Influences of Corrosive Sulfur on Copper Wires and Oil-Paper Insulation in Transformers
Abstract
:1. Introduction
2. Experiments
Type of Specimen | Description | Temperature (°C) | Aging Time t (h) | |||
---|---|---|---|---|---|---|
N1 | Nynas oil + bare copper + paper-wrapped copper | 130 | 72 | 144 | 216 | 288 |
N2 | Nynas oil + bare copper + paper-wrapped copper | 150 | 24 | 48 | 72 | / |
K1 | Karamay oil + bare copper + paper-wrapped copper | 130 | 72 | 144 | 216 | / |
N3 | Nynas oil + bare copper + paper-wrapped copper + passivator | 130 | 72 | 144 | 216 | / |
N4 | Nynas oil + insulation paper | 130 | 72 | 144 | 216 | / |
3. Results
3.1. Appearance of the Copper Wires and Insulation Paper
3.2. SEM of Copper Wires and Insulation Paper
3.3. XPS of Copper Wires and Insulation Paper
Element | Percentage of Element Content (%) | |||||
---|---|---|---|---|---|---|
Wire 1 | Wire 2 | Wire 3 | Wire 4 | Wire 5 | Wire 6 | |
C | 74.19 | 66.92 | 65.98 | 66.63 | 62.31 | 46.58 |
O | 18.43 | 20.33 | 22.26 | 21.66 | 21.50 | 19.38 |
S | 2.22 | 3.64 | 3.68 | 1.18 | 0.96 | 3.32 |
Cu | 4.28 | 9.11 | 8.08 | 6.43 | 10.16 | 18.55 |
Aging Time (h) | Percentage of Element Content (%) | |||
---|---|---|---|---|
C | O | S | Cu | |
72 | 73.72 | 17.74 | 4.43 | 4.10 |
144 | 48.56 | 23.78 | 15.14 | 12.51 |
216 | 56.05 | 14.53 | 14.48 | 14.945 |
3.4. Dielectric Properties of Insulating Oil
Aging Time (h) | N1 | K1 | N3 | N4 |
---|---|---|---|---|
72 | 0.0490 | 0.0385 | 0.0560 | 0.0490 |
144 | 0.1470 | 0.0490 | 0.0700 | 0.0665 |
216 | 0.2485 | 0.0700 | 0.0700 | 0.1155 |
Aging Time (h) | 130 °C | Aging Time (h) | 150 °C | ||
---|---|---|---|---|---|
N1 | K1 | N3 | N2 | ||
72 | 2.41 | 2.56 | 2.28 | 24 | 2.18 |
144 | 2.26 | 2.63 | 2.40 | 48 | 4.09 |
216 | 2.78 | 3.41 | 2.48 | 72 | 3.88 |
3.5. Dielectric Properties of Insulation Paper
Aging Time (h) | 130 °C | Aging Time (h) | 150 °C | |||
---|---|---|---|---|---|---|
N1 | K1 | N3 | N4 | N2 | ||
72 | 35.4 | 39.5 | 38.9 | 40.3 | 24 | 38.7 |
144 | 31.7 | 37.4 | 37.5 | 38.1 | 48 | 35.5 |
216 | 25.1 | 35.3 | 35.8 | 36.2 | 72 | 32.4 |
4. Discussion
Aging Time (h) | Insulation | Permittivity | Change (%) | |
---|---|---|---|---|
N4 | N1 | |||
216 | oil | 2.63 | 2.41 | 8.36 |
paper | 7.13 | 5.10 | 28.47 |
5. Conclusions
- (1)
- The amount of Cu2S deposition on insulation paper and copper wire surface increase with the aging time.
- (2)
- Sulfur corrosion of copper wires can reduce the permittivity of oil-paper insulation.
- (3)
- The electrical breakdown strength of oil-paper insulation with copper sulfide depositions declines greatly, and this would lead to internal insulation failure of transformers.
- (4)
- The results provide a basic investigation that could contribute to fault diagnosis of copper sulfur corrosion in power transformers.
Acknowledgments
References
- Okabe, S.; Kohtoh, M.; Amimoto, T. Investigation of electrostatic charging mechanism in aged oil-immersed transformers. IEEE Trans. Dielectr. Electr. Insul. 2011, 17, 287–293. [Google Scholar] [CrossRef]
- Lessard, M.C.; van Nifterik, L.; Masse, M.; Penneau, J.F.; Grob, R. Thermal aging study of insulating papers used in power transformers. IEEE Annu. Rep. Conf. Electr. Insul. Dielectr. Phenom. 1996, 2, 854–859. [Google Scholar]
- Kachler, J.; Höhlein, I. Ageing of cellulose at transformer service temperatures, part 1. Influence of type of oil and air on the degree of polymerisation of pressboard, dissolved gases and furanic compounds in oil. IEEE Electr. Insul. Mag. 2005, 21, 15–21. [Google Scholar] [CrossRef]
- Höhlein, A.; Kachler, J. Ageing of cellulose at transformer service temperatures, part 2. Influence of moisture and temperature on degree of polymerisation and formation of furanic compounds in free breathing systems. IEEE Electr. Insul. Mag. 2005, 21, 20–24. [Google Scholar] [CrossRef]
- Clark, F.M.; Raab, E.L. The detection of corrosive sulfur compounds in mineral transformer oil. In Presented at the Society Meeting, ASTM Publication: Philadelphia, PA, USA, 21–25 June 1948; pp. 1201–1210.
- Höhlein, I.; Heinzig, P.; Kachler, A.J. Transformer materials as a prerequistite for transformer reliability—knowledge, properties and limits. In Proceedings of International Council on Large Electric Systems (CIGRE), Paris, France, 2006.
- CIGRE WG A2-32: Copper sulphide in transformer insulation. ELECTRA 2007, 230, 12–17.
- Amimoto, T. Identification of affecting factors of copper sulfide deposition on insulating paper in oil. IEEE Trans. Dielectr. Electr. Insul. 2009, 16, 265–272. [Google Scholar] [CrossRef]
- Lewand, L.R. The role of corrosive sulfur in transformers and transformer oil. In Proceedings of the Sixty-Ninth Annual International Conference of Doble Clients, Boston, MA, USA, 2002.
- Singh, B.P.; Murthy, T.S.R.; Jayraman, G.; Adikesavulu, A.K.; Malik, J.M.; Bhageria, S.C.; Khan, M.I. Effect of mercaptan sulphur on insulation performance of HVDC converter transformers. In Proceedings of International Council on Large Electric Systems (CIGRE), Paris, France, 2006.
- Scatiggio, F.; Tumiatti, V.; Maina, R.; Tumiatti, M.; Pompili, M.; Bartnikas, R. Corrosive Sulfur in Insulating Oils: Its Detection and Correlated Power Apparatus Failures. IEEE Trans. Power Deliv. 2008, 23, 508–509. [Google Scholar] [CrossRef]
- Hajek, J.; Dahlund, M.; Pettersson, L. Quality of oil makes the difference. ABB discovers the solution to transformer breakdowns. ABB Rev. 2004, 3, 61–63. [Google Scholar]
- Wiklund, P.; Levin, M.; Pahlavanpour, B. Copper dissolution and metal passivators in insulating oil. IEEE Electr. Insul. Mag. 2007, 23, 6–14. [Google Scholar] [CrossRef]
- Scatiggio, F.; Pompili, M.; Bartnikas, R. Oils with presence of corrosive sulfur: mitigation and collateral effects. In Proceedings of the IEEE Electrical Insulation Conference, Montreal, Canada, 2009; pp. 478–481.
- Scatiggio, F.; Pompili, M.; Bartnikas, R. Effects of Metal Deactivator Concentration upon the Gassing Characteristics of Transformer Oils. IEEE Trans. Dielectr. Electr. Insul. 2011, 18, 701–706. [Google Scholar] [CrossRef]
- Nunes, J. The copper corrosion phenomenon. In Nynas Presentation at Nynas Naphthenics, Stockholm, Sweden, 2007; p. 5.
- Standard Test Method for Corrosive Sulfur in Electrical Insulating Oils; ASTM Standard D1275; Electrical Protective Equipment, Annual Book of ASTM Standards; ASTM Publication: West Conshohocken, PA, USA, 2001; Volume 10.03.
- Yasuda, M.; Goto, K.; Okubo, H.; Ishii, T.; Mori, E.; Masunage, M. Suppression of static electrification of insulating oil for large power transformer. IEEE Trans. Power Appar. Syst. 1982, 101, 4272–4280. [Google Scholar] [CrossRef]
- Insulating liquids–Test Method for Detection of Potentially Corrosive Sulfur in Used and Unused Insulating Oil; IEC Standard 62535, Edition 1.0; IEC: Geneva, Switzerland, 2008.
- Lance, R.L. Passivators, what they are and how they work. NETA World 2006, Spring. 1–3. [Google Scholar]
- Augusta, M.; Martins, G.; Gomes, A.R.; Pahlavanpour, B. Experimental study of a passivated oil corrosiveness, after depletion of the passivator. IEEE Electr. Insul. Mag. 2009, 25, 23–27. [Google Scholar]
- Kuffel, E.; Zaengl, W.S.; Kuffel, J. High Voltage Engineering Fundamentals, 2nd ed.; Butterworth-Heinemann: Oxford, UK, 2000. [Google Scholar]
© 2011 by the authors; licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution license (http://creativecommons.org/licenses/by/3.0/).
Share and Cite
Li, J.; He, Z.; Bao, L.; Yang, L. Influences of Corrosive Sulfur on Copper Wires and Oil-Paper Insulation in Transformers. Energies 2011, 4, 1563-1573. https://doi.org/10.3390/en4101563
Li J, He Z, Bao L, Yang L. Influences of Corrosive Sulfur on Copper Wires and Oil-Paper Insulation in Transformers. Energies. 2011; 4(10):1563-1573. https://doi.org/10.3390/en4101563
Chicago/Turabian StyleLi, Jian, Zhiman He, Lianwei Bao, and Lijun Yang. 2011. "Influences of Corrosive Sulfur on Copper Wires and Oil-Paper Insulation in Transformers" Energies 4, no. 10: 1563-1573. https://doi.org/10.3390/en4101563
APA StyleLi, J., He, Z., Bao, L., & Yang, L. (2011). Influences of Corrosive Sulfur on Copper Wires and Oil-Paper Insulation in Transformers. Energies, 4(10), 1563-1573. https://doi.org/10.3390/en4101563