radiators.