2.1. System Description
The characteristics of the analyzed heating systems are proposed by Assotermica [
5] on the basis of the most widely used heating devices in the Italian territory. All the input data of the heating system layouts arise from an exhaustive statistical market analysis and are accepted by Assotermica as representative of the typical heating systems in the North of Italy.
The reference residential building is composed of 12 apartments, with an average net surface of about 65 m2 each, set out on three floors. The building lies in the Italian climatic zone E, characterized by 2101–3000 degree days. The heating season starts on 15th October and ends on 15th April.
To evaluate the most significant part of existing building stock, four different thermal envelopes have been considered, classified by construction period: new (year 2010), recent (year 2006), 1960s and 1930s. These structures constitute the most of the residential buildings in Northern Italy. The U-values of external structures are reported in
Table 1.
Table 1.
U-values [W/m2K] of external structures for the different construction periods.
Table 1.
U-values [W/m2K] of external structures for the different construction periods.
| 2010 | 2006 | 1960 | 1930 |
---|
Outer Wall | 0.31 | 0.36 | 1.32 | 0.84 |
Staircase-space wall | 0.33 | 0.37 | 1.25 | 1.17 |
Floor | 0.31 | 0.47 | 2.37 | 2.01 |
Roof | 0.30 | 0.43 | 1.49 | 1.46 |
Door | 0.80 | 0.80 | 1.32 | 1.32 |
Glass | 1.20 | 1.90 | 5.80 | 5.80 |
Window | 1.56 | 2.13 | 5.33 | 5.33 |
In the analysis of heating systems in the new building (year 2010) both independent and centralized natural gas fired generators are considered: the first one is installed inside each apartment and satisfies the required heat and DHW; the latter provides heat and DHW to the entire building and is installed in a dedicated room. For each independent and centralized plant, two generator types have been considered: traditional and condensing.
The heating system layouts are reported in
Figure 1 and
Figure 2. The heating systems are controlled by an external temperature probe; the internal temperature is controlled by a thermostat. In independent systems DHW production is instantaneous; instead in centralized ones there is a storage tank, kept at 60 °C to avoid the proliferation of Legionnaire’s bacteria. Integration of DHW production with a centralized solar plant has been considered both in independent and centralized systems coupled just with condensing generators.
Figure 1.
Independent heating coupled with a radiant floor system.
Figure 1.
Independent heating coupled with a radiant floor system.
Figure 2.
Centralized heating system.
Figure 2.
Centralized heating system.
The solar plant requires an additional pump (50 W), has an overall area of 20 m
2 and produces 60% of the DHW consumption with an efficiency of 48.4 % [
6]. In this case a different independent boiler that can be coupled with a storage tank is considered.
Table 2 summarizes the main technical data of the boilers: independent traditional (IT), independent condensing (IC), independent condensing with solar plant (IC*), centralized traditional (CT) and centralized condensing (CC).
Table 2.
Technical data of the considered boilers: independent traditional (IT), independent condensing (IC), independent condensing with solar plant (IC*), centralized traditional (CT) and centralized condensing (CC).
Table 2.
Technical data of the considered boilers: independent traditional (IT), independent condensing (IC), independent condensing with solar plant (IC*), centralized traditional (CT) and centralized condensing (CC).
| IT | IC | IC* | CT | CC |
---|
Maximum nominal heat input [kW] | 25.9 | 24.9 | 12.3 | 69 | 74.6 |
Maximum nominal heat output [kW] | 24 | 24 | 12 | 62.2 | 72.6 |
Minimum nominal heat input [kW] | 0.7 | 5 | 2 | 35 | 18.5 |
Minimum nominal heat output [kW] | 9.3 | 4.7 | 1.9 | 31.6 | 18.1 |
Fan electric power [W] | 41 | 43 | 28 | 70 | 72 |
Chimney losses with burner on max [%] | 6.4 | 2 | 2 | 7.8 | 2.3 |
Chimney losses with burner on min [%] | 12.1 | 1.7 | 2.2 | 11 | 1.7 |
Chimney losses with burner off [%] | 0.02 | 0.15 | 0.02 | 0.04 | 0.01 |
Casing losses [%] | 0.7 | 0.7 | 0.89 | 0.7 | 0.4 |
Two types of emitters are considered: high temperature (design temperature 65/55 °C) and low temperature (37.5/32.5 °C). The considered low temperature emitters are radiant floor. The energy consumption of the circulation pumps is also evaluated. In
Table 3 pump electrical powers for space heating are reported.
Table 3.
Analyzed heating systems and electric pumps consumption for space heating.
Table 3.
Analyzed heating systems and electric pumps consumption for space heating.
Description of Heating System | Nomenclature | Pumps’ Electric Power [W] |
---|
1. Independent traditional gas-fired boiler coupled with radiators | ITR | 40 |
2. Centralized traditional gas-fired boiler coupled with radiators | CTR | 248 |
3. Independent traditional gas-fired boiler coupled with radiant floor | ITRF | 105 |
4. Centralized traditional gas-fired boiler coupled with radiant floor | CTRF | 388 |
5. Independent condensing gas-fired boiler coupled with radiators | ICR | 45 |
6. Centralized condensing gas-fired boiler coupled with radiators | CCR | 248 |
7. Independent condensing gas-fired boiler coupled with radiant floor | ICRF | 115 |
8. Centralized condensing gas-fired boiler coupled with radiant floor | CCRF | 388 |
9. Independent condensing gas-fired boiler coupled with radiators and solar heating plant for DHW | IC*R+SHP | 45 |
10. Centralized condensing gas-fired boiler coupled with radiators and solar heating plant for DHW | CCR+SHP | 248 |
11. Independent condensing gas-fired boiler coupled with radiant floor and solar heating plant for DHW | IC*RF+SHP | 115 |
12. Centralized condensing gas-fired boiler coupled with radiant floor and solar heating plant for DHW | CCRF+SHP | 388 |
Independent systems, coupled with radiators, have only the built-in circulation pump [
7], with a three positions speed control. This type of pump switches off after 15 minutes from burner switch off. In independent systems coupled with low temperature emitters, a hydraulic disjunctor is necessary (
Figure 1). For this reason there are two pumps: the built-in generator pump, that works only when the burner is operating, and the secondary circuit pump (three positions speed control), that switches off after 15 minutes from burner switch off. In all centralized systems there is a hydraulic disjunctor: the primary circuit pump (three positions speed control) works only when the burner is operating, the secondary circuit pump has a variable speed control and switches off after 1 hour from burner switch off (
Figure 2).
Hereafter the analysis of heating systems in building dates back to 2006, 1960s and 1930s is reported. Effectuating a simple retro-fit, only independent and centralized heating systems with traditional or condensing boiler are considered, discarding radiant floor solution and solar plant integration. In 2006 buildings an increase of radiators surfaces is necessary to operate at the same temperatures of heating systems installed in new buildings (65/55 °C). An increase of emitter surfaces is not sufficient instead in 1960s and 1930s buildings, where is also necessary to increase emitter temperatures, from 65/55 °C to 80/70 °C. The increase of energy demand in 1960s and 1930s buildings requires centralized generators with higher nominal heat output,
Table 4; on the contrary the thermal output of independent systems is still sufficient. The pump electric powers for space heating are subsequently modified as reported in
Table 5.
Table 4.
Technical data of the considered boilers: centralized traditional installed in buildings dating back to 1960s and 1930s (CT 1960–1930) and centralized condensing installed in buildings dating back to 1960s and 1930s (CC 1960–1930).
Table 4.
Technical data of the considered boilers: centralized traditional installed in buildings dating back to 1960s and 1930s (CT 1960–1930) and centralized condensing installed in buildings dating back to 1960s and 1930s (CC 1960–1930).
| CT 1960–1930 | CC 1960–1930 |
---|
Maximum nominal heat input [kW] | 165 | 175 |
Maximum nominal heat output [kW] | 150 | 170 |
Minimum nominal heat input [kW] | 121 | 44 |
Minimum nominal heat output [kW] | 110 | 43 |
Fan electric power [W] | 170 | 229 |
Chimney losses with burner on max [%] | 7.8 | 2.3 |
Chimney losses with burner on min [%] | 11 | 1.7 |
Chimney losses with burner off [%] | 0.04 | 0.01 |
Casing losses [%] | 0.7 | 0.4 |
Table 5.
Electric pumps consumption [W] for space heating for the different construction periods.
Table 5.
Electric pumps consumption [W] for space heating for the different construction periods.
Heating System | 2006 | 1960 | 1930 |
---|
Independent traditional gas-fired boiler coupled with radiators (ITR) | 40 | 90 | 90 |
Centralized traditional gas-fired boiler coupled with radiators (CTR) | 319 | 583 | 472 |
Independent condensing gas-fired boiler coupled with radiators (ICR) | 45 | 90 | 90 |
Centralized condensing gas-fired boiler coupled with radiators (CCR) | 319 | 583 | 472 |
2.2. Calculation Method
The energy analysis is carried out in the following way: firstly the heating demand of the building is calculated through the dynamic simulation software TRNSYS
® [
8] every 15 minutes, afterwards the primary energy consumption is calculated through a simplified steady-state model based on the EN 15316, considering heat losses of the following different sub-systems: emission, control, storage, distribution and generation. Each subsystem is analysed, taking into account energy inputs, energy outputs, system thermal losses, auxiliary energy consumption and recoverable thermal losses. The motivations to base the method on EN 15316 are: the Italian current regulation requires, for technical analysis, the utilization of a method based on Italian or European Standards; the only officially accepted and widely adopted method in all European countries is the European Standard. The utilization of more sophisticated but less impartial and shared methods would have hindered the acceptance of the results.
The dynamic behaviour of the system components is not actually modelled, but it is considered as a succession of steady-state conditions, that vary with a quarter-hourly time step. When solar collectors are considered, the heat production of the solar plant is evaluated through the software TSol
® [
9].
The reference building is composed of apartments with different solar radiation exposures; therefore the comparison of primary energy consumption between independent and centralized systems is carried out considering the sum of each apartment consumptions. The energy demand for space heating depends on energy losses through the building envelope, air infiltration, solar and internal gains. Heat demand is calculated on quarter hourly basis through TRNSYS®.
The internal building temperature is assumed equal to the set-point at 20 °C during the daytime, from 7 a.m. till 9 p.m., while the heating system is switched off during the night, when the internal temperature decreases, depending on building characteristics. The internal gains are considered constant at the value of 5 W/m
2, as suggested in EN ISO 13790 [
10].
The energy need for domestic hot water is equal to 108 litres per day for every apartment, calculated in accordance with EN 15316, considering appropriate load profiles for independent and centralized heating systems,
Figure 3. The former shows peaks in the morning, at midday and in the evening, the latter presents instead a continuous trend.
Figure 3.
DHW load profile in different heating systems [
9].
Figure 3.
DHW load profile in different heating systems [
9].
Thermal losses of emission, control, storage, distribution and generation sub-systems are calculated considering system extensions, duties and loads in accordance with EN 15316 and UNI/TS 11300-2 [
11], that is a technical specification for the nationwide application of EN 15316. Thermal losses of each sub-system are calculated every quarter hour as follows:
Emission thermal losses: efficiency values are taken from Table 17 of UNI TS 11300-2. For radiator, values vary from 0.97 to 0.90, instead for radiant floor, values vary from 0.98 to 0.96. The latter is characterized by further downward heat losses equal to 10% of the heat supplied by the emission sub-system [
12,
13]. These losses are assumed to contribute to the space heating of the apartment below and for this reason they affect negatively only the energy balance of top floor apartments.
Control thermal losses: efficiency values are taken from Table 20 of UNI TS 11300-2. For radiators, values vary from 0.98 to 0.96, instead for radiant floor, values vary from 0.97 to 0.95.
Storage thermal losses are evaluated with [
11]:
where:
Ql,S is the thermal energy losses [kWh];
SS is the external surface of the storage [m2];
dS is the thickness of storage thermal insulation [m];
TS is the average temperature of the storage [°C];
Tamb is the temperature of the ambient where the storage is installed [°C];
tS is the operation time of the storage [h];
λS is the thermal conductivity of storage insulation [W/mK].
Distribution thermal losses are evaluated with [
4]:
where:
U is the linear thermal transmittance of considered pipe section [W/mK];
L is the length of considered pipe section [m];
Tw is the average hot water temperature of considered pipe section [°C];
Tamb is the average ambient temperature around considered pipe section [°C];
t is the operation time at the corresponding temperatures [h].
The linear thermal transmittance of the different pipe sections is calculated in accordance with [
14]. Thickness of pipes thermal insulation (thermal conductivity of 0.04 W/mK) has been chosen in accordance with [
15].
The average hot water temperature of pipe section for space heating, considering constant flow rate and supply temperature control depending on the outdoor temperature, is calculated with the following [
4]:
where:
∆Tdes is the temperature difference between mean emission system design temperature and room temperature [°C];
βdis is the partial load of the distribution system;
n is the exponent of the emission system;
Tamb is the room temperature [°C].
Generation thermal losses are evaluated with boiler cycling method [
16]. The input data to the method has been evaluated from experimental results [
5].