1. Introduction
Improved power factor means that, in a defined part of the installation, the necessary steps are taken to increase the power factor by locally delivering the necessary power to reduce current values and power flows through the upstream network with the same output power required. In this way, lines, generators, and transformers can be sized to lower power. The size of generators and transformers depends on the apparent power. At the same active power, the smaller the reactive power provided, the smaller the apparent power. Therefore, by improving the power factor, this equipment can be sized for less apparent power, but still provide the same active power. The devices that produce reactive power are synchronous generators, synchronous condensers, static VAR compensators, and capacitors banks [
1,
2].
The shunt compensation with capacitors banks of the reactive power can be used at load level, power substations, or transmission (at various voltage levels from low voltage to high voltage). Compensation must be provided as close to the consumption point as possible, in order to avoid the distribution of this power elsewhere in the network.
From a strictly technical point of view, even a suitable size installation can work properly in the case of low power factors. However, improving the power factors is a solution that can achieve technical and economic benefits and, in fact, managing low-cost installations will increase costs for power generation [
3,
4,
5,
6].
The main advantages of power factor correction can be summarized as follows: better use of electrical machines, better use of electrical lines, loss reduction, and lower voltage drops.
The correction of the power factor also allows us to obtain benefits for the size of the cables. In fact, at the same output power, the current decreases by increasing the power factor. This current reduction can enable the selection of conductors with lower cross section areas.
There are no general rules for all types of installations and, in theory, capacitors can be installed at any place, but the appropriate practical and economic feasibility must be assessed. The main methods of improving power factor correction depend on the position of the capacitors banks, as follows: the distribution power factor correction, the group power factor correction, the central power factor correction, the combined power factor correction, and the automatic power factor correction. According to the literature, improving the power factors in power engineering can lead to cost savings of 10 to 30% [
7,
8,
9,
10,
11].
Power factor is related to the power quality. Currently, linear and non-linear consumers are connected to power substations (due to switching sources), which, together with the capacitors (used to improve the power factor), cause current distortion (power quality is affected). In practice, the voltage is not perfectly sinusoidal. The harmonic currents generated by the load will circulate in the circuit through the impedance of the source and all other branches in parallel. Consequently, harmonic voltages will appear on the impedance of the power supply and they will be present everywhere in the installation. The main equipment that produce harmonics are personal computers, LED lamps, fluorescent and gas expanding lamps, static converters, variable speed drives, welding machines, and arc and induction furnaces [
12].
The presence of harmonics (currents or/and voltages) in electrical networks may cause equipment failure, such as the overloading of neutral conductors, increasing transformer losses, and causing torque disturbances in motors. More important problems occur when distortions reach high values and the danger of resonances between power factor correction systems and electrical networks are present [
13,
14].
In three-phase systems, the capacitors bank is composed of three capacitors with the same capacity and can have wye or delta connections. The capacitors banks can be combined with the inductors to limit the harmonic on the network and reduce inrush currents. In fact, the combination capacitor–inductor forms a harmonic filter. In this way, the component inductors–capacitors provide a very low reaction in correspondence to the elimination of harmonics that circulate in the component without affecting the entire network. Also, to limit the distortion of the current, AC reactors can be used that are connected in series with the electrical consumers [
15,
16,
17,
18,
19].
Normally, two options are used to solve power quality problems (non-sinusoidal current), as follows: passive power factor correction (to improve power factor by filtering harmonics with passive filters) and active power factor correction (using a switching converter to modulate distorted waves and shape them into sine waves). For ordinary electrical consumers who have a switching source, a power factor correction circuit is added to the energy supply circuit to increase the power factor and/or reduce the harmonics. There are three power factor correction techniques: passive with reactors, active that controls a current at high frequency using a switching device, and partial switching with switching devices to regulate currents several times per mains cycle and whose applications are limited [
20,
21].
Power passive filters can be used to improve power factors in electrical systems. It is difficult to use passive filters to increase power factor and to decrease deformation (currents) because they must also take into account consumer specificities (linear or non-linear, capacitive or inductive characteristics). Reactive power and negative sequence currents generated by inductive unbalanced loads not only increase line losses, but also cause relay protection devices to fail due to negative sequence components of the power grid, threatening the safe operation of the power system. Reactive power compensation and unbalance suppression were achieved in three-phase wye connectors, with complex electronic structures for inductive unbalanced electric consumers [
7,
14,
22,
23].
Real-time control of the reactive power is currently the most efficient solution to avoid voltage fluctuations and maintain the standard limits. For this purpose, capacitors banks, reactors, synchronous generators, synchronous condensers, and FACTS (Flexible Alternating Current Transmission Systems) installations are used. Types of FACTS installations are SVC (Static VAR Compensator), STATCOM (Static Synchronous Compensator), SSCR (Switched Shunt-Capacitor and Reactor), UPFC (Unified Power Flow Controller) and D-STATCOM (Distribution STATCOM) that provide control of reactive power to obtain voltage stabilization and ensure mitigation solutions for voltage changes, swelling, interruptions, and flashes. These solutions are usually used for medium and high voltages. For the power substation, the most common solution for improving the power factor is the use of capacitors banks controlled by a power factor controller (which makes the adjustment according to the displacement power factor) mounted in the point of common coupling [
24,
25,
26].
This paper is divided into five sections. The second section is about materials and methods and presents theoretical aspects about electrical parameters used in the deforming regime and the power factor controller with capacitors banks used for improving power factors. The third section presents the experimental results (20 groups of experiments) with capacitors (without coils connected in series), AC reactors, and LC shunt filters. The fourth section is a detailed discussion about the use of power factor controllers in different conditions. Conclusions on the use of the power factor controller are presented in the last section.
3. Results
The purpose of the experimental measurements is to analyze the operation of the PFC with different numbers of capacitors banks (from 2 to 6 stages), when using the same values or different values for the capacitors banks, and when using the capacitors banks connected to coils (each terminal of the capacitors bank is in series with a coil).
To experimentally analyze the PFC (Roederstein ESTAmat RPR type, Vishay), two induction motors (inductive character, linear) and two compact fluorescent lamps (CFLs, capacitive character, non-linear consumers) were used (
Figure 4) which connected to the installation in
Figure 2. The characteristics of consumers are as follows:
M1, three-phase induction motor with the following data (ASI 90L-24-2 type): 2.2 kW; 2780 rpm; 400 V; 4.95 A; PF = 0.855;
M2, three-phase induction motor with the following data (N 80 L type): 750 W; 1450 rpm; 400 V; 2.13 A; PF = 0.72;
Compact fluorescent lamps, connected in parallel on the phase where CT (15/5 A, SM 5VA, Metra type) is also connected with the following data: CFL1: 220 V, 50 Hz, 85 W, 6400 K; CFL2: 220–240 V, 50/60 Hz, 120 W, 580 mA, 4000 K.
Figure 4.
The electrical consumers used in the experiments depicted in the diagram in
Figure 2 [
27].
Figure 4.
The electrical consumers used in the experiments depicted in the diagram in
Figure 2 [
27].
Induction motors work without mechanical loads to have a power factor as low as possible and the two CFLs work in parallel. Consumers can be connected manually through electrical separators (S1, S2, S3—
Figure 4). The measurements were made with a power quality analyzer (CA 8334B type, Chauvin-Arnoux).
The main electrical characteristics of the consumers used in the experiments are listed in
Table 1. In all the tables, the quantities have the following meanings: P—active power; Q—reactive power; S—apparent power; PF—power factor; DPF—displacement power factor; THDc—total harmonic distortion for current. In all the tables, for Q, PF, and DPF, for the numerical values, i represents the inductive character and c represents the capacitive character.
Figure 5 shows a view of the experimental setup used in the experiments.
In the following tables i represents the inductive character, and c represents the capacitive character of the loads.
Although it also measures the deforming regime of voltage and current, PFC ensures the regulation of capacitors banks according to the displacement power factor (DPF). It would be impossible for the PFC to improve the PF in the installation by introducing CBs, under the conditions that, by connecting the CBs, it determines the pronounced deformation of the current and the PF decreases (all the more as the deforming regime increases). From a practical point of view, it is not possible to ensure a fine adjustment of the DPF in the electrical installation (due to the stages to which the CBs are connected), but it is possible to ensure an adjustment in stages (depending on the combination of CBs).
During the experiments, all the capacitors used were new (they have very low dielectric loss) and were working at 450 V, 50 Hz. The neutral power factor for low voltages is 0.9, value adjusted at PFC. In experiments, wye connection for CBs were used.
With Equation (11) and with the data from
Table 1, the (theoretical) capacities of the capacitors (on a branch of the wye-connected bank) that must be inserted in parallel with the inductive consumers were determined as follows:
for Uf = 220 V, f = 50 Hz: for electric motor M1: CM1 = 35.57 µF; for the electric motor M2: CM2 = 18.01 µF, and when the two motors are operating, the total capacity CM = 53.58 µF;
for Uf = 230 V, f = 50 Hz: for electric motor M1: CM1 = 32.55 µF; for the electric motor M2: CM2 = 16.47 µF, and when the two motors are operating, the total capacity CM = 49.02 µF.
Using Equation (11), the equivalent capacity was determined for CFLs:
for Uf = 220 V, f = 50 Hz: CCFLs = 7.76 µF;
for Uf = 230 V, f = 50 Hz: CCFLs = 7.1 µF.
Table 2 shows some examples of combinations of electrical consumers (M1, M2, and/or CFLs) together with capacitors (on phase L1) that ensure a certain DPF.
The power factor controller (Roederstein ESTAmat RPR type, Vishay; software version 4.1.2) used in the experiments is a typical regulator (measurement of current on a single phase through a CT; with identification of CBs values; DPF adjustment using a single CT; timed switch on/switch off of CBs; identification of the pronounced deforming regime in the case of connecting a certain CB; possibilities to adjust the DPF according to a set value; multiple display), which is commonly used in power substations (where inductive consumers are connected, usually in industry) for improving the power factor in low-voltage electrical installations. Depending on the DPF value on phase L1 (the phase difference between the fundamental voltage and the fundamental current), the regulator timed switch on or switch off of one or several CBs. From a practical point of view, the PFC can have between 6 and 14 stages and the CBs can be identical or different (on one CB there are identical capacitors in wye or delta connection). An example of the worsening of the deforming regime when the displacement power factor is improved is presented in
Figure 6.
When supplying voltage to the PFC, a calibration (value, symmetry) of the CBs on each stage is performed. Obviously, if there is no CB connected to a certain step, it is not taken into account in the adjustment. The identification of the connected CBs is carried out three times, in an interval of approx. 3 min.
In order to carry out the calibration, it is necessary to connect an electrical consumer in the installation. During several experiments, calibrations were made with linear consumers (e.g., induction motors) or with non-linear consumers (e.g., CFLs). It was found that the capacitors banks are correctly identified, regardless of the type of electrical consumer (linear or non-linear) used for calibration (at the beginning of the PFC’s operation).
The transformation ratio of the current transformer (CT) must be chosen in such a way (depending on the consumers and the CBs) that the current in the secondary CT is not less than 150 mA and does not exceed 5 A. A CT 15A/5A (Metra) was used for the experiments.
Several experiments were carried out to identify the operation of the PFC with different numbers of CBs (identical or not), when using coils in series per phase (
Figure 3) and when using coils in series with capacitors banks (LC shunt filters,
Figure 7). The main quantities monitored during the experiments were DPF (quantity according to which the adjustment is made by the PFC) and total harmonic distortion for the current (THDc).
In the following, the experiments refer to the capacitors on a branch from the bank in wye connection. In the vast majority of the cases analyzed, capacitors were used to compensate the reactive power of the consumers (in the worst case).
To make it easier to understand the results of the experiments, measurements are presented only for phase L1 for the current and for the voltage between L1 and null (N). A current transformer (CT,
Figure 2) is mounted on the L1 phase, which has a secondary connection to the PFC, where the current is measured, which ensures the connection of the capacitors banks (wye connections).
3.1. Connecting Consumers without PFC and without Capacitors Banks
A first experiment was carried out without PFC and without CBs, only with electrical consumers connected in a certain order (
Table 3).
Induction motors, being inductive and linear consumers, will cause a large phase shift (DPF has very small values) between voltage and current (current follows the voltage), and THDc has values of the order of percentages (current is more distorted than voltage).
If CFLs are introduced in parallel with IMs, which have a capacitive and non-linear character, they will cause a slightly smaller phase shift between voltage and current (DPF has small values), and the current will be more distorted (compared to the previous situation).
Next, when the value of a capacitor is specified, it refers to the capacitor on a branch of a capacitors bank in wye connection.
3.2. Single-Step PFC, C1 = 54 μF
In these experiments, a single stage was connected with a capacitor (on the branch) of 54 µF (
Table 4).
The use of a single CB leads to the impossibility of adjusting the DPF in the installation where the DPF is modified within wide limits. A high-capacity CB also introduces a greater distortion of the current (high THDc) in the situation where only inductive consumers are connected. If non-linear and capacitive consumers are connected, THDc decreases.
If the capacitive reactive power is too high, the bank is not connected into the circuit.
If the two induction motors are used, the PFC connects the capacitors bank. The capacity, being large, will determine a large DPF, the current drops considerably, but the current will be highly distorted (high THDc).
By introducing CFLs, the DPF increases and the THDc decreases almost by half (and due to the diversity affect that can determine this effect).
3.3. Single-Step PFC, C1 = 54 µF and AC Reactor of 9 mH
In the following experiments, a phase coil was used, inserted with consumers and CB (
Table 5). A single capacitors bank was used.
If it is connected into circuit M1, by inserting CB (using the PFC), this having high capacitors, the character of the consumers will be capacitive and the current will be distorted (THDc = 52.3%).
If M2 is also connected, the current becomes lower, the DPF will be high (inductive character), but the current will be very distorted.
If CFLs are also connected, the DPF will have a maximum value, and the current will be very distorted (THDc = 62.6%).
By disconnecting M2, the remaining consumers will have a capacitive character and the current will be distorted. When using some coils inserted with the consumers, the absorbed currents will be more distorted (higher THDc) compared to the experiments from
Section 3.2. It is mentioned that the usual adjustment of the DPF is carried out in the inductive range (e.g., if the DPF has been set to 0.9, the PFC adjusts the DPF in the inductive range 0.9–0.99).
3.4. Single-Step PFC (Stage 1), LC Shunt Filter LC, C = 54 µF, L = 9 mH
The PFC does not immediately connect (case a,
Table 6) the LC shunt filter (f = 228.3 Hz) but does so after a period of time (case b in
Table 6). If a filter is used and connected in parallel with the consumers, it is found that THDc increases and DPF decreases.
3.5. PFC with Two Identical Steps, C1 = 20 μF, C2 = 20 μF
If two stages are used, with identical CBs, a finer adjustment of the DPF can be achieved (it has both inductive and capacitive values) compared to the previous situation (
Table 7).
By using two identical CBs, finer adjustment of the DP is not obtained and the current will be equally distorted (high THDc). Larger capacities will lead to greater current distortion. However, in this situation there is an under-dimensioning of the CBs.
3.6. PFC with Two Different Steps, C1 = 20 μF, C2 = 40 μF
If two different steps are used (
Table 8), an adjustment of the DPF can be made (it has values in the inductive as well as capacitive character), but THDc has higher values compared to
Section 3.5.
3.7. PFC with Three Identical Steps, C1 = 20 μF, C2 = 20 μF, C3 = 20 μF
When three identical CBs are used (
Table 9), a DPF of high values is not obtained (
Table 9). Since the CBs are identical, a finer adjustment cannot be achieved compared to
Section 3.6.
Surprisingly, by using three identical CBs, the DPF has lower values than in
Section 3.6, but the current will be less distorted.
In all situations, the current is distorted, having large harmonics, the largest being 3, 5, 7, 9, 13, etc. When using only electric motors, the third harmonic is much reduced.
3.8. PFC with Three Different Steps, C1 = 10 μF, C2 = 20 μF, C3 = 30 μF
When CBs of different values are used (but which have the same reactive power as in
Section 3.7), the PFC works better, the DPF has an inductive character only (
Table 10). When CBs of large values are introduced and electric motors are used, then the current is distorted the most (high THDc).
Three CBs of different values will result in better DPF tuning, but THDc will be higher.
3.9. PFC with Three Identical Steps, C1 = 20 μF, C2 = 20 μF, C3 = 20 μF and AC Reactor of 9 mH
When using the PFC with three identical CBs, together with AC reactors, a DPF is obtained that is both inductive and capacitive (
Table 11).
The DPF has higher values compared to the case in
Section 3.7 and the THDc has lower values (by 3–5%).
3.10. PFC with Three Different Steps, C1 = 10 μF, C2 = 20 μF, C3 = 30 μF and with AC Reactor of 9 mH
The combined use of PFC with three different stages and with AC reactors leads to DPF with only inductive character (
Table 12). THDc will have higher values when only electric motors are used and will have lower values when combinations of consumers are used compared to
Section 3.7.
3.11. PFC with Five Different Steps, C1 = 1.9 μF, C2 = 4 μF, C3 = 8 μF, C4 = 16.9 μF, C5 = 31.9 μF
Five different capacitors banks connected at five stages to the PFC are used. The values of the capacitors were chosen so that they are (approx.) twice the other, with the aim of obtaining a smaller number of steps. In this situation, inductive DPFs were obtained with values above 0.92 (
Table 13). When the M2 motor was disconnected, steps 2,3,4 were initially connected (case a), then, after a period of time (case b), steps 1,2,3,4 were connected.
THDc has high values when using electric motors and values are reduced by half when using a combination of electrical consumers. Higher capacity CBs lead to higher current distortion.
When only electric motors are used, high harmonics are recorded, fitting with the 5th order.
When a combination of consumers is used, the amplitudes of the harmonics decrease (due to the diversity effect).
3.12. PFC with Six Identical Steps, C1 = C2 = C3 = C4 = C5 = C6 = 10 µF
The use of six identical CBs leads to an inductive DPF adjustment with values above 0.93. THDc has 10–15% lower values compared to using five-stage PFC (
Table 14).
3.13. PFC with Six Steps with Different Capacitors, C1 = 1.9 μF, C2 = 2.5 μF, C3 = 4 μF, C4 = 10 μF, C5 = 15 μF, C6 = 20 μF
When using the PFC with six different CBs, an adjustment of the inductive DPF over 0.9 was obtained (
Table 15). THDc has high values, compared to the measurements made in
Section 3.11.
By using six stages with different CBs, DPF adjustment is obtained, but THDc will have high values when IM is connected.
When electric motors are used, the harmonics starting with rank 5 will have high values.
With the combined use of electrical consumers, the third order harmonic increases, but the higher order ones decrease.
3.14. PFC with Three Steps with LC Shunt Filters, Case 1
In the following experiments, LC filters were introduced instead of CBs (
Table 16). The values are as follows:
Step 1 (Filter LC 1): L1 = 97.07 mH; C1 = 10 µF; If1 = 0.74 A; f = 161.54 Hz;
Step 2 (Filter LC 2): L2 = 26.42 mH; C2 = 20 µF; If2 = 1.43 A; f = 218.94 Hz;
Step 3 (Filter LC 3): L3 = 15.48 mH; C3 = 30 µF; If3 = 2.24 A; f = 233.54 Hz.
Consumer Status | Connected Steps | DPF (-) | I (A) | THDc (%) | Figure |
---|
Connection M1 + M2 | 2,3 | 0.86 i | 0.992 | 103.7 | Figure 37 |
Connection CFLs | 2,3 | 1 | 1.42 | 49.9 | Figure 38 |
Disconnection M2 | 2,3 | 0.98 i | 1.22 | 60.4 | Figure 39 |
Disconnection CFLs | 3 | 0.73 i | 0.583 | 78.6 | |
Inductive DPF was obtained in all cases, but the filters did not reduce THDc.
A decalibration of the coils and, implicitly, of the filters will lead to a lower value DPF and a THDc of over 100%.
Current harmonics are large for ranks 3, 5, 7, 9, etc.
3.15. PFC with Three Steps with LC Shunt Filters, Case 2
In the following experiments, LC filters were introduced instead of CBs. The values are as follows:
Step 1 (Filter LC 1): L1 = 97.07 mH; C1 = 10 µF; If1 = 0.74 A; f = 161.53 Hz;
Step 2 (Filter LC 2): L2 = 10.81 mH; C2 = 20 µF; If2 = 1.42 A; f = 342.29 Hz;
Step 3 (Filter LC 3): L3 = 24.26 mH; C3 = 30 µF; If3 = 2.3 A; f = 186.55 Hz.
In all experiments, the inductive DPF is adjusted. When only electric motors are used, THDc is reduced considerably (by tens of %)—
Table 17.
When using consumers, the filters can amplify some harmonics (e.g., of the 5th order).
3.16. PFC with Three Steps with LC Shunt Filters, Case 3
In the following experiments, LC filters were introduced instead of CBs (
Table 18). The values are as follows:
Step 1 (Filter LC 1): L1 = 10.78 mH; C1 = 20 µF; If1 = 1.45 A; f = 342.76 Hz;
Step 2 (Filter LC 2): L2 = 10.78 mH; C2 = 20 µF; If2 = 1.45 A; f = 342.76 Hz;
Step 3 (Filter LC 3): L3 = 10.78 mH; C3 = 20 µF; If3 = 1.45 A; f = 342.76 Hz.
Consumer Status | Connected Steps | DPF (-) | I (A) | THDc (%) |
---|
Connection M1 + M2 | 1,3 | 0.42 i | 1.31 | 65.9 |
Connection CFLs | 1,3 | 0.76 i | 1.69 | 54.1 |
Disconnection M2 | 1,3 | 0.97 c | 1.3 | 73.9 |
Disconnection CFLs | 1,3 | 0.92 c | 0.6 | 142.7 |
Lower values of coil inductances can lead to a decrease in DPF (inductive and capacitive character) and a slight increase in THDc (
Table 18).
3.17. PFC with Six Different Steps with LC Shunt Filters
In the following experiments, LC filters were introduced instead of CBs (
Table 19). The values are as follows:
Step 1 (Filter LC 1): L1 = 97.07 mH; C1 = 4 µF; f = 255.41 Hz;
Step 2 (Filter LC 2): L2 = 97.07 mH; C2 = 5 µF; f = 228.45 Hz;
Step 3 (Filter LC 3): L3 = 26.42 mH; C3 = 11.9 µF; f = 283.84 Hz;
Step 4 (Filter LC 4): L4 = 15.48 mH; C4 = 16.9 µF; f = 311.16 Hz;
Step 5 (Filter LC 5): L5 = 24.26 mH; C5 = 7,5 µF; f = 373.11 Hz;
Step 6 (Filter LC 6): L6 = 47 mH; C6 = 10 µF; f = 232.15 Hz.
Consumer Status | Connected Steps | DPF (-) | I (A) | THDc (%) |
---|
Connection M1 a | 4–6 | 0.7 i | 0.63 | 101.3 |
Connection M1 b | 2,4–6 | 0.99 i | 0.58 | 116.6 |
Connection M2 a | 2–6 | 0.75 i | 1 | 105.6 |
Connection M2 b | 1–6 | 0.92 i | 0.979 | 108.5 |
Connection CFLs | 2–6 | 0.97 i | 1.62 | 88.1 |
An inductive DPF was obtained, but the THDc has very high values (
Table 19).
The use of a greater number of stages, which also fulfill the function of LC filters, will not lead, at the same time, to the increase in the DPF and to the decrease in the deforming regime.
3.18. PFC with Six Different Steps with LC Shunt Filters
In the following experiments, LC filters were introduced instead of CBs (
Table 20). The values are as follows:
Step 1 (Filter LC 1): L1 = 11.45 mH; C1 = 10 µF; f = 470.58 Hz;
Step 2 (Filter LC 2): L2 = 11.45 mH; C2 = 10 µF; f = 470.58 Hz;
Step 3 (Filter LC 3): L3 = 11.45 mH; C3 = 10µF; f = 470.58 Hz;
Step 4 (Filter LC 4): L4 = 63.6 mH; C4 = 10 µF; f = 199.66 Hz;
Step 5 (Filter LC 5): L5 = 63.6 mH; C5 = 10µF; f = 199.66 Hz;
Step 6 (Filter LC 6): L6 = 63.6 mH; C6 = 10 µF; f = 199.66 Hz.
Consumer Status | Connected Steps | DPF (-) | I (A) | THDc (%) |
---|
Connection M1 + M2 | 1–5 | 0.86 i | 0.393 | 80.4 |
Connection CFLs | 1–5 | 0.99 i | 1.49 | 61.9 |
Disconnection M2 | 3–5 | 0.99 i | 1.35 | 69 |
Disconnection CFLs | 3–5 | 0.69 i | 0.581 | 95.5 |
When adjusting the DPF, only inductive characteristics were obtained and THDc decreased (by 15–20%) compared to the previous case (
Table 20).
The results are better than in
Section 3.18. DPF is higher (above 0.69) and THDc is lower (below 96%).
3.19. PFC with Six Steps with Capacitors and AC Reactor of 3 mH
CBs were used in the following experiments and AC reactors were introduced in series with the consumers. The values are as follows:
Step 1: C1 = 4 µF;
Step 2: C2 = 5 µF;
Step 3: C3 = 11.9 µF;
Step 4: C4 = 16.9 µF;
Step 5: C5 = 7.5 µF;
Step 6: C6 = 10 µF.
In the analyzed situations, DPFi had an inductive character (with values over 0.96), and THDc had lower values compared to the use of LC filters (
Table 21).
It is a combination between the coil inserted with consumers and capacitors C. The capacity of the capacitors when using L-C filters must be chosen 10–15% higher compared to the case of using only single capacitors banks.
3.20. PFC with Six Steps with LC Shunt Filters and AC Reactor of 3 mH
In the following experiments, LC filters were introduced instead of CBs and AC reactors were introduced in series with the consumers. The values are as follows:
Step 1 (Filter LC 1): L1 = 47 mH, C1 = 4 µF, f = 367.25 Hz;
Step 2 (Filter LC 2):L2 = 26.29 mH, C2 = 5 µF, f = 439.2 Hz;
Step 3 (Filter LC 3):L3 = 15.48 mH, C3 = 11.9 µF, f = 371 Hz;
Step 4 (Filter LC 4):L4 = 26.42 mH, C4 = 16.9 µF, f = 238.3 Hz;
Step 5 (Filter LC 5):L5 = 24.26 mH, C5 = 7.5 µF, f = 373.11 Hz;
Step 6 (Filter LC 6):L6 = 97.07 mH, C6 = 10 µF, f = 161.62 Hz.
In the analyzed situations, DPF had an inductive character, but THDc has higher values compared to the previous cases (
Table 22).
The combined use of AC reactors and LC filters is not recommended for a PFC with a large number of stages.
4. Discussion
The most common PFCs are those that have a large number of stages (6–14) of capacitors that can be connected in the electrical installation and that are intended for DPF regulation in three-phase installations. Typically, these PFCs measure (via a CT) the line current and a phase voltage to determine the DPF. The improvement of the power factor of these PFCs is achieved by obtaining a DPF above a certain preset value (e.g., the neutral power factor). In deforming mode, things are more complicated because there are differences between the power factor and DPF (the more deforming the regime, the bigger the difference between PF and DPF). Obviously, the number of steps is chosen depending on the number, type, and operating mode of the consumers that are supplied from the power station. A large number of steps can ensure a finer adjustment of the DPF, but it decreases the reliability of the entire installation (it becomes more complex, with more switching and protection equipment and more CBs). Usually, the PFC works properly when an inductive DPF (not capacitive) is obtained with values higher than the preset value (0.9).
In the following (
Table 23,
Table 24 and
Table 25), the experimental measurements from
Section 3 are presented, depending on the connection of consumers used in the experiments, DPF and THDc, after which PFC introduced CBs or LC filters.
A relatively fine adjustment of the DPF can be obtained even if there are fewer steps (e.g., three steps with different CBs). With one stage (with a high capacity per stage), two stages (identical or different), or three identical stages, DPF can be obtained several times. Under these conditions, the use of coils inserted when one, two, or three stages are used does not result in a decrease in THDc (it can even result in an increase of 5 to 7%).
The DPF is best adjusted when using 5 and 6 steps, where, in all situations, an inductive DPF is obtained. If 6 stages are used, all different, with capacities to compensate the inductive reactive power, in the most disadvantageous case (inductive consumers), slightly higher inductive DPFs are obtained, but also a higher THDc compared to the use of six identical stages.
An interesting case is the use of five different stages, where each stage has double the capacity of the other. In this case, inductive DPFs have slightly higher values than in the case of using the six-step regulator, but THDc is also higher. So, if it uses steps with double the capacity compared to each other, it can obtain an even better adjustment of the DPF than in the case of six steps (with different or identical values).
It is important to choose the values of the capacitors to improve the DPF when all the inductive consumers are connected. The use of deforming consumers that also have a capacitive character determines a slight improvement of the DPF.
If an LC shunt filter is used instead of a single stage, DPF can be lower and THDc higher, compared to the situation of a single stage (with high capacity) or a coil inserted with consumers and a single stage.
If PFC is used with three different stages, each stage having an LC shunt filter, it is possible to increase the DPF (above the value of 0.9) and decrease the THDc (by 5–7%). It is important to properly adjust the filters (quite difficult in practice), otherwise they can cause a slight increase in the DPF (does not reach 0.9) and an increase in the THDc (higher values compared to using only capacitors for the PFC). The use of LC filters, with identical capacitors leads to inductive and capacitive DPF, and the THDc can have higher values (compared to the use of LC shunt filters, with different capacities connected to the PFC).
It has been determined experimentally that the use of a large number of steps (e.g., 6) of LC shunt filters or combinations of coils inserted with consumers and LC shunt filters does not lead, at the same time, to the increase in DPF and to the decrease in THDc. With a large number of steps, it is more efficient to use AC reactors, compared to the use of LC filters on each step. Practically, it is difficult to tune several LC filters, and resonances can appear when the LC filters are operating in parallel. The best performances were achieved with three stages with LC filters, where the capacities have different values.
Some electrical consumers can be inductive, while others can have a capacitive character. Depending on the place where PFC is used in the power substations, there are, usually, three-phase linear electrical consumers (e.g., induction motors) or single-phase consumers (electric heaters), but there can also be three-phase non-linear consumers (e.g., variable frequency drives) and non-linear single-phase consumers (e.g., compact fluorescent lamps). Through the intelligent distribution of the various consumers on phases, an improvement of the DPF can be ensured, and perhaps a reduction in the THDc (the phenomenon of diversity also appears, which can reduce the THDc). For example, at a transformer substation that supplies many non-linear capacitive consumers (e.g., transformer substations that supply households and residential and educational institutions [
20]), a classic PFC with capacitors banks no longer proves its usefulness because, overall, consumers have a capacitive character with a high value DPF (0.9–1). At the same time, it must be taken into account that most consumers are single-phase ones that determine an unbalance on the three-phases in the point of common coupling of the installation and even a significant current through the neutral conductor (due to both the unbalance and the consumers non-linearity).
For classic PFCs that measure a single line current, it is important to choose the phase on which the CT is mounted (usually, it is mounted on the most loaded phase). Another important aspect concerns the choice of an optimal transformation ratio for the CT. A too-low value of the transformation ratio may exceed the maximum value of the current measured by the PFC, and a too-high value of the transformation ratio may determine a current below the sensitivity limit of the PFC (e.g., below 150 mA, the current is no longer measured correctly and the DPF adjustment is no longer performed correctly).
For unbalanced electrical networks that have slightly deforming consumers, it is recommended to use high-performance PFCs with a large number of capacitors banks (of different values, appropriately sized) that perform the regulation of the reactive power independently on each phase separately (by using three CTs mounted on each phase separately). The installation can also have AC reactors to reduce the deforming regime. The use of different steps, where each step has double the value of the other, can achieve the DPF adjustment with a smaller number of steps, and the reliability of the installation increases. A large number of steps reduces the reliability of the entire installation. For unbalanced electrical networks that have high deformation consumers, it is recommended to use a small number of PFCs (e.g., three) of high-performance LC filters (with different capacities in each phase) to control the reactive power independently in each phase (using three CTs mounted in each phase and measuring the DPF independently in each phase), while reducing (to some extent) the deformation regime.
To reduce the deforming regime, the combined use of AC reactors and LC filters is not recommended (even if they are sized appropriately for common operation, there is a high chance that the deforming regime will be amplified due the resonance).