Article

Study on Winter Comfort Temperature in Mixed Mode and HVAC Office Buildings in Japan

1
Graduate School of Environmental and Information Studies, Tokyo City University, 3-3-1 Ushikubo-nishi, Tsuzuki-ku, Yokohama 224-8551, Japan
2
Department of Restoration Ecology and Built Environment, Tokyo City University, 3-3-1 Ushikubo-nishi, Tsuzuki-ku, Yokohama 224-8551, Japan
3
Graduate School of Environmental Studies, Nagoya University, Furo-cho, Chikusa-ku, Nagoya 464-8603, Japan
4
Osaka Institute of Technology, Department of Architecture, 5-16-1 Omiya, Asahi-ku, Osaka 535-8585, Japan
5
Department of Architecture, Mukogawa Women’s University, 1-13 Tozaki-cho, Nishinomiya 663-8121, Japan
6
Graduate School of Engineering, Nagasaki University, 1-14 Bunkyo-machi, Nagasaki 852-8521, Japan
7
Graduate School of Humanities and Social Sciences, Hiroshima University, Hiroshima 739-8524, Japan
8
Department of Architecture, Faculty of Environmental and Urban Engineering, Kansai University, 3-3-35 Yamate-cho, Osaka 564-8680, Japan
9
Faculty of Engineering, Department of Architecture, Shinshu University, 4-17-1 Wakasato, Nagano 380-8553, Japan
10
Graduate School of Advanced Science and Engineering, Hiroshima University, Hiroshima 739-8527, Japan
11
Department of Architecture and Environment Systems, Akita Prefectural University, 84-4 Tsuchiya, Akita 015-0055, Japan
12
Graduate School of Engineering, Hokkaido University, Kita 13 Nishi 8, Kita-ku, Sapporo 060-8628, Japan
*
Author to whom correspondence should be addressed.
Energies 2022, 15(19), 7331; https://doi.org/10.3390/en15197331
Submission received: 19 August 2022 / Revised: 26 September 2022 / Accepted: 28 September 2022 / Published: 6 October 2022
(This article belongs to the Special Issue Thermal Comfort and Energy Use in Buildings)

Abstract

:
Comfort temperature is important to investigate because the chosen office indoor temperatures affect the energy used in a building, and a thermally comfortable environment makes the occupants be more productive. The effects of temperature on comfort are broadly recognized for thermal comfort. Japanese office buildings are well equipped with air-conditioning systems to improve the thermal comfort of the occupants. The main objectives of this research were to compare the winter comfort temperature in mixed mode (MM) and heating, ventilation and air-conditioning (HVAC) office buildings and to investigate the relationship between the comfort temperature and the indoor air temperature. This study measured the thermal environmental conditions of the office buildings and surveyed the thermal comfort of the occupants. The field survey was conducted during winter in seven office buildings located in the Aichi prefecture of Japan. In total, 4466 subjective votes were collected from 46 occupants. The result suggested that the occupants were found to be more satisfied with the thermal environment of MM buildings than that of HVAC office buildings. Overall, 95% of comfort temperatures were in the range 22~28 °C in MM and HVAC buildings, which were higher than the indoor temperature of 20 °C recommended by the Japanese government. The comfort temperature was highly correlated to the indoor air temperature of the MM buildings than to that of HVAC buildings. This indicated that the occupants were more adapted towards the given thermal environment of MM buildings.

1. Introduction

1.1. Overview

Today, people spend most of their time in an indoor environment. According to the survey conducted by the University of Maryland in early nineties, people spend 87% of their time inside buildings [1]. The occupants expect a level of thermal comfort that ensures comfort as well as wellbeing. Due to this reason, it is necessary that the conditions inside these office buildings remain thermally comfortable. Even gentle fluctuations in the indoor environment can cause discomfort, which may lead to a sudden change in the behavior or the activity of the occupants [2]. Temperature drifts with ±1 K of the customary temperature would attract little notice; ±2 K could cause mild discomfort among a small proportion of the occupants [3]. The adaptive principle states that “if change occurs so as to produce discomfort, occupants react in ways which tend to restore their comfort” [2]. Office workers use a variety of “adaptive opportunities” to regulate their indoor thermal environment and secure their thermal comfort [4]. It is important to adjust the indoor environment of the office with natural ventilation by opening the windows even when the air-conditioning (AC) is being used because many HVAC systems recycle the air from room to room increasing the risk of pathogens indoor [5,6,7,8] and in consideration of energy saving. Field surveys especially in naturally ventilated (NV), mixed mode (MM) and heating, ventilation, and air conditioning (HVAC) buildings around the world consider the comfort temperature. Indoor thermal environments can significantly influence human health and comfort as well as the energy consumption in the buildings.
The adaptive thermal comfort model is established around the world as ASHRAE standard 55 [9] and for European countries as European Standard EN 15251 [10]. The ASHRAE standard has accumulated a thermal comfort database for the naturally ventilated office buildings by defining an indoor thermal environment from field studies from across the world in different seasons [11], whereas the CEN standard [10] has accumulated a thermal comfort database from 26 office buildings from five European countries [12]. The major aim of these models is to define thermal comfort [3]. However, these standards do not include data from Japanese office buildings. This has overshadowed the understanding of the comfort temperature for Japanese office buildings. Japanese office buildings are well equipped with AC systems for maintaining indoor thermal comfort. Japanese government introduced the “Warm Biz” programs in the year 2005, where occupants were free to wear flexible clothing in winter, which recommend an indoor temperature of 20 °C for heating to ensure energy saving [13]. However, this value was not based on a field survey and lacked supporting evidence from a large database. Moreover, the adjustment of the indoor temperature by changing the clothing level may not give any assurance on whether the occupants are able to achieve the target of improving thermal comfort and reducing energy consumption [14], because any discomfort acquired by the occupants leads to behavioral changes to make themselves comfortable [15].

1.2. Previous Studies in Japanese Office Buildings

Comfort temperatures are important to investigate because the chosen office indoor temperatures affect the energy consumption in the building, and people in thermally comfortable environment are generally more productive. Based on field surveys, the comfort temperatures in Japanese offices was investigated by several researchers as shown in Table 1 [14,16,17,18,19,20,21,22]. The comfort temperature was found to be 25.0 °C, 25.4 °C and 24.3 °C for free-running mode (FR), cooling mode (CL) and heating mode (HT), respectively in the Kanto area of Japan [21]. Khadka et al. [22] found that the mean comfort temperature was 24.8 °C for MM and 25.0 °C for FR in Japanese office buildings. Tanabe et al. [23] found the comfort temperature was below 27 °C. These research works were mostly focused on the summer season or year-round and did not analyze the comfort temperature in detail for the winter season in MM and HVAC office buildings due to insufficient data or data collected for short periods of time. Shahzad and Rijal [24] found that MM offices had a higher level of occupants’ comfort and satisfaction, while they also had the potential for low-energy use. Thus, it is necessary to pay attention to understanding the comfort temperature in the winter season in these buildings.

1.3. Objectives

The main objectives of this research were to compare the comfort temperature in MM and HVAC buildings in winter and to investigate the relationship between the comfort temperature and the indoor air temperature. The findings could be used to create guidelines and standards for cold climatic conditions facilitating the design of MM and HVAC buildings in the future. This understanding can also help to decrease the temperature setting for heating of existing buildings during the winter season to realize energy savings in the buildings.

2. Methodology

The field study focused on the environmental conditions of office buildings, the occupants’ characteristics, thermal measurements and subjective questionnaires of thermal comfort. Figure 1 shows the flowchart of this study. We created this flowchart by referring to previous studies [25,26]. The data collection, data entry and data analysis are explained in the flowchart. We used the same research methodology for the Kanto region of Japan [15,21].

2.1. Study Area and Investigated Buildings

The study area was located in the Aichi prefecture of Japan (Figure 2). The location features a humid subtropical climate (Köppen climate classification: Cfa), which is characterized by hot and humid summer and cool winter. Figure 3 indicates the monthly mean outdoor air temperature and relative humidity of Nagoya’s meteorological station. The chosen office buildings were 4.8 to 22 km away from the Nagoya meteorological station. Moreover, the microclimatic conditions of the investigated buildings were similar to those at the meteorological station. The average annual temperature in Nagoya reaches 15.5 °C. The temperatures are highest on average in August, at around 27.8 °C, and lowest in January, at around 4.1 °C, as shown in Figure 3. The average relative humidity varies from 60 to 77% in different months of the year.
The field survey was conducted in seven office buildings which were further classified as five MM and two HVAC office buildings located in the Aichi prefecture from December 2021 to February 2022. The MM buildings were selected if they had operable windows for thermal adjustment. The HVAC buildings with fixed windows were also selected to compare with MM buildings. The five investigated office buildings were of change-over mixed-mode type defined as having operable door/windows and HVAC systems depending on the seasons or time of the day [29]. Two HVAC office buildings used heating or cooling throughout the year. Figure 4 shows the general overview of the seven investigated office buildings.

2.2. Thermal Measurements

The indoor environmental variables were measured by using instruments as shown in Table 2. The environmental variables were air temperature and relative humidity, measured by a digital instrument sensor, which was placed 1.1 m above the floor level, away from direct sunlight at ten-minute interval. In seven office buildings, 12 instruments were installed (Table 3). The survey method was the same as the survey conducted in the Kanto region of Japan [15].

2.3. Thermal Comfort Survey

The questionnaire sheets were distributed to the office workers of each office where the purpose of the survey and how to fill out the questionnaire were explained briefly. Moreover, the N6 and N7 office buildings carried out the survey through an excel sheet on a PC. The longitudinal survey was conducted each day by the occupants while digital instruments were installed at the office buildings for that period of time. The thermal comfort survey was conducted with 46 occupants: 28 males and 18 females (Table 3). Generally, the occupants voted 4 times a day: 2 times in the morning and 2 times in the afternoon. The survey was conducted in Japanese.
Table 4 shows the scale used for the thermal sensation vote. The full questionnaire sheet is shown in Appendix A. Each state of heating use, cooling use and window opening was recorded in binary form during the survey (0 = heating/cooling off or window closed, 1 = heating/cooling on or window open). We collected 4466 votes from seven office buildings (MM = 3364 votes and HVAC= 1102 votes).

2.4. Calculation of Comfort Temperature

2.4.1. Regression Method

Regression analysis is the most common method used to examine the trend of the mean response over the range of temperatures encountered [3,30]. The relationship that links thermal sensation and the indoor air temperature can be expressed as a linear equation that predicts thermal sensation from the indoor air temperature.
TSV = a Ti + b
where TSV is the thermal sensation vote, a is the gradient of the line (regression coefficient), Ti is the independent variable (indoor air temperature in this case) and b is the intercept on the vertical axis.

2.4.2. Griffiths’ Method

Based on the occupants’ votes of thermal sensation and the corresponding values of measured indoor air temperature, we estimated the comfort temperature by using the following Griffiths’ equation [31,32]:
Tc = Ti + (4 − TSV)/a
where Tc is the comfort temperature (°C) and a is Griffiths’ constant (=0.50).
The previous studies [21] show that when using each Griffiths’ constant (0.25, 0.33 and 0.50), there was hardly any differences in the results obtained for the mean comfort temperature. Therefore, we used a Griffiths’ constant of 0.50 to estimate the comfort temperature, similar to other studies [15,32]. The comfort temperature calculated using a coefficient 0.50 is a representation of a 2 °C rise for a unit change in thermal sensation vote.

3. Results and Discussion

The data were divided into MM and HVAC for the analysis. The data of MM buildings were further categorized as free-running mode (FR), and heating mode (HT). During FR, the office buildings do not make any use of mechanical heating or cooling, and in HT, the office buildings use heating systems such as air-conditioning and heater to keep a warm indoor environment. All the data were analyzed by SPSS version 19.

3.1. Distribution of the Outdoor and Indoor Air Temperatures during the Voting

To know the investigated conditions during the voting, indoor and outdoor air temperature were analyzed. The thermal condition of MM and HVAC buildings might be different, and thus we analyzed them separately. We also needed to clarify how these buildings behaved for a given outdoor air temperature.
The mean outdoor air temperature was 7.3 °C and 7.8 °C for MM and HVAC office buildings, respectively. Figure 5 shows the distribution of the indoor air temperature. The mean indoor air temperature during the voting was 24.5 °C and 24.3 °C for MM and HVAC office buildings, respectively. The standard deviation of indoor air temperatures in MM buildings was higher than that of HVAC buildings. The result also showed that the occupants were mostly maintaining the indoor air temperature at a range of 23–27 °C in MM condition whereas it was 24–26 °C in the HVAC condition in response to the low outdoor air temperature, which was similar to that of Shahzad and Rijal [24]. The results suggest that the mean indoor air temperature of the office buildings was significantly higher than that of the value recommended by Japanese government: 20 °C.
Figure 6 shows the relation between indoor and outdoor air temperatures with a 95% band of data points. With the increase in outdoor air temperature, indoor air temperature is also increasing. The reason might be that the occupants opened the windows and introduced fresh air directly through them in MM buildings, and outdoor fresh air was introduced by the air conditioning system in HVAC buildings. The heating temperature setting may also have been different in these buildings for a given outdoor air temperature. The range of indoor air temperatures was small compared to that of outdoor air temperatures in both MM and HVAC buildings. We found the following regression equations from the regression analysis.
MM Ti = 0.13 Tout + 23.6 (N = 2909, R2 = 0.08, S.E. = 0.008, p < 0.001)
HVAC Ti = 0.16 Tout + 23.0 (N = 889, R2 = 0.28, S.E. = 0.008, p < 0.001)
Overall Ti = 0.13 Tout + 23.5 (N = 3798, R2 = 0.10, S.E. = 0.007, p < 0.001)
Tout: outdoor air temperature (°C), N: number of the sample, R2: coefficient of determination, S.E.: standard error of the regression coefficient and p: significant level of regression coefficient.
The coefficient of determination in MM buildings was lower than that of HVAC buildings. The reason might be that the indoor air temperature distribution was wide in MM buildings as occupants were opening the windows during the heating cycle to minimize the risk of COVID-19. The indoor air temperature band of MM (±3 °C) was wider than HVAC (±2 °C) buildings. Arens et al. [33] found that it required more energy to maintain a narrow indoor temperature range than a wider range. MM buildings had 6.2% (= 209/3364 × 100) of votes from the FR mode, which did not use any energy to control the indoor thermal environment. These suggest that the MM buildings might be effective for energy saving. Due to the heating use in MM and HVAC buildings, the regression coefficient or correlation coefficient was significantly low. It was weak, but the indoor air temperature was significantly correlated to the outdoor air temperature. The equations can be used to estimate the indoor air temperature of similar office buildings. For example, if the outdoor air temperature was 10 °C, the indoor air temperature would be 24.9 °C in MM buildings and 24.6 °C in HVAC buildings.

3.2. Distribution of Thermal Sensation Vote

In the previous section, we analyzed the indoor and outdoor air temperatures. In this section, we evaluate the thermal response of the office workers for a given thermal environmental condition. The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) defines thermal comfort as “the condition of the mind in which satisfaction is expressed with the thermal environment” [9]. A subjective evaluation is required to understand the actual thermal comfort of occupants in office buildings.
Figure 7 shows the distribution of thermal sensation votes in MM and HVAC buildings. The mean thermal sensation vote for MM and HVAC buildings was obtained as 3.8 and 3.7, respectively. The occupants mostly voted “4. Neutral”, which accounted for 72% and 70% of the votes in MM and HVAC buildings. Generally, thermal sensation votes “3. Slightly cold”, “4. Neutral” and “5. Slightly hot” are considered as the thermal comfort zone and it accounted for 99% and 91% of votes for MM and HVAC buildings respectively. The results showed that the occupants were highly satisfied with the office thermal environment, but the thermal satisfaction level of MM was higher than that the HVAC buildings. However, about 4% of votes in MM and 5% of votes of HVAC buildings were “5. Slightly hot” in winter, and thus energy could be saved by reducing the temperature settings in the offices.

3.3. Comfort Temperature

Comfort temperature is defined as the temperature judged by a population to be neutral on the ASHRAE scale, or comfortable on the Bedford scale: this is usually assumed to be the desired temperature [3]. It is considered as one of the key variables to understand the thermal comfort of office workers. It is used as the standard to adjust the indoor thermal environment and to give satisfactory thermal comfort to the occupants. Humphreys [34] found that the comfort temperature varied according to the region and seasons. Later, de Dear and Brager [11] also confirmed this finding from a field survey. In this section, we want to clarify and establish the winter comfort temperature in MM and HVAC office buildings.

3.3.1. Regression Method

In this section, we analyzed the comfort temperature by a regression method similar to other studies [35,36,37,38]. The linear regression analysis of the thermal sensation votes (TSVs) and indoor air temperature for the raw and binned data was conducted as shown in Figure 8. The thermal sensation was positively correlated with the indoor air temperature. The indoor air temperature data were binned at 1 °C intervals according to the building, by applying a weighted linear regression which was similar to that of other studies [15,39]. The regression line indicated that the thermal sensation votes of HVAC buildings were more related to the indoor air temperature. We obtained the following regression equations.
MM Raw TSV = 0.11 Ti + 1.2 (N = 2909, R2 = 0.10, S.E. = 0.006, p < 0.001)
Binned TSV = 0.11 Ti + 1.2 (N = 2909, R2 = 0.57, S.E. = 0.002, p < 0.001)
HVAC Raw TSV = 0.29 Ti − 3.3 (N = 889, R2 = 0.17, S.E. = 0.022, p < 0.001)
Binned TSV = 0.26 Ti − 2.6 (N = 889, R2 = 0.88, S.E. = 0.003, p < 0.001)
Overall Raw TSV = 0.13 Ti + 0.6 (N = 3798, R2 = 0.11, S.E. = 0.006, p < 0.001)
Binned TSV = 0.13 Ti + 0.7 (N = 3798, R2 = 0.58, S.E. = 0.002, p < 0.001)
The equations of raw data were almost similar to those of the binned data. However, the coefficient of determination of the binned data was much higher than that of the raw data. The slopes for the raw data of MM and HVAC buildings and overall were 0.11/°C, 0.29/°C and 0.13/°C, which indicated that for every 9.1 °C, 3.4 °C and 7.7 °C, respectively, of change in indoor air temperature, the thermal sensation vote had a unit change. The slope of MM buildings was especially unreliable. These trends were similar in previous studies conducted in different areas as shown in Table 5. In a climate chamber study, Fanger [40] found a regression coefficient of 0.33 where the temperature change required to shift a unit thermal sensation vote (Treq) would be 3 °C (= 1/0.33). According to Nicol et al. [41], a regression coefficient of 0.25 was often obtained in a field survey, and thus up to 4 °C of temperature required to change one thermal sensation vote might be reasonable. The field survey conducted in Japanese dwellings [42] and Nepalese dwellings [43] also obtained a low slope which was similar to this study. Kumar et al. [38] stated that the lower slope was an indication of the higher adaptation of the occupants to the indoor environment. The low slope of this study might be due to the presence of an adaptive behavior and hence it can be misleading when used to estimate the comfort temperature by a regression method as found in previous studies [42,44]. We thus estimated the comfort temperature by Griffiths’ method in the next section.

3.3.2. Griffiths’ Method

The comfort temperature was estimated by Griffiths’ method [31,32,38]. This method can be used to estimate comfort temperature with any single vote in the seven-point scale of thermal sensation given the assumption of equidistance in points. It is considered as useful when a linear regression is not reliable to estimate the comfort temperature.
Figure 9 shows the distributions of the comfort temperature. The mean comfort temperature was 25.0 °C and 24.8 °C in MM and HVAC buildings. Overall, 95% of the comfort temperatures were in the range of 21.8~28.2 °C in MM and 21.8~27.8 °C in HVAC buildings. The result showed that the mean or range of comfort temperatures was comparable to that of the indoor air temperatures during the survey as shown in the Figure 5. Again, the comfort temperature of this study was significantly higher than the recommended temperature of 20 °C for the “Warm Biz” condition for both MM and HVAC buildings. Generally, a reduction of 1 °C in indoor temperature could save 10% of heating energy in winter [3]. Rijal et al. [45] also confirmed from the literature review that the heating energy could be saved by lowering the temperature setting for heating.
Figure 10 shows the mean comfort temperature by gender. The mean comfort temperatures in MM and HVAC buildings were quite similar but in the case of HVAC buildings, the females’ comfort temperature was 1.4 °C higher than that of the males. The reason might be that the indoor air temperature in HVAC buildings was lower than that of MM buildings and females wore short skirts, and thus they may have felt colder than males. Fanger [40] concluded that there was no significant difference in comfort temperature between males and females, but our study showed opposite results. Humphreys et al. [30] found that the females were somewhat more sensitive than males to temperature. Rijal et al. [44] found that the comfort temperature for males and females was very similar (the greatest difference was in the month of November: 0.6 °C) in Japanese dwellings. The result indicated that there may be gender difference in the comfort temperature.
We compared the comfort temperatures in this study with that of previous studies which used the regression and Griffiths’ methods as shown in Table 6. For this study, the mean comfort temperature observed was similar to that of the studies that were conducted in Kanto (Japan) and India, whereas the comfort temperature was found to be lower than that of Bangladesh, and higher than that of China, Columbia, Australia, the USA and Canada. The results indicated that the comfort temperature might be different depending on the various climatic conditions.

3.4. Relationship between the Comfort Temperature and Indoor Air Temperature

Humphreys [53] found that if the occupants had adapted to their indoor temperature, the optimum temperature for comfort should be highly correlated with the mean temperature they had experienced. HVAC buildings were highly controlled by using heating systems in winter, which resulted in a narrow range of indoor air temperature differences. In this section, we analyzed how the comfort temperature of MM and HVAC buildings related to the indoor air temperature, as in other studies [15,48,54,55].
A regression analysis was used to examine the relationship between comfort temperature and indoor air temperature for raw and binned data as shown in Figure 11. The data were binned at 1 °C intervals of indoor air temperatures according to the buildings, by applying a weighted linear regression similar to other studies [15,39]. When the indoor air temperature was low, the comfort temperature was slightly high, and when the indoor air temperature was high, the comfort temperature was slightly low in the raw and binned data. However, the MM buildings showed a higher correlation as the regression line was close to the diagonal line drawn (Tc = Ti) than that of HVAC buildings. We found the following regression equations.
MM Raw Tc = 0.79 Ti + 5.7 (N = 2909, R2 = 0.60, S.E. = 0.012, p < 0.001)
Binned Tc = 0.76 Ti + 6.4 (N = 2909, R2 = 0.94, S.E. = 0.004, p < 0.001)
HVAC Raw Tc = 0.42 Ti + 14.6 (N = 889, R2 = 0.09, S.E. = 0.44, p < 0.001)
Binned Tc = 0.40 Ti + 15.2 (N = 889, R2 = 0.87, S.E. = 0.005, p < 0.001)
Overall Raw Tc = 0.74 Ti + 6.9 (N = 3798, R2 = 0.49, S.E. = 0.012, p < 0.001)
Binned Tc = 0.71 Ti + 7.6 (N = 3798, R2 = 0.91, S.E. = 0.004, p < 0.001)
The coefficient of determination of the binned data was much higher than that of the raw data, which indicated a strong correlation between the indoor air temperature and comfort temperature. It is interesting to note that the slope of both raw and binned data was almost similar. The regression coefficient and the correlation coefficient of MM buildings were much higher than those of HVAC buildings. People became more adapted to the indoor temperatures they experienced in MM buildings, while at the same time they adjusted the indoor temperature to make themselves comfortable, which was similar to the results of Rijal et al. [21]. As shown in Table 7, we found similar trends to the previous studies. If we know the indoor temperature, we can estimate the comfort temperature of similar office buildings. For example, if the indoor air temperature was 24 °C, the comfort temperature would be 24.7 °C in MM and HVAC buildings for the raw data.

4. Discussion

The current study of a daily field survey in winter investigated the comfort temperature in five MM and two HVAC office buildings of the Aichi prefecture. In this study, a comparison of the thermal sensation and comfort temperature was shown between MM and HVAC office buildings. The subjective evaluation of the thermal comfort of the occupants was satisfactory in both MM and HVAC offices. While considering the comfort zone of the seven-point scale, 99% of votes in MM and 91% in HVAC buildings were in that range, which showed that the MM was more resilient than HVAC in terms of thermal comfort.
The comfort temperature estimated using a regression method indicated that it was not a suitable method as the slope of the equation obtained was small. The slope of this study was similar to that of previous studies [21,35,36,37,38]. Therefore, Griffiths’ method was adapted to estimate the comfort temperature. The comfort temperatures obtained by Griffiths’ method for MM and HVAC buildings were 25.0 °C and 24.8 °C, respectively. However, the value obtained for the comfort temperature was found to be 4~5 °C higher than the Japanese government’s recommendation. In such a case, if the indoor air temperature could be lowered gradually, then it might be possible that the occupant would be able to adapt to the lower indoor temperature, which would eventually contribute to energy savings.
A regression analysis between the indoor air temperature and the comfort temperature was conducted. The raw data were validated by binning the data and it was found that the coefficient of determination of the binned data was higher in comparison to the raw data. Thus, a strong correlation between the indoor air temperature and the comfort temperature was obtained, similar to previous studies [15,39]. However, the slope of the raw and binned data was almost similar. The regression coefficient and correlation coefficient of MM office buildings were higher than those of HVAC office buildings. This showed that the occupants became more adapted to the indoor temperature they experienced in the MM buildings.

5. Conclusions

We conducted a daily field survey on winter comfort temperature in five MM and two HVAC office buildings in the Aichi prefecture of Japan. We found the following results:
  • The proportion of neutral thermal sensation was 72% and 70% in MM and HVAC buildings. The percentage of the votes in the comfort zone was 99% and 91% in MM and HVAC buildings. Thus, the occupants were highly satisfied with their office environment, but they were more satisfied in MM buildings.
  • Overall, 95% of the comfort temperatures were in the range of 21.8~28.2 °C in MM and 21.8~27.8 °C in HVAC buildings, which were higher than the recommended value (20 °C) of the Japanese government for the winter. If we reduced the temperature setting similar to the recommended value, a significant amount of heating energy could be saved.
  • The comfort temperature and indoor air temperature were highly correlated in MM buildings. The result indicated that the occupants adapted more to the given thermal environment of MM buildings than that of HVAC buildings.
In conclusion, this research indicated that the occupants were satisfied with the indoor thermal environment of the investigated office buildings. Although the Japanese government recommends an indoor temperature of 20 °C for heating, the mean comfort temperature was found to be 5.0 °C and 4.8 °C higher in MM and HVAC buildings, respectively. If the indoor air temperature could be lowered gradually, then occupant would be able to adapt to the low indoor temperature as well, because the comfort temperature was correlated with the indoor air temperature. A low indoor temperature setting would be helpful to realize the recommended temperature of the Japanese government, which would be effective for saving energy.
In this research, only the indoor air temperature was considered to estimate the comfort temperature, whereas the results from considering globe temperatures might be slightly different. Since the analysis was for the winter season, it is necessary to clarify the results from the other seasons to know the seasonal differences in comfort temperature [15,56]. A detailed analysis of various modes should be conducted. As the field survey was a daily survey, the individual and gender differences in comfort temperature need to be analyzed. The comfort temperature was estimated considering the indoor air temperature; it should be analyzed with the outdoor temperature to propose an adaptive model. It is necessary to analyze the behavioral adaptation of the occupants such as clothing adjustments, window opening and fan use, to understand the adaptive mechanism of the occupants.

Author Contributions

Data entry and writing—original draft preparation S.K.; data collection, paper review, corrections and supervision H.B.R.; data collection K.A.; data collection and review T.S.; review H.I., T.U., K.G., H.T., K.T., T.N., D.N., K.H. and T.M. All authors have read and agreed to the published version of the manuscript.

Funding

This research is supported by the Grant-in-Aid for Scientific Research (B) (21H01496) of Japan Society for the Promotion of Science (JSPS).

Data Availability Statement

Not applicable.

Acknowledgments

We would like to sincerely thank the Itsuwa Denki Kogyo Co., Ltd., Kimura Kohki Co., Ltd., SEEDS Co., Ltd., Shinwa Electric Co., Ltd., Yasui Architects & Engineers, Inc. and local governments for their kind cooperation.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

CfaHumid-subtropical
ETEffective temperature (°C)
pSignificant level of regression coefficient
R2Coefficient of determination
TaAir temperature (°C)
TcComfort temperature (°C)
TgGlobe temperature (°C)
TiIndoor air temperature (°C)
TopOperative temperature (°C)
ToutOutdoor air temperature (°C)
TreqTemperature change required to shift one thermal sensation vote (°C)
ACAir Conditioning
ASHRAEThe American Society of Heating, Refrigerating and Air-Conditioning Engineers
CENComité Européen de Normalisation
CLCooling mode
FRFree-running mode
HTHeating mode
HVACHeating, ventilation, and air conditioning
MMMixed-mode
NVNaturally ventilated buildings
PCPersonal computer
S.D.Standard deviation
S.E.Standard error
SPSSStatistical package for the social sciences
TSVThermal sensation votes

Appendix A

Figure A1. The questionnaire sheet for the thermal comfort survey.
Figure A1. The questionnaire sheet for the thermal comfort survey.
Energies 15 07331 g0a1

References

  1. Roberts, T. We Spend 90% of Our Time Indoors. Says Who? Available online: https://www.buildinggreen.com/blog/we-spend-90-our-time-indoors-says-who. (accessed on 10 August 2022).
  2. Humphreys, M.A.; Nicol, J.F. Understanding the adaptive approach to thermal comfort. ASHRAE Trans. 1998, 104, 991–1004. [Google Scholar]
  3. Nicol, J.F.; Humphreys, M.A.; Roaf, S. Adaptive Thermal Comfort: Principles and Practice; Earthscan: London, UK, 2012. [Google Scholar]
  4. Rijal, H.B.; Humphreys, M.A.; Nicol, J.F. Behavioural Adaptation for the Thermal Comfort and Energy Saving in Japanese Offices. J. Inst. Eng. 2019, 15, 14–25. [Google Scholar] [CrossRef]
  5. Hayashi, M.; Yanagi, U.; Azuma, K.; Kagi, N.; Ogata, M.; Morimoto, S.; Hayama, H.; Mori, T.; Kikuta, K.; Tanabe, S.; et al. Measures against COVID-19 concerning Summer Indoor Environment in Japan. Jpn. Arch. Rev. 2020, 3, 423–434. [Google Scholar] [CrossRef]
  6. SHASE (The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan); AIJ (Architectural Institute of Japan). Role of Ventilation in the Control of COVID-19 Infection: Emergency Presidential Discourse. 2020. Available online: https://www.aij.or.jp/jpn/databox/2020/20200323_Eng_final.pdf (accessed on 16 August 2022).
  7. Kurabuchi, T.; Yanagi, U.; Ogata, M.; Otsuka, M.; Kagi, N.; Yamamoto, Y.; Hayashi, M.; Tanabe, S. Operation of air-conditioning and sanitary equipment for SARS-CoV-2 infectious disease control. Jpn. Arch. Rev. 2021, 4, 608–620. [Google Scholar] [CrossRef]
  8. Roaf, S. Chapter 19 Trust, windows and the psychology of resilience. In The Routledge Handbook of Resilient Thermal Comfort; Nicol, J.F., Rijal, H.B., Roaf, S., Eds.; Routledge: London, UK, 2022; pp. 551–581. ISBN 9781032155975. [Google Scholar]
  9. ASHRAE Standard 55; Thermal Environmental Conditions for Human Occupancy. ANSI/ASHRAE: Atlanta, GA, USA, 2013.
  10. Standard EN 15251-2007; Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics. European Committee for Standardization (CEN): Brussels, Belgium, 2007.
  11. de Dear, R.J.; Brager, G.S. Towards an adaptive model of thermal comfort and preference. ASHRAE Trans. 1998, 104, 145–167. [Google Scholar]
  12. McCartney, K.J.; Nicol, J.F. Developing an adaptive control algorithm for Europe. Energy Build. 2002, 34, 623–635. [Google Scholar] [CrossRef]
  13. Enomoto, H.; Ikeda, K.; Azuma, K.; Tochihara, Y. Observation of the thermal conditions of the workers in the ‘cool biz’ implemented office. J. Occup. Saf. Health Jpn. 2009, 2, 5–10. [Google Scholar] [CrossRef]
  14. Takasu, M.; Ooka, R.; Rijal, H.B.; Indraganti, M.; Kumar, M.S. Study on adaptive thermal comfort in Japanese offices under various operation modes. Build. Environ. 2017, 118, 273–288. [Google Scholar] [CrossRef]
  15. Rijal, H.B.; Humphreys, M.A.; Nicol, J.F. Adaptive approaches to enhancing resilient thermal comfort in Japanese offices. In The Routledge Handbook of Resilient Thermal Comfort; Nicol, J.F., Rijal, H.B., Roaf, S., Eds.; Routledge: London, UK, 2022; Chapter 17; pp. 279–299. ISBN 9781032155975. [Google Scholar]
  16. Nakano, J.; Tanabe, S.-I.; Kimura, K.-I. Differences in perception of indoor environment between Japanese and non-Japanese workers. Energy Build. 2002, 34, 615–621. [Google Scholar] [CrossRef]
  17. Tanabe, S.; Iwahashi, Y.; Tsushima, S.; Nishihara, N. Thermal comfort and productivity in offices under mandatory electricity savings after the Great East Japan earthquake. Arch. Sci. Rev. 2013, 56, 4–13. [Google Scholar] [CrossRef]
  18. Indraganti, M.; Ooka, R.; Rijal, H.B. Thermal comfort in offices in summer: Findings from a field study under the ‘setsuden’ conditions in Tokyo, Japan. Build. Environ. 2013, 61, 114–132. [Google Scholar] [CrossRef]
  19. Mustapa, M.S.; Zaki, S.A.; Rijal, H.B.; Hagishima, A.; Ali, M.S. Thermal comfort and occupant adaptive behaviour in Japanese university buildings with free running and cooling mode offices during summer. Build. Environ. 2016, 105, 332–342. [Google Scholar] [CrossRef]
  20. Damiati, S.A.; Zaki, S.A.; Rijal, H.B.; Wonorahardjo, S. Field study on adaptive thermal comfort in office buildings in Malaysia, Indonesia, Singapore, and Japan during hot and humid season. Build. Environ. 2016, 109, 208–223. [Google Scholar] [CrossRef]
  21. Rijal, H.B.; Humphreys, M.A.; Nicol, J.F. Towards an adaptive model for thermal comfort in Japanese offices. Build. Res. Inf. 2017, 45, 717–729. [Google Scholar] [CrossRef]
  22. Khadka, S.; Shrestha, M.; Rijal, H.B. Investigation of the thermal comfort and productivity in Japanese mixed-mode office buildings. J. Eng. Res. 2022, 19, 63–72. [Google Scholar] [CrossRef]
  23. Tanabe, S.; Nishihara, N.; Haneda, M. Indoor temperature, productivity, and fatigue in office tasks. HVAC R Res. 2007, 13, 623–633. [Google Scholar] [CrossRef]
  24. Shahzad, S.; Rijal, H.B. Chapter 20 Mixed mode is better than air-conditioned offices for resilient comfort. In The Routledge Handbook of Resilient Thermal Comfort; Nicol, J.F., Rijal, H.B., Roaf, S., Eds.; Routledge: London, UK, 2022; pp. 329–346. ISBN 9781032155975. [Google Scholar]
  25. Ozarisoy, B.; Altan, H. A novel methodological framework for the optimisation of post-war social housing developments in the south-eastern Mediterranean climate: Policy design and life-cycle cost impact analysis of retrofitting strategies. Sol. Energy 2021, 225, 517–560. [Google Scholar] [CrossRef]
  26. Imagawa, H.; Rijal, H.B.; Shukuya, M. Development of integrated occupant-behavioural stochastic model including the fan use in Japanese dwellings. Energy Build. 2020, 226, 110326. [Google Scholar] [CrossRef]
  27. Wada, K. Correlation of ‘Google Flu Trends’ with sentinel surveillance data for influenza in 2009 in Japan. Open Public Health J. 2011, 4, 17–20. [Google Scholar] [CrossRef] [Green Version]
  28. Japan Meteorological Agency. 2022. Available online: https://www.jma.go.jp/jma/indexe.html. (accessed on 19 August 2022).
  29. CBE. Mixed Mode. 2021. Available online: https://cbe.berkeley.edu/mixedmode/index.html. (accessed on 19 August 2022).
  30. Humphreys, M.A.; Nicol, J.F.; Roaf, S. Adaptive Thermal Comfort: Foundations and Analysis; Routledge: London, UK, 2016. [Google Scholar]
  31. Griffiths, I.D. Thermal comfort in buildings with passive solar features: Field studies. In Report to the Commission of the European Communities (EN3S-090); University of Surrey: Guildford, UK, 1990. [Google Scholar]
  32. Humphreys, M.A.; Rijal, H.B.; Nicol, J.F. Updating the adaptive relation between climate and comfort indoors; New insights and an extended database. Build. Environ. 2013, 63, 40–55. [Google Scholar] [CrossRef]
  33. Arens, E.; Humphreys, M.A.; de Dear, R.; Zhang, H. Are ‘class A’ temperature requirements realistic or desirable? Build. Environ. 2010, 45, 4–10. [Google Scholar] [CrossRef] [Green Version]
  34. Humphreys, M.A. Outdoor temperatures and comfort indoors. Build. Res. Pract. 1978, 6, 92–105. [Google Scholar] [CrossRef]
  35. Karyono, T.H. Report on thermal comfort and building energy studies in Jakarta, Indonesia. Build. Environ. 2000, 35, 77–90. [Google Scholar] [CrossRef]
  36. Indraganti, M.; Ooka, R.; Rijal, H.B.; Brager, G.S. Adaptive model of thermal comfort for offices in hot and humid climate of India. Build. Environ. 2014, 74, 39–53. [Google Scholar] [CrossRef]
  37. Rupp, R.F.; Toftum, J.; Ghisi, E. Chapter 18 Thermal comfort and occupant disposition in mixed-mode offices in a Brazilian subtropical climate. In The Routledge Handbook of Resilient Thermal Comfort; Nicol, J.F., Rijal, H.B., Roaf, S., Eds.; Routledge: London, UK, 2022; pp. 279–299. ISBN 9781032155975. [Google Scholar]
  38. Kumar, S.; Singh, M.K.; Loftness, V.; Mathur, J.; Mathur, S. Thermal comfort assessment and characteristics of occupant’s behavior in naturally ventilated buildings in composite climate of India. Energy Sustain. Dev. 2016, 33, 108–121. [Google Scholar] [CrossRef] [Green Version]
  39. Gautam, B.; Rijal, H.B.; Shukuya, M.; Imadegawa, H. A field investigation on the wintry thermal comfort and clothing adjustment of residents in traditional Nepalese houses. J. Build. Eng. 2019, 26, 100886. [Google Scholar] [CrossRef]
  40. Fanger, P.O. Thermal Comfort: Analysis and Applications in Environmental Engineering; Danish Technical Press: Copenhagen, Denmark, 1970. [Google Scholar]
  41. Nicol, J.F.; Jamy, G.N.; Sykes, O.; Humphreys, M.A.; Roaf, S.; Hancock, M. A Survey of Thermal Comfort in Pakistan Toward New Indoor Temperature Standards; Oxford Brookes University: Oxford, UK, 1994. [Google Scholar]
  42. Rijal, H.B.; Honjo, M.; Kobayashi, R.; Nakaya, T. Investigation of comfort temperature, adaptive model and the window-opening behaviour in Japanese houses. Archit. Sci. Rev. 2013, 56, 54–69. [Google Scholar] [CrossRef]
  43. Rijal, H.B. Thermal adaptation of buildings and people for energy saving in extreme cold climate of Nepal. Energy Build. 2021, 230, 110551. [Google Scholar] [CrossRef]
  44. Rijal, H.B.; Humphreys, M.A.; Nicol, J.F. Adaptive model and the adaptive mechanisms for thermal comfort in Japanese dwellings. Energy Build. 2019, 202, 109371. [Google Scholar] [CrossRef]
  45. Rijal, H.B.; Yoshida, K.; Humphreys, M.A.; Nicol, J.F. Development of an adaptive thermal comfort model for energy-saving building design in Japan. Archit. Sci. Rev. 2021, 64, 109–122. [Google Scholar] [CrossRef]
  46. Kumar, S.; Singh, M.K.; Mathur, A.; Kosir, M. Occupant’s thermal comfort expectations in naturally ventilated engineering workshop building: A case study at high metabolic rates. Energy Build. 2020, 217, 109970. [Google Scholar] [CrossRef]
  47. Hossain, M.; Robin, W.; Benson, L.; Brian, F. Thermal comfort guidelines for production spaces within multi-storey garment factories located in Bangladesh. Build. Environ. 2019, 157, 319–345. [Google Scholar] [CrossRef]
  48. Cao, B.; Zhu, Y.; Ouyang, Q.; Zhau, X. Field study of human thermal comfort and thermal adaptability during summer and winter in Beijing. Energy Build. 2011, 43, 1051–1056. [Google Scholar] [CrossRef]
  49. García, A.; Olivieri, F.; Larrumbide, E.; Ávila, P. Thermal comfort assessment in naturally ventilated offices located in a cold tropical climate, Bogotá. Build. Environ. 2019, 158, 237–247. [Google Scholar] [CrossRef]
  50. Ballantyne, E.; Hill, R.; Spencer, J. Probit analysis of thermal sensation assessments. Int. J. Biometeorol. 1977, 21, 29–43. [Google Scholar] [CrossRef] [PubMed]
  51. Schiller, G.; Arens, E.; Bauman, F.; Benton, C.; Fountain, M.; Doherty, T. A field study of thermal environments and comfort in office buildings. ASHRAE Trans. 1988, 94, 280–308. [Google Scholar]
  52. Donnini, G.; Nguyen, V.H.; Lai, D.H.C.; LaFlamme, M.; Haghighat, F.; Molina, J.; Lai, H.K.; Martello, C.; Chang, C.Y. Field Study of Occupant Comfort and Office Thermal Environments in a Cold Climate. United States. 1997. Available online: https://www.aivc.org/sites/default/files/airbase_10531.pdf (accessed on 6 August 2022).
  53. Humphreys, M.A. Field studies of thermal comfort compared and applied. Build. Serv. Eng. 1976, 44, 5–27. [Google Scholar]
  54. Kuchen, E.; Fisch, M.N. Spot Monitoring: Thermal comfort evaluation in 25 office buildings in winter. Build. Environ. 2009, 44, 839–847. [Google Scholar] [CrossRef]
  55. Nicol, J.F.; Raja, I.A.; Allaudin, A.; Jamy, G.N. Climatic variations in comfortable temperatures: The Pakistan projects. Energy Build. 1999, 30, 261–279. [Google Scholar] [CrossRef]
  56. Ozarisoy, B.; Altan, H. Regression forecasting of ‘neutral’ adaptive thermal comfort: A field study investigation in the south-eastern Mediterranean climate of Cyprus. Build. Environ. 2021, 202, 108013. [Google Scholar] [CrossRef]
Figure 1. Flowchart of this study.
Figure 1. Flowchart of this study.
Energies 15 07331 g001
Figure 2. Location of the investigated office buildings [27].
Figure 2. Location of the investigated office buildings [27].
Energies 15 07331 g002
Figure 3. Monthly mean outdoor air temperature and relative humidity in Nagoya (Japan Meteorological Agency [28]).
Figure 3. Monthly mean outdoor air temperature and relative humidity in Nagoya (Japan Meteorological Agency [28]).
Energies 15 07331 g003
Figure 4. Overview of the investigated office buildings (N1~N7).
Figure 4. Overview of the investigated office buildings (N1~N7).
Energies 15 07331 g004
Figure 5. Distribution of indoor air temperature in MM and HVAC.
Figure 5. Distribution of indoor air temperature in MM and HVAC.
Energies 15 07331 g005
Figure 6. Relationship between the indoor and outdoor air temperatures with a 95% band of data point.
Figure 6. Relationship between the indoor and outdoor air temperatures with a 95% band of data point.
Energies 15 07331 g006
Figure 7. Distribution of thermal sensation votes.
Figure 7. Distribution of thermal sensation votes.
Energies 15 07331 g007
Figure 8. Relationship between thermal sensation vote and indoor air temperature: (a) raw data and (b) binned data.
Figure 8. Relationship between thermal sensation vote and indoor air temperature: (a) raw data and (b) binned data.
Energies 15 07331 g008
Figure 9. Distribution of comfort temperatures by Griffiths’ method.
Figure 9. Distribution of comfort temperatures by Griffiths’ method.
Energies 15 07331 g009
Figure 10. Comfort temperature according to gender with 95% confidence interval (mean ± 2 S.E.).
Figure 10. Comfort temperature according to gender with 95% confidence interval (mean ± 2 S.E.).
Energies 15 07331 g010
Figure 11. Relationship between comfort temperature and indoor air temperature: (a) raw data and (b) binned data.
Figure 11. Relationship between comfort temperature and indoor air temperature: (a) raw data and (b) binned data.
Energies 15 07331 g011
Table 1. Literature review of comfort temperature in Japanese office buildings.
Table 1. Literature review of comfort temperature in Japanese office buildings.
ReferencesAreaNumber of BuildingsMode of
Operation
SeasonsNumber of VotesIndex
Temperature (°C)
Comfort Temperature (°C)Method
Nakano et al. [16]Tokyo1HVACFour seasons406TopMale = 22.9
Female = 25.1
Regression
Tanabe et al. [17]Tokyo5AC modeSummer1340Ta26.3Regression
Indraganti et al. [18]Tokyo4MMSummer2402TgFR = 25.8
CL = 27.2
Griffiths
Mustapa et al. [19]Fukuoka2Split-type AC systemSummer401Tg26.6Griffiths
Damiati et al. [20]Yokohama
Tokyo
3
1
MMAutumn173
282
Top25.8Griffiths
Takasu et al. [14]Tokyo and Kanagawa5MMAll seasons2722Top23.5 to 25.8Griffiths
Rijal et al. [21]Tokyo and Yokohama11HVAC
MM
Summer/winter4660TgFR = 25.7
CL = 25.5
HT = 24.3
Griffiths
Khadka et al. [22]Tokyo,
Yokohama, Odawara
17MMAll seasons3000TgMM = 22–26
FR = 23–25
Regression
Top: operative temperature (°C), Tg: indoor globe temperature (°C), Ta: indoor air temperature (°C) FR: free-running mode, CL: cooling mode, HT: heating mode.
Table 2. Description of the instrument used.
Table 2. Description of the instrument used.
Parameter MeasuredName of the InstrumentsRangeAccuracy
Air temperatureTR-76Ui and TR-74Ui0 to 55 °C,±0.5 °C
Relative humidity10–95% RH±5% RH, at 25 °C, 50% RH
Table 3. Description of buildings, instruments and occupants.
Table 3. Description of buildings, instruments and occupants.
Building CodeInvestigated FloorModeNumber of
Measurement Points
Number of OccupantsNumber of FemalesNumber of MalesNumber of Votes
N12FMM2422522
N21F, 2FMM2853939
N34FHVAC111-2
N42FMM1835839
N54FMM21019764
N627FHVAC310461100
N75FMM1523300
Total 124618284466
Table 4. Scale of thermal sensation vote.
Table 4. Scale of thermal sensation vote.
No.Scale
1Very cold
2Cold
3Slightly cold
4Neutral
5Slightly hot
6Hot
7Very hot
Table 5. Regression equation from previous studies.
Table 5. Regression equation from previous studies.
ReferencesCountryAreasModeScale for TSVEquationsR2Treq (°C)
This studyJapanAichiMM
HVAC
Overall
1–7 **TSV = 0.11 Ti + 1.2
TSV = 0.29 Ti − 3.3
TSV = 0.13 Ti + 0.6
0.10
0.17
0.11
9.1
3.4
7.7
Karyono [35]IndonesiaJakartaNV, AC and Hybrid±3 *TSV = 0.32 Ti − 8.430.413.2
Indraganti et al. [36]IndiaChennai and HyderabadNV±3 *TSV = 0.26 Tg − 7.090.163.8
Rupp et al. [37]BrazilFlorianopoMM±3 *TSV = 0.09 Top − 2.050.0311.1
Kumar et al. [38]IndiaJaipurNV±3 *TSV = 0.15 Top − 8.430.566.7
Rijal et al. [21]JapanTokyo,
Yokohama
MM
HVAC
1–7 **FR: TSV = 0.183 Tg − 0.6
CL: TSV = 0.228 Tg − 1.7
HT: TSV = 0.168 Tg − 0.3
0.25
0.08
0.08
5.5
4.4
6.0
TSV: thermal sensation vote, *: ASHRAE scale, **: modified thermal sensation scale, R2: coefficient of determination, Treq: temperature change required to shift one thermal sensation vote (°C), TSV: thermal sensation vote, Tg: indoor globe temperature (°C), Ti: indoor air temperature (°C), Top: operative temperature (°C), FR: free-running mode, CL: cooling mode, HT: heating mode.
Table 6. Comparison of comfort temperatures with previous studies.
Table 6. Comparison of comfort temperatures with previous studies.
ReferencesCountryAreaBuilding TypeMode of OperationSeasonsIndex Temperature (°C)Comfort Temperature (°C)Method
This studyJapanAichi prefectureOffice
buildings
MM
HVAC
WinterTi25.0
24.8
Griffiths
Rijal et al. [15]JapanKanto regionOffice
buildings
MMAll seasonsTgFR = 24.9
HT = 24.3
Griffiths
Kumar et al. [46]IndiaJalandharWorkshopNVAutumn + winterTop25.9Griffiths
Hossain et al. [47]BangladeshDhakaWorkshopNVCool and dry seasonTop25.9–26.1Regression
Kumar et al. [38]IndiaJaipurOfficeNVWinterTg25.2Griffiths
Cao et al. [48]ChinaBeijingClassroom/offices of universitySpace heatingWinterTop20.7Regression
García et al. [49]ColumbiaBogotaOffice
buildings
NV19 February to 11 May 2018Top23.5Griffiths
Ballantyne et al. [50]AustraliaHighettOffice
buildings
AC4 weeks summer
5 weeks
winter (1974)
ET21.3Probit
Schiller et al. [51]USASan Francisco Bay AreaOffice
buildings
NVWinterET22.0Regression
Donnini et al. [52]CanadaMontreal, Longueuil, Gramby,
Cap-de-la-Medeliene, Shawinigan, Trois Rivieres, Hull and Maniwaki
Office
buildings
Heated in winter cooled in summerWinterET23.lProbit
Ti: indoor air temperature, Tg: indoor globe temperature, Top: operative temperature, ET: effective temperature.
Table 7. Comparison of comfort temperature and indoor temperature.
Table 7. Comparison of comfort temperature and indoor temperature.
ReferencesCountryAreaModeSeasonEquationR2
Rijal et al. [15]JapanTokyo, KanagawaMM and HVACAll seasonsTc = 0.74 Tg + 6.90.34
García et al. [49]ColumbiaBogotaNV19th February to
11th May 2018
Tc = 0.72 Ti + 6.50.45
Kuchen and Fisch [54]GermanyBerlin, Braunschweig, Hamburg,
Hannover, Gelsenkirchen, Helmstedt, Leverkusen, Magdeburg, Mannheim,
Osnabruck, Wolfburg
MM, AC and NVWinterTc = 0.82 Top + 3.850.79
Nicol et al. [55] PakistanKarachi, Multan, Peshwar, Quetta,
Saidu Sharif
MM and HVACSummer and winterTc = 0.55 Tg + 11.70.82
Tc: comfort temperature (°C), Tg: indoor globe temperature (°C), Ti: air temperature (°C), Top: operative temperature (°C), R2: coefficient of determination.
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Khadka, S.; Rijal, H.B.; Amano, K.; Saito, T.; Imagawa, H.; Uno, T.; Genjo, K.; Takata, H.; Tsuzuki, K.; Nakaya, T.; et al. Study on Winter Comfort Temperature in Mixed Mode and HVAC Office Buildings in Japan. Energies 2022, 15, 7331. https://doi.org/10.3390/en15197331

AMA Style

Khadka S, Rijal HB, Amano K, Saito T, Imagawa H, Uno T, Genjo K, Takata H, Tsuzuki K, Nakaya T, et al. Study on Winter Comfort Temperature in Mixed Mode and HVAC Office Buildings in Japan. Energies. 2022; 15(19):7331. https://doi.org/10.3390/en15197331

Chicago/Turabian Style

Khadka, Supriya, Hom B. Rijal, Katsunori Amano, Teruyuki Saito, Hikaru Imagawa, Tomoko Uno, Kahori Genjo, Hiroshi Takata, Kazuyo Tsuzuki, Takashi Nakaya, and et al. 2022. "Study on Winter Comfort Temperature in Mixed Mode and HVAC Office Buildings in Japan" Energies 15, no. 19: 7331. https://doi.org/10.3390/en15197331

APA Style

Khadka, S., Rijal, H. B., Amano, K., Saito, T., Imagawa, H., Uno, T., Genjo, K., Takata, H., Tsuzuki, K., Nakaya, T., Nishina, D., Hasegawa, K., & Mori, T. (2022). Study on Winter Comfort Temperature in Mixed Mode and HVAC Office Buildings in Japan. Energies, 15(19), 7331. https://doi.org/10.3390/en15197331