1. Introduction
High-temperature heat pumps (HTHPs) represent a pivotal innovation in the industrial sector, promising to revolutionise thermal management approaches by enhancing energy efficiency and reducing the environmental impact of processes. The term HTHP is commonly used alongside “Industrial Heat Pumps” (IHPs), indicating a different application from civil/residential heating [
1], where what we could call “civil” heat pumps (CHPs—civil heat pumps) have been gaining ground in recent years. For IHPs, the field of application lies in the production of medium- to high-temperature process heat, often including the recovery of industrial waste heat (WHR—waste heat recovery). In the majority of applications, this process heat is required at temperatures above 80 °C, so this temperature is the lowest limit to consider a heat pump as “high temperature”.
The need to reach higher thermal levels sometimes requires the use of additional components and a choice of fluids, even innovative ones, suitable for the required outputs. Moreover, stringent regulations that annually reduce the availability of refrigerants, mainly for environmental reasons, compel deeper exploration of the landscape of new sustainable working fluids.
High-temperature IHPs should indeed be the most promising technological solution for phasing out industrial boilers using fossil fuels, in all those sectors where process heat is required at temperatures below 200 °C. IHPs would allow the utilisation of waste heat from the industrial process as a cold source, thus providing a thermal upgrade; using only electrical energy as an input would ensure, at least at the component level, a significant reduction in greenhouse gas emissions compared with the less sustainable solution based on fossil fuels. In the perspective of achieving decarbonisation goals [
2,
3], mandated at various levels by numerous governmental organisations (i.e., the European Green Deal [
4], which sets a target of climate neutrality in the EU by 2050), high-temperature heat pumps for industrial applications would be the “renewable tool” within industrial realities (provided that the electricity for their operation is produced through renewables) [
5].
1.1. Working Fluids Utilised in Vapour Compression Heat Pumps
Theoretically, any chemical compound capable of undergoing evaporation and condensation could operate as the working fluid within a vapour compression cycle [
6]. Nevertheless, several characteristics must be taken into account when selecting the working fluid: specific requirements, like those concerning environmental impacts or human health risks, impose stringent limitations during the selection process, while functional criteria, such as thermodynamic properties, guide the choice towards fluids capable of delivering optimal energy performance. There are three primary requirements that a working fluid must fulfil:
Environmental requirements: ODP, GWP, and TEWI are parameters that quantify the potential impact of a refrigerant’s release on the environment.
Safety requirements: Toxicity and flammability determine the danger the refrigerant poses to human health.
Functional requirements: Thermodynamic and transport properties, compatibility with materials, and lubricating oil; these criteria enable the assessment of achievable energy performance and the practical suitability of the working fluid.
In accordance with these requirements, various categories of pure working fluids are presented as they are currently employed in the state of the art. Two main categories can be distinguished: synthetics (HFC, HFO, and HCFO) and natural (ammonia, CO2, hydrocarbons, and water) fluids. It is worth noting that mixtures could be also considered working fluids for HTHP, but they will not be included in this work, which focuses only on pure fluids.
1.1.1. Hydrofluorocarbons (HFC)
R134a has been widely employed in medium-temperature heat pumps, owing to its favourable thermodynamic characteristics. However, its GWP of 1430 has led to its phase-out process. R152a is a low-GWP HFC, and along with R161, it has been evaluated as a drop-in substitute for R134a.
R245fa is currently the most used fluid in HTHPs due to its critical point of 153.9 °C and 36.51 bar and NBP of 15 °C. Its GWP = 1030 makes it unsuitable for use, at least in the European context.
R236fa and R236ea have been developed as substitutes for R114, a CFC used for high-temperature applications (thanks to its high critical temperature of 146 °C). They have a global warming potential of 9810 and 1370, respectively.
R365mfc was developed by Solvay for high-temperature applications or as a foaming agent. Its GWP of 804 is lower than the previously listed ones, but still high enough to make it unsuitable for EU regulations. It is a flammable fluid, and over time, this issue has been addressed by blending it with R227ea or perfluoropolyether (Solkatherm SES36); however, these modifications raise the GWP to 1110 and 3126, respectively [
1,
6].
1.1.2. Hydrofluoroolefins and Hydrochlorofluoroolefins (HFO and HCFO)
Hydrofluoroolefins represent the category of synthetic refrigerants boasting the lowest GWP (<20), and many of them function as drop-in substitutes for HFCs prohibited by F-gas regulation [
7] and the Kigali Amendment to the Montreal Protocol [
8]. The tetrafluoropropene series (R1234yf, R1234ze(Z), and R1234ze(E)), and exafluorobutene series (R1336mzz(Z) and R1336mzz(E)) stand out as the most commonly utilised HFOs in the development and examination of HTHPs. HCFOs like R1233zd(E) and R1224yd(Z) contain chlorine, indicating that the ODP of these fluids is not zero (0.00034 and 0.00012, respectively); nevertheless, their atmospheric lifespan is brief, resulting in a negligible impact on the ozone layer.
1.1.3. Ammonia
Ammonia (R717) has been widely utilised in both heating and cooling applications, especially where high thermal powers are required. Ammonia possesses a high enthalpy of vaporisation, which results in excellent volumetric heat capacities (VHCs). This allows for a more compact system, not only concerning pipelines, valves, and heat exchangers but especially for the compressor, which is the most expensive component of the system.
Its relatively low critical temperature (132.4 °C) currently limits the use of ammonia to thermal output levels not exceeding 100 °C. Simultaneously, the critical pressure is notably high (113.6 bar): for a condensation temperature of 80 °C, condenser pressures reach approximately 40 bar, necessitating the oversizing of components to withstand high mechanical stresses. Its normal boiling point (NBP) of −33.3 °C ensures that compression ratios are not excessive, benefiting compressor efficiency. The shape of the (“bell-shaped”) limit curve results in particularly high compression discharge temperatures (also considering the relatively low density in a superheated vapour field) [
9].
Ammonia’s compatibility with materials such as steel, iron, and aluminium is excellent, but it corrodes copper, zinc, and copper compounds like brass or bronze. Additionally, the circuit must not contain corroding materials due to the hazards of ammonia toxicity and flammability.
Indeed, ammonia is a highly toxic and slightly flammable fluid (the concentration in air must be between 16 and 25% to pose a risk), with a lower flammability limit of 0.116 kg/m3 and an autoignition temperature of 630 °C, placing it in class B2L.
In an HTHP application, ammonia must cope with the high pressures required to condense at high temperatures and the high discharge temperature of the compressor. These are the two issues that limit its use for thermal outputs not exceeding 100 °C. Therefore, in the range of 80–100 °C, as the temperature of the hot source, different configurations can be adopted depending on the lift that the HTHP needs to address. For low lifts (up to 50 K), and thus, in cases where waste heat from industrial processes between 30 and 50 °C is used as a cold source, the single-stage configuration allows the ammonia to cope with the necessary compression ratios; otherwise, for higher lifts (lower evaporation temperatures), multistage configurations must be used.
1.1.4. CO2
Carbon dioxide (R744) is an inert, non-toxic, non-flammable, safe, and chemically stable gas. Its environmental sustainability (compared to synthetic fluids) is maximal; the global warming potential (GWP) of other fluids is calculated in relation to the unit value assigned to carbon dioxide. Regarding its thermodynamic properties, its high conductivity, high specific heat at a constant pressure, and considerable density in a gaseous form (a high volumetric heat capacity) allow for a significant miniaturisation of the system, benefiting investment costs. However, the critical point, characterised by a low temperature (T
crit = 31.2 °C) and high pressure (P
crit = 73.8 bar), is the limiting feature of this fluid: in refrigeration applications, a CO
2 cycle, being required to discharge heat into the environment, generally operates with a transcritical cycle, thus without condensation [
10]. In high temperature heat pump (HTHP) applications, such a cycle is absolutely the only alternative. The condenser is therefore replaced by a gas cooler, with significantly larger exchange surfaces (and also thicker ones to withstand high pressures) to ensure the transfer of the desired thermal power to the hot source.
1.1.5. Hydrocarbons
Hydrocarbons constitute a class of natural refrigerants (ODP = 0, GWP < 10) with excellent thermodynamic properties. As the number of carbon atoms increases, so does the molar mass and critical temperature, making heavier hydrocarbons particularly suitable for use in HTHP applications. However, their flammability poses a significant concern. The hydrocarbons conventionally used do not exceed the carbon number of five (pentane).
Except for R1270 (propylene) and R290 (propane), with NBPs of −47.62 °C and −42.11 °C, respectively, and for butane (R600) and isobutane (R600a), which in HTHP applications for waste heat recovery (WHR) seldom evaporate at temperatures below 30–40 °C, pentane (R601) and isopentane (R601a), with boiling temperatures under normal conditions of 36.06 °C and 27.83 °C, respectively, may evaporate at pressures lower than atmospheric, posing the risk of air infiltration, which is detrimental due to flammability concerns.
1.1.6. Water
Water is the most economical and widely distributed natural refrigerant worldwide, being non-toxic and non-flammable (together with CO2, the only natural refrigerant that meets all safety requirements). Its thermodynamic properties offer high potential for HTHP applications, especially for extreme thermal levels, given its critical temperature of 374.15 °C and critical pressure of 221.3 bar. Its high latent heat of vaporisation, 2442 kJ/kg at 25 °C, is 14 times higher than that of R134a, which is definitely advantageous considering that water must necessarily operate in a subcritical cycle.
However, significant challenges persist in its use in vapour compression cycles: many prototypes of R718 cycles have been realised, also at high TRLs, but their commercial diffusion is still limited. Water’s high polytrophic exponent, high specific volume of steam, and low molecular weight result in excessively high discharge temperatures, volumetric flow rates, and compression ratios. Its normal boiling point is 100 °C (NBP), necessitating evaporation at pressures lower than atmospheric (sometimes significantly lower).
1.2. Background and TRL Positioning of HTHP
Numerous studies and industrial undertakings have explored HTHP applications with the fluids examined in this study.
Table 1 illustrates the positioning of current HTHP investigations involving some of the assessed fluids, while
Table 2 provides a summary of relevant findings from the literature.
1.3. Previous Studies on Working Fluid Selection for HTHPs
Works in the literature already exist that have yielded intriguing findings when comparing fluids for HTHP [
1,
20,
21]. Particularly, Arpagaus C. et al., 2018 [
1], presented an overview of high-temperature heat pumps (HTHPs) designed to operate within a sink temperature range of 90 to 160 °C. They conducted a comprehensive analysis of the operational characteristics of heat pump cycles and performed a market assessment, revealing the availability of over 20 HTHPs from 13 manufacturers, all capable of producing heat sink temperatures exceeding 90 °C. The predominant configuration for HTHP cycles is single-stage, with variations primarily determined by the choice of refrigerant (such as R245fa, R717, R744, R134a, or R1234ze(E)) and compressor type. The investigation of refrigerant selection encompassed an analysis of several fluids, including R1336mzz(Z), R718, R245fa, R1234ze(Z), R600, and R601, with R1336mzz(Z) identified as enabling the achievement of exceptionally high-heat-sink temperatures of up to 160 °C.
Wu et al. (2021) [
20] presented an overview encompassing 17 distinct pure low-GWP refrigerants suitable for integration into vapour compression heat pumps. These refrigerants include natural options like R717, R718, and R744, hydrocarbons such as R290, R600, R600a, R601, and R1270, hydrofluorocarbons like R152a and R161, hydrofluoroolefins such as R1234yf, R1234ze(E), R1234ze(Z), R1336mzz(Z), and R1336mzz(E), as well as hydrochlorofluorolefins including R1233zd(E) and R1224yd(Z).
Bamigbetan et al. (2017) [
21] conducted a comprehensive investigation into the current landscape of high-temperature heat pumps (HTHPs) utilising vapor compression cycles (VCC). Both pure working fluids and their combinations were examined, assessing their effectiveness across different contexts. Furthermore, the review highlighted how diverse optimisation techniques have been applied in the literature to match the selected fluid with the most appropriate cycle system. Analyses have also been carried out to identify the most efficient heat transfer methods, including sensible heat, latent heat, and leveraging the temperature glide of mixed fluids within heat exchangers.
Frate et al. (2019) [
22] conducted a similar analysis to the one proposed in this work, but exclusively with variable lift without providing information on the transport properties of the analysed fluids and on their heat transfer potentials; their list was of great utility for the compilation of the set of fluids analysed in this work. The authors explored appropriate working fluids for a HTHP in a 50 °C to 150 °C heat sink temperature range. They considered environmental and technical factors to select fluids like acetone, benzene, cyclopentane, and dichloroethane, offering economic benefits despite their flammability. Synthetic refrigerants such as HFO R1336mzz(Z), R1234ze(Z), HCFO R1233zd(E), and R1224yd(Z) provide safety and efficiency alternatives. However, prioritising parameters other than COP may lead to efficiency losses of 10% to 20%, underlining the need for careful analysis. Additionally, efficient fluids have lower volumetric heat capacity (VHC) compared to traditional ones, where substituting with high-VHC fluids may decrease efficiency, with R1233zd(E) offering a balanced compromise.
As demonstrated by the literature review, a gap in providing comprehensive guidelines for selecting the working fluid in a high-temperature heat pump seems to appear. This is due to several factors that must be considered, including flammability, sustainability, toxicity, economic viability, and thermodynamic performance. The objective of this paper is thus to shed light on the selection process of the appropriate working fluid, focusing on thermodynamic characteristics. This will involve the establishment of figures of merit and the development of a simple 1D code to assess the performance of each fluid.
This study will be structured as follows: Firstly, the methodology will be outlined in
Section 2, encompassing the initial fluid selection process (
Section 2.1), the characteristics of the thermodynamic model (
Section 2.2), and the comparison metrics employed (
Section 2.3). Subsequently,
Section 3 will present the results obtained, categorised into findings from numerical simulations conducted with a constant lift configuration (
Section 3.1), and those with a variable lift configuration (
Section 3.2). Following the results,
Section 4 will introduce guidelines for fluid selection (
Section 4), elaborating on each category (
Section 4.1) and providing pertinent information regarding toxicity and flammability considerations (
Section 4.2). Finally,
Section 5 will conclude the study with a discussion of the findings and overall conclusions drawn.
3. Results
Two types of analyses were carried out, one keeping the lift between the evaporator and condenser temperature constant, and the other varying this temperature difference. The following subsections will provide the results of such analyses.
3.1. Constant Lift
In this section, comparative results will be delineated for ΔTlift = 40 K. This level is a good choice as most of the tested fluids can indeed be used in a real HTHP (high-temperature–high-pressure) setup with a basic layout like the one analysed in this study.
The key parameter of interest that facilitates an immediate comparison once the thermal levels at the evaporator and condenser are established is the compression ratio required by the compressor to achieve the desired output. As the condensation temperature increases, there is a general trend of decreasing compression ratio for all fluids.
Figure 5a illustrates trends only for some of the 25 selected fluids; by shifting the cycle (at constant lift) towards higher thermal levels, isobars condense as one approaches the critical point in a T–s diagram, and as depicted in
Figure 5b, the “height” of the cycle in the p–h diagram decreases when the reduced pressure (defined as the ratio between the pressure at a point and the critical pressure) approaches unity.
The most demanding conditions arise at a condensation temperature of 80 °C (Tevap = 40 °C). At this level, all commonly used fluids (12 out of 25) exhibit a compression ratio below 3.5, thus posing no issues regarding compressor selection. Therefore, employing a standard single-stage configuration for these fluids is entirely suitable. However, for unconventional fluids like hexane, isohexane, cyclohexane, acetone, and hexamethyldisiloxane, the compression ratio at the same thermal levels falls below 4.5, indicating the preference for volumetric compressors in these cases. Volumetric compressors permit higher compression ratios with a single stage, though the choice must consider the required processing capacity as well (mass flow rate and size). Aromatic hydrocarbons, alcohols, and water exhibit the most extreme values, with betas ranging from 5 to 6.5 (for toluene and water, respectively). In these instances, the maximum achievable compression ratio with a single-stage compressor is certainly at its limit, suggesting the selection of alternative volumetric or screw compressors based solely on this parameter.
Considering the decreasing trend of this comparison parameter, all these fluids can be appropriately utilised with any compressor type as they move towards higher thermal levels, including centrifugal dynamic compressors. While such compressors restrict compression ratios to no more than 3.5 per single stage, they can accommodate much higher flows, essential for large-scale HTHP (>1 MW) applications.
Clearly, the primary outcome of the compression ratio’s decrease is the reduction in the work linked to this transformation.
Figure 5b furnishes a graphical illustration of this decrease; within the p–h diagram for cyclopentane, it becomes apparent that across the three cycles featuring evaporation and condensation temperatures of 40/80, 100/140, and 140/160 (with a constant lift at 40 K), the diminishing cycle height correlates with a decrease in the projection along the x axis of the enthalpies, a hallmark of the compression process.
The parameter allowing performance evaluation is the coefficient of performance (COP), defined as the ratio between the power per unit mass achievable at the condenser and the power per unit mass absorbed by the compressor. Both of these terms decrease with increasing condensation temperature. However, the trend of their ratio is particularly interesting because it exhibits a maximum zone. In
Figure 6b, as an example, the COP (and its related terms) are plotted against the variation in the condensation temperature (with a fixed lift of 40 K) for methanol.
For methanol, the maximum point occurs at a condensation temperature of approximately 185 °C; the values for the representative points of the trend are listed in
Table 5. In the first temperature range from 80 °C to the maximum point, the percentage decrease in specific thermal power at the condenser is lower compared with the percentage decrease in specific power absorbed by the compressor (−33% vs. −43.7%, respectively). In the second segment, from the maximum point to the critical temperature, the percentage reduction reverses, with the specific work decreasing less compared with the decrease in specific heat at the condenser (−30.8% vs. −45.9%, respectively).
Figure 6a depicts the trends of the COPs for several of the 25 tested fluids. In general, a higher critical temperature of the fluid corresponds to a higher COP. However, fluids such as propane (R290), R152, isobutane (R600a), and ammonia (R717) do not display a clearly defined maximum, unlike the other fluids. This discrepancy is solely attributable to the analysis range specified for high-temperature heat pumps, which was set at a condensation temperature of 80 °C. Consequently, the actual maximum point for these fluids would be several degrees lower. It is worth noting that these fluids are extensively utilised in refrigeration applications, where they demonstrate optimal performance.
The distribution of the maximum points indicates a necessity to further examine their positioning relative to the critical temperature of each fluid. By utilising the reduced condensation temperature instead of the condensation temperature as the reference parameter, a very interesting arrangement of these points emerges, as depicted in
Figure 7. It can be concluded that with a 40 K lift between the two thermal levels of evaporation and condensation, the maximum points for all fluids converge within the range of reduced condensation temperatures, approximately from 0.85 to 0.9. However, R152a, R290, and DME yield incoherent outcomes because, given that the analysis commenced from a condensation temperature of 80 °C, these fluids exhibit maximum performance at levels lower than those required for HTHPs.
3.2. Variable Lift
The coefficient of performance experiences a significant decrease as the temperature lift between the two thermal levels of evaporation and condensation increases, indicating the need for further efforts to address emerging issues, particularly when exceeding a 120 °C lift.
In
Figure 8, the COP trends for water at four different evaporation levels are depicted. These findings align naturally with the constant lift analysis conducted previously. It is worth noting that with a 40 °C lift, the COP increases with the T
evap, although it does not reach the maximum depicted in
Figure 6. As the lift increases, the influence of the evaporation temperature diminishes, and a reversal point is observed at around a 200 °C lift.
Additionally, it is important to emphasise the advantage of a heat pump over a traditional gas-fired boiler. Let us consider a practical example to evaluate its economic viability. Let us suppose there is the need to install a heating system capable of delivering 10 kWh of energy. If a condensing gas boiler is considered, we can assume an efficiency level of 100% (the worst-case scenario for the heat pump). Considering methane’s lower heating value (LHV) of 9.3 kWh/m
3, we can make further assessments. Alternatively, if we explore the option of a heat pump, let us assume a coefficient of performance (COP) of 2.5. For our calculations, let us take into account a purchase cost of EUR 0.90 per cubic metre of methane and EUR 0.21 per kWh of electricity. For the boiler, the hourly thermal energy consumption is 10 kWh. This corresponds to about 1.08 cubic metres of hourly fuel consumption. Consequently, the hourly ignition cost amounts to EUR 0.97, derived from multiplying 1.08 cubic metres by 0.90 EUR/m
3. For the heat pump, dividing 10.0 kWh by 2.5 gives us 4 kWh of hourly electricity consumption. Hence, the hourly ignition cost equals EUR 0.84, calculated by multiplying 4 kWh by EUR 0.21/kWh.
Figure 8, therefore, highlights that for a T
evap of 40 °C, the maximum lift for cost-effectiveness compared with a boiler is about 100 °C, while for T
evap = 160 °C, it increases to approximately 130 °C.
In
Figure 9, a comparison is made between some of the 25 fluids assessed at four evaporation temperatures (40/80/120/160 °C). The superior performance (albeit minimal) of o-xylene compared with that of water (and even of cyclopentane with up to ΔT
lift = 160 °C) immediately catches the eye, which may seem inconsistent with the trends in
Figure 6.
However, it is important to remember that in this variable lift parametric analysis, the IHX plays a fundamental role in fluids with a positively inclined upper limit curve, allowing for a significant reduction in lamination losses (as well as avoiding the compression of the liquid–vapour mixture). For water (as well as for alcohols and ammonia), on the other hand, no component is included to resolve the lamination loss issue, which is primarily felt at low evaporation temperatures. In fact, even when evaporating at 120 °C, the COP of water is higher than that of o-xylene.
5. Discussion and Conclusions
The selection of the working fluid is a crucial aspect in the design of a heat pump, with its choice being subject to numerous factors. The thermodynamic performance is not the only requirement to be considered; these fluids have to be evaluated alongside the safety and environmental prescriptions subjected to several legislative limitations. In this perspective, a careful selection of fluids usable in high-temperature heat pumps has been carried out, favouring natural fluids not subject to legislative limitations. However, synthetic fluids have also been examined, which currently represent the state of the art for high-temperature heat pumps. The future of this refrigerant family, including HFCs, HFOs, and HCFOs, is particularly uncertain. Restrictions on GWP (the current limit of which is 150, though this is expected to decrease) practically exclude all HFCs from use in HTHPs. At the same time, it seems that the industrial sector is heavily shifting towards other types of synthetic fluids without realising the significant environmental issues associated with TFA and PFAS. Our analysis deliberately chose not to exclude fluids that did not comply with legal terms a priori; between the six synthetic fluids tested, HFC R365mfc, with a GWP of 804, could not be used at all due to F-gas regulations. However, the obtained results show that this fluid provides the best performance in high-temperature applications (among synthetic refrigerants); compared, for example, with HFO R1336mzz(Z) and R1234ze(Z), it offers a higher COP of 5 and 15%, respectively. Considering that industrial HTHPs should operate continuously throughout the year, choosing fluids with lower performance does not seem like a wise choice, especially if a high-GWP fluid is replaced by another synthetic fluid with still-unclear environmental and human health repercussions. Moreover, it is worth considering that in national contexts where electricity is still conventionally produced using fossil fuels, the indirect emissions resulting from increased consumption (lower performance at the same output provided) would not be negligible at all. Under these perspectives, parameters that consider the entire life cycle of the refrigerant should be taken into stronger consideration. In this sense, an important role should be acquired by TEWI, which encompasses GWP but also takes into account the fluid’s usage context.
All this being said, the direction of natural refrigerants seems to be strongly marked. However, natural fluids also have specific issues, which are mainly safety-related, as well as environmental. Many of the natural fluids tested are hydrocarbons and thus are flammable and sometimes, as in the case of aromatics, particularly toxic. The “case” of ammonia, however, is an example of how a “dangerous” fluid can be managed safely if its thermodynamic characteristics demonstrate its clear superiority over other fluids. Therefore, the interesting results in terms of performance of innovative fluids such as alcohols (methanol and ethanol), aromatic hydrocarbons (primarily xylenes), acetone, and high-carbon cycloalkanes (cyclohexane and cyclopentane) should be interpreted in this light. As already emphasised, there is no optimal fluid in all fields, and in fact, all of these suffer from technical problems related to compressor selection (high compression ratios and large dimensions required due to low characteristic densities).
Increasing the temperatures at which the fluids must operate is beneficial if there is an overall shift in both thermal levels, both at the condenser and at the evaporator. The thermodynamic optimum in terms of performance (COP) occurs, for all fluids, when they condense at temperatures between 85 and 90% of their critical temperature, benefiting from the decrease in compression ratios and the consequent decrease in power absorbed by the compressor. Therefore, industrial applications that offer the possibility of using waste heat sources at temperatures above 100 °C would therefore be advantaged in terms of performance.
At the same time, however, increasing the condensation temperature (and therefore the thermal output) without a parallel increase in the evaporation temperature results in drastic decreases in the cycle’s COP. The need to cope with high compression ratios does require the implementation of multistage configurations but also a resolution of problems such as the high compressor discharge temperature and the high degree of flash loss. The latter turns out to be the bottleneck for all fluids characterised by a “skewed” limit curve, and this can be remedied by using an internal heat exchanger (as carried out in this work), which is also necessary to prevent liquid formation inside the compressor. This component, on the contrary, does not provide an improvement in performance in all those fluids characterised by “bell-shaped” limit curves (such as water, alcohols, and ammonia), so the flash loss for the latter leads to slightly lower COPs compared with those for xylenes and cycloalkanes. Remedying this problem is of primary importance in both cases, and solutions can range from the use of a fluid separator to advanced solutions such as ejection recovery systems. In particular, the latter could be the only viable option given the flammability issue of many of these fluids. Using a component like a separator, which collects a considerable amount of fluid, could conflict with current laws limiting the amount of highly flammable refrigerant charge within the reverse machine.
Conversely, water does not pose any concerns regarding flammability. Its versatility allows an exploration of all available plant configurations without precluding any. Moreover, if there is a need to go to high temperatures beyond 240 °C, water is 1 of the 4 fluids (out of the total of 25) capable of working at such levels (in a subcritical configuration). Considering that cyclohexane has the problem of a low auto ignition temperature, and aromatic hydrocarbons are characterised by high COPs but also a low latent heat of condensation, in industrial applications requiring fluid evaporation (the chemical or paper industry), water would be advantageous in terms of flows at the same required power (the densities of these fluids are comparable to that of water).
The major problem for this fluid is obviously its low density, especially at low temperatures, which necessitates the use of a particularly high number of compression stages (up to six) if it is necessary to evaporate at such thermal levels. Since the problem does not exist when high-temperature heat sources are available, it might be convenient to explore the possibility of configuring a cascading HTHP, using more suitable fluids for low thermal levels in the lower cycles.
The modelling and comparative analysis presented in this study indicate that different working fluids are preferable at various temperature ranges. For low temperatures (HTs), such as those encountered in certain applications, ammonia emerges as the preferred choice. At medium temperature levels (VHTs), alcohols like methanol or ethanol exhibit advantages. Conversely, for ultra-high-temperature (UHT) applications, water emerges as the optimal fluid choice. These findings are succinctly summarised in
Figure 14.
In conclusion, the analysis conducted in this study represents the initial groundwork necessary to establish a robust foundation for further investigation. Subsequent endeavours should include comprehensive life cycle assessments, economic analyses, and specific case studies, taking into consideration various cycle configurations. These efforts will build upon the already promising findings uncovered in this study, contributing to a deeper understanding of the subject matter.