Article

Impact of Spotted Hyena Optimized Cascade Controller in Load Frequency Control of Wave-Solar-Double Compensated Capacitive Energy Storage Based Interconnected Power System

by
Arindita Saha
1,
Puja Dash
2,
Naladi Ram Babu
3,
Tirumalasetty Chiranjeevi
4,*,
Bathina Venkateswararao
5 and
Łukasz Knypiński
6,*
1
Department of Electrical Engineering, Regent Education & Research Foundation Group of Institutions, Kolkata 700121, West Bengal, India
2
Department of Electrical and Electronics Engineering, Gayatri Vidya Parishad College of Engineering (Autonomous), Visakhapatnam 530048, Andhra Pradesh, India
3
Department of Electrical & Electronics Engineering, Aditya Engineering College, Surampalem 533437, Andhra Pradesh, India
4
Department of Electrical Engineering, Rajkiya Engineering College Sonbhadra, Sonbhadra 231206, Uttar Pradesh, India
5
Department of EEE, V R Siddhartha Engineering College, Vijayawada 520007, Andhra Pradesh, India
6
Institute of Electrical Engineering and Electronics, Faculty of Automatic Control, Robotic and Electrical Engineering, Poznan University of Technology, 60-965 Poznan, Poland
*
Authors to whom correspondence should be addressed.
Energies 2022, 15(19), 6959; https://doi.org/10.3390/en15196959
Submission received: 22 August 2022 / Revised: 8 September 2022 / Accepted: 15 September 2022 / Published: 22 September 2022
(This article belongs to the Special Issue Power System Dynamics and Renewable Energy Integration)

Abstract

:
The concept of automatic generation control has an immense role in providing quality power in an interconnected system. To obtain quality power by controlling the oscillations of frequency and tie-line power, a proper controller design is necessary. So, an innovative endeavor has been undertaken to enforce a two-stage controller with the amalgamation of a proportional-derivative with filter (PDN) (integer-order) and a fractional order integral-derivative (FOID), i.e., PDN(FOID). In an effort to acquire the controller’s gains and parameters, a bio-inspired meta-heuristic spotted hyena optimizer is applied. Various examinations manifest the excellence of PDN(FOID) over other controllers such as integral, proportional–integral, proportional–integral-derivative filter, and fractional order PID from perspectives concerning the diminished amount of peak anomaly oscillations, and the instant of settling for a three-area system. The system includes thermal–bio-diesel in area-1; a thermal–geothermal power plant in area-2; and a thermal–split-shaft gas turbine in area-3. It is also observed that the presence of renewable sources such as wave power plants and photovoltaics makes the system significantly better compared to the base system, when assessed individually or both together. Action in a combination of capacitive energy storage with duple compensation is also examined using the PDN(FOID) controller, which provides a noteworthy outcome in dynamic performance. Moreover, PDN(FOID) parameter values at a nominal condition are appropriate for the random patterns of disturbance needed for optimization.

1. Introduction

The principle of automatic generation control (AGC) is to maintain the balance between power generation and power demand along with losses [1,2,3]. If this equilibrium is not maintained then it will lead to excessive fluctuations from the nominal values of frequency and tie-line power connecting areas. Back in earlier days, most of the literature in AGC learning highlighted work in isolated systems [4,5,6]. Later works were reported on interconnected systems for two-area, and even five-area, thermal systems [7,8,9,10,11,12]. Nowadays, the literature reflects the usage of multiple sources as generating units such as hydro, gas, and diesel along with thermal as a base generating unit [13,14,15,16]. However, far fewer works have been reported on another form of gas turbine, which is the split-shaft gas turbine (Ss (GT)) [17]. So, many studies can be conducted on thermal-Ss (GT) systems.
The increasing use of the same conventional sources is extensively depleting them. Conventional sources also affect the environment with their many by-products, which calls for the association of renewable sources with conventional means. The most common forms of renewable sources that are readily available are solar and wind. Many works have been reported in the literature about the involvement of solar and wind in AGC learning in a single area as well as in interconnected systems. Arya [18] reported on the use of a photovoltaic (PV) system in a hydro-thermal system. In addition to these, geothermal and bio-diesel are also coming into the picture. Geothermal energy is a type of thermal energy that is stored by the earth itself. Thus, this type of energy can be extracted from the earth’s crust. Tasnin et al. [19] reported on the application of geothermal in AGC learning. Bio-diesel plants utilize bio-diesel to drive generators. Bio-diesel is produced from oil that has been extracted from various plants such as sunflower, palm, or soybean. The most common form is the use of palm oil. Bio-diesel is a type of renewable fuel. Barik et al. [20] highlighted the use of bio-diesel in an isolated system. In addition, wave power plants (WavePPts) have found minimal consideration in AGC. WavePPts have Archimedes energy translation parts that convert wave energy into electrical energy. Hasanien et al. [21] united a WavePPt with AGC knowledge for a dual-arena thermal scheme. The amalgamation of a geothermal power plant (GPP) and a bio-diesel plant along with a WavePPt and photovoltaic (PV) in AGC learning has not yet been reflected in the literature. Thus, a thermal-Ss (GT) system incorporating GPP, bio-diesel, a WavePPt, and PV calls for further extensive assessments.
The perception of AGC leads to a great effort to decrease the anomaly of frequency along with tie-line power, interlinking diverse areas from their basic value. However, periodically, a state may ascend when oscillations grow to an excessive amount so that a scheme might bring uncertainty. In this circumstance, if the scheme is involved with an energy storage unit, such as capacitive energy storage (CES), then it can avoid such an alteration. As such, CES will draw an extra amount of power, which indicates less usage of kinetic energy to subdue small load needs. CES [22] has found its application in AGC learning. It can be used in the existence of duple compensation or in the absence. The influence of the contrast of CES with/without duple compensation on scheme dynamics is hitherto to be discovered.
In the scheme of AGC knowledge, there is a dual diverse sort of control similar to a primary control and subordinate control. A major consideration in AGC knowledge concerning control is the appropriate choice of secondary controllers. Numerous categories of subordinate controllers such as integer order (InO), fractional order (FrO), and cascade controllers are described in the literature associated with AGC. Diverse authors have described numerous InO controllers, such as integral (I) [23], proportional–integral (PI) [24], and proportional–integral-derivative with filter (PIDN) [25], in AGC. Dual [26] or trio [27] higher grade of freedom subordinate controllers have also been examined in this arena of learning, and correspond to the InO sort. The few FrO controllers, which initiate its application, are FOPI [28] and FOPIDN [29]. The AGC knowledge literature reflects the practice of InO order two-stage controllers PD-PID [30], and FrO two-stage controllers FOPI-FOPD [19], as well as a grouping of InO and FrO controllers (PIDN-FOPD) [31]. A dual-stage controller with the amalgamation of InO PDN with FrO FOID, termed PDN(FOID), is never hitherto specified in AGC works. Furthermore, the utilization of the PDN(FOID) subordinate controller in this trio-area thermal–bio-diesel–GPP-Ss (GT) scheme along with WavePPt, PV, and CES has not been stated beforehand, so it claims the necessity of examination.
The performance of each subservient controller is exceptionally solitary if the finest amount of gain and related constraints are appropriately favored. These could be executed with the assistance of typical or optimization measures. However, the usage of typical methods such as straight pursuit, arbitrary pursuit, incline pursuit, and numerous others is pretty arduous and delivers substandard consequences, as well as craving a great number of repetitions to deliver outcomes. The optimization procedures that have previously been found in AGC knowledge are whale optimization algorithm (WOA) [17], bacterial foraging optimization (BFO) [24], cuckoo search (CS) [26], differential evolution (DE) [32], particle swarm optimization (PSO) [33], firefly algorithm (FA) [34], grey wolf optimization (GWO) [35], imperialist competitive algorithm (ICA) [36], flower pollination algorithm (FPA) [37], honey badger algorithm [38], AdaBoost algorithm [39], and improved moth-flame algorithm [40]. A newly developed bio-inspired meta-heuristic algorithm titled spotted hyena optimizer (SHO) [41] is obtainable from the literature. SHO was established from the behavioral nature of spotted hyenas, which portrays the social bond between the spotted hyena and their collaborative deeds. To our great surprise, the implementation of SHO has not been identified in AGC learning for its ability to obtain the best values of controller gains and parameters, and this demands a complete investigation.
With reference to the above-mentioned discussions, the prime purpose of the present article is as follows:
(a)
Formulation of a three-area scheme with a thermal–bio-diesel in area-1, thermal–GPP in area-2, and thermal–Ss (GT) in area-3;
(b)
The gains of I/PI/PIDN/PDN(FOID) are simultaneously optimized individually using the SHO algorithm in order to obtain an excellent controller;
(c)
The scheme stated in (a) is combined with WavePPt in area-1, and its impact on the system dynamics is assessed;
(d)
The scheme stated in (a) is combined with PV in area-3, and its impact on the system dynamics is assessed;
(e)
The scheme stated in (a) is combined with WavePPt in area-1 and PV in area-3 together, and their impact on the system dynamics is assessed;
(f)
The scheme stated in (e) is combined with CES with/without duple compensation separately, and their impact on the system dynamics is studied on an individual basis;
(g)
Sensitivity investigation is undertaken to examine the toughness of the superlative ‘controller’s gains when subjected to a random pattern of load disturbance.
For ease of understanding, the present article is schematically represented in Figure 1.

2. Structure Portrayal

2.1. Overall Portrayal of Structure

A trio-area scheme of uneven sort is contemplated for scrutiny, confining the area size ratio in the arrangement of 2:3:4. The scheme encompasses a bio-diesel–thermal plant in area-1. In the same manner, thermal–geothermal power plants (GPP) in area-2, and thermal–split-shaft gas turbine (Ss (GT)) in area-3. The parameters values are provided in Appendix A. Typical diesel plants are currently being substituted by bio-diesel plants since they are nonpoisonous, as well being ecologically friendly, and pretty bulky with curtailed viscidity; additionally, they emit a relatively small amount of carbon monoxide. Thus, they could be employed as a reserve for power origination. The following comprises the valve controller and ignition engine. The first order transfer functions (Tfn) of the valve controller and ignition engine of a bio-diesel plant are detailed by (1) and (2) on an individual basis.
T f v a l v e   r e g u l a t o r B i o d i e s e l = K V R 1 + s T V R ,
KVR and TVR are the bio-diesel plant valve regulator’s gain and time constants individually.
T f C o m b u s t i o n   e n g i n e B i o d i e s e l = K C E 1 + s T C E
KCE and TCE are the bio-diesel plant combustion engine’s gain and time constants individually.
Geothermal energy is a potential renewable source (RWS) of energy where underground thermal energy is transformed into electricity. The Tfn modeling of GPP is similar to thermal plants, but it does not have a boiler for reheating steam [19]. The first order Tfn of the governor and turbine of GPP is given by (3) and (4), respectively.
T f n G G P P = 1 1 + s G G P P ,
T f n T G P P = 1 1 + s T G P P
GGPP and TGPP are varied constants of GPP, independently. These values are obtained by the optimization technique SHO within the prescribed limits [19]. The participation factors (pf) of each generating unit of the respective areas are pf11 = 0.7, pf12 = 0.3 in area-1; pf21 = 0.6, pf22 = 0.4 in area-2; and pf31 = 0.65, pf32 = 0.35 in area-3. This is supposed to be scheme-1. Afterward, the structure is unified with a wave power plant (WavePPt) in area-1. This is supposed to be scheme-2. Afterward, structure-1 will be involved with the photovoltaic (PV) system in arena-3. This is scheme-3. Next, both the WavePPt and PV are integrated into scheme-1 with the WavePPt in area-1 and PV in area-3. This is scheme-4. When the WavePPt and PV are both present in the system, then the pf’s are: pf11 = 0.7, pf12 = 0.3 in arena-1; pf21 = 0.6, pf22 = 0.4 in arena-2; and pf31 = 0.5, pf32 = 0.3, and pf33 = 0.2 in arena-3. After that, the energy storing component, namely, capacitive energy storage (CES) is included in all areas. This is treated as scheme-5. Again, structure-5 is provided with CES having duple compensation in all areas. This is scheme-6. The representation and transfer function (Tfn) model of the arrangements is replicated in Figure 2. The Tfn model of Ss (GT) is obtained from [17]. The elementary values of structure parameters are specified in the addendum. The best values of controller gains and correlated constraints are attained with the assistance of the spotted hyena optimizer algorithm by taking into account the integral squared error as a performance index (PiISE) specified by (5)
P i I S E = 0 T { ( Δ f 1 ) 2 + ( Δ f 2 ) 2 + ( Δ f 3 ) 2 + ( Δ P t i e 1 2 ) 2 + ( Δ P t i e 2 3 ) 2 + ( Δ P t i e 1 3 ) 2 }   d t .

2.2. RWS—Wave Power Plant (WavePPt)

The power of the WavePPt is attained from sea surf. For accomplishing this rendition, Archimedes-wave swing (AdWS), which is a sort of translation segment pooled with a permanent magnet synchronous generator (PtMSg), converts sea surf mechanical to electrical energy. The Tfn of AdWS attached to PtMSg is established. Here, the WavePPt is unified to area-1 through the assistance of a Converter|generator sideways/grid sideways inverter. All components of studied system were modelled MATLAB R2020a software. The converter present near a generator is employed in order to attain situations of extreme power point trailing. Mutually, the converter and inverter are intended for a gain value of 1 and a period constant of 0.01 s. The first order Tfn prototype of AdWS of the WavePPt is specified by (6)
T f n P P t A W S W a v e = K W a v e P P t A W S 1 + s T W a v e P P t A W S ,
KWavePPtAWS and TWavePPtAWS are the gain and time constants of the AdWS of the WavePPt, respectively.

2.3. Energy Storage Device—Capacitive Energy Storage (CES)

An energy storage device such as a capacitive energy storage device (CES) is equipment that usually employs a capacitor for storage along with a power adaptation segment, which is connected to the AC network with the assistance of a rectifier/inverter. The CES unit responds instantly to the system in the case of instant recurrent or current drift. Subsequently, any manner of unpredictability is moderated; CES yet again reestablishes the initial voltage amount in the plates of the capacitor by employing the additional energy obtainable in the scheme.
The Tfn of CES is specified by (7)
T f n C E S = K C E S 1 + s T C E S ,
KCES is the gain and TCES are the time constants of CES.
The CES plays the role of a frequency mediator in the case of a twofold compensation technique. The additive revision in power yield of CES with twofold compensation is detailed by (8)
Δ P C E S ( d u p l e   c o m p e n s a t i o n ) = [ K C E S ( d u p l e   c o m p e n s a t i o n ) 1 + s T C E S ( d u p l e   c o m p e n s a t i o n ) ] [ 1 + s T 1 1 + s T 2 ] [ 1 + s T 3 1 + s T 4 ] Δ f i ( s ) ,
KCES(duple compensation) and TCES(duple compensation) are the CES with duple compensation gain and time constants, individually. T1, T2, T3, and T4 are varied time factors of the recompensed segment of CES.

3. The Proposed Approach

3.1. Problem Declaration

The emphasis of the present learning is on the frequency excursion approach with the utilization of an innovative metaheuristic method to optimize the InO and FrO amalgamated controller in a renewable source integrated power system structure. The main aim is to obtain a zero error for aberration in frequency and tie-line power by interconnecting different areas using a suitable control input.

3.2. Commended Controller

The commended controller is an aggregate of integer order (InO) together through a fractional order (FrO) controller. The commended controller is an I/O proportional-derivative with filter (PDN) with FrO integral-derivative (FOID), hence, PDN(FOID). The arrangement of PDN(FOID) is substantiated in Figure 3. Segment-1 (B1) and Segment-2 (B2) are the layouts of PDN and FOID one-to-one. Rsi (s) is the antecedent signal and Osi (s) is the outcome signal for the PDN(FOID) controller. The Trfn of B1i (s) is manifested by (9)
B 1 i ( s ) = K P i s + K D i N i ( s + N i ) .
The InO proportional gain is symbolized as KPi and the derivative gain as KDi for the i-th suggested area, Ni is PDN controller’s filter. Summarization of Riemann–Liouville for the FrO integrator and derivative are obtainable from (10) and (11) [42,43,44]
α D t - α f ( t ) = 1 Γ ( n ) α t ( t - τ ) α - 1 f ( τ ) d τ ,   n - 1 α < n , n   is   an   integer
α D t α f ( t ) = 1 Γ ( n - α ) d n d t n α t ( t - τ ) n - α - 1 f ( τ ) d τ
α D t α is the fractional operator, and Γ(.) is the Euler’s gamma function. The alteration of the Fro integral and derivative in the Laplace domain is given by (12)
L { α D t α f ( t ) } = s α F ( s ) - k = 0 n - 1 s k α D t α - k - 1 f ( t ) | t = 0
The detriment of boundless computation of poles and zeros by virtue of absolute resemblance is manifested by Oustaloup, Mathieu, and Lanusse (1995) [45]. Here, a convenient Trfn is propounded that can approximate FrO derivatives together with integrators by dint of recursive distribution around poles and zeros substantiated by (13)
s α = K n = 1 M 1 + ( s ω Z , n ) 1 + ( s ω p , n )
Suppose, attuned gain K = 1, gain = 0 dB through 1 rad/s frequency, M = Count of poles along with zeros (fixed beforehand), and frequencies choice for poles and zeros are manifested by (14)–(18).
ω Z , l = ω l n
ω p , n = ω Z , n ε ,   n = 1 ,   ,   M
ω Z , n + 1 = ω p , n η
ε = ( ω h ω l ) v M
η = ( ω n ω l ) ( 1 v ) M
The Trfn of B2i (s) is manifested by (19).
B 2 i ( s ) = K F I i s λ i + s μ i K F D i
In the above expressions, λ is the FrO integrator’s fragment and µ is the FrO derivative’s fragment. KFIi is the FrO’s integral fragment gain, and KFDi is the FrO’s derivative fragment gain of the suggested area.

3.3. Objective Function

The main purpose of the controller design is the proper optimization task including the minimization of a particular cost function considering the constraints of controller gains and parameters with its confines. Here, in the present AGC learning, an integral squared error (ISE) is involved as the cost function. The mathematical expression of ISE as a performance index is provided by (20).
P i I S E = 0 T { ( Δ f i ) 2 + ( Δ P t i e i j ) 2 }   d t .
Here, i and j are number of areas, where i = 1, 2, 3, and ij.
In (20), the independent variables are KP, KD, N, KFI, λ, KFD, and µ, and the assumed constraints are provided in (21).
K P m i n K P K P m a x ,   K D m i n K D K D m a x ,   N m i n N N m a x , K F I m i n K F I K F I m a x , λ m i n λ λ m a x ,   K F D m i n K F D K F D m a x , μ m i n μ μ m a x

4. Spotted Hyena Optimizer

Spotted Hyenas Optimizers (SHOs) are known as competent chasers. They are the bulkiest of the hyena breed. The spotted hyenas are also renowned as laughing hyenas since they sound like humans laughing. They are highly complex, brainy, and hugely communal creatures. The SHs trail their victims by their vision, auditory, and odor features. This nature of SH inspired Dhiman et al. [41] to develop the meta-heuristic algorithm SHO. The authors have outlined the mathematical design of the communal acquaintance of SH and collegial agility to undergo optimization. The trio events allied with SHO are tracking down capture, encompassing, and conspicuous capture.
1.
Encompassing capture: To develop the numerical prototype, it is assumed that the present finest contender is the destined capture, which is closest to the optimum given that the chase arena was not known previously. The remaining chase agents will seek to renew their spot with reference to the response of the finest contender about the finest location. The numerical prototype is manifested by (22) and (23)
D h = | B P p ( x ) P ( x ) |
P ( x + 1 ) = P p ( x ) E D h
In the above expressions, D h is the stretch between the Pr of the hunt, and P   is the spot vector of SH. B   and E   are computed as in (24)–(26)
B = 2 r d 1
B = 2 h r d 2 h  
h = 5 ( i t e r a t i o n ( 5 max iteration ) ) ,   i t e r a t i o n = 1 ,   2 ,   3 , max i t e r a t i o n  
For appropriately corresponding the exploration and exploitation, h in straight line declined from 5 to 0 over the duration of the maximum iteration. Additionally, this execution indorses extra exploitation as the count value rises. However, r d 1   and r d 2   are arbitrary vectors within [0, 1].
2.
Trapping: In order to characterize the conduct of SH numerically, it is assumed that the finest chase agent has information regarding the spot of the hunt. The remaining chase agents form groups toward the finest chase agent and save the finest results attained so far to restore their spots according to the following Equations (27)–(29)
D h = | B P h ( x ) P ( x ) |
P k = P h E D h
C h = P k + P k + 1 + .... + P k + N
P h describes the spot of initial finest SH, and P k describes the spot of further SH. At this time, N designates the figure of SH, which is figured as follows:
N = c o u n t n o s ( P h ,   P h + 1 ,   P h + 2 , ,     ( P h + M ) )
M   is the arbitrary vector in [0.5, 1], the numbers outline the figure of the results and the totality of all the contender results, afterward adding M , which is far from comparable to the finest ideal result in the specified hunt space, and C h , which is an assembly of N figure of ideal results.
3.
Encroaching hunt (exploitation): To numerically model for invading the hunt, the h   value is lessened. The disparity in E   is also reduced from 5 to 0 in due course of the count. |E| < 1 forces the assembly of SH to attack on the way to the hunt. The numerical design for invading the hunt is
P ( x + 1 ) = c h N
P ( x + 1 ) stores the finest result and revises the spot of further chase agents as per the spot of the finest chase agent.
4.
Hunt for target (exploration): SH mostly chase the hunt, as per the spot of the assembly of the SH that exist in C h . They shift apart from one another to chase and to combat for the hunt. Then, they utilize E with arbitrary values >1 or <−1 to compel the chase agents to shift far away from the hunt. This mechanism permits the SHO algorithm to hunt in a wide-reaching manner. The SHO’s flowchart is provided in Figure 4.

5. Methodology

A three-area system with a capacity ratio of 2:3:4 is considered for investigation. The investigated system comprises of thermal, bio-diesel, and wave power plant in area-1; thermal and geothermal power plant in area-2; and thermal, split-shaft gas turbine, and solar photovoltaic in area-3. System is also incorporated with an energy storage device. Investigations are carried out considering PDN(FOID) controller whose parameters are obtained by the SHO method with ISE as the performance index. The optimization technique is coded in MATLAB R2022a software, and the investigated system is modeled in Simulink with the FOMCON toolbox.
Studies are carried out for: (1) selection of best controller; (2) selection of appropriate performance index; (3) selection of best optimization method; (4) influence of wave power plant, PV, individually and both together; (5) influence of CES with or without duple compensation; (6) sensitivity assessment.

6. Outcomes and Valuation

6.1. Evaluation of Dynamic Outcome for the Choice of Superlative Controller

The scheme under evaluation embraces thermal including bio-diesel in area-1, GPP along with thermal in area-2, and Ss (GT) along with thermal in area-3 (Scheme-1). This scheme is familiarized with I/PI/PIDN/FOPID/PDN(FOID) controllers on a specific base. Evaluation is accomplished considering a 1% disturbance of the step content in area-1. The finest obtainable values of individual controller gains and related parameters are attained by employing SHO by means of PiISE. The scheme is initially familiarized through a I controller to attain its gain values and also the parameters of GPP using SHO. The governor and turbine time constants obtained are 0.1 s, respectively. These values of GGPP and TGPP are kept the same for the remainder of the work. Subsequently, PI, PIDN, and FOPID in addition to PDN(FOID) controllers are cast off independently. The finest conceivable values are assembled in Table 1, and dynamic outcomes are associated, as revealed in Figure 5. Significant interpretation of each outcome articulates around the fineness of the PDN(FOID) overtop additional controllers concerning the diminished stage of peak_overshoot (Pk_O), extent-of-oscillations, and peak_undershoot (Pk_U), besides the duration of settling (S_Time). Thus, it is revealed that the SHO-optimized PDN(FOID) controller outperforms other controllers in terms of lessened Pk_O (Δf1 = 0.0007 Hz, Δf2 = 0 Hz, ΔPtie1–2 = 0 Hz, and ΔPtie1–3 = 0 Hz), Pk_U (Δf1 = 0.0112 Hz, Δf2 = 0.0038 Hz, ΔPtie1-2 = 0.0039 Hz, and ΔPtie1-3 = 0.0039 Hz), and S_Time (Δf1 = 25.81 s, Δf2 = 35.31 s, ΔPtie1–2 = 21.71 s, and ΔPtie1–3 = 21.04 s). In Table 2, the matching outcomes of Pk_O, Pk_U, and S_Time values are recorded, which imitates the improved conduct of the PDN(FOID) overtop remainder of the subordinate controllers.

6.2. Nomination of Performance Index

The excellent outcome of the performance index (Pi) among the integral squared error (PiISE), integral time squared error (PiITSE), integral absolute error (PiIAE), and integral time absolute error (PiITAE) are procured by assisting system-1 with each of the Pi on individual terms using the PDN(FOID) controller. The premium standards of PDN(FOID) controller gains and related parameters are attained using the SHO algorithm. The expressions for PiITSE, PiIAE, and PiITAE are given by (32)–(34), respectively, and for PiISE, it is given by (5)
P i I T S E = 0 T { ( Δ f 1 ) 2 + ( Δ f 2 ) 2 + ( Δ f 3 ) 2 + ( Δ P t i e 1 2 ) 2 + ( Δ P t i e 2 3 ) 2 + ( Δ P t i e 1 3 ) 2 } t   d t
P i I A E = 0 T { | Δ f 1   | + | Δ f 2 | + | Δ f 3 | + | Δ P t i e 1 2 | + | Δ P t i e 2 3 | + | Δ P t i e 1 3 | }   d t
P i I T A E = 0 T { | Δ f 1   | + | Δ f 2 | + | Δ f 3 | + | Δ P t i e 1 2 | + | Δ P t i e 2 3 | + | Δ P t i e 1 3 | } t   d t
With the help of illustrious values accomplished for PDN(FOID) controller’s gains and correlated parameters in each case, the dynamic responses are contrasted in Figure 6a–c, and the corresponding Pk_O, Pk_U, and S_Time values are marked down in Table 3. A critical view of the responses says that responses considering PiISE as Pi have a better performance compared to others with respect to lessened Pk_O, Pk_U, S_Time, and oscillations. Thus, it is revealed that the SHO-optimized PDN(FOID) controller using ISE as a performance index outperforms other Pi in terms of lessened Pk_O (Δf1 = 0.0007 Hz, Δf2 = 0 Hz, and ΔPtie1–2 = 0 Hz), Pk_U (Δf1 = 0.0112 Hz, Δf2 = 0.0038 Hz, and ΔPtie1–2 = 0.0039 Hz), and S_Time (Δf1 = 25.81 s, Δf2 = 35.31 s, and ΔPtie1–2 = 21.71 s). Further, the values of Pi are PiISE = 0.00021, PiITSE = 0.00084, PiIAE = 0.1053, and PiITAE = 0.7233, which reveals the better performance of the system with PiISE. The convergence characteristics for system-1 using different Pi’s is reflected in Figure 6d. It is observed that convergence characteristics using ISE as Pi converge faster in fewer iterations than other Pi’s.

6.3. Nomination of Algorithm

For the nomination of the algorithm, system-1 is provided with different algorithms, separately, using PDN(FOID) controllers. The algorithms used here are the firefly algorithm (FA), cuckoo search algorithm (CS) [46], particle swarm optimization (PSO) [47], whale optimization algorithm (WOA), and SHO. The tuned values for FA are β0 = 0.3, α = 0.5, γ = 0.4, count of fireflies = 50, and maximum number of generations = 100. For CS, nests count = 50, rate of discovery = 0.5, exponent of levy = 1.5, maximum generation = 100, and count of dimensions = 10. For PSO, the tuned parameters values are w = 1, wdamp = 0.99, c1 = 1.4, c2 = 1.98, population size = 50, and maximum generation number = 100. For WOA, figure of hunt agents = 50, and number of repetitions = 100. For each of the algorithms, the best values for the PDN(FOID) controller are obtained. The values are not provided here. With these values, the responses of different algorithms are contrasted in Figure 7a–c. The corresponding responses of Pk_O, Pk_U, and S_Time values are given in Table 4. In Table 4, it can be seen that Pk_O, Pk_U, and S_Time values obtained by the SHO-optimized PDN(FOID) controller are much better compared to other algorithms. Thus, it is revealed that the SHO-optimized PDN(FOID) controller outperforms other algorithms in terms of lessened Pk_O (Δf1 = 0.0007 Hz, Δf3 = 0 Hz, and ΔPtie1–3 = 0 Hz), Pk_U (Δf1 = 0.0112 Hz, Δf3 = 0.0052 Hz, and ΔPtie1-3 = 0.0039 Hz), and S_Time (Δf1 = 25.81 s, Δf3 = 23.53 s, and ΔPtie1–3 = 21.04 s). Further, the supremacy is judged by the convergence curve provided in Figure 7d, where it is observed that the response with the SHO-optimized PDN(FOID) controller converges faster and has the least value of PiISE. Therefore, further analyses are carried out using the SHO algorithm.

6.4. Evaluation of Influence of the Wave Power Plant on Dynamics of System

In the preceding Section 6.1, it is perceived that the SHO-optimized PDN(FOID) is equipped with admirable pursuance for scheme-1. Now, scheme-1 is integrated with an additional RWS, namely, a wave power plant (WavePPt) in area-1, observed as scheme-2. Forthwith, scheme-2 is integrated with PDN(FOID) as the subservient controller, and the interrelated finest measure of gains in addition to related parameters is accomplished by employing the SHO. The premium values are furnished in Table 5. The assessment is performed for a step change in the WavePPt. With the finest values attained, the evaluation is accomplished for the impact of the WavePPt on the dynamic system by contrasting responses for the system with and without the WavePPt, as in Figure 8. In the outcomes in Figure 8, the vast decline in the values of Pk_U and S_Time is evidently noticeable. Even Pk_O shows slightly lessened values. With the WavePPt, the values of Δf2 have shown improvement in Pk_U and S_Time from 0.0038 to 0.00186 Hz (Pk_U) and 35.31 to 30.12 s (in comparison to the system without WavePPt), respectively. Similarly, for Δf3, the improvement is 0.0052 to 0.00287 Hz (Pk_U) and 23.53 to 21.96 s; for ΔPtie1–3, the improvement is 0.0039 to 0.00197 Hz and 21.04 to 20.22 s; and for ΔPtie2–3, the improvement is 0.00077 to 0.000381 Hz (Pk_O), 0.00052 to 0.00027 Hz (Pk_U), and 24.65 to 20.09 s. Thus, the presence of the WavePPt improved the dynamics of the scheme.

6.5. Evaluation of Influence of PV on Scheme Dynamics

From the previous analysis in Section 6.1, it can be concluded that the SHO-optimized PDN(FOID) provides with the best performance for system-1 over the I/PI/PIDN/FOPID controllers. Now, system-1 is involved with another RWS, namely, a photovoltaic (PV) unit in area-3, viewed as scheme-3. Then, scheme-3 is included with PDN(FOID) as the subordinate controller in all areas and its finest values of gains and the related parameters are accomplished via the SHO. The finest values are shown in Table 6. Employing the finest values, the evaluation is accomplished for the impact of the PV on a dynamic system by contrasting responses for the system with and without the PV unit, as in Figure 9. In the outcomes in Figure 9, the massive diminution in the values of Pk_O, Pk_U, and S_Time is undoubtedly noticeable. With PV, the values of Δf1 have shown improvement in Pk_O, Pk_U, and S_Time from 0.0007 to 0 Hz (Pk_O), 0.0112 to 0.00109 Hz (Pk_U), and 25.81 to 20.11 s (in comparison to the system without PV). Similarly, for Δf2, the improvement is 0.0038 to 0.00278 Hz (Pk_U) and 35.31 to 33.09 s; for Δf3, the improvement is 0.0052 to 0.00298 Hz and 23.53 to 22.54 s; and for ΔPtie2–3, the improvement is 0.00077 to 0.00011 Hz (Pk_O), 0.00052 to 0.000181 Hz (Pk_U), and 24.65 to 20.01 s. Thus, the presence of PV has improved the dynamics of the system.

6.6. Assessment of Impact of Both WavePPt and PV on Scheme Dynamics

In the above Section 6.4 and Section 6.5, it is observed that RWSs WavePPt and PV, respectively, have a noteworthy impact on the dynamics of the system when assessed individually. Now, system-1 is incorporated with both WavePPt and PV. WavePPt is associated with area-1 and PV in area-3. Thus, this system with both WavePP and PV is considered as system-4. In this case, the SHO-optimized PDN(FOID) controller is also used to analyze the impact of both WavePPt and PV together on the dynamics of the system. The premium standards of gains and related parameters of the PDN(FOID) controller are in Table 7. The dynamic responses for the system with and without both WavePPt and PV are contrasted in Figure 10. Critical assessment in Figure 10 reveals the better performance of the system with both WavePPt and PV with regard to the lessened values of Pk_O, Pk_U, and S_Time. With both WavePPt and PV, the values of Δf1 showed improvement in Pk_O, Pk_U, and S_Time from 0.0007 to 0.00001 Hz, 0.0112 to 0.0063 Hz, and 25.81 to 22.65 s (in comparison to the system without WavePPt and PV). Similarly, for Δf2, the improvement is 0.0038 to 0.00125 Hz (Pk_U) and 35.31 to 27.98 s; for ΔPtie1–2, the improvement is 0.0039 to 0.00178 Hz and 21.71 to 19.81 s; and for ΔPtie1–3, the improvement is 0.0039 to 0.00161 Hz and 21.04 to 20.01 s. Thus, the presence of both WavePPt and PV has a noteworthy impact on the system’s performance, so further analysis is carried out for both WavePPt and PV.

6.7. Evaluation of the Influence of CES through/without Duple Compensation on Scheme Changing Aspects

In order to stabilize the system energy storing device, CES is incorporated into the system. Initially, CES without duple compensation is integrated into system-4 in all areas. Hence, this is system-5. The best-obtained controller PDN(FOID) from previous sections is used here to assess the impact of the energy-storing device. In this case, the best values of gains and parameters PDN(FOID) obtained using SHO are marked down in Table 8. Next, system-4 is integrated with CES with duple compensation in all areas. This is considered as system-6. The gains and related parameters of the PDN(FOID) controller for the scheme through CES involving duple compensation are provided in Table 9. With the values obtained in Table 8 and Table 9, the dynamic responses are plotted and contrasted against the system response without having any forms of CES. This contrast is reflected in Figure 11. In Figure 11, it is observed that any form of CES has a better impact. However, if the responses for the system with/without CES with duple compensation are viewed, then they articulate the better performance of the system in existence with CES with duple compensation in terms of diminished Pk_U and S_Time. With CES, the values of Δf2 showed improvement in Pk_U and S_Time from 0.00125 to 0.0008 Hz and 27.98 to 21.82 s (in comparison to the system without energy storage). Similarly, for Δf3, the improvement is 0.00125 to 0.00078 Hz and 19.51 to 18.65 s; for ΔPtie1–2, the improvement is 0.00178 to 0.00145 Hz and 19.81 to 17.55 s; for ΔPtie1–3, the improvement is 0.00161 to 0.00143 Hz and 20.01 to 18.65 s. Next, with CES with duple compensation, the values of Δf2 showed improvement in Pk_U and S_Time from 0.0008 to 0.0006 Hz and 21.82 to 13.65 s (in comparison to the system with CES). Similarly, for Δf3, the improvement is 0.00078 to 0.00075 Hz and 18.65 to 13.75 s; for ΔPtie1–2, the improvement is 0.00145 to 0.00123 Hz and 18.65 to 16.61 s; for ΔPtie1-3, the improvement is 0.00143 to 0.00132 Hz and 18.65 to 16.58 s. So, CES with duple compensation will serve better in damping out oscillations and stabilizing the system when there are any fluctuations in demand.

6.8. Sensitivity Determination When Subjected to Random Disturbance

The exploration of sensitivity is executed to perceive the heftiness of SHO-augmented PDN(FOID) controller gains traced at the basic event to comprehensive variance in the structure state of the thermal–bio-diesel–WavePPt in area-1, thermal–GPP in area-2, and thermal–Ss (GT)–PV in area-3 schemes along with CES with duple compensation. Here, the inspected scheme is stated with a random pattern of disturbance from a basic 1% step load disturbance. The augmented gains of the PDN(FOID) controller reflected in Table 10 are attained by retaining the SHO. The dynamic outcomes for the finest values analogous to the foundation and diverse outcomes are distinguished in Figure 12. In Figure 12a–d, it is indicated that all responses obtained with optimized values for the proposed controller (from Table 9) are stable for random load disturbance. Evaluation affirms that the outcomes are moderately identical, which claims that there are no circumstances for the added retuning of the finest values for modification.

7. Conclusions

An innovative endeavor was placed to put into effect a two-stage controller through the amalgamation of a proportional-derivative with filter (PDN) (InO) and integral-derivative (FOID) (FrO) in AGC. A lately established biologically influenced meta-heuristic algorithm articulated as the spotted hyena optimizer (SHO) was proficiently employed for attaining gains and additional related parameters of diverse controllers. The superiority of PDN(FOID) was realized over additional classical controllers for the thermal–bio-diesel–geothermal power plant (GPP)–split-shaft gas turbine (Ss (GT)) system. The assessment shows that when the basic system was incorporated with either the wave power plant (WavePPt) or photovoltaic (PV) unit, the system responses improved in terms of lessened peak_overshoot, peak_undershoot, and settling_time using the PDN(FOID) controller. Much better responses were obtained when the system was involved with both the WavePPt and PV. Analysis also revealed the better performance of capacitive energy storage (CES) with duple compensation over the system with CES without duple compensation and systems without any form of CES. The robustness of the PDN(FOID) controller was undertaken by examining the system (having WavePPt, PV, and CES with duple compensation) when subjected to a random load of disturbance. It demonstrated that the finest values attained, considering PDN(FOID) gains and additional related constraints, were satisfactory and sufficient, and there were not, by any means, alterations under random load.

Author Contributions

Conceptualization, A.S. and P.D.; methodology, N.R.B.; software, T.C.; validation, A.S., P.D. and N.R.B.; formal analysis, N.R.B.; investigation, A.S.; resources, T.C. and B.V.; data curation, T.C.; writing—original draft preparation, A.S.; writing—review and editing, A.S., T.C., B.V. and Ł.K.; visualization, P.D.; supervision, N.R.B.; adaptation of optimization procedure, Ł.K. All authors have read and agreed to the published version of the manuscript.

Funding

Optimization procedure research was partially supported by the Poznan University of Technology, grant number (0212/SBAD/0568).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

fBalance point valuation of frequency measured in Hertz (Hz).
*Best aggregate suggested by exponent.
kCount of areas suggested.
BkPortion of frequency bias of areas engaged.
TkjPortion of synchronization.
TTotal moment of simulation measured in seconds.
fkModification of frequency of areas engaged.
∆PDkDegree of load modification of areas engaged.
HkDegree of inertia constant of areas engaged.
DkDegree of load modification of areas engaged (p.u. MW)/Modification of frequency of areas engaged (Hz).
RkFactor related to governor’s speed regulation of area suggested.
βkAttributions of frequency outcome of area suggested.
KpkGain constant of power system representation.
TpkTime constant of power system prototypes.
PrkConsiderable rated power of area suggested.
akjConsiderable rated power of area-k/Considerable rated power of area-j
pfArea contribution factor.
Tg, Tt, TrTime constants of thermal generating parts in seconds (s).
KrReheater’s gain.

Appendix A

  • Basic Power System: f = 60 Hz; Primary loading = 50%, Kpm = 120 Hz/p.u. MW, Tpm = 20 s, Tm = 0.086 s, Hm = 5 s; Dm = 0.00833 p.u. MW/Hz; βm = 0.425 p.u. MW/Hz; Rm = 2.4 Hz/p.u MW
  • Thermal: Trm = 10 s, Krm = 5, Ttm = 0.3 s, Tgm = 0.08 s;
  • Bio-diesel: Kvr = 1, Tvr = 0.05 s, Kce = 1, Tce = 0.5 s;
  • Ss(GT): Lmax = 1, T3 = 3 s, T1 = T2 = 1.5 s, KT = 1, FOVmax = 1, FOVmin = −0.02, Dtur = 0 p.u;
  • CES: KCES = 0.3, TCES = 0.0352 s;
  • CES with duple compensation: KCES (duple compensation) = 0.3, TCES (duple compensation) = 0.046 s, T1 = 0.280, T2 = 0.025, T3 = 0.0411, T4 = 0.39;
  • PV: A = 900, B = −18, C = 100, D = 50.

References

  1. Elgerd, O.I. Electric Energy Systems Theory: An Introduction; McGraw-Hill: New Delhi, India, 2007. [Google Scholar]
  2. Kundur, P. Power System Stability and Control; McGraw-Hill: New Delhi, India, 1993. [Google Scholar]
  3. Ibraheem Kumar, P.; Kothari, D.P. Recent philosophies of automatic generation control strategies in power systems. IEEE Trans. Power Syst. 2005, 20, 346–357. [Google Scholar] [CrossRef]
  4. Das, D.; Aditya, S.K.; Kothari, D.P. Dynamics of diesel and wind turbine generators on an isolated power system. Electr. Power Energy Syst. 1999, 21, 183–189. [Google Scholar] [CrossRef]
  5. Das, D.C.; Roy, A.K.; Sinha, N. GA based frequency controller for solar thermal–diesel–wind hybrid energy generation/energy storage system. Int. J. Electr. Power Energy Syst. 2012, 43, 262–279. [Google Scholar] [CrossRef]
  6. Ismayil, C.; Sreerama, K.R.; Sindhu, T.K. Automatic generation control of single area thermal power system with fractional order PID (PIλDμ) controllers. In Proceedings of the 3rd International Conference on Advances in Control and Optimization of Dynamical Systems, Kanpur, India, 13–15 March 2014; pp. 552–557. [Google Scholar]
  7. Elgerd, O.I.; Fosha, C.E. Optimum Megawatt-Frequency Control of Multiarea Electric Energy Systems. IEEE Trans. Power Appar. Syst. 1970, 89, 556–563. [Google Scholar] [CrossRef]
  8. Bhatt, P.; Roy, R.; Ghoshal, S.P. GA/particle swarm intelligence based optimization of two specific varieties of controller devices applied to two-area multi-units automatic generation control. Int. J. Electr. Power Energy Syst. 2010, 32, 299–310. [Google Scholar] [CrossRef]
  9. Nanda, J.; Saikia, L.C. Comparison of performances of several types of classical controller in automatic generation control for an interconnected multi-area thermal system. In Proceedings of the Power Engineering Conference, 2008. AUPEC ‘08. Australasian Universities, Sydney, Australia, 14–17 December 2008. [Google Scholar]
  10. Nanda, J.; Mishra, S.; Saikia, L.C. Maiden application of bacterial foraging based optimization technique in multi area automatic generation control. IEEE Trans. Power Syst. 2009, 24, 602–609. [Google Scholar] [CrossRef]
  11. Golpira, H.; Bevrani, H.; Golpira, H. Application of GA optimization for automatic generation control design in an interconnected power system. Energy Convers. Manag. 2011, 52, 2247–2255. [Google Scholar] [CrossRef]
  12. Dhamanda, A.; Dutt, A.; Bhardwaj, A.K. Automatic Generation Control in Four Area Interconnected Power System of Thermal Generating Unit through Evolutionary Technique. Int. J. Electr. Eng. Inform. 2015, 7, 569–583. [Google Scholar]
  13. Saikia, L.C.; Nanda, J.; Mishra, S. Performance comparison of several classical controllers in AGC for multi-area interconnected thermal system. Int. J. Electr. Power Energy Syst. 2011, 33, 394–401. [Google Scholar] [CrossRef]
  14. Nanda, J.; Mangla, A.; Suri, S. Some new findings on automatic generation control of an interconnected hydrothermal system with conventional controllers. IEEE Trans. Energy Convers. 2006, 21, 187–194. [Google Scholar] [CrossRef]
  15. Saikia, L.C.; Chowdhury, A.; Shakya, N.; Shukla, S.; Soni, P.K. AGC of a multi area thermal system using firefly optimized IDF controller. In Proceedings of the 2013 Annual IEEE India Conference (INDICON), Mumbai, India, 13–15 December 2013. [Google Scholar]
  16. Pradhan, P.C.; Sahu, R.K.; Panda, S. Firefly algorithm optimized fuzzy PID controller for AGC of multi-area multi-source power systems with UPFC and SMES. Eng. Sci. Technol. Int. J. 2016, 19, 338–354. [Google Scholar] [CrossRef] [Green Version]
  17. Saha, A.; Saikia, L.C. Renewable energy source-based multiarea AGC system with integration of EV utilizing cascade controller considering time delay. Int. Trans. Electr. Energy Syst. 2019, 29, e2646. [Google Scholar] [CrossRef]
  18. Arya, Y. AGC of PV-thermal and hydro-thermal energy systems using CES and a new multistage FPIDF-(1+PI) controller. Renew. Energy 2019, 134, 796–806. [Google Scholar] [CrossRef]
  19. Tasnin, W.; Saikia, L.C. Performance comparison of several energy storage devices in deregulated AGC of a multi-area system incorporating geothermal power plant. IET Renew. Power Gener. 2018, 12, 761–772. [Google Scholar]
  20. Barik, A.K.; Das, D.C. Expeditious frequency control of solar photobiotic/biogas/biodiesel generator based isolated renewable microgrid using Grasshopper Optimisation Algorithm. IET Renew. Power Gener. 2018, 12, 1659–1667. [Google Scholar]
  21. Hasanien, M.H. Whale optimisation algorithm for automatic generation control of interconnected modern power systems including renewable energy sources. IET Gener. Transm. Distrib. 2018, 12, 607–614. [Google Scholar]
  22. Dhundhara, S.; Verma, Y.P. Capacitive energy storage with optimized controller for frequency regulation in realistic multisource deregulated power system. Energy 2018, 147, 1108–1128. [Google Scholar]
  23. Pathak, N.; Verma, A.; Bhatti, T.S.; Nasiruddin, I. Modeling of HVDC tie-links and their utilization in AGC/LFC operations of multi-area power systems. IEEE Trans. Ind. Electron. 2019, 66, 2185–2197. [Google Scholar] [CrossRef]
  24. Kumari, N.; Malik, N.; Jha, A.N.; Mallesham, G. Design of PI Controller for Automatic Generation Control of Multi Area Interconnected Power System using Bacterial Foraging Optimization. Int. J. Eng. Technol. 2016, 8, 2779–2786. [Google Scholar] [CrossRef]
  25. Jagatheesan, K.; Anand, B.; Samanta, S.; Dey, N.; Ashour, A.S.; Balas, V.E. Design of a proportional-integral-derivative controller for an automatic generation control of multi-area power thermal systems using firefly algorithm. IEEE/CAA J. Autom. Sin. 2019, 6, 503–515. [Google Scholar]
  26. Dash, P.; Saikia, L.C.; Sinha, N. Comparison of performances of several FACTS devices using Cuckoo search algorithm optimized 2DOF controllers in multi-area AGC. Electr. Power Energy Syst. 2015, 65, 316–324. [Google Scholar] [CrossRef]
  27. Rahman, A.; Saikia, L.C.; Sinha, N. AGC of dish-stirling solar thermal integrated thermal system with biogeography based optimised three degree of freedom PID controller. IET Renew. Power Gener. 2016, 10, 1161–1170. [Google Scholar] [CrossRef]
  28. Reddy, P.J.; Kumar, T.A. AGC of three-area hydro-thermal system in deregulated environment using FOPI and IPFC. In Proceedings of the 2017 International Conference on Energy, Communication, Data Analytics and Soft Computing (ICECDS), Chennai, Indian, 1–2 August 2017; pp. 2815–2821. [Google Scholar] [CrossRef]
  29. Pan, I.; Das, S. Fractional order AGC for distributed energy resources using robust optimization. IEEE Trans. Smart Grid 2016, 7, 2175–2186. [Google Scholar] [CrossRef]
  30. Dash, P.; Saikia, L.C.; Sinha, N. Automatic generation control of multi area thermal system using Bat algorithm optimized PD–PID cascade controller. Int. J. Electr. Power Energy Syst. 2015, 68, 364–372. [Google Scholar] [CrossRef]
  31. Saha, A.; Saikia, L.C. Utilisation of ultra-capacitor in load frequency control under restructured STPP-thermal power systems using WOA optimised PIDN-FOPD controller. IET Gener. Transm. Distrib. 2017, 11, 3318–3331. [Google Scholar] [CrossRef]
  32. Sahu, R.K.; Panda, S.; Rout, U.K.; Sahoo, D.K. Teaching learning based optimization algorithm for automatic generation control of power system using 2-DOF PID controller. Int. J. Elect. Power Energy Syst. 2016, 77, 287–301. [Google Scholar] [CrossRef]
  33. Haroun, A.H.G.; Li, Y.-Y. A novel optimized hybrid fuzzy logic intelligent PID controller for an interconnected multi-area power system with physical constraints and boiler dynamics. ISA Trans. 2017, 71, 364–379. [Google Scholar] [CrossRef]
  34. Padhan, S.; Sahu, R.K.; Panda, S. Application of firefly algorithm for load frequency control of multi-area interconnected power system. Electr. Power Compon. Syst. 2014, 42, 1419–1430. [Google Scholar] [CrossRef]
  35. Sharma, Y.; Saikia, L.C. Automatic generation control of a multi-area ST—thermal power system using Grey Wolf Optimizer algorithm based classical controllers. Electr. Power Energy Syst. 2015, 73, 853–862. [Google Scholar] [CrossRef]
  36. Kumar, N.; Kumar, V.; Tyagi, B. Multi area AGC scheme using imperialist competition algorithm in restructured power system. Appl. Soft Comput. 2016, 48, 160–168. [Google Scholar] [CrossRef]
  37. Dash, P.; Saikia, L.C.; Sinha, N. Flower pollination algorithm optimized PI-PD cascade controller in automatic generation control of a multi-area power system. Int. J. Electr. Power Energy Syst. 2016, 82, 19–28. [Google Scholar] [CrossRef]
  38. Khan, M.H.; Ulasyar, A.; Khattak, A.; Zad, H.S.; Alsharef, M.; Alahmadi, A.A.; Ullah, N. Optimal Sizing and Allocation of Distributed Generation in the Radial Power Distribution System Using Honey Badger Algorithm. Energies 2022, 15, 5891. [Google Scholar] [CrossRef]
  39. Sun, S.; Zhang, Q.; Sun, J.; Cai, W.; Zhou, Z.; Yang, Z.; Wang, Z. Lead–Acid Battery SOC Prediction Using Improved AdaBoost Algorithm. Energies 2022, 15, 5842. [Google Scholar] [CrossRef]
  40. Zhu, L.; He, J.; He, L.; Huang, W.; Wang, Y.; Liu, Z. Optimal Operation Strategy of PV-Charging-Hydrogenation Composite Energy Station Considering Demand Response. Energies 2022, 15, 5915. [Google Scholar] [CrossRef]
  41. Dhiman, G.; Kumar, V. Spotted hyena optimizer: A novel bio-inspired based metaheuristic technique for engineering applications. Adv. Eng. Softw. 2017, 114, 48–70. [Google Scholar] [CrossRef]
  42. Chiranjeevi, T.; Biswas, R.K. Discrete-Time Fractional Optimal Control. Mathematics 2017, 5, 25. [Google Scholar] [CrossRef]
  43. Chiranjeevi, T.; Biswas, R.K. Closed-Form Solution of Optimal Control Problem of a Fractional Order System. J. King Saud Univ. –Sci. 2019, 31, 1042–1047. [Google Scholar] [CrossRef]
  44. Chiranjeevi, T.; Biswas, R.K.; Devarapalli, R.; Babu, N.R.; Marquez, P.G. On optimal control problem subject to fractional order discrete time singular systems. Arch. Control. Sci. 2021, 31, 849–863. [Google Scholar]
  45. Oustaloup, A.; Mathieu, B.; Lanusse, P. The CRONE Control of Resonant Plants: Application to a Flexible Transmission. Eur. J. Control. 1995, 1, 113–121. [Google Scholar] [CrossRef]
  46. Knypiński, Ł.; Kuroczycki, S.; Márquez, F.P.G. Minimization of Torque Ripple in the Brushless DC Motor Using Constrained Cuckoo Search Algorithm. Electronics 2021, 10, 2299. [Google Scholar]
  47. Devarapalli, R.; Kumar Sinh, N.; Bathinavenkateswara, R.; Knypiński, Ł.; Jaya Naga, N.; Marquez, F.P.G. Allocation of real power generation based on computing over all generation cost: An approach of Salp Swarm Algorithm. Arch. Electr. Eng. 2021, 70, 337–349. [Google Scholar] [CrossRef]
Figure 1. Schematic representation of the entire work.
Figure 1. Schematic representation of the entire work.
Energies 15 06959 g001
Figure 2. The representation and Tfn model of an unequal three-area system with thermal–biodiesel–WavePPt in area-1, thermal–GPP in area-2, and thermal–Ss (GT)–PV in area-3: (a) Schematic diagram of six different systems in a step-by-step method, (b) Tfn model of the ultimate system.
Figure 2. The representation and Tfn model of an unequal three-area system with thermal–biodiesel–WavePPt in area-1, thermal–GPP in area-2, and thermal–Ss (GT)–PV in area-3: (a) Schematic diagram of six different systems in a step-by-step method, (b) Tfn model of the ultimate system.
Energies 15 06959 g002aEnergies 15 06959 g002b
Figure 3. Layout of the proposed controller (PDN(FOID)).
Figure 3. Layout of the proposed controller (PDN(FOID)).
Energies 15 06959 g003
Figure 4. Flowchart of the SHO algorithm.
Figure 4. Flowchart of the SHO algorithm.
Energies 15 06959 g004
Figure 5. Evaluation of outcomes of subordinate controllers for scheme-1 for 1% step load disorder contrast time: (a) Anomaly of frequency of area-1, (b) Anomaly of frequency of area-2, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Figure 5. Evaluation of outcomes of subordinate controllers for scheme-1 for 1% step load disorder contrast time: (a) Anomaly of frequency of area-1, (b) Anomaly of frequency of area-2, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Energies 15 06959 g005
Figure 6. Evaluation for the recommendation of the Pi amongst IAE, ITAE, ITSE, and ISE for employing PDN(FOID) controller in the case of scheme-1 contrast time: (a) Anomaly of frequency of area-1, (b) Anomaly of frequency of area-2, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Convergence curve for the system with different Pi.
Figure 6. Evaluation for the recommendation of the Pi amongst IAE, ITAE, ITSE, and ISE for employing PDN(FOID) controller in the case of scheme-1 contrast time: (a) Anomaly of frequency of area-1, (b) Anomaly of frequency of area-2, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Convergence curve for the system with different Pi.
Energies 15 06959 g006aEnergies 15 06959 g006b
Figure 7. Evaluation for the recommendation of algorithm amid FA/CS/PSO/WOA/SHO techniques for obtaining finest values of PDN(FOID) controller for scheme-1 contrast time: (a) Anomaly of frequency in area-2, (b) Anomaly of Tie-line power interlinking area-1 and area-2, (c) Anomaly of Tie-line power interlinking area-1 and area-3, (d) Convergence curve.
Figure 7. Evaluation for the recommendation of algorithm amid FA/CS/PSO/WOA/SHO techniques for obtaining finest values of PDN(FOID) controller for scheme-1 contrast time: (a) Anomaly of frequency in area-2, (b) Anomaly of Tie-line power interlinking area-1 and area-2, (c) Anomaly of Tie-line power interlinking area-1 and area-3, (d) Convergence curve.
Energies 15 06959 g007
Figure 8. Evaluation of the influence of WavePPt on system changing aspects employing SHO-optimized PDN(FOID) controller in view of 1% step load disturbances for system-2 contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-3, (c) Anomaly of Tie-line power interlinking area-1 and area-3, (d) Anomaly of Tie-line power interlinking area-2 and area-3.
Figure 8. Evaluation of the influence of WavePPt on system changing aspects employing SHO-optimized PDN(FOID) controller in view of 1% step load disturbances for system-2 contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-3, (c) Anomaly of Tie-line power interlinking area-1 and area-3, (d) Anomaly of Tie-line power interlinking area-2 and area-3.
Energies 15 06959 g008aEnergies 15 06959 g008b
Figure 9. Valuation of influence of PV on system changing aspects employing SHO-optimized PDN(FOID) controller given 1% step load disturbances for system-3 contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-2, (c) Anomaly of frequency in area-3, (d) Anomaly of Tie-line power interlinking area-2 and area-3.
Figure 9. Valuation of influence of PV on system changing aspects employing SHO-optimized PDN(FOID) controller given 1% step load disturbances for system-3 contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-2, (c) Anomaly of frequency in area-3, (d) Anomaly of Tie-line power interlinking area-2 and area-3.
Energies 15 06959 g009
Figure 10. Assessment of the impact of both WavePPt for system-4 contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-2 vs. time, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Figure 10. Assessment of the impact of both WavePPt for system-4 contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-2 vs. time, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Energies 15 06959 g010
Figure 11. Valuation of influence of CES with/without duple compensation on scheme dynamics employing SHO-optimized PDN(FOID) controller taking into account 1% step load disturbances for system-5 and system-6 individually contrast time: (a) Anomaly of frequency in area-2, (b) Anomaly of frequency in area-3, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Figure 11. Valuation of influence of CES with/without duple compensation on scheme dynamics employing SHO-optimized PDN(FOID) controller taking into account 1% step load disturbances for system-5 and system-6 individually contrast time: (a) Anomaly of frequency in area-2, (b) Anomaly of frequency in area-3, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Energies 15 06959 g011aEnergies 15 06959 g011b
Figure 12. Evaluation of system-6 outcomes employing SHO-optimized PDN(FOID) controller after exposure to random load disturbance contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-3, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Figure 12. Evaluation of system-6 outcomes employing SHO-optimized PDN(FOID) controller after exposure to random load disturbance contrast time: (a) Anomaly of frequency in area-1, (b) Anomaly of frequency in area-3, (c) Anomaly of Tie-line power interlinking area-1 and area-2, (d) Anomaly of Tie-line power interlinking area-1 and area-3.
Energies 15 06959 g012aEnergies 15 06959 g012b
Table 1. Finest values of gains and related parameters of subordinate controllers for scheme-1.
Table 1. Finest values of gains and related parameters of subordinate controllers for scheme-1.
Name of ControllersCorresponding Gains and Correlated ParametersArea-1Area-2Area-3
IKIi *0.98850.98970.9876
PIKPi *0.35650.55330.5538
KIi *0.47450.64970.7584
PIDNKPi *0.69750.97280.9739
KIi *0.59820.98360.9878
KDi *0.63150.31400.3041
Ni *10.7711.4111.25
FOPIDKFPi *0.00940.00950.0096
KFIi *0.37650.83540.9379
λi1.43521.18761.1587
KFDi *0.45490.63570.5366
μi *1.04770.07680.1585
PDN(FOID)KPi *0.86860.51880.6875
KDi *0.57960.73620.9421
Ni *55.5868.8379.77
KFIi *0.99760.90410.7454
λi *1.00990.94540.9710
KFDi *0.85080.82610.8554
μi *0.78530.28040.7216
* Signify the optimum values.
Table 2. Peak anomaly and duration of settling for outcomes in Figure 5 in the case of system-1 employing SHO-optimized I/PI/PIDN/FOPID/PDN(FOID) controllers.
Table 2. Peak anomaly and duration of settling for outcomes in Figure 5 in the case of system-1 employing SHO-optimized I/PI/PIDN/FOPID/PDN(FOID) controllers.
ResponsesName of ControllersPk_OPk_US_Time (in Seconds)
Δf1 (Figure 5a)I0.01030.019139.42
PI0.00920.018635.53
PIDN0.00510.015631.42
FOPID0.00450.011327.84
PDN(FOID)0.00070.011225.81
Δf2 (Figure 5b)I0.00210.004843.52
PI0.00080.005142.23
PIDN0.00010.004539.63
FOPID0.00060.004139.97
PDN(FOID)00.003835.31
ΔPtie1–2 (Figure 5c)I0.00010.005939.45
PI00.005739.41
PIDN00.004434.24
FOPID0.00080.004133.87
PDN(FOID)00.003921.71
ΔPtie1–3 (Figure 5d)I0.00020.006242.23
PI00.005834.88
PIDN00.004434.24
FOPID0.00110.004137.02
PDN(FOID)00.003921.04
Table 3. Peak anomaly and duration of settling for outcomes in Figure 6a–c in the case of scheme-1 employing SHO-optimized PDN(FOID) controller for diverse performance indices.
Table 3. Peak anomaly and duration of settling for outcomes in Figure 6a–c in the case of scheme-1 employing SHO-optimized PDN(FOID) controller for diverse performance indices.
ResponsesName of
Performance Indices
Pk_OPk_US_Time (in Seconds)
Δf1 (Figure 6a)IAE0.00210.014229.57
ITAE0.00270.014527.16
ITSE0.00190.014626.65
ISE0.00070.011225.81
Δf2 (Figure 6b)IAE0.00190.014436.37
ITAE0.00280.014737.72
ITSE0.00200.014636.01
ISE00.003835.31
ΔPtie1–2 (Figure 6c)IAE0.00130.004544.73
ITAE0.00130.004642.74
ITSE0.00010.004750.24
ISE00.003921.71
Table 4. Peak aberration and duration of settling for outcomes in Figure 7a–c, in the case of system-1 using FA/CS/PSO/WOA/SHO-optimized PDN(FOID) controller on an individual basis.
Table 4. Peak aberration and duration of settling for outcomes in Figure 7a–c, in the case of system-1 using FA/CS/PSO/WOA/SHO-optimized PDN(FOID) controller on an individual basis.
ResponsesName of AlgorithmsPk_OPk_US_Time (in Seconds)
Δf1 (Figure 7a)FA0.00260.0120132.95
CS0.00290.011333.79
PSO0.00180.001333.04
WOA0.00210.011829.19
SHO0.00070.011225.81
Δf3 (Figure 7b)FA0.00110.005336.03
CS0.00130.005330.06
PSO0.00080.005338.04
WOA0.00090.005526.84
SHO00.005223.53
ΔPtie1–3 (Figure 7c)FA0.00120.004133.76
CS0.00100.004136.09
PSO0.00110.004037.15
WOA0.00060.004130.23
SHO00.003921.04
Table 5. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-2.
Table 5. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-2.
Name of ControllerCorresponding Gains and Correlated ParametersArea-1Area-2Area-3
PDN(FOID)KPi *0.98980.96870.9603
KDi *0.97850.42520.9232
Ni *72.2456.0778.85
KFIi *0.57250.55750.8418
λi *1.04840.39971.0965
KFDi *0.96320.33260.6901
μi *0.59110.75090.8949
* Signify optimum values.
Table 6. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-3.
Table 6. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-3.
Name of ControllerCorresponding
Gains and Correlated Parameters
Area-1Area-2Area-3
PDN(FOID)KPi *0.98980.63240.7416
KDi *0.79920.49000.4163
Ni *44.4265.9444.87
KFIi *0.77520.48820.6698
λi *1.03050.62130.5595
KFDi *0.80850.83410.7768
μi *0.65450.66400.7541
* Signify optimum values.
Table 7. Best values of gains and related parameters of PDN(FOID) controllers for scheme-4 (thermal–bio-diesel–GPP-Ss (GT) system including both WavePPt, PV).
Table 7. Best values of gains and related parameters of PDN(FOID) controllers for scheme-4 (thermal–bio-diesel–GPP-Ss (GT) system including both WavePPt, PV).
Name of ControllerCorresponding Gains and Correlated ParametersArea-1Area-2Area-3
PDN(FOID)KPi *0.98990.85100.6775
KDi *0.59570.46200.4404
Ni *39.0850.1342.96
KFIi *0.46070.85220.5740
λi *1.09160.95880.7276
KFDi *0.93790.83740.9869
μi *0.99470.73150.7899
* Signify optimum values.
Table 8. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-5 (thermal–bio-diesel–GPP-Ss (GT) system including WavePPt, PV, and CES without duple compensation).
Table 8. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-5 (thermal–bio-diesel–GPP-Ss (GT) system including WavePPt, PV, and CES without duple compensation).
Name of ControllerCorresponding Gains and Correlated ParametersArea-1Area-2Area-3
PDN(FOID)KPi *0.98970.97690.2093
KDi *0.66810.51510.8276
Ni *74.9063.3793.11
KFIi *0.59530.93680.5812
λi *1.08141.20860.9863
KFDi *0.84340.98930.7160
μi *0.56780.00270.6173
* Signify optimum values.
Table 9. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-6 (thermal–bio-diesel–GPP-Ss (GT) system including WavePPt, PV, and CES with duple compensation) (* Signify optimum values).
Table 9. Finest values of gains and related parameters of PDN(FOID) controllers for scheme-6 (thermal–bio-diesel–GPP-Ss (GT) system including WavePPt, PV, and CES with duple compensation) (* Signify optimum values).
Name of ControllerCorresponding
Gains and Correlated Parameters
Area-1Area-2Area-3
PDN(FOID)KPi *0.98990.92880.1632
KDi *0.97850.45330.4110
Ni *44.1954.5543.39
KFIi *0.89000.95290.4464
λi *1.09140.00950.1938
KFDi *0.96320.96300.7367
μi *0.79890.79190.8705
Table 10. Finest values of gains and correlated parameters of PDN(FOID) controllers for scheme-6 when conditional to a random pattern of disturbance.
Table 10. Finest values of gains and correlated parameters of PDN(FOID) controllers for scheme-6 when conditional to a random pattern of disturbance.
Name of ControllerCorresponding
Gains and Correlated Parameters
Area-1Area-2Area-3
PDN(FOID)KPi *0.80950.89650.2588
KDi *0.89210.51450.5147
Ni *48.3662.3651.36
KFIi *0.84780.91470.5147
λi *1.05490.00890.2147
KFDi *0.89560.88990.8144
μi *0.68970.75140.8566
* Signify optimum values.
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Saha, A.; Dash, P.; Babu, N.R.; Chiranjeevi, T.; Venkateswararao, B.; Knypiński, Ł. Impact of Spotted Hyena Optimized Cascade Controller in Load Frequency Control of Wave-Solar-Double Compensated Capacitive Energy Storage Based Interconnected Power System. Energies 2022, 15, 6959. https://doi.org/10.3390/en15196959

AMA Style

Saha A, Dash P, Babu NR, Chiranjeevi T, Venkateswararao B, Knypiński Ł. Impact of Spotted Hyena Optimized Cascade Controller in Load Frequency Control of Wave-Solar-Double Compensated Capacitive Energy Storage Based Interconnected Power System. Energies. 2022; 15(19):6959. https://doi.org/10.3390/en15196959

Chicago/Turabian Style

Saha, Arindita, Puja Dash, Naladi Ram Babu, Tirumalasetty Chiranjeevi, Bathina Venkateswararao, and Łukasz Knypiński. 2022. "Impact of Spotted Hyena Optimized Cascade Controller in Load Frequency Control of Wave-Solar-Double Compensated Capacitive Energy Storage Based Interconnected Power System" Energies 15, no. 19: 6959. https://doi.org/10.3390/en15196959

APA Style

Saha, A., Dash, P., Babu, N. R., Chiranjeevi, T., Venkateswararao, B., & Knypiński, Ł. (2022). Impact of Spotted Hyena Optimized Cascade Controller in Load Frequency Control of Wave-Solar-Double Compensated Capacitive Energy Storage Based Interconnected Power System. Energies, 15(19), 6959. https://doi.org/10.3390/en15196959

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop