1. Introduction
As a kind of renewable energy equipment driven by electricity, heat pumps obtain waste heat and other low-grade energy from environmental mediums to provide available high-grade heat energy. It can yield three times or more heat per portion of the energy consumed, which has greatly improved energy utilization efficiency, and it is also an efficient and energy-saving energy product [
1]. The steam compression system is the main application form of the heat pump, but it is complex in structure, large in volume, low in efficiency, and traditional artificial refrigerants such as freon are the main factors leading to global warming. As the Montreal Protocol and its amendments come into effect, countries have tightened controls on refrigerants with strong greenhouse effects [
2].
EC refrigeration technology has recently developed and become a research hotspot because of the advent of new EC materials. The energy reversibility of EC materials is high (>90%), and the energy of the actuating electric field can be efficiently recovered and reused (>80%). Other advantages of the EC materials include the simple way to impose the electric field, the light equipment, and the simple system structure [
3]. Hence, EC refrigeration or heat pump technology is well known as a promising solid-state refrigeration or heat pump technology. ECE refers to the temperature or entropy change caused by the external electric field in polar materials. An adiabatic temperature change greater than 10 K in EC materials is generally known as the “giant ECE” [
4]. Initially, because the ECE in the EC material and its adiabatic temperature change were too small, the development of EC refrigeration technology was seriously limited. It was not until the 21st century that there was some progress in EC materials. Professor Zhang Qiming [
5] discovered the giant ECE in ceramic and polymer materials in 2006. Subsequently, Neese [
6] found the giant ECE in ferroelectric polymer P(VDF-TrFE-CFE) near room temperature, which laid the foundation for the application of the ECE in the actual refrigeration or heat pump device and thus contributed to the emergence of a series of EC models and devices. Although the ECE has been studied for nearly 20 years, the developed models and numerical investigations proposed in the literature still need to grow. EC devices are divided into different types according to whether there are intermediate heat-carrying mediums and whether the EC module can be moved. The first EC devices have no moving parts or intermediate heat-carrying mediums. Farrukh Najmi [
7] first proposed a conceptual prototype of an all-solid heat pump using two layers of EC material without moving parts, and the heat was transferred during three steps theoretically. Since there is no auxiliary heat transfer fluid, the heat exchange of the heat pump completely depends on the EC material itself. Guo et al. [
8] proposed the first three-dimensional fluid-based EC refrigeration device, categorized as an intermediate heat-carrying fluid refrigeration device without moving parts. Brahim K et al. [
9] also designed an EC device based on different nanofluids. In such immovable EC devices, heat transfer efficiency can be improved effectively by introducing an intermediate heat-carrying medium. The COP reached around 10, and a temperature span of more than 10 degrees was obtained.
The third kind of EC device has moving parts but no intermediate medium. Haiming Gu et al. [
10] manufactured and studied an EC oscillatory refrigeration device (ECOR) for chip-level refrigeration, in which the EC module moved from the left side to the right side periodically to transport the heat and establish the temperature gradient within both the EC module and regenerator. Nevertheless, experimental and simulation results showed that the temperature span achieved by the device is no more than 3 K. Moreover, a similar movable EC device was designed by Ma et al. [
11]. Laminate sheets of EC material that could be moved up and down were confined between the heat source and heat sink. Then, Yuan Meng et al. [
12] designed a cascade EC cooling device with a similar structure in 2020, and the maximum temperature lift (no thermal load) was 8.7 K. These devices cannot obtain a large temperature span because the high thermal interface resistance exists among different pieces of EC solid materials, resulting in low heat transfer efficiency in the EC device. The last kind of EC device has moving parts and intermediate heat-carrying mediums. Yanbing Jia and Y. Sungtaek Ju reported a continuous EC refrigeration cycle with glycerol as a thermal interface to achieve reliable high-contrast thermal switching between an EC material and a heat source/sink [
13]. However, due to the limitation of EC materials, the maximum temperature span achieved by the device could only reach about 1 Kelvin, and the mechanical drive increased the instability of the device. Qiang Li et al. designed an efficient rotating ECOR device based on the relaxation ferroelectric polymer P(VDF-TrFE-CFE). The EC parts rotate periodically through the electric field region, and the fluid flows through the EC parts to transfer the heat [
14,
15]. With the introduction of ferroelectric polymers having the giant ECE, the cooling performance of the device was improved to some extent with COP no more than 8 and a temperature span no more than 10 K. However, the rotating structure greatly increases the complexity and unreliability of the device, making it difficult to conduct experiments practically.
In brief, using a proper intermediate heat-carrying medium would improve heat transfer efficiency, and the immovability of the device would significantly increase the device’s reliability and reduce the device’s complexity, making it easy to apply. Most above-mentioned EC devices are removable, which greatly increases the complexity of the devices, and they have some disadvantages like low temperature spans, small COP, and small power density. Therefore, there is still much space for future progress in the research of highly efficient EC refrigeration or heat pump devices. In particular, EC material with giant ECE and heat transfer intensification are key to achieving the above goal. The former determines the upper limit of the temperature span that the EC device could achieve, which is mainly up to the material’s breakdown electric field strength. The latter may include a suitable configuration of heat transfer mediums, a reasonable structural design, and other factors so that the quantity of the heat and cooling capacity produced by the ECE could be utilized efficiently.
To design an EC heat pump with excellent performance, we innovatively use Ga-based liquid metal, which has super high thermal conductivity, as the heat transfer medium to effectively transfer the quantity of heat and cooling capacity produced by the EC material to the corresponding heat exchanger. Both positive ECE and negative ECE are utilized in a single cycle, and a simple layered structure is adopted to make the device easy to apply. Thus, a plate-laminar and non-mobile EC heat pump that uses Gallium-based liquid metal as the intermediate medium is designed, providing the possibility of substantial performance improvements and making it possible to apply the EC heat pump in an actual application scenario. The fluid–thermal conjugated (non-isothermal flow) heat transfer was employed to meet the demand for highly efficient and compact heat transfer. The positive and negative EC materials with giant ECE were made into thin films and stacked on top of each other to form a layered structure with channels in between where Gallium-based liquid metal flows to achieve highly efficient heat transfer. Compared with steam compression refrigeration, the positive EC material realized the function of the compressor, and the negative EC material acts as the expander. The performance of the EC heat pump was studied under different design and structural parameters. The study aims to find the relationship between different operational parameters and the performance of the EC heat pump to give reasonable optimization strategies and provide important guidance for the subsequent study of EC heat pumps.
4. Results and Discussion
The simulations were carried out using the control variable method under different operating conditions. Coefficient of performance (COP) and unit volume heating power (UVHP) were used to evaluate the heating performance of the EC heat pump. COP measures the overall heating performance of the EC heat pump, while UVHP is an economic indicator. COP was defined as the ratio of the heating capacity to the electric power P consumed by the heat pump. As assumed, not only was there no heat leakage during the heat transfer process, but the energy loss of adiabatic temperature change of EC module was also not considered. Hence, according to the law of energy conservation, the consumed power is represented as
Thus, the COP can be calculated as follows:
In addition, UVHP is defined as
Subscript f indicates the fluid, subscript h indicates the hot heat exchanger, and subscript heat indicates the hot fluid after absorbing heat from the EC material.
4.1. Heating Performance of Different Heat Transfer Fluids
Using different heat transfer fluids for the same EC heat pump with the same boundary conditions and initial value will obtain different heat transfer effects.
Figure 8 exhibits the COP and UVHP of the EC heat pump using different fluids as intermediate heat-carrying mediums at the temperature span of 10 K.
Water, as the intermediate heat-carrying fluid among the three fluids, has the smallest COP and UVHP. The COP of the EC heat pump using Gallium-based liquid metal as the intermediate heat-carrying medium is 2.34 times that of nanofluid and 6.12 times that of water. While the UVHP of the EC heat pump using nanofluid as the intermediate heat-carrying medium is 1.37 times that of Gallium-based liquid metal and 1.69 times that of water. COP measures the heat transfer efficiency of the EC heat pump, and UVHP is an economic indicator which reflects the unit volume heating capacity of the EC heat pump. Hence, the effect of liquid metal on heat transfer efficiency is greater than the effect of nanofluid on cost reduction. In addition, the economic consideration of this paper mainly refers to the EC material cost and intermediate heat-carrying fluid cost. Since there is only one EC device for different fluids, the EC material cost is the same. And it should be known that the preparation of nanofluid is more complicated than Gallium-based liquid metal, and there is the problem of particle aggregation. Thus, the actual heat transfer of nanofluid is greatly compromised compared to the simulation results. Because the fluid velocity was given determinately, greater density leads to greater mass flow, which is one of the reasons why the heat pump that uses nanofluid as the intermediate heat-carrying fluid has higher UVHP than that of the Gallium-based liquid metal. Therefore, Gallium-based liquid metal is the most suitable intermediate heat-carrying medium.
4.2. Heating Performance at Different Temperature Spans
Adopting the control variable method, the temperature of the hot heat exchanger remained constant at 30 °C while the temperature of the cold heat exchanger rose successively from 18.5 °C to 23 °C with intervals of 1.5 K at the same electric field intensity of 125
and the same cyclic period of 8 s. As seen from
Figure 9, COP decreases with the increase in the temperature span, and the largest COP reaches 8.13. Generally, the COP for air-conditioning using vapor compression refrigeration in heating mode is approximately 4.0–6.0 [
26]. However, an EC heat pump with a volume of cubic millimeter level can achieve a COP of 8.13 at a temperature span of 7 K, indicating that the EC heat pump has unlimited potential in the development of heat pumps. UVHP also decreases with the increase in temperature span. A maximum of 746.1
is obtained at the temperature span of 7 K.
When the temperature span successively increases from 7 K to 11.5 K, the UVHP decreases by 1.16%, 6.8%, and 0.17%, respectively, while COP decreases most when the temperature span changes from 7 K to 8.5 K. COP depends on the relative size between
and
, while there are two variables in Formula 16 that determined the size of UVHP, i.e.,
and
. To analyze the effect of temperature span only,
was the same for different cycles. Hence, the differential form of
can be written as
; C is constant coefficient. The differential form of
is
;
is also a constant coefficient. As the temperature of the cold heat exchanger decreased equally,
varied with
and then caused
to change because the fluid’s temperature at the end of the previous cycle always affected the next cycle.
Figure 10 presents the temperature variation trend of the fluid at four different cases shown in
Table 3. Taking Case 4 as an example, the red and blue shadows in the figure represent the integral regions of
and
, respectively. After the cycle tended to be stable,
and
decreased with the increase in temperature span, thus leading to the decrease in both heat production
and cooling capacity
. However,
decreases more as COP decreases with the increase in temperature span.
It is known that only the EC device was simulated in COMSOL Multiphysics.
Figure 9 shows that only in Case 1 does the fluid that finishes the cycle end up with a temperature close to the original temperature of the EC device, which demonstrates that Case 1 is the most ideal cycle among the four cycles.
Figure 11 shows the temperature contour of the center plane of the EC heat pump in a complete cycle at Case 1. Among them, 1.18 s and 5.34 s are the highest and lowest moments of the fluid domain’s temperature in the cycle, respectively. The temperature on the left side of the EC material dropped more than that on the right side, and the temperature of the EC material in the middle position dropped more than that on the upper and lower sides after the end of the first half of the cycle. When it comes to the second half of the cycle, the same situation of temperature inhomogeneity happens again. For the layered EC heat pump device, the temperature imbalance between left and right is normal, but the temperature imbalance between upper and lower should be minimized to utilize the heat production and cooling capacity of the EC material most effectively. Therefore, increasing the number of layers of EC material is expected to ensure sufficient heat transfer between fluid and EC material. Hence a four-layer EC heat pump is further simulated at the same operating conditions of Case 1.
The structure of the four-layer EC heat pump is shown in
Figure 12. By changing the relative height of the EC material layer and the fluid layer while keeping the total height of the EC heat pump unchanged, the EC material layer’s and fluid layer’s thickness are 0.8 mm and 0.225 mm, respectively. The length and width of the device are still 25 mm × 5 mm, respectively.
The comparison of the heating performance between the four-layer EC heat pump and the three-layer EC heat pump is exhibited in
Table 4. As can be seen from the table, the performance of the four-layer EC heat pump is significantly improved compared to the three-layer EC heat pump, with COP increasing by 25.46% and UVHP increasing by 28.45%. Therefore, the number of layers of the EC heat pump can effectively improve the heating performance due to the increase in heat transfer area. Hence, increasing the number of layers of the EC heat pump can be considered when designing the actual EC heat pump without increasing the material cost.
4.3. Heating Performance at Different Cyclic Periods
The cyclic period has a significant effect on the heating performance of the device. It has been tested that the whole simulation will fall into an unstable state when the cyclic period is less than 5 s. Therefore, the cyclic periods set in this study are all more than 5 s, and the time of every simulation contains at least four cycles to ensure cycle stabilization. Moreover, the electric field intensity is fixed at 150 , and the temperature span is 10 K.
As illustrated in
Figure 13, the COP and UVHP of the heat pump reach maximum and minimum values at the cyclic period of 8 s and 5 s, respectively.
Figure 14 presents the temperature variation trend of fluid at different periods. It can be seen from the figure that the cycle is closest to the ideal cycle at the cyclic period of 10 s because the fluid’s temperature at the end of the cycle is closest to the initial temperature of the device. However, the COP and UVHP of the heat pump at the cyclic period of 10 s are not the best. Since the temperature span and fluid velocity are certain, heat transfer time is the main factor that affects the heat transfer between the fluid and the EC material. After the cyclic period increases, the corresponding heat transfer time between the fluid and the EC material increases, making fluid and EC material transfer heat more adequately. Thus,
becomes larger when the cyclic period increases from 5 s to 8 s, which makes the heating capacity increase. However, the COP and UVHP of the heat pump decrease, on the contrary, as the cyclic period continues to increase, which is because the heat production of the ECE is finite under the same electric field, and no excess heat could be exchanged with the fluid even if the heat transfer time increases further. Thus, a longer cyclic period can ensure that the fluid returns to the initial state after the end of the cycle, but it cannot guarantee that the performance of the heat pump is the best.
4.4. Heating Performance in Different Electric Fields
In this study, we investigate the influence of electric field intensity on the heating performance of the EC heat pump while keeping the cyclic period and temperature span constant. The changing trend of electric field intensity and fluid velocity in each cycle is shown in
Figure 15. The temperature change of the EC material under different electric field intensities is illustrated in
Figure 16. The temperatures of the cold and hot heat exchangers are settled at 20 °C and 30 °C, respectively.
As exhibited in
Figure 16, a higher electric field can induce larger ECE so that the temperature change of the EC material becomes more intense. Consequently, the values of
and
will be larger because the fluid exchanges more heat with the EC material, which is consistent with the variation trend of
and
depicted in
Figure 17. However, COP fluctuates with the increase in electric field intensity and reaches the maximum when the electric field intensity is 150
.
Figure 16 shows that the temperature of the EC material after a complete cycle is only closer to room temperature at 175
and subsequent electric field intensities. Meanwhile, the temperature of the EC material at the end of a cycle is lower than room temperature when the electric field intensity is less than 175
, limiting the temperature lift of the first half period of the next cycle. It can be seen from the figure that this phenomenon has a larger effect when the electric field intensity is 150
so that
becomes smaller and is adjacent to
, making COP bigger than the others. When the electric field is 125
, COP is smaller because the ECE is smaller, and the corresponding heat transfer is less. Therefore, different electric field intensities will affect the overall heat transfer under the same cyclic period and temperature span, which is related to whether the parameters are the most perfect fit. For this reason, proper coordination between the electric field and other parameters is needed to obtain a perfect cycle when designing an EC heat pump.
As shown in
Figure 18, UVHP shows a different trend. It increases with the electric field intensity in general. Moreover, the growth rate of UVHP is increasingly larger with the increase in electric field intensity. When the electric field intensity increases from 175
to 200
, the growth rate of UVHP reaches 92.86%. Within the range of electric field intensity that the EC material can withstand, the bigger the electric field intensity is, the greater the ECE and the temperature variation range of the EC material. In this way, the fluid can also obtain more heat through heat transfer. On the other hand, the temperature of the cold and the hot heat exchangers is invariable, so the temperature difference between the fluid and the terminal becomes larger. According to Formula (16), the greater the temperature difference, the greater the heating power.
5. Conclusions
This paper designed an EC heat pump with highly efficient heat transfer, which is possible to apply in an actual application scenario because of its simple structure. The introduction of negative EC material and Gallium-based liquid metal make the designed EC heat pump system better and more efficient. Different comparative simulation experiments using the control variable method were carried out in COMSOL Multiphysics. COP and UVHP were used as evaluation parameters to measure the performance of the EC heat pump. The principle for the different results was analyzed in detail to give reasonable optimization strategies and provide important guidance for subsequent studies of EC heat pumps. The schemes for optimizing the design of the EC heat pump were given based on the simulation results. The results are as follows:
With high thermal conductivity and a low melting point, Gallium-based liquid metal is the new optimum selection for an intermediate heat-carrying medium. COP was up to 14.84, and UVHP was up to 2763.8 when Gallium-based liquid metal was used as heat transfer fluid under the same operating conditions with other fluids.
The heating performance of the EC heat pump decreased as the temperature span increased gradually. The maximum COP of the EC heat pump reached 8.13, and the maximum UVHP reached 746.1 at a temperature span of 7 K. Furthermore, the performance of a four-layer EC heat pump under the same conditions with Case 1 was studied, and the UVHP increased by 28.45% and COP increased by 25.46% due to the increase in heat transfer area.
At a constant temperature span, the maximum COP and UVHP of 14.84 and 2763.8 , respectively, were obtained at a cyclic period of 8 s.
According to the results, UVHP increased gradually with the increase in electric field intensity, and the maximum UVHP reached 7132.7 at the electric field intensity of 200 , while COP peaked at 14.84 when the electric field intensity was 150 .
In summary, the present work reported a simple-structured EC heat pump using Ga-based liquid metal with high thermal conductivity that could achieve highly efficient heat transfer and confirmed its potential for a practical EC heat pump. The overall heating performance of the EC heat pump is closely related to the optimal match among each parameter like electric field intensity, cyclic period, temperature span, electric field intensity, number of layers of the EC heat pump, and so on. Due to the limitation of the EC material, only a small number of EC devices can be studied. In the future, a library in which the different optimal fits of different parameters are listed could be established to offer guiding suggestions for researchers. Furthermore, researchers could devote themselves to developing calculation models in software of different EC materials to promote the advanced development of EC refrigeration or heat pump technology.