Next Article in Journal
Radio-Oxidation of Electric Cabled Models: Ageing Evaluation at the Atomic Scale
Previous Article in Journal
Compensation of Voltage Drops in Trolleybus Supply System Using Battery-Based Buffer Station
Previous Article in Special Issue
Effects of Air Supply Terminal Devices on the Performance of Variable Refrigerant Flow Integrated Stratum Ventilation System: An Experimental Study
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Numerical and Experimental Investigation of a Confluent Jets Ventilation Supply Device in a Conference Room

1
Department of Building Engineering, Energy Systems and Sustainability Science, University of Gävle, 80176 Gävle, Sweden
2
Division of Energy Systems, Department of Management and Engineering, Linköping University, 58183 Linköping, Sweden
*
Author to whom correspondence should be addressed.
Energies 2022, 15(5), 1630; https://doi.org/10.3390/en15051630
Submission received: 25 January 2022 / Revised: 16 February 2022 / Accepted: 17 February 2022 / Published: 22 February 2022
(This article belongs to the Special Issue Sustainable Buildings: Heating, Ventilation and Air-Conditioning)

Abstract

:
In this study, confluent jets ventilation (CJV) supply devices with three different nozzle arrays (1 × 19, 2 × 19, 3 × 19) were investigated both numerically and experimentally at two different airflow and supply air temperature set-ups. The performance of the CJV supply devices was investigated concerning thermal comfort, indoor air quality (IAQ), and heat removal effectiveness in a conference room environment. A comparison between the experimental and numerical results showed that the   ϑ 2 ¯ f model had the best agreement out of the investigated turbulence models. The numerical results showed that the size of the array had a great impact both on near-field development and on the conditions in the occupied zone. A larger array with multiple rows and a lower momentum conserved the inlet temperature and the mean age of the air better than a single-row array with a higher momentum. A larger array with multiple rows had a higher IAQ and a greater heat removal effectiveness in the occupied zone because the larger array conserved the mean age of air better and the buoyancy driven flow was slightly better at removing the heat. Because of the lower inlet velocities, they also had lower velocities at ankle level, which decreased the risk of draft and thermal discomfort.

1. Introduction

Heating, ventilation, and air conditioning (HVAC) systems account for about 50% of the total energy use in buildings and more than 10% of total national energy use [1]. The aim of ventilation is to maintain a comfortable indoor climate and indoor air quality (IAQ). It is therefore important to design ventilation supply devices that utilize energy-efficient ventilation strategies that are appropriate for the constraints of the ventilated space.
The most documented and well-defined ventilation strategy is mixing ventilation [2]. The principle behind mixing ventilation is to dilute the contaminated air in the room by supplying fresh air at higher velocities (often at ceiling level) to mix the air and lower the concentration of contaminants. The mixing conditions generally generate good thermal comfort and a uniform indoor environment. The Air Change Effectiveness (ACE) and Heat Removal Effectiveness (εT) for well-mixed conditions in a mixing ventilation system is 100% [3], which means that the occupied zone has a uniform temperature and an even dilution of contaminants.
Displacement ventilation is an air distribution system that uses natural buoyancy from the heat sources in the occupied zone to create stratified conditions. This is ensured by supplying cool air (3–5 °C below ambient air temperature) [4] at the floor level with low inlet velocities (<0.5 m/s) [2]. The cooler air displaces the warmer air and the local contaminants, which follow the natural plumes to ceiling level where they are removed via the exhaust [5]. Displacement ventilation generally has an ACE and εT above 100% [2]. This increase in efficiency has been calculated to reduce energy usage by as much as 20–34% in test chambers [6,7], 21–25% in offices [8,9], 41% in classrooms [8], and 33% in retail shops [8] compared to mixing ventilation. However, some studies have shown that displacement ventilation has some problems with thermal comfort [2,4,10,11], as the stratification can be disrupted by movement or obstacles in the occupied zone [4,12] and the penetration of the air supply is limited in cases with long distances and high heat loads (>35 W/m2) in the occupied zone [2,13].
There are many so-called hybrid ventilation strategies that combine different aspects of both mixing and displacement ventilation, such as impinging jet ventilation [2,4,14,15,16], under floor air distribution [4,17,18], wall attached ventilation [4,19], and confluent jet ventilation (CJV) [2,4,20]. The aim of the hybrid systems is generally to overcome some of the limitations of displacement ventilation by increasing the momentum of the supplied air while still maintaining semi-stratified conditions [4].
Confluent jets (CJ) can be defined as multiple interacting jets issuing from different nozzles [3]. Numerous studies have been completed on the near-field development of confluent jets both experimentally [21,22,23,24,25] and numerically [26,27,28,29]. Generally, the near-field development of CJ is divided into initial, converging merging, and combined regions. After a certain distance downstream from the nozzles, the combined jets behave as a single jet, where the individual jets can no longer be identified; this region is called the confluent core zone. In an array of free-moving jets where the number of columns is the same as the number of rows, the length of the regions downstream can be estimated based on the jet diameter (d) [23,24,26,28]. In the initial region (0d to 2d) the jets show no sign of interaction with each other or any decrease in velocity. In the converging region (2d to 4d) the jets bend towards the central line of the array and the jets at the edges bend faster than those close to the center. In the merging region (4d to ~9d–14d) the jets start to merge, which happens faster for the edge jets and later for the central jets. In the combined region (~9d–14d to ~20d) the minimum velocity of the combined flow field is no less than 90% of the maximum velocity. In the confluent core zone (~20d to ~11 × d × n, where n is the number of rows) the jets have combined to a single jet with uniform streamwise velocity and low turbulence in the central line of the array. The two parameters that have the highest influence on the near-field development are the jet diameter (d) and the spacing between the jets (S). The combined factor (S/d) has the highest influence on the jet development. An increase in (S/d) increases the length of the converging and merging regions. A higher (S/d) also prolongs the confluent core zone but lowers its velocity and turbulence. The factor (S/d) does not however affect the entrainment rate of the combined jet. CJ on a curved surface behaves similarly, but will produce a slightly more oblong jet instead of a uniform one [27,30].
When CJ are implemented in the ventilation supply device, the array of jets is placed parallel to a wall directed towards the floor, called a wall confluent jet (WCJ). The jets attach to the wall due to the Coanda effect and become a wall jet. This occurs in three regions, which can be described based on the jet diameter (d), the distance between the jets and the wall (x), and the distance from the nozzles (r) [21]. The process begins with the free jet region (0 < √(r/d) < 5.9) where the jets bend towards the wall and decelerate due to the adverse pressure gradient. How fast the airflow decelerates in this region depends on the distance to the wall. Airflow close to the wall (√(x/d) < 1.6) decelerates less than airflow in the centerline of the array due to less entrainment. In the Coanda effect region (5.9 < √(r/d) < 11) the combined jets behave as a wall jet with similar velocities both close to the wall and in the centerline. At the start of the wall jet region (5.9 < √(r/d) < 11), the airflow behaves as a wall jet with similar velocities and decays near the wall and in the centerline. However, at the end of the wall jet region (15.5 < √(r/d)) the air in the centerline is more influenced by outside forces (impinging pressure from floors, etc.) [21]. Studies have shown that WCJ conserves the momentum better than other types of jets (free confluent jets, free plane jet, and plane wall jet) [21,31].
The application of CJ for hybrid ventilation strategies has been studied since the early 2000s [20,32]. Numerous experimental and numerical studies have been performed on CJV in classrooms [10,32,33,34,35,36,37], offices [17,25,31,38,39,40,41,42,43,44] and assembly halls [45]. The results show a span of εT from 95% to 131% and an ACE between 99 and 124% depending on the type of room and the configuration of the supply device.
Since the design parameters for CJV (nozzle spacing, nozzle diameter, jet exit velocity, and jet direction) greatly affect the airflow development and conditions in the occupied zone, it is vital to investigate how these parameters interact under different operational conditions (airflow rate and supply temperature) and how these interactions affect the CJV performance. This study is part of a series of studies [10,33,46] investigating a novel CJ supply device that uses a lower momentum than most other CJ devices and is mounted in the ceiling rather than a wall. The aim of this series of studies is to optimize the configuration of this kind of supply device for energy efficiency, IAQ, and thermal comfort.
The key objectives of this work are:
To validate a numerical turbulence model for simulating low momentum confluent jets in a conference room environment;
To investigate how the number of nozzle rows affects the near-field of the confluent jets’ (0–50d) temperature and flow development as well as thermal comfort, indoor air quality (IAQ), and heat removal effectiveness.

2. Experimental Set-Up

2.1. The Studied Supply Devices

In the present study, the supply device was a circular duct (0.25 m diameter and 2 m long) mounted 0.05 m below the ceiling level which had 57 nozzles on each side (d = 0.028 m) placed in three rows with 19 nozzles each. The configuration of each side can be seen in Figure 1, the spacing between columns was 3 jet diameters and the spacing between the top and bottom rows was 1 jet diameter, see [33] for more details, shown in Figure 1 and Figure 2. Supply device nozzles can be fitted with caps that block the nozzles.

2.2. Test Facilities

The study was performed in a climate chamber (7.2 × 4.2 × 2.7 m3) at the University of Gävle in Sweden, representing a typical conference room environment. The climate chamber is versatile and has previously been used to investigate different indoor environments, e.g., open-plan offices [17,41], classrooms [33,34,35,47], and small offices [15,48].

2.3. Equipment

Thermocouples and constant temperature anemometers (CTA) were used to measure temperatures. In total, 38 thermocouples (type K with an accuracy of ±0.2° C) were used. They were used to measure the wall, ceiling, and floor temperature, and to measure the vertical temperature gradient (VTG) at two different locations in the occupied zone (front and back), see Figure 3. Additionally, two thermocouples measured the supply and outlet temperature.
CTA probes were used to measure the air speed, root mean square (RMS) of the velocity and temperature. Eight probes were used to measure two velocity profiles in the ceiling in front of the middle of the supply device, one velocity profile was located 0.6 m from the center of the supply device (called velocity profile 0.6 m) and one velocity profile was located 1.2 m from the center of the supply device (called velocity profile 1.2 m). Twenty-two probes were placed in eleven pairs with a distance of 0.45 m at eleven different heights (0.1, 0.3, 0.5, 0.7. 0.9, 1.1, 1.3, 1.5, 1.7, 1.9 and 2.1 m) and traversed over a distance of 2.5 m (stopping at 11 locations) to measure the wall, manikin, and symmetry zone on both sides of the room, see Figure 3. At each location, the traverser stopped, and 2 × 15 min measurements were carried out. After the measurements, the traversing system was moved to measure a new series of 2 × 11 × 11 measurement points for a total of three series. This gave a total number of 734 (11 × 11 × 2 × 3 + 4 × 2) measurement points for the CTA probes. The CTA probes were calibrated for the velocity range 0.05 and 1.00 m/s and had an air speed accuracy of ±0.05 m/s anda temperature sensor accuracy of ±0.2 °C. The CTA probes had a response time of 0.2 s to 90% of a step change and the sampling interval was 60 s. The air speed was averaged over the 2 × 15 min measurements for each point.
To calculate the nominal time constant (τn) and the local mean age of air (τp), the decay method was used by measuring the local mean age of air at the locations A, B, C, D, E, and F (outlet) with tracer gas (sulfur hexafluoride (SF6)). The human heat load was simulated using six manikins consisting of a 0.32 m diameter steel tube covered with fabric, with a sensible heat load of 100 W each, see [49]. The measurement equipment added 50 W of extra internal heat load and no lighting was used during the measurement. Figure 3 shows the positions of the measurement points.

2.4. Case Set-Up

Six experimental cases were investigated, see Table 1. The cases were named after supply temperature, airflow rate, and number of rows. Three cases had TS = 17.5 °C and an airflow rate of 50 L/s. Each of these cases had one, two, or three rows of nozzles open on each side of the supply device, while three cases had TS = 16.5 °C and 70 L/s. The airflow rate and number of nozzle rows affected the jet inlet velocity (U0) for each supply device and case, see Table 1. The two airflow rates were chosen together with the number of nozzles to give a wide span of inlet velocities. The airflow rate 50 L/s conformed to Category (III) in the EN 16798–1:2019 standard (low polluting building, LPB-2) and the airflow rate 70 L/s conformed to Category (II) in the EN 16798–1:2019 standard (low polluting building, LPB-2) [50]. The Nozzle configuration for the 3 rows can be seen in Figure 1, for the 2-row cases the top row was blocked, for the 1-row cases the two top rows were blocked.

2.5. Measurement Procedure and Analysis

Each case was set up with airflow rate, supply temperature, and number of open rows. The measurement was running for at least 16 h to ensure quasi-steady state conditions. The temperature data were collected and analyzed to make sure that steady-state conditions had been reached. The CTA probes were then traversed in three series to measure the air speed and temperature. Afterwards, the CTA measurements were taken.
Trace gas measurements were taken by distributing the gas throughout the room and mixing room air with movable fans (for three minutes) to ensure a homogeneous concentration of about 400 ppm. Tracer gas measurements were left running until the concentration levels became negligible. Previous laboratory studies using the same climate chamber and measurement procedure estimated the tracer gas measurements to have an accuracy of ±7% ([15,41,48]).
The local mean age of air (ACEp) was calculated according to:
ACE p = τ n τ p
where τn is the nominal time constant and τp is the local mean age of air. The local heat removal effectiveness (εT) was calculated according to:
ε T = T E T S T P T S
where TE, TS, and TP are the temperatures for the exhaust, supply, and the specific measurement point, respectively. The Archimedes number (AR) was calculated according to [5]:
AR   = β g Δ T A 0 U 0 2
where ΔT is the difference between the inlet temperature and the wall temperature, β is the volume thermal expansion coefficient, g is the gravitational constant, A0 is the area of the inlet, and U0 is inlet velocity [5].
The draft rating was calculated using the equation [51]:
DR   = 34 T a × U a 0.05 0.62 × 0.37 U a × T I + 3.14
where Ta is air temperature, Ua is the air speed, and TI is turbulence intensity.

3. Computational Set-Up and Numerical Schemes

3.1. Geometrical Set-Up and Boundary Conditions

The geometrical set-up had the same dimensions as the physical set-up, but was divided by a symmetry plane in the middle of the 4.2 m side. The model therefore only modeled one half of the room (the right side), see Figure 3, in order to reduce the computation time. The manikins had the same dimensions as the physical ones and were simulated as internal heat loads with 100 W each. The velocity components (u, v and w) for each individual nozzle were calculated from a numerical model (Andersson et al., 2018) of the supply device, where k and ω were used to determine the k, ε and ϑ 2 ¯ at the inlet. The experimental measurements for the inlet/wall/ceiling/floor temperatures were used to set the corresponding temperature in the numerical model (see Section 4.1). The pressure outlet was chosen for the outlet boundary condition and the outlet was extended by 8d in the numerical model by axial extrusion in order to ensure convergence. All the surfaces were assumed to be grey with an emissivity of 0.95, except for the highly polished surface of the supply device which was set to 0.7.

3.2. Governing Equations

The model was assumed to be steady-state and three-dimensional. The buoyancy effect was included in the momentum equation, where the density was modeled by the incompressible ideal gas law. The radiation heat was accounted for by the discrete ordinates (DO) model. Based on these assumptions, the Reynolds-Averaged Naiver–Stokes (RANS) equations were given by:
( U i ) x i = 0
U j U i x j = 1 ρ P x i + υ x j U i x j + U j x i + x j u i u j ¯ + 1 ρ o ρ g i
U j T x j = x j α T x j + x j u i T ¯
where u i u j ¯ and u i θ ¯ are extra terms and unknown, called Reynolds stresses and turbulent heat fluxes, respectively. By using the Boussinesq hypothesis, ( u i u j ¯ ) and ( u i θ ¯ ) are defined by:
u i u j ¯ = υ t U i x j + U j x i + 2 3 δ i j k
where υ t is the kinematic turbulence viscosity with dimensions m2/s. υ t can be expressed as the product of a turbulence velocity scale and length scale. k is turbulent kinetic energy defined as k = u i u i ¯ / 2 and δij is the Kronecker delta:
S i j = 0.5 U i x j + U j x i
The turbulence heat fluxes are modelled in a similar way by:
u i θ ¯ = υ t σ t Θ x j
where σt is turbulence Prandtl number and assumed to be constant in this study.

3.3. Turbulence Modeling

The choice of turbulence model needed to be investigated cautiously. The physics of the flow, knowledge about the pros and cons of the turbulence models, the outcome from previous similar studies [43], the CPU and time resources as well as the computational accuracy are examples of the issues one needs to be aware of. In a series of simulations, five different turbulence models, i.e., the kε model, the kε model RNG, the k—ω model, the SST kω model, and the ϑ 2 ¯ f model were investigated. The ϑ 2 ¯ f model was found to have the best accuracy and had the smallest number of numerical instabilities.
In the ϑ 2 ¯ f model, the additional transport equation of ϑ 2 ¯ is solved together with an equation for elliptical relaxation function (f). This model solved the governing equation of k and ε all the way down to the wall surface without using wall functions. The velocity fluctuation normal to the streamlines was used as the velocity scale to calculate the near-wall turbulence eddy viscosity. The turbulence kinetic energy k and its dissipation ε, the wall normal stress ϑ 2 ¯ , and the elliptic relaxation function, f are given by:
ρ U j k x j = x j μ + μ t σ k k x j + P k ρ ε
ρ U j ε x j = x j μ + μ t σ ε ε x j + C ε 1 , P k C ε 2 ρ ε T t s
ρ U j v 2 ¯ x j = x j μ + μ t σ k v 2 ¯ x j + ρ k f + 6 ρ v 2 ¯ ε k
f L 2 2 f x i x i = C 1 1 T t s 2 3 v 2 ¯ k + C 2 1 ρ k μ t U i x j + U j x i U i x j + 5 T t s v 2 ¯ k
With:
Eddy viscosity:
μ t = ρ μ t v 2 ¯ T t s
Turbulence production:
P k = μ t S 2   S = 2 S i j S i j
Turbulence time scale:
T t s = min max K ε , C t v ε 1 2 , α 3 k v 2 ¯ C μ 2 S i j S i j
Turbulence length:
L = C L max min k 3 2 ε , 1 3 k 3 2 v 2 ¯ C μ 2 S i j S i j ,   C η v 3 ε 1 / 4
The constants are:
C ε 1 = C ε 1 1 + 0.045 k / v 2 ¯   ,   C ε 1 = 1.4   ,   C ε 2 = 1.9   , C 1 = 1.4   , C 2 = 0.3   ,   C μ = 0.22   , C L = 0.23   ,   C η = 70   ,   σ ε = 1.3 m   ,   σ k = 1.0 ,   α = 0.6   ,

3.4. Numerical Details

The commercial finite volume solver Fluent 19.5 (Ansys 2019) was used to numerically solve the governing equations. The installed memory was 128 GB and 24 × 2.50 GHz processors (Intel Xeon E5–2680 v3) were used. The SIMPLE algorithm was used to control the pressure–velocity coupling. The gradient was solved with the least squares cell-based method. The pressure term used the PRESTO! scheme and an under-relaxation factor of 0.5. The momentum term used a third order-scheme (3rd MUSCLE) and an under-relaxation factor of 0.5. Both terms for the turbulent kinetic energy and the specific dissipation rate used a third-order scheme (3rd MUSCLE) and both used an under-relaxation factor of 0.8. The parameters for the DO Radiation model were set to 10 energy iterations per radiation iteration, 2 Theta Divisions, 3 Phi Divisions, 1 Theta Pixels, and 3 Phi Pixels. The solution was considered converged if the residual was less than 10−3 for the continuity and less than 10−4 for u, v, w, k, ε, f and ϑ 2 ¯ . At least 20,000 iterations were used for each case.3.5. Mesh Strategy
Different mesh densities and grid configurations were tested in order to establish grid independence with regards to spatial convergence. The difference in the velocity and temperature results for different mesh densities was calculated according to:
  D i f f e r e n c e   U   %   = i = 1   365 U i , G r i d   A U i , G r i d   B U 0 2 365
  D i f f e r e n c e   T   %   = i = 1   365 T i , G r i d   A T i , G r i d   B T E T S 2 365
The mesh size was increased by roughly doubling the number of cells between each mesh refinement from 6.5 to 24.5 million in two steps. The difference in results was 6.6% for the velocities and 0.6% for the temperatures in the first step, and 0.5% for the velocities and 0.5% for the temperatures in the second step. Since the second step between 12.2 million cells and 24.5 million cells changed the result by only 0.5%, the mesh with 12.2 million cells was used.
A range of different mesh strategies and densities were used in the different parts of the geometry. The highest mesh density was located in and around the nozzles. An unstructured tetrahedral mesh with cell sizes between 1.0 mm and 15 mm was used in the critical areas around the nozzles to better capture the sharp velocity gradients (see Figure 4 right side). The total number of cells in this part of the mesh was 2.7 million. The ceiling and wall part of the mesh downstream from the supply device where the near-field development of the confluent jet was assumed to occur was meshed using uniform quad strategy with 3.9 million cells with a maximum cell size of 10 × 16 × 40 mm (see Figure 4 left side). An inflation of 20 layers was used at the walls and ceiling to keep y+ less than 1. The part around the three manikins had an unstructured mesh with an inflation layer at the floor and around the manikins and the maximum cell size was 40 mm. Likewise, the outlet had an unstructured mesh with inflation layers and the outlet was extended to 8 diameters of the outlet to prevent backflow. The other parts of the mesh were all structured mesh with a maximum cell size of 40 × 40 × 16 mm with inflation layers at the walls, ceilings, and floors. The mesh was the computationally efficient compromise between grid independence, aspect ratio, skewness, and y+, see Table 2.

4. Results and Discussion

4.1. Experimental Results

4.1.1. Air Speed and Temperature Measurement

The results from the air-speed measurements show the same pattern for all six cases. The airflow attached itself to the ceiling due to the Coanda effect as shown by the two velocity profiles, see Figure 5. The airflow had the highest velocities (0.25–0.71 m/s) at 2.6 m close to the ceiling and dropped to 0.1–0.13 m/s at the heights of 2.3 and 2.4 m. Due to the entrainment of the surrounding air, the confluent jet stream became wider and the maximum velocity decreased with distance from the inlets. The airflow followed the ceiling until it hit the wall opposite of the supply device and entered the wall zone, where it had higher velocities in the center of the confluent jet. The velocity profile of the confluent jet smoothed out as the jet approached the floor, see Figure 5. A distinct discontinuity in the pattern occurred between height 1.1 m and 1.3 m for all six cases where the velocity profiles dropped by roughly 0.05–0.10 m/s. This difference in velocity also occurred in the manikin zone and the symmetry zone. An explanation for this discontinuity can be found in Section 4.3.2 of this paper. Some of the air followed the floor into the occupied zone, which was indicated by the higher velocities close to the floor at a height of 0.1 m, see Figure 5 (middle). The velocities in the occupied zone (manikin and symmetry zones) were very low (<0.2 m/s) even for the case with the highest inlet velocity (Case 4, see Figure 4). If one compares the velocities in the wall and symmetry zones, one can see that the velocities were slightly higher at the back of the measured distance in the wall zone, whereas in the symmetry zone they were slightly higher in the front, close to the outlet. The velocity profiles on the left and right side of the room were very similar and the patterns were repeated on both sides with only minor variations in amplitude in some points.
As Table 3 shows, the average velocity in the wall zone was dependent upon the number of rows as the cases with only one row of nozzles (Cases 1 and 4) had the highest velocities in this zone. However, the average velocities in the manikin and symmetry zones were independent of the inlet velocity as well as the airflow rate and supply temperature.
Table 4 shows the average temperatures in the different zones in the room, which shows that the temperature in the wall zone was on average 0.2–0.3 °C colder than in the two other zones because of the higher velocities and the lower infiltration of the surrounding air. The cases with a lower supply temperature and a higher airflow rate (Cases 4–6) had on average a 1.8 °C lower room temperature than the other three cases. The outlet temperature was slightly higher than the temperature in the occupied zone for all six cases, which resulted in an average heat removal effectiveness of 1.02–1.04, which was close to a mixing system. All measured vertical temperature gradients (VTG) were very small (<1.0 °C) and the overall temperature distributions in the occupied zone were uniform with only small variations. There was no considerable difference in the wall temperature between the left and right side for any of the six cases. There was a consistent difference in temperature between the front side and the back side of the room. The temperature of both the front VTG and the front wall was 0.5 °C warmer than the back VTG and back wall for all six cases. This was probably because the heat load (manikins) was slightly closer to the front of the room. The floor was slightly warmer than the ceiling because of the cooling effect from the jets and the heat from the manikins.
Figure 6 shows the temperature measurement for Case 4, which had the largest difference in temperature difference between left and right side. All cases had slightly higher temperatures on the right side of the room. The pattern of the temperature curves was the opposite of the velocity profiles with the lowest temperature in the middle of the horizontal stretch in the wall zone. Higher temperatures were in the front of symmetry zone and lower temperatures were in the back of the symmetry zone, compare Figure 4 and Figure 5. The amplitude of the pattern was somewhat higher on the left side of the room in Case 4, see Figure 5. It is worth noting that the difference in velocities between the heights of 1.1 m and 1.3 m did not significantly affect the VTG in any of the zones. The velocities increased above 1.1 m, but the VTG remained relatively flat above 0.7 m in all three zones on both sides of the room, see Figure 5. See the explanation in Section 4.3.2.
The average absolute difference in air speed between each of the measurement points on the left and the right side of the room can be calculated according to the equation:
  U D i f f e r e n c e   %   = j = 1 363 U R i g t h . j U L e f t . j U 0 2 363
Likewise, the average absolute difference in air speed between each of the measurement points on the left and the right side of the room can be calculated according to the equation:
  T D i f f e r e n c e   %   = j = 1 363 T R i g t h . j T L e f t . j Texhaust Tsupply   2 363
Table 5 shows that with regards to velocity, the differences between the left and right side were on average much smaller than the accuracy of the CTA equipment. With regards to the temperature, the difference was smaller than the accuracy for four of the six cases. The two cases with one row of nozzles, Cases 1 and 4, had slightly more differences than the accuracy and a slightly uneven temperature distribution. Although the two cases had a slightly uneven temperature distribution between the two sides of the room, the shape of the temperature and velocity profiles was very similar and the overall statistical analysis shows that the air distribution can be regarded as symmetrical. This means that a numerical model with a symmetry plane along the middle of the supply device should be able to predict the velocity and temperature distribution by only simulating one side of the room using a symmetry plane and therefore reduce the simulation cost by 50%.

4.1.2. Tracer Gas Measurement

Table 6 shows some variation in the total airflow between the cases. The nominal time constant τn (F outlet) was 25.6 min for cases 1–3 and 18.9 min for cases 4–6. This means that mean age of air in the outlet for all the cases was very close to the nominal case (<4%). The ACEp values in the occupied zone (A–C) were close to mixing conditions (0.95–1.05) and the points in the ceiling close to the supply device were higher at 1.01–1.20 with an average of 1.12. The flow was not fully mixed when the air passed by the measurement points D and E.

4.2. Validation of the Numerical Model

The numerical model was validated via a statistical analysis by comparing each case against the measured results. Since there was a slight difference in the temperature profiles of the two sides of the room, an average (over the two sides) of both the velocity and temperature measurement was used for the validation of the numerical model. In the cases where there was an oscillation in the results (Cases 2 and 3), average values from the CFD results over one cycle (4000 iterations) were used for the statistical analysis (the case with the best statistical match is presented in the figures). The error between the measured and predicted result was calculated according to:
  T D i f f e r e n c e   %   = j = 1 363 T C T A . j T C F D . j T E T I 2 363
  U D i f f e r e n c e   %   = j = 1 363 U C T A . j U C F D . j U 0 2 363
  τ p D i f f e r e n c e   %   = j = 1 5 τ p M . j τ p C F D . j τ n M 2 5
Table 7 shows the difference between the CFD and the measurements for each case. The difference in the mean age of air was on average 1.8 min (5.4%), which was within the estimated accuracy of the tracer gas measurements. The numerical predictions showed the same pattern as the measurement of high ACEp in the ceiling and mixed conditions in the occupied zone and without stagnation zones. The difference in the nominal time constant was between ±6% with an average of −1.5%, which was less than the accuracy of the tracer gas measurements. The error for velocity was on average 0.04 m/s (3.1%) and 0.32 °C (4.5%) for the temperature, which was close to the accuracy of the CTA anemometer. The difference became larger as the inlet velocity decreased and the cases that had oscillations also had the lowest inlet velocities (Cases 2 and 3). This was due to the difficulty involved in model jets passing a buoyancy driven flow with a non-transient model [51]. The greatest source of error in both Case 2 and 3 was the wall zone where the CFD model slightly overpredicted the velocities. The model did however show a good correlation in the manikin and symmetry zones for velocity as well as a good correlation of mean age of air for both Case 2 and 3. Figure 7 and Figure 8 show the velocity and temperature profiles close to the ceiling for both the CFD and the measurements. The model predicted the values and the slope of the curve very accurately in most cases. The profiles for the one-row cases (1 and 4) were identical to the behavior of WCJ. The velocity profile 0.6 m (√(r/d) = 4.7) looked similar to the WCJ in the free jet region (0 < √(r/d) < 5.9) [21] and the velocity profile 1.2 m (√(r/d) = 6.7) was very similar to a WCJ in the Coanda region (5.9 < √(r/d)<11) [21], see Figure 7. The profiles for the three row cases (3 and 6) were somewhat similar to profiles that have been measured for an impinging jet [15,43]. This could be because the third nozzle row was aimed at 30° angle (from the horizontal plane) towards the ceiling, which meant it could create a small impinging effect, whereas Cases 2 and 5 seem to have had velocity profiles somewhere between an impinging jet and a WCJ.
Figure 9 and Figure 10 show the results from case 5 where the CFD model predicted the two velocity profiles at ceiling level more accurately and therefore had better results in the wall zone. The numerical results captured the profile and average velocity for each horizontal measurement line in all three zones fairly well. It did however slightly overpredict the amplitude for each horizontal line, with more variation between each measurement point. This could be because the CFD slightly underpredicted the dissipation of momentum.
For all six cases, the CFD model underpredicted the temperature in the same two areas, at the floor level (0.1–0.9 m) in the manikin zone and in the symmetry zone. The underpredictions in these two areas were above the accuracy of the CTA (0.2 °C) and ranged from 0.3 to 0.7 °C. This underprediction was the reason why the average error of the temperature ranged between 0.3 and 0.4 °C, see Table 5. In all other areas the model captured the measurement results well, both in amplitude and pattern. There was, as with the velocities, a slight overprediction of the amplitude for each horizontal profile, see Figure 10 for an illustration of these trends for Case 5.
The numerical model slightly overpredicted the velocities in the wall zone in cases with low inlet velocities and the measurements showed that the room did not have a completely symmetrical temperature distribution. The overprediction of velocities and the underprediction of temperatures in some zones was most likely due to an underprediction of the dissipation of momentum, which led to slightly less thermal mixing in the model causing slightly lower temperatures. However, the model predicted the ceiling velocity and temperature profile well enough to investigate the effects of the number of nozzle rows on the near-field development. This and the good correlation both statistically and qualitatively show that the model was proficient enough to predict the indoor environment factors in the occupied zone necessary to perform a parametric study with regards to energy efficiency and IAQ.

4.3. Simulation Results

4.3.1. Jet Development

The number of rows had a profound effect on the jet development, especially on the entrainment of the surrounding air into the jet. Figure 11 shows the velocity profiles at different distances downstream. Case 4 had an inlet velocity that was three times higher than case 6 and therefore had higher velocities downstream. However, since the color in Figure 11 was normalized based on inlet velocities, it shows that the velocities declined at a faster rate in case 4 than in case 6. At a distance of 50d, case 6 had a maximum velocity of 0.44 m/s (44% of U0), while case 4 had a maximum velocity of 0.85 m/s (28% of U0).
Case 6 also conserved the inlet temperature (16.5 °C) better than case 4. At a distance of 50d, the average temperature of the confluent jet was roughly 20 °C in case 6, while in case 4 it was almost 2 °C higher (22 °C), see Figure 12. This was due to the lower entrainment of the surrounding air, because of a lower TI (due to lower velocities) because in Case 6 a coherent confluent jet was created faster (because of the smaller distance between the nozzles) and therefore the jet had a smaller “surface area” against the surrounding air. Both the temperature and velocity plots show that the confluent jet attached itself faster to the ceiling in case 6 than in case 4. This was because the two rows closest to the ceiling were aimed slightly upwards because of the curvature of the channel. The airflow from these two rows changed the angle for the confluent jet and the jet reached the ceiling faster. The confluent jet was also wider in case 6 than in case 4 because the starting array of the confluent jet was wider.
Figure 13 shows the mean age of air in cases 4 and 6; the entrainment of air into the confluent jet was much slower in case 6 than case 4. At a distance of 5d in case 6, part of the jet still had a mean age of air less than 0.25 τn, while the jet in case 4 was mostly above 0.50 τn. At 10d, most of the jet in Case 4 was close to 0.75 τn, so most of the air entrainment in Case 4 occurred before a coherent confluent jet was formed. At 10d in Case 6 however, a coherent jet was formed and because of the attachment to the ceiling a “protective layer” below the boundary layer of the ceiling was formed which slowed down the entrainment of the air attached to the ceiling. This effect continuedto 50d where the air close to the ceiling was still only 50% mixed in Case 6, while in Case 4 most of the jet’s air was above 0.75 τn.

4.3.2. Indoor Air Quality, Energy Efficiency and Thermal Comfort

The effects on the jet development also affected the temperature, velocity, and IAQ on the occupied zone of the room. Figure 14 shows the jet with the highest velocity in Case 4 when it reached the occupied zone. However, because of high entrainment the jet had been mixed more with the air from the occupied zone. The jet in cases 5 and 6 had a lower penetration (see velocity isoform at velocity = 0.3 m/s) and much lower entrainment with the air from the occupied zone, which resulted in the isoform for the mean age of air reaching much further into the room.
This increase in the penetration of air into the room resulted in differences in ACE for the different cases. Table 8 shows that a larger array with lower momentum was more efficient in terms of IAQ. The three cases with a lower airflow, cases 1–3, had higher ACE than the other cases. It should however be noted that the mean age of air in cases 4–6 was still lower than in cases 1–3 because of the higher air change rate.
Figure 15 illustrates that the case with the highest inlet velocity (Case 4) had the lowest energy efficiency in terms of both heat removal and ACE in the part of the room away from the outlet. Case 6 with the same airflow, but one-third of the inlet velocity, had a much more even ACE in the BZ. Since the ACE in some of the cases and εT in all of the cases were above 100% it means that the system theoretically could use a lower air volume than a mixing system and still achieve the same comfort in the occupied zone. This would reduce the energy demand of the ventilation system since a lesser air volume would have to be heated/cooled and the power of the fans would be reduced.
As previously mentioned in Section 4.1.1 there were lower measured velocities below 1.3 m in the manikin zone and to a lesser degree in the symmetry zone. The vector field in Figure 16 shows that there was a stagnation point in the velocity behind the back of the manikins between the downwards airflow at the wall and the upwards airflow from the manikins. In the multiple row array cases (2, 3, 5 and 6), buoyancy forces (AR > 0.049) from the manikins were the main driving force in the occupied zone, moving the air up from floor level similar to displacement ventilation. In the one-row cases (1 and 4), however, the momentum from the jet was the main driving force (AR < 0.01), bending the vector field towards the jet, distorting the plumes from the manikins and drawing in the air from the occupied zone. This resulted in cases 5–6 having much lower temperatures (0.7 °C) than Case 4 in the occupied zone where the heat and old air were forced upwards in the plumes, but the heat and air were not directly entrained into the center of the confluent jet as show in Figure 12 and Figure 13. Cases 1 and 4 had no clear plumes because of the distortion from the momentum of the confluent jets, but the low airflow Cases 2 and 3 had more well developed plumes than high airflow cases 4 and 5 because of higher Archimedes numbers.
The high inlet velocity case (Case 4) also underperformed in terms of local thermal comfort compared to the five other cases. The five other cases had similar values for draft rate (DR) [52] and velocities, see Table 9. All cases had ADPI values above 90%, which indicates uniform thermal conditions in the occupied zone. Cases 1–4, 6 had very low velocities (<0.2 m/s) and a low DR (<20) in at least 98% of the occupied zone; their highest velocity was 0.26 m/s (Case 1) and the highest DR was 23% (Case 6) in the occupied zone. Case 4 had high velocities and a high DR close to the floor because the momentum of the high inlet velocity was conserved into the occupied zone. The maximum velocity was 0.40 m/s and the highest DR was 40% at ankle level in the occupied zone, which would cause thermal discomfort.
The variation of temperature at ankle level in case 4 was very small (<1.0 °C); therefore, the high DR values were not caused by uneven temperature distribution. There was however a high correlation between the DR and variation in velocities at ankle level in case 4, see Figure 17.

5. Conclusions

The main conclusions from the present study are:
  • The ϑ 2 ¯ f -model in combination with the DO radiation model is an adequate turbulence model to study the confluent jet ventilation (CJV) supply devices and showed few tendencies for numerical instabilities. The numerical predictions with ϑ 2 ¯ f model had the best agreement with the experimental results, both statistically and qualitatively, and is computationally cost-efficient enough to run numerous cases needed for a parametric study.
  • A larger array with multiple rows and a lower inlet momentum conserves the inlet temperature and mean age of air better than a single-row array with higher inlet momentum due to the confluent effect. Since the single row has a higher momentum because of a smaller inlet area, the velocities downstream are higher which leads to higher velocities at floor/ankle level in the occupied zone, even though the velocities decline at a faster rate for a single row array at 0–50d.
  • The results show that the size of the array has a great impact both on near-field development and on the conditions in the occupied zone. The multiple row arrays had a higher IAQ in the occupied zone because the larger array conserves the mean age of air better. Because of lower inlet velocities, they also had lower velocities at ankle level, which decreases the risk of draft and thermal discomfort.

6. Future Work

Based on this work a parametric study is proposed to optimize the nozzle array with regards to heat removal effectiveness, indoor air quality, and thermal comfort. The parametric study should consider such factors as number of nozzles, length and width of nozzle array, inlet temperature, and airflow rate.

Author Contributions

Conceptualization, H.A., M.C. and B.M.; methodology H.A., M.C. and B.M.; formal analysis, H.A., M.C. and B.M.; investigation, H.A.; data curation, H.A.; writing—original draft preparation, H.A.; writing—review and editing, H.A., M.C. and B.M.; visualization, H.A; supervision, M.C. and B.M.; project administration, H.A.; funding acquisition, B.M. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Repus Ventilation AB and the Knowledge Foundation (KK-Stiftelsen), grant number 20120273.

Data Availability Statement

The data presented in this study are available on request from the corresponding author. The data are not publicly available due to the large size of the data-space required to host the CFD-files.

Acknowledgments

The authors gratefully acknowledge the support from the University of Gävle, Repus Ventilation AB and the Knowledge Foundation (KK-Stiftelsen). The authors are also thankful for the guidance from industrial post-graduate school REESBE (Resource-Efficient Energy Systems in the Built Environment) and the assistance from the personnel at the Laboratory of Ventilation and Air Quality at University of Gävle, Sweden.

Conflicts of Interest

The authors declare no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, or in the decision to publish the results.

Nomenclature

dInside diameter of nozzle (mm)
pPerson (-)
QTotal airflow (L/s)
QpAirflow per person (L/(sp))
TTemperature (°C)
TaAir temperature (°C)
TEExhaust temperature (°C)
TPPoint temperature (°C)
TSSupply temperature (°C)
U0Jet inlet velocity (m/s)
UaAir speed (m/s)

Abbreviations

ACEAir Change Effectiveness
ACEPLocal Air Change Effectiveness
ADPIAir Diffusion Performance Index
CAVConstant Air Volume
CJConfluent Jets
CJVConfluent Jet Ventilation
DRDraft Rate
DVDisplacement Ventilation
HREHeat Removal Effectiveness
HTDHorizontal Temperature Distribution
IAQIndoor Air Quality
εTHeat Removal Effectiveness
MVMixing Ventilation
RMSRoot Mean Square
TDTemperature Distribution
TITurbulence Intensity
VAVVariable Air Volume
VTGVertical Temperature Gradient

CFD

C1, C2, Cε1Coefficients in turbulence models (-)
C′ε1, C2εCoefficients in turbulence models (-)
Cμ, Cη, CLCoefficients in turbulence models (-)
CL, α, σkCoefficients in turbulence models (-)
u i u j ¯ Reynolds stresses (m2 s2)
υ t Kinematic turbulence viscosity (m2/s)
kTurbulence kinetic energy (m2/s2)
εRate of dissipation of turbulent kinetic energy (m2/s3)
μtEddy viscosity (kg/m·s)
ρDensity (kg/m3)
δijKronecker delta (-)
σtTurbulence Prandtl number (-)
PkTurbulence production (m2 s−3)
TtsTurbulent time scale, (s)
LTurbulence length scale (m)
fElliptic relaxation factor (-)
ϑ 2 ¯ Wall normal Reynolds stress component (m2/s2)

References

  1. Pérez-Lombard, L.; Ortiz, J.; Pout, C. A review on buildings energy a review on buildings energy consumption information. Energy Build. 2008, 40, 394–398. [Google Scholar] [CrossRef]
  2. Cao, G.; Awbi, H.; Yao, R.; Fan, Y.; Sirén, K.; Kosonen, R.; Zhang, J.J. A review of the performance of different ventilation and airflow distribution systems in buildings. Build. Environ. 2014, 73, 171–186. [Google Scholar] [CrossRef]
  3. Awbi, H.B. Ventilation of Buildings, 2nd ed.; Spon Press: London, UK, 2003. [Google Scholar]
  4. Yang, B.; Melikov, A.K.; Kabanshi, A.; Zhang, C.; Bauman, F.S.; Cao, G.; Awbi, H.; Wigö, H.; Niu, J.; Cheong, K.W.; et al. A review of advanced air distribution methods—Theory, practice, limitations and solutions. Energy Build. 2019, 202, 109359. [Google Scholar] [CrossRef] [Green Version]
  5. Etheridge, D.; Sandberg, M. Building Ventilation—Theory and Measurement; John Wiley & Sons: Chichester, UK, 1996. [Google Scholar]
  6. Chen, Q.; van der Kooi, J. A methodology for indoor airflow computations and energy analysis for a displacement ventilation system. Energy Build. 1990, 14, 259–271. [Google Scholar] [CrossRef]
  7. Awbi, H.B. Air Distribution in Rooms: Ventilation for Health and Sustainable Environment; Elsevier: Oxford, UK, 2000; Volume 2. [Google Scholar]
  8. Lin, Z.; Lee, C.K.; Fong, S.; Chow, T.T.; Yao, T.; Chan, A.L.S. Comparison of annual energy performances with different ventilation methods for cooling. Energy Build. 2011, 43, 130–136. [Google Scholar] [CrossRef]
  9. Fan, Y.; Ito, K. Energy consumption analysis intended for real office space with energy recovery ventilator by integrating BES and CFD approaches. Build. Environ. 2012, 52, 7–67. [Google Scholar] [CrossRef]
  10. Andersson, H.; Cehlin, M.; Moshfegh, B. Energy-Saving Measures in a Classroom Using Low Pressure Drop Ceiling Supply Device: A Field Study. In Proceedings of the 2016 Ashrae Winter Conference Papers, Orlando, FL, USA, 23–27 January 2016; pp. 1–8. [Google Scholar]
  11. Melikov, A.; Pitchurov, G.; Naydenov, K.; Langkilde, G. Field study on occupant comfort and the office thermal environment in rooms with displacement ventilation. Indoor Air 2005, 15, 205–214. [Google Scholar] [CrossRef]
  12. Matsumoto, H.; Ohba, Y. The Influence of a Moving Object on Air Distribution in Displacement Ventilated Rooms. J. Asian Archit. Build. Eng. 2004, 3, 71–75. [Google Scholar] [CrossRef] [Green Version]
  13. Awbi, H.B. Ventilation Systems: Design and Performance, 1st ed.; Taylor & Francis: London, UK, 2008. [Google Scholar]
  14. Karimipanah, T.; Awbi, H.B. Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation. Build. Environ. 2002, 37, 1329–1342. [Google Scholar] [CrossRef]
  15. Ameen, A.; Cehlin, M.; Larsson, U.; Karimipanah, T. Experimental investigation of the ventilation performance of different air distribution systems in an office environment—Cooling mode. Energies 2019, 12, 1354. [Google Scholar] [CrossRef] [Green Version]
  16. Chen, H.; Moshfegh, B.; Cehlin, M. Computational investigation on the factors influencing thermal comfort for impinging jet ventilation. Build. Environ. 2013, 66, 29–41. [Google Scholar] [CrossRef]
  17. Arghand, T.; Karimipanah, T.; Awbi, H.B.H.B.; Cehlin, M.; Larsson, U.; Linden, E. An experimental investigation of the flow and comfort parameters forunder-floor, confluent jets and mixing ventilation systems in an open-plan office. Build. Environ. 2015, 92, 48–60. [Google Scholar] [CrossRef]
  18. Xu, H.; Niu, J. Numerical procedure for predicting annual energy consumption of the under-floor air distribution system. Energy Build. 2006, 38, 641–647. [Google Scholar] [CrossRef]
  19. Ji, W.; Luo, Q.; Zhang, Z.; Wang, H.; Du, T.; Heiselberg, P.K. Investigation on thermal performance of the wall-mounted attached ventilation for night cooling under hot summer conditions. Build. Environ. 2018, 146, 268–279. [Google Scholar] [CrossRef]
  20. Cho, Y.J.; Awbi, H.B.; Karimipanah, T. The characteristics of wall confluent jets for ventilated enclosures. In Proceedings of the 9th International Conference on Air Distribution in Rooms (Roomvent 2004), Coimbra, Portugal, 5 September 2004. [Google Scholar]
  21. Cho, Y.; Awbi, H.B.H.B.; Karimipanah, T. Theoretical and experimental investigation of wall confluent jets ventilation and comparison with wall displacement ventilation. Build. Environ. 2008, 43, 1091–1100. [Google Scholar] [CrossRef]
  22. Ghahremanian, S.; Svensson, K.; Tummers, M.J.M.J.; Moshfegh, B. Near-field development of a row of round jets at low Reynolds numbers. Exp. Fluids 2014, 55, 1789. [Google Scholar] [CrossRef]
  23. Svensson, K.; Rohdin, P.; Moshfegh, B.; Tummers, M.J.M.J. Numerical and experimental investigation of the near zone flow field in an array of confluent round jets. Int. J. Heat Fluid Flow 2014, 46, 127–146. [Google Scholar] [CrossRef]
  24. Ghahremanian, S.; Svensson, K.; Tummers, M.J.M.J.; Moshfegh, B. Near-field mixing of jets issuing from an array of round nozzles. Int. J. Heat Fluid Flow 2014, 47, 84–100. [Google Scholar] [CrossRef]
  25. Janbakhsh, S.; Moshfegh, B. Experimental investigation of a ventilation system based on wall confluent jets. Build. Environ. 2014, 80, 18–31. [Google Scholar] [CrossRef]
  26. Svensson, K.; Rohdin, P.; Moshfegh, B. A computational parametric study on the development of confluent round jet arrays. Eur. J. Mech. B/Fluids 2015, 53, 129–147. [Google Scholar] [CrossRef]
  27. Ghahremanian, S. Near-Field Study of Multiple Interacting Jets: Confluent Jets; Linköping University Electronic Press: Linköping, Sweden, 2015. [Google Scholar]
  28. Svensson, K. Experimental and Numerical Investigations of Confluent Round Jets; Linköping University Electronic Press: Linköping, Sweden, 2015. [Google Scholar]
  29. Ghahremanian, S.; Moshfegh, B. A study on proximal region of low reynolds confluent jets—Part 2: Numerical prediction of the flow field. ASHRAE Trans. 2014, 120, 271–285. [Google Scholar]
  30. Ghahremanian, S.; Moshfegh, B. Investigation in the Near-Field of a Row of Interacting Jets. J. Fluids Eng. Trans. ASME 2015, 137, 1–18. [Google Scholar] [CrossRef]
  31. Karimipanah, T.; Awbi, H.B.; Moshfegh, B. The Air Distribution Index as an Indicator for Energy Consumption and Performance of Ventilation Systems. J. Hum.-Environ. Syst. 2008, 11, 77–84. [Google Scholar] [CrossRef] [Green Version]
  32. Karimipanah, T.; Awbi, H.B.; Blomqvist, C.; Sandberg, M. Effectiveness of confluent jets ventilation system for classrooms. In Proceedings of the 10th International Conference on Indoor Air Quality and Climate, Beijing, China, 4–9 September 2005; pp. 3271–3277. [Google Scholar]
  33. Andersson, H.; Kabanshi, A.; Cehlin, M.; Moshfegh, B. On the ventilation performance of low momentum confluent jets supply device in a classroom. Energies 2020, 13, 5415. [Google Scholar] [CrossRef]
  34. Kabanshi, A.; Wigö, H.; Ljung, R.; Sörqvist, P. Human perception of room temperature and intermittent air jet cooling in a classroom. Indoor Built Environ. 2017, 26, 528–537. [Google Scholar] [CrossRef]
  35. Kabanshi, A.; Wigö, H.; Sandberg, M. Experimental evaluation of an intermittent air supply system—Part 1: Thermal comfort and ventilation efficiency measurements. Build. Environ. 2016, 95, 240–250. [Google Scholar] [CrossRef]
  36. Bakó-Biró, Z.; Clements-Croome, D.J.; Kochhar, N.; Awbi, H.B.; Williams, M.J. Ventilation rates in schools and pupils’ performance. Build. Environ. 2012, 48, 215–223. [Google Scholar] [CrossRef]
  37. Karimipanah, T.; Awbi, H.B.; Sandberg, M.; Blomqvist, C. Investigation of air quality, comfort parameters and effectiveness for two floor-level air supply systems in classrooms. Build. Environ. 2007, 42, 647–655. [Google Scholar] [CrossRef]
  38. Zolfaghari, A.; Izadi, M.; Hooshmand, S.M.; Rateghi, R. Experimental Assessment of Temperature Distribution and Draught Discomfort for a Personalized CJV System Personalized CJV System. Proceedings of The 28th Annual International Conference of Iranian Society of Mechanical Engineers-ISME2020, Tehran, Iran, 27–29 May 2020. [Google Scholar]
  39. Tan, D.; Li, B.; Cheng, Y.; Liu, H.; Chen, J. Airflow pattern and performance of wall confluent jets ventilation for heating in a typical office space. Indoor Built Environ. 2020, 29, 67–83. [Google Scholar] [CrossRef]
  40. Conceição, E.Z.E.; Lúcio, M.J.R.M.; Awbi, H.B. Improvement of comfort conditions using confluent jets ventilation located near the floor level in an experimental chamber. In Proceedings of the 8th Windsor Conference, Windsor, UK, 10–13 April 2014; pp. 1035–1049. [Google Scholar]
  41. Cehlin, M.; Karimipanah, T.; Larsson, U.; Ameen, A. Comparing thermal comfort and air quality performance of two active chilled beam systems in an open-plan office. J. Build. Eng. 2019, 22, 56–65. [Google Scholar] [CrossRef]
  42. Vachaparambil, K.; Cehlin, M.; Karimipanah, T. Comparative Numerical Study of the Indoor Climate for Mixing and Confluent Jet Ventilation Systems in an Open-plan Office. In Proceedings of the 4th International Conference on Building Energy Environment, Melbourne, Australia, 5–9 February 2018; pp. 73–78. [Google Scholar]
  43. Chen, H.; Janbakhsh, S.; Larsson, U.; Moshfegh, B. Numerical investigation of ventilation performance of different air supply devices in an office environment. Build. Environ. 2015, 90, 37–50. [Google Scholar] [CrossRef]
  44. Karimipanah, T.; Moshfegh, B. On the performance of confluent jets ventilation system in office space. In Proceedings of the 10th International Conference on Air Distribution in Rooms (Roomvent 2007), Helsinki, Finland, 13–15 June 2007. [Google Scholar]
  45. O’Donohoe, P.G.; Gálvez-Huerta, M.A.; Gil-Lopez, T.; Dieguez-Elizondo, P.M.; Castejon-Navas, J. Air diffusion system design in large assembly halls. Case study of the Congress of Deputies parliament building, Madrid, Spain. Build. Environ. 2019, 164, 106311. [Google Scholar] [CrossRef]
  46. Andersson, H.; Cehlin, M.; Moshfegh, B. Experimental and numerical investigations of a new ventilation supply device based on confluent jets. Build. Environ. 2018, 137, 18–33. [Google Scholar] [CrossRef]
  47. Kabanshi, A.; Ameen, A.; Yang, B.; Wigö, H.; Sandberg, M. Energy simulation and analysis of an intermittent ventilation system under two climates. In Proceedings of the SEEP 2017, Bled, Slovenia, 27–30 June 2017. [Google Scholar]
  48. Ameen, A.; Choonya, G.; Cehlin, M. Experimental evaluation of the ventilation effectiveness of corner stratum ventilation in an office environment. Buildings 2019, 9, 169. [Google Scholar] [CrossRef] [Green Version]
  49. Mattsson, M. On the Efficiency of Displacement Ventilation with Particular Reference to the Influence of Human Physical Activity; University of Gävle: Gävle, Sweden, 1999. [Google Scholar]
  50. CEN. EN 16798 Energy Performance of Buildings—Part 1: Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics; European Committee for Standardization: Brussels, Belgium, 2019. [Google Scholar]
  51. Nielsen, P.V. Fifty years of CFD for room air distribution. Build. Environ. 2015, 91, 78–90. [Google Scholar] [CrossRef]
  52. ISO 7730. Moderate thermal Environment -Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal comfort; International Organization for Standardization: Geneve, Switzerland, 2005. [Google Scholar]
Figure 1. (a): Schematic of the studied nozzle. (b): Nozzle configuration for 3 rows.
Figure 1. (a): Schematic of the studied nozzle. (b): Nozzle configuration for 3 rows.
Energies 15 01630 g001
Figure 2. Photo of the test room with the supply device, manikins, and test equipment.
Figure 2. Photo of the test room with the supply device, manikins, and test equipment.
Energies 15 01630 g002
Figure 3. Placement of the measurement points in the CFD model (right side of the room). + CTA, + Thermocouples and + Tracer gas.
Figure 3. Placement of the measurement points in the CFD model (right side of the room). + CTA, + Thermocouples and + Tracer gas.
Energies 15 01630 g003
Figure 4. Mesh. Left: mesh profile OZ; Right: mesh profile nozzle.
Figure 4. Mesh. Left: mesh profile OZ; Right: mesh profile nozzle.
Energies 15 01630 g004
Figure 5. Measurement velocity on the ● Left and × Right side of the room for Case 4 at different heights, from back to front. See Figure 2 and Figure 3 for definitions of left/right/front/back.
Figure 5. Measurement velocity on the ● Left and × Right side of the room for Case 4 at different heights, from back to front. See Figure 2 and Figure 3 for definitions of left/right/front/back.
Energies 15 01630 g005
Figure 6. Temperature on the ● Left and × Right side of the room for Case 4 at different heights, from back to front.
Figure 6. Temperature on the ● Left and × Right side of the room for Case 4 at different heights, from back to front.
Energies 15 01630 g006
Figure 7. Velocities (x-axis, [m/s]) of the CFD and ● CTA (× = measurement range CTA) for all cases at different heights (y-axis, [m]). Left: Velocity profile 0.6 m Right: Velocity profile 1.2 m.
Figure 7. Velocities (x-axis, [m/s]) of the CFD and ● CTA (× = measurement range CTA) for all cases at different heights (y-axis, [m]). Left: Velocity profile 0.6 m Right: Velocity profile 1.2 m.
Energies 15 01630 g007
Figure 8. Temperature (x-axis, [°C]) of the CFD and ● CTA (× = measurement range CTA) for all cases at different heights [m] (y-axis). Left: Temperature profile 0.6 m Right: Temperature profile 0.6 m.
Figure 8. Temperature (x-axis, [°C]) of the CFD and ● CTA (× = measurement range CTA) for all cases at different heights [m] (y-axis). Left: Temperature profile 0.6 m Right: Temperature profile 0.6 m.
Energies 15 01630 g008
Figure 9. Velocities of the CFD and ● CTA for case 5 at different heights, from back to front.
Figure 9. Velocities of the CFD and ● CTA for case 5 at different heights, from back to front.
Energies 15 01630 g009
Figure 10. Temperatures of the CFD and ● CTA for case 5 at different heights, from back to front.
Figure 10. Temperatures of the CFD and ● CTA for case 5 at different heights, from back to front.
Energies 15 01630 g010
Figure 11. Velocity profiles downstream for Cases 4 and 6. X = maximum velocity at 50d = 0.85 m/s (28% of U0) for Case 4 and 0.44 m/s (44% of U0) for Case 6.
Figure 11. Velocity profiles downstream for Cases 4 and 6. X = maximum velocity at 50d = 0.85 m/s (28% of U0) for Case 4 and 0.44 m/s (44% of U0) for Case 6.
Energies 15 01630 g011
Figure 12. Temperature profiles downstream for Cases 4 and 6.
Figure 12. Temperature profiles downstream for Cases 4 and 6.
Energies 15 01630 g012
Figure 13. Mean age of air downstream for Cases 4 and 6.
Figure 13. Mean age of air downstream for Cases 4 and 6.
Energies 15 01630 g013
Figure 14. Isoform of velocity = 0.30 m/s and age of air = 0.8 τn, with temperature between 19 and 23 °C for Cases 4–6.
Figure 14. Isoform of velocity = 0.30 m/s and age of air = 0.8 τn, with temperature between 19 and 23 °C for Cases 4–6.
Energies 15 01630 g014
Figure 15. ACE > 0.95 and εT at 1.1 m for Cases 4 and 6. The black line indicates the occupied zone.
Figure 15. ACE > 0.95 and εT at 1.1 m for Cases 4 and 6. The black line indicates the occupied zone.
Energies 15 01630 g015
Figure 16. Two-dimensional profile of center manikin with velocity vector field and temperature plot for Cases 4–6, with measurement points (+) for wall, manikin and symmetry zone (at heights 0.1–2.1 m).
Figure 16. Two-dimensional profile of center manikin with velocity vector field and temperature plot for Cases 4–6, with measurement points (+) for wall, manikin and symmetry zone (at heights 0.1–2.1 m).
Energies 15 01630 g016
Figure 17. Velocity and draft rate (DR) at a height of 0.1 m for Case 4. ―― = DR = 20%, ―― = DR = 30% and ―― = DR = 40%. The black line indicates the occupied zone.
Figure 17. Velocity and draft rate (DR) at a height of 0.1 m for Case 4. ―― = DR = 20%, ―― = DR = 30% and ―― = DR = 40%. The black line indicates the occupied zone.
Energies 15 01630 g017
Table 1. Case set-up.
Table 1. Case set-up.
NozzlesU0 (m/s)Heat Load (W/m2)ACH (-)
Case 1—17.5 °C-50 L/s-1R382.2222.3
Case 2—17.5 °C-50 L/s-2R761.1222.3
Case 3—17.5 °C-50 L/s-3R1140.7222.3
Case 4—16.5 °C-70 L/s-1R383.0223.2
Case 5—16.5 °C-70 L/s-2R761.5223.2
Case 6—16.5 °C-70 L/s-3R1141.0223.2
Table 2. Mesh skewness, orthogonal quality, aspect ratio, and y+.
Table 2. Mesh skewness, orthogonal quality, aspect ratio, and y+.
Skewness
QualityExcellentVery goodGoodAcceptablePoorUnacceptable
Value0–0.250.25–0.500.50–0.800.80–0.940.95–0.970.98–1.00
Number of cells9,763,9102,091,122356,09226,40510
% of cells79.8%17.1%2.9%0.2%0.0%0.0%
Orthogonal Quality
QualityExcellentVery goodGoodAcceptablePoorUnacceptable
Value0.95–1.000.70–0.950.20–690.15–0.200.001–0.140–0.001
Number of cells6,594,6823,825,1281,676,45615,4987170
% of cells54.4%31.6%13.8%0.1%0.0%0.0%
Aspect Ratio
Value1–1010–2525–3535–4545–5555–68.6
Number of cells10,928,2551,061,709119,207117,007850319
% of cells89.4%8.7%1.0%1.0%0.0%0.0%
y+
Case123456
Avg10.90.81.110.9
Max2.92.52.13.12.72.5
Table 3. Measured average velocity in different zones.
Table 3. Measured average velocity in different zones.
Case 1Case 2Case 3Avg.Case 4Case 5Case 6Avg.
Wall Zone avg.0.160.140.140.150.210.190.160.19
Man. Zone avg.0.090.090.100.090.100.090.090.09
Sym. Zone avg.0.110.110.100.110.120.110.100.11
Table 4. Average temperature measurement for all cases.
Table 4. Average temperature measurement for all cases.
Case 1Case 2Case 3Avg.Case 4Case 5Case 6Avg.
Inlet(°C)17.4917.6017.4217.5016.4916.4316.3716.43
Outlet (°C)24.7024.8024.8324.7823.3822.7622.7822.97
Diff-in-out (°C)7.217.207.417.276.896.336.416.54
Wall Zone (°C) avg.24.4624.5224.3924.4622.9522.3322.4122.56
Man. Zone (°C) avg.24.6724.7324.6324.6823.2822.6722.7322.89
Sym. Zone (°C) avg.24.6024.6624.6424.6323.3622.7522.5422.88
VTG front (°C) avg.24.7824.8724.8624.8423.4922.8622.8623.07
VTG back (°C) avg.24.2124.2624.2824.2522.9922.3522.3322.56
Left wall (°C) avg.24.5024.6724.7124.6323.4222.7422.7522.97
Right Wall (°C) avg.24.6224.6824.7924.7023.3722.7322.7422.94
Ceiling (°C) avg.23.8223.9423.9423.9022.4722.0722.0522.19
Floor (°C) avg.24.5024.6724.6424.6023.3822.7322.7122.94
Back wall (°C) avg.24.3724.5324.9524.6123.3422.7122.6922.91
Front wall (°C) avg.25.0425.2425.2625.1824.0023.3523.3223.55
LHRE1.021.021.041.031.031.031.041.03
Table 5. Difference between the left and right side of the room.
Table 5. Difference between the left and right side of the room.
Case 1Case 2Case 3Case 4Case 5Case 6Avg.
Air Speed
(m/s)0.020.010.020.020.020.010.02
(%)0.9%0.9%2.9%0.7%1.3%1.0%1.3%
Temperature
(°C)0.310.110.150.410.100.200.21
(%)4%2%2%6%2%3%3%
Table 6. ACEp and mean age of air for all six cases.
Table 6. ACEp and mean age of air for all six cases.
ACEPMEAN AGE OF AIR [MIN]
CASE:123456123456
A1.020.990.960.950.951.0125.125.427.120.219.219.2
B1.041.021.020.981.031.0324.624.625.619.517.818.8
C1.011.031.050.960.971.0025.324.424.819.818.819.4
D1.171.121.111.011.091.1321.922.523.51916.817.2
E1.151.101.091.091.081.2022.222.924.017.616.916.1
OUTLET1.001.001.001.001.001.0025.625.226.019.118.319.4
Table 7. Difference between the measurements and simulation for all cases.
Table 7. Difference between the measurements and simulation for all cases.
Case 1Case 2Case 3Case 4Case 5Case 6Avg.
Air Speed
(m/s)0.0360.0330.0440.0540.0370.0370.040
(%)1.7%3.2%6.1%1.8%2.4%3.7%3.1%
Temperature
(°C)0.290.350.420.270.300.280.32
(%)3.6%4.2%6.0%4.0%4.9%4.4%4.5%
Mean Age of Air (τp)
(min)2.30.90.70.81.01.01.1
(%)9.0%3.5%2.6%4.2%5.3%5.4%5.0%
Table 8. ACE for each manikin, εT and AR in Case 1–6.
Table 8. ACE for each manikin, εT and AR in Case 1–6.
ACE Manikins *ACE BZ **εT OZ ***ACE-0.95AR
CaseLeftCenterRightAvg.
1100%102%100%100%102%104%100%0.009
2105%102%99%102%103%105%99%0.049
3107%107%100%105%103%105%88%0.139
499%94%88%94%94%103%40%0.004
5101%100%91%98%97%104%53%0.021
6101%103%98%101%102%105%100%0.056
Avg.102%101%96%100%100%104%80%0.046
* = volume of hemisphere (r = 0.2m) at 1.1 m in front of manikin. ** = average ACE at horizontal plane at 1.1 m. *** OZ = 0.075 m from floor −1.8 m; 0.6 m to internal wall, ASHRAE Standard 62. ACE-0.95 percentage of area at 1.1 with ACE > 0.95. AR = Archimedes number.
Table 9. ADPI, DR, and velocities (Vel. [m/s]).
Table 9. ADPI, DR, and velocities (Vel. [m/s]).
CaseU0 [m/s]Occupied ZoneVolume of Occupied Zone with
ADPIDR-MaxVel.-MaxVel. < 0.1DR < 10 *Vel.< 0.2DR < 20 **
12.293%220.2669%89%98%99%
21.195%150.2376%95%100%100%
30.792%170.2380%95%100%100%
4397%400.4051%56%88%89%
51.594%220.2471%78%98%99%
6190%230.2475%81%99%99%
* = Category A in ISO-7730:2005. ** = Category B in ISO-7730:2005 [52].
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Andersson, H.; Cehlin, M.; Moshfegh, B. A Numerical and Experimental Investigation of a Confluent Jets Ventilation Supply Device in a Conference Room. Energies 2022, 15, 1630. https://doi.org/10.3390/en15051630

AMA Style

Andersson H, Cehlin M, Moshfegh B. A Numerical and Experimental Investigation of a Confluent Jets Ventilation Supply Device in a Conference Room. Energies. 2022; 15(5):1630. https://doi.org/10.3390/en15051630

Chicago/Turabian Style

Andersson, Harald, Mathias Cehlin, and Bahram Moshfegh. 2022. "A Numerical and Experimental Investigation of a Confluent Jets Ventilation Supply Device in a Conference Room" Energies 15, no. 5: 1630. https://doi.org/10.3390/en15051630

APA Style

Andersson, H., Cehlin, M., & Moshfegh, B. (2022). A Numerical and Experimental Investigation of a Confluent Jets Ventilation Supply Device in a Conference Room. Energies, 15(5), 1630. https://doi.org/10.3390/en15051630

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop