1. Introduction
The building sector is the single largest energy consumer and responsible for approximately 42% of energy consumption, 35% to 40% of CO
2 emissions, 20% of all waste and 40% of all materials used in Europe [
1]. It is estimated that almost 75% of the building stock is energy inefficient, while only 0.4% to 1.2% of it is renovated each year [
2]. Among existing buildings, the historical ones—about 30% of all European buildings [
3]—have a significant potential to improve EU energy efficiency.
The thermal insulation of such inefficient building is thus a necessary step to meet the European energy efficiency objectives. In the case of historic buildings, however, external thermal insulation is often not suitable due to the need of preserving the facades along with their aesthetical, heritage, and cultural values. For this reason, internal insulation is generally considered as a valid alternative to external insulation in order to improve the buildings’ thermal performance. However, its design and application could be technically complex entailing several risks [
4,
5]. For instance, the risks of internal dampness, mold growth, interstitial condensation, and freeze-thaw damage may further lead to structural deterioration, aesthetical damages, and eventually a reduced service life for the whole renovation intervention. At present, there is a lack of knowledge on how to apply correctly internal insulations and handle the inherent risks. The EU project RIBuild (Robust Internal Thermal Insulation of Historic Buildings) aims to fill this gap, by investigating how and under which conditions internal insulation can be safely used [
6].
Regarding insulation materials and systems for historical buildings, there is a large number of products available in the market, including natural materials (e.g., cellulose, cork), conventional materials (e.g., mineral wool, glass wool, polyurethane, expanded polystyrene, insulating plaster) and other advanced materials (e.g., calcium silicate, aerated concrete) [
7,
8]. According to Vereecken, internal insulation systems can be categorized into three types: (i) condensate-preventing insulation systems, based on vapor-tight insulation materials or metal foil; (ii) condensate-limiting insulation systems with normal or smart vapor barrier; (iii) condensate-tolerating insulation systems with capillary active materials [
9].
However, when selecting the most appropriate insulation system, multiple key performance indicators must be considered, not only related to the energy performance but also to the hygrothermal risk, the life cycle environmental impacts, and costs.
The environmental performance of internal insulation must be evaluated through a consolidated, comprehensive, and systematic method, in order to provide real decision support during the design stage. Life Cycle Assessment (LCA) is a standardized and internationally recognized method to quantify resource consumption, environmental impacts, and emissions linked to a product or service through its whole life cycle. Part of the RIBuild project includes the development of a stochastic approach for the assessment of the internal insulation hygrothermal performance [
5], life-cycle costs (LCC) [
10,
11], and life cycle environmental impacts (LCA) [
12], by coupling specific calculation models to Monte-Carlo (MC) simulation and Probability Density Functions (PDFs) for data inputs.
In the past, several EU projects already focused on energy efficiency measures for historic buildings. For instance, the EFFESUS project focused on the development of a holistic assessment methodology, including economic, environmental, and cultural aspects, in order to choose the best retrofit solutions for historic buildings [
13]. Exemplary environmental and economic assessments of internal insulation solutions have been carried out for some building case studies [
14].
The 3encult project developed passive and active solutions aimed at combining both the instance of conservation and of energy retrofit [
15]. The NEW4OLD project was aimed at facilitating the integration of renewable energy and energy efficiency technologies into historic buildings and at contributing to their protection [
16].
In the context of these projects, innovative insulation materials have been also developed and tested to verify their thermal performance and suitability for historic buildings, in terms of easy application, reversibility, and material compatibility [
17,
18]. However, none of these projects was especially focused on internal insulation solutions, also aiming at developing “probabilistic” approaches for the assessment of their performance from energy, economic and environmental points of view, as made in the RIBuild project.
With the growing demand in the energy and climate mitigation targets, the number of LCA studies in the building field increased significantly, as shown by the recent reviews reported in [
19,
20,
21]. Several authors focused on the LCA of various types of building internal insulation systems [
22,
23,
24], even if the LCA application of internal insulation solutions for historic buildings is limited to fewer studies [
1,
25,
26].
Moreover, there is an increasing trend to develop and apply “probabilistic” approaches to LCA analysis, in order to fully capture the inherent uncertainties related to data quality and calculation methods [
27,
28,
29,
30]. Indeed, neglecting uncertainties and variabilities of various life cycle parameters and scenarios may affect the results’ reliability and robustness for final decisions.
In the state of the art, several studies in the building field deal with “probabilistic” approaches to LCA [
31,
32,
33,
34]. Some works especially focus on materials or structural components, mainly addressing parameter uncertainties, which can be traced from more than one source, such as material quantities, the unitary environmental impact of materials, heat transmission losses, service life (SL) estimation, etc.
For instance, Hoxha et al. investigated the impact of construction materials uncertainties on LCA reliability in few works [
35,
36,
37]. In [
37], the authors used the statistical method to identify parameters having the greatest contribution to the uncertainty of the final result. They focused on the service life of the building component, the environmental impact of building component’s production, and the amount of material used within the building. In [
35], by evaluating the impact of 30 residential projects situated in France, the authors identified the building materials that have the largest relative contribution to buildings’ impacts and uncertainties and found insulation materials as the key building materials controlling this uncertainty. Moreover, Häfliger et al. aimed to assess the sensitivity of construction materials to the different modeling choices (database choices, system boundary definitions, and replacement scenarios) in order to highlight their consequences at the building scale. Results clearly show the importance of these choices, especially for some materials as thermal insulation [
38].
Among uncertainty analysis methods, Monte-Carlo simulation is one of the most used techniques, even if other approaches are also available, such as the fuzzy set theory [
39,
40], Taylor series expansions [
35,
36], Bayesian theorem [
41], and Markov Chain modeling [
42]. However, their applications in the building sector are limited in comparison to other fields. Pomponi et al. used primary data for embodied energy collected from European manufacturers as inputs for the stochastic modeling of uncertainty, considering two alternative distributions (data normally or uniformly distributed) [
43]. Results showed that the hypothesis on the data no longer influences the results after a high enough number of random samplings in the MC simulation.
An example of a Monte-Carlo simulation application to assess uncertainty on building insulation LCA is provided by Su et al., which compared the life cycle performance of eight types of insulation materials [
24]. The authors transformed the inventory analysis results into a probability distribution around a mean value and propagate data uncertainty using MC iterations. Results revealed that physical parameters, as density and thermal conductivity, have a significant contribution to the uncertainty of LCA results [
24]. In a preliminary work of the same authors of this work, Favi et al. extended this approach considering several uncertainty sources for the LCA of a historic building renovation based on internal insulation and performed an MC-based global sensitivity analysis [
26].
This paper provides a further contribution in this context, by presenting the stochastic LCA approach developed within the RIBuild project for internal insulation of historical buildings and the illustration of its application on five internal insulation solutions. When performing a building LCA, different backgrounds for life cycle inventory (aggregated data or industry data) can be adopted. Aggregated data is available through commercial databases where datasets are defined based on available statistics and sources of literature and usually associated with a high degree of uncertainty. Over the past three decades, LCA databases (such as ecoinvent) have been developed, trying to cluster general information [
44]. At the same time, European environmental policies are pushing the use of Environmental Product Declarations (EPDs) for building materials [
45]. EPDs are based on the actual production data from a specific manufacturer and reviewed by an independent third party prior to publication. In this respect, the LCA data refer to the specific product. However, for the same product, generic datasets from commercial databases and EPD’s data may be not directly comparable, due to the different data sources [
46].
Based on the stochastic LCA approach developed by the authors, this work analyses the environmental performance of five insulation solutions and, in addition, investigates the impact of data availability and data quality on the variability of LCA results, by using input data from different sources (i.e., a generic international database and EPDs). Indeed, when a building designer wants to assess the environmental performance of several design alternatives, he may have to deal with different data sources. In the early design stage, a designer may not have identified yet the specific products to use and therefore uses data from generic databases for the product category. However, data are not always available, especially for specific and new materials and products that the building market is developing ever more rapidly. Even for these products, EPDs may be available or not. As these two types of sources (i.e., a generic international database and EPDs) refer to different background data, this paper aims to understand whether the use of generic data or of EPD for the materials composing internal systems leads to substantial differences, starting from the point of view of a building designer/consultant.
The results of the stochastic LCA of the insulation systems are presented both as probability distributions (defining the range and likelihood of impacts) and using a traditional “deterministic way”, representing the ranking of their environmental profiles based on the mean values of the distributions, in order to compare results’ effectiveness and representativeness.
The paper is outlined in the following structure:
Section 2 presents the developed stochastic LCA methodology, while
Section 3 illustrates its application on five internal insulation solutions.
Section 4 reports the obtained results. A discussion of results including future developments in the field of historic building renovation is finally drawn in
Section 5 and complemented by conclusions in
Section 6.
2. The Stochastic LCA Methodology for Internal Insulation
This section briefly describes the stochastic LCA methodology developed for the evaluation of the environmental impacts of internal insulation solutions of historic buildings, which has been developed within the RIBuild project [
12].
The stochastic LCA approach couples the calculation model of the environmental impacts to Monte-Carlo simulations. Based on data inputs PDFs, the output probability distribution is thus obtained for the analysis of global uncertainty and sensitivity. The uncertainty analysis aims at representing the range of possible environmental impacts for the various scenarios. The sensitivity analysis aims at identifying which parameters contribute the most to the overall uncertainty.
The methodology has been implemented in a software tool accessible through the RIBuild project web page [
6], using R, an open-source programming language and software environment for statistical computing and graphics [
47], and Shiny, an R package addressed to build interactive and user-friendly web apps straight from R. This “LCA/LCC probabilistic tool” includes both the stochastic LCA and LCC methodologies developed during the project, allowing a real-time calculation of the economic and environmental impacts of internal insulation systems applied to wall case studies under several possible scenarios.
2.1. Overview
The stochastic LCA methodology follows the typical steps used by analytical methods to treat uncertainty [
29,
30], and which are described in detail in the next sections (
Figure 1):
Definition of the LCA model. The LCA model to assess the environmental performance of internal insulation solutions is established according to relevant international standards.
Uncertainty characterization. The uncertain data inputs of the LCA model are identified, and specific procedures for their characterization through PDFs are proposed.
Uncertainty propagation. The MC method is applied to propagate input distributions and obtain the output PDF.
Uncertainty and Sensitivity Analysis. The output distribution is represented and interpreted. Sensitivity indices can be calculated to establish which parameters’ uncertainties are most influential on the output variance.
2.2. LCA Model
The probabilistic LCA is performed at “component level” (insulated wall) and is based on the procedures defined in ISO 14040, ISO 14044, EN 15804, and EN 15978 standards [
48,
49,
50,
51].
2.2.1. Goal and Scope Definition
The goal of the study is to assess the environmental impacts of internal insulation measures installed on historic building facades. The functional unit (FU) is defined as “the insulation measure performed by several possible internal insulation systems and technologies required to cover 1 m2 of historical building façade, to reach a given thermal transmittance [W/m2K], for a reference study period expressed in years”. The FU for the LCA of a building component can use different thermal transmittance values and reference study period depending on the goal of the study. The reference flows that accomplish the FU are reached through the insulation thickness compliant to a given thermal transmittance (based on renovation standards or other factors). Other functions, as the need to have a “safe” solution from a hygrothermal point of view, can be added, requiring a preliminary assessment of this aspect before the LCA.
The scope of the study comprises the environmental impact assessment of installing the new internal insulation systems assuming a given “building heating system scenario”, i.e. a heat source to convert the heat transmission losses into final energy. The impacts of the new internal insulation systems after renovation cover the material manufacture, the use phase impacts related to the building heating energy needs and the possible repair and replacement of material layers, as well as the dismantling at the end-of-life. As a result, the following life cycle stages are considered: (i) the production stage (modules A1–A3), (ii) the use stage (modules B2 maintenance, B4 replacement, and B6 operational energy use), and (iii) the End of Life (EoL) stage (modules C1–C4). Based on the literature survey and reports of LCA practitioners, the construction processes are less relevant in the LCA of building components than the operational ones [
37,
52,
53,
54]. The distinction between modules B2 (maintenance), B3 (repair), B4 (replacement) is considered according to EeBGuide guidance recommendations [
55]. Hence, the maintenance is considered as the periodic wall re-painting; while replacement involves the whole insulation system, according to its estimated service life.
Several design options (internal insulation measures, comprising different layers of materials) and scenarios (original wall typologies, building heating systems, reference study periods) can be defined. In the following, a “case-study” is set when a certain insulation system is applied in a certain original wall configuration under certain climatic conditions. The same case study can be assessed in several building heating systems scenarios and reference study periods.
2.2.2. Life Cycle Inventory (LCI)
Life cycle inventory requires the definition of each parameter referred to the reference flow for each system covered by the functional unit. It encompasses all the life cycle stages covered within the functional unit. The LCA data used to model the environmental impacts of an internal insulation renovation can be collected from different sources. As illustrated later, within
Section 3 (case study), LCA data are collected from two sources and used for two alternative simulations sets: (i) the Environmental Products Declarations (EPD) provided by the manufacturers of the materials composing the insulation systems and (ii) data from an LCI generic database (i.e., ecoinvent).
2.2.3. Life Cycle Impact Assessment (LCIA)
Several life cycle impact assessment (LCIA) methodologies have been applied in the building sector (e.g., CML, ReCiPe, CED, etc.) Standard EN 15978 leaves to LCA practitioners the possibility to choose the most suitable LCIA method (usually based on geographic location or type of measures). In the case study reported in
Section 3, the unitary environmental impacts are calculated according to the CML LCIA method [
56]. In particular, the CML-2001 baseline V3.02/EU25 LCIA method is chosen, as it is widely applied in the building sector [
21,
57] and, above all, as it is referenced in most of the EPDs found for the materials composing the insulation systems. Midpoint impact categories from the CML-2001 baseline method are reported in
Table 1 [
56].
Wall Transmission Heat Loss Calculation Method
The LCA requires information on the operational energy use (module B6 of EN 15978) before and after the application of the internal insulation, in order to account for the use phase and determine the environmental burden savings. The LCA is performed at the “component level”; this means that the operational energy use (module B6 according to EN 15978) is considered as the annual heat transmission through the building facade.
The heat losses and gains through the façade do not cover the entire heating or cooling demand of a building, which depends on several factors, such as solar gains, ventilation losses, thermal bridges, etc. Considering that the internal insulation especially affects the heat transmission losses and gains through the facade, while the other factors remain almost unchanged, for the sake of simplicity these factors are not taken into account in the LCA methodology developed.
The annual heat transmission through the building facade can be obtained in different ways such as (i) through coupled heat and mass transfer numerical models based on hourly climate data, (ii) monthly calculation between the internal temperature and the average monthly temperature, and (iii) annual calculation based on Heating and Cooling Degree Days.
Concerning the first two methods, within the RIBuild project, a “probabilistic” approach to the hygrothermal performance assessment of interior insulation is developed, based on heat and mass transfer numerical models coupled to MC simulations [
5,
58]. Furthermore, a stochastic monthly calculation is developed [
12]. Based on these choices, wall heat transmission can be defined through accurate PDFs [
12].
Within the exemplary case illustrated in
Section 3, for the sake of brevity and simplicity, the third method is presented, limited to the heat transmission loss through the wall during the heating season. It is based on the Heating Degree Days (HDD) method according to the following Equation (1):
where
Qh is the annual heat transmission loss through the wall [kWh/m2]. Qh can refer to the heat losses before (Qhpre) or after (Qhpost) the insulation intervention;
U is the wall thermal transmittance (U-value) [W/m2K];
HH is the heating hours a day [h] (set at 24 h);
HDD are the annual heating degree-days [K].
The U-value of the wall is calculated with the following Equation (2):
where
Life Cycle Impacts Calculation Method
The environmental impact of the
j-th insulation system, composed by several materials
k, for a given LCA indicator is calculated, considering the previously defined life cycle phases and during a certain calculation period
cp, through the following Equation (3):
where
IG is the Global Impact for a given indicator;
i is the year of the calculation period;
is the j-th system environmental impact related to production phase;
is the j-th system environmental impact related to the End of Life phase;
is the number of replacements of the j-th system within cp;
is the unitary impact of the energy vector at year i;
is the environmental impact related to the system periodic maintenance.
is defined in the following Equation (4):
where
, the number of replacements of the
j-th system within
cp, considering its Service Life
SLj [years], is defined in the following Equation (5):
is defined in the following Equation (6), where
EOLk is the unitary End of Life impact of the
k-th material composing the
j-th system:
is defined in the following Equation (7):
where
is the number of replacements of the
k-th material within the calculation period
cp, calculated considering the
k-th material Service Life
slk [years] through the following Equation (8):
2.2.4. Interpretation
Life cycle interpretation is the last phase identified within the ISO 14040 and 14044 standards [
48,
49]. Both standards specify that interpretation comprises the following elements: (i) an identification of the significant issues (hotspots); (ii) an evaluation that considers completeness, sensitivity, and consistency checks; and (iii) conclusions, limitations, and recommendations for end-users and stakeholders. ISO 14044 defines uncertainty analysis as a systematic procedure to quantify the uncertainty introduced in the results. Since the stochastic LCA approach developed within the
RIBuild project is oriented to the characterization of uncertainties in data input and sensitivity analysis of the results, this phase is in the critical path and serves to: (i) better understand the obtained results, (ii) increase the level of confidence in the decision-making process, and (iii) support the robustness and applicability of the study results.
2.3. Uncertainty Characterization
The stochastic approach couples MC simulations to the wall transmission heat loss calculation (Equations (1) and (2)) and to the LCA model (Equation (3) to Equation (8)). Thus, the method requires defining the PDFs of all data input, identifying the uncertainty sources, and characterizing them based on available information. In general, the uncertainty characterization of input parameters entails data collection based on literature and commercial databases for each uncertainty source identified and eventually depending on the national context. A quantitative approach based on parameter estimation techniques and goodness-of-fit test can be used to fit distributions when sufficient data is available. When limited data are available or uncertainty is subjective, experts’ judgment can help to define the proper PDF. As previously stated, in this work, the heat transmission losses through the wall are obtained through a stochastic annual HDD method, thus the following input parameters are characterized with PDFs for each case study:
The thermal resistance of the historic wall [m2K/W];
The thermal resistance of the insulation system [m2K/W];
Annual heating degree-days HDD [K].
Regarding the LCA model, two levels of uncertainty can be identified for the input parameters: (i) the one related to the LCI background data for material manufacturing, end of life and heating systems, and (ii) the one related to the design option under study (i.e., service life and mass of materials). The following input parameters are then considered as stochastic variables of the LCA assessment:
Unitary environmental impact of each material layer;
Unitary environmental impact of the building heating system;
Masses of the material layers;
The service life of the whole insulation system (influencing the number of replacements) and of the material layers (influencing the number of replacements of the internal finishing layer = re-painting (maintenance)).
When using manufacturer’s information on the environmental impacts, i.e., EPDs, background PDFs for the unitary environmental impact of a specific dataset are replaced with “deterministic” values retrieved in EPDs.
Once the PDFs for the unitary environmental impact of the component materials are defined, it is necessary to calculate the unitary environmental impact at the whole insulation system level, considering the masses (and related uncertainties) of each material.
In
Table 2, the uncertain parameters identified in the LCA model are reported for each LCA stage. In
Section 3.2, the uncertainty characterization procedures of input data for the specific exemplary application are described.
2.4. Uncertainty Propagation and Analysis, Sensitivity Analysis
MC method is used to propagate the heat losses and LCA parameter uncertainties into a distribution of the output variable, reflecting the combined parameter uncertainties. According to MC method, values from the input PDFs are drawn and inserted into the output equations for a given number of times—set based on convergence evaluation—to obtain the output parameters distributions. Minimization of iterations (required runs) can be obtained through a sampling strategy. In this study, Sobol’s sequences are used as sampling technique, in order to generate samples as uniformly as possible and effectively perform the sensitivity analysis through a variance-based decomposition technique (Sobol’s method) identifying the most influential parameters’ uncertainty on the output variance [
60,
61].
The output sample can then be visually represented by PDFs, Cumulative Distribution Functions (CDF), or box whiskers plots, which can be used to compare the performance of several design options under the same scenarios (or under several scenarios), as shown in the exemplary case presented in
Section 3.
5. Discussion
At the early design stage of a building renovation project, the building designers could evaluate to use alternative internal insulation solutions that may be functionally equivalent, but differ in their environmental performances. With the increasing climate challenges and public concerns, designers and decision-makers are urged to choose an optimal solution to mitigate the environmental burdens.
However, when performing an LCA, they may deal with different LCI data sources. If specific products are not identified and for common materials used in insulation systems (e.g., common plasters, insulation materials, etc.), they may acquire data from generic databases. At the same time, in such databases, they may not find datasets for specific and new products in the building market, e.g., “vapor-open capillary active insulation materials”, specific mortars with advanced hygrothermal properties, “smart” vapor barriers, etc. In this case, if available, they may be forced to use EPDs.
Based on the stochastic LCA approach developed by the authors during the EU project RIBuild, presented in
Section 2 of the paper, this work investigates the impact of data availability and quality on the variability of the results of an LCA of five internal insulation systems applied to a historic building in Italy. The LCI data for materials’ manufacturing has been collected from two sources: a commercial LCI database or the EPDs of specific products selected among the most widespread in the Italian market. This led to two different simulation groups, which have been conducted under two different building heating systems scenarios.
The environmental performance of the insulation solutions has been analyzed both considering the whole impacts distributions ranges (as provided by the stochastic assessment) and the mean values (thus following a standard “deterministic” approach). At first, the environmental performance is analyzed only considering the material production phase, to highlight the outcomes differences obtained using EPD or ecoinvent data (respectively simulation groups 1 and 2); then, the whole life-cycle performance, including building use phase and EoL, was assessed.
The following points summarize the main findings obtained:
From a preliminary screening of the datasets on the unitary environmental production impact of the component materials, a remarkable difference between the deterministic (EPD) and stochastic (ecoinvent) data is ascertainable. This finding is in line with previous studies [
24,
38,
46]. All the considered materials present at least one impact value from EPD “out” of the Ecoinvent PDF 5–95 percentile rank range. Even for those values within the range, high percentage differences are observed between EPD values and the mean values of the Ecoinvent lognormal distributions, ranging between 0% and 110%. Even if generic and EPD’s data are not directly comparable, as they refer to different background data, this analysis highlights that the starting points for an LCA of internal insulation, based on generic or specific datasets depending on the available information for the real products on the market, could be quite different.
At the production stage, an insulation systems’ environmental ranking can be quite easily performed for the simulation group 1 (EPDs data), as results present low uncertainties (generally gCV of 2% to 3%). However, the ranking is highly dependent on the environmental indicator selected. On the contrary, a clear ranking for group 2 (ecoinvent data) is not straightforward: A high distributions’ scattering is detected, with gCV ranging from 9% to 36%, due to the uncertainties on materials’ impact values. A similar amplitude of the coefficients of variation was obtained by Su et al. in their study [
24]. Moreover, in group 2, while the EPS and CaSi systems are clearly respectively the best and worst-performing solutions, for all the indicators, the CDFs of the other insulation systems overlap. It is also worth noting that the environmental performance of solutions in simulation group 1 is better than that of group 2. Although previous studies, e.g., in [
1,
22,
23,
24,
25,
26], carried out an LCA of different insulation materials, a direct comparison of the results is not possible, due to the different preconditions of the studies (e.g., assumptions, database, functional units) and to the innovative insulation materials addressed in this study (CaSi, AAC).
Looking at the overall life cycle impact assessment, what primarily emerges is that the general trend of CDFs is quite similar among simulation groups and insulation systems. This means that the environmental performance differences among solutions at the production phase, due to materials’ impact and eventually to the different input datasets, are relatively “flattened”. This result is due to the operational energy use phase that in this case study accounts for more than 80% of the global impacts for the majority of simulated cases and which is assumed the same for all systems (with minor deviations due to slightly different wall U-values). As a result, the insulation thickness needed to reach the U-value of 0.36 W/m2K remains relatively low compared to the “optimal insulation thickness” from a life cycle impact assessment point of view for which the energy savings would compensate only the manufacturing impacts. In other words, in the current building energy norms, in the renovation, the influential parameter remains the heat demand and the energy carrier type.
The average environmental payback time of the five insulation systems is quite low, ranging from 1 to 5 years (depending on the specific system) considering GWP and AP indicators, while it is extremely high considering EP (between 20 and 110 years). Hence, it can be concluded that insulating is a good option in general, but the choice among different systems should be made by analyzing several indicators.
The LCA results obtained for all insulations systems, in both simulation groups and building heating systems scenarios, are affected by high uncertainty (with a maximum CV of 16% for the GWP indicator, ranging from 10% to 36% for the AP indicator, and from 15% to 61% for the EP indicator). For this reason, and due to the overlap of distributions in many cases, a ranking of the solutions based on the mean values, according to a “deterministic” approach, risks to provide misleading information.
The implications of the results obtained in this work are twofold. Firstly, they highlight the urgent need for consistent databases and to push for the development of accurate EPDs, especially for new and specific building materials with advanced properties, which are spreading more and more in the market. Secondly, it demonstrates the potential of the use of stochastic LCA approaches in building decision making, which needs to be encouraged. Indeed, the information provided by the stochastic approach—estimates of the range and likelihood of impacts, rather than deterministic values—is more realistic and useful in the context of decision-making.
It should be considered that the work presents some limitations due to the specific assumptions made for the case study. Firstly, the stochastic LCA method within the RIBuild project was developed “at component level”. Even if this facilitates the immediate comparison between different solutions, it neglects the complexity and uncertainty sources present at the whole building level.
The use phase was limited to the operational energy use, while components maintenance or replacement needs were neglected. The EoL scenario was assumed to be the same for all systems. Further developments of the study could extend the range of validity of the results including and/or differentiating further the LCA phases.
In addition, the operational energy use was considered to be almost the same for all systems (except for slight differences due to the thickness of the insulation) and relatively high, thus reducing the influence of the other life stages on the overall impact. Moreover, it was calculated based on a simplified HDD method, neglecting the cooling behavior and how systems’ real hygrothermal performance could affect the life cycle performance, i.e., influencing the annual energy consumption and the periodical maintenance and replacement tasks.
Indeed, the high potential of the stochastic LCA developed for the evaluation of internal insulation is that it could be joined to a “probabilistic” hygrothermal performance assessment, in order to fully capture the real—different—life cycle behavior of alternative insulation measures, in this way effectively supporting decision-making. By doing so, outputs coming from the stochastic hygrothermal simulations and risk damage assessments could be used as inputs for the stochastic LCA, delivering more substantial results.
Using this approach could even overturn the ranking among the insulation systems obtained in the case study presented in this work, supporting solutions with higher production impact but safer from a hygrothermal point of view. This constitutes a future research direction.