Pilot Protection Based on Zero-Sequence Current Resistance-Capacitance Component for Large-Scale Inverter-Interfaced Power Stations
Abstract
:1. Introduction
2. Fault Characteristic Analysis of Large-Scale Centralized IGPS
2.1. Fault Characteristic Analysis of Tie Line
- Zero-sequence current I0M flowing through the fault tie line MNm and the M side of the system bus is the vector sum of the current I0R of the zero-sequence resistance branch and zero-sequence capacitive current to ground of cable lines in all non-fault IGPSs, as shown in Equation (7). The zero-sequence current flowing through the Nm side of the photovoltaic bus is the zero-sequence capacitive current I0m of IGPSm.
- The zero-sequence current flowing through the non-fault tie line MNj (j = 1, 2,…, m–1) is the zero-sequence capacitance current I0j of IGPSj.
- The zero-sequence current flowing through the installation of protection on collector lines is the zero-sequence capacitive current to the ground of its own line.
2.2. Fault Characteristic Analysis of Collector Line
2.2.1. Fault of Collector Line Directly Connected to Booster Station
- Zero-sequence current I01-N1 flowing through fault collector line 1-N1 (side M of system bus) is the vector sum of resistance current I0R and zero-sequence capacitive current to the ground of all non-fault collector lines in the system (including all collector lines from IGPS2 to IGPSm and non-fault collector lines from IGPS1).
- The zero-sequence current flowing through the installation of non-fault collector line protection is the zero-sequence capacitive current to the ground of this line.
- The zero-sequence current flowing through the non-fault tie line MNi is the zero-sequence capacitive current of its subordinate IGPSi, especially that the zero-sequence current flowing through MNm is the zero-sequence capacitive current I0m of IGPSm.
2.2.2. Fault of Collector Line at the Lower Level of the Tie Line
- Zero-sequence current I0m-nm through the first end of the fault collector line is the vector sum of the resistance current I0R and the zero-sequence capacitive current of all the non-fault collector line in the collection system, including all the collector line of the non-fault photovoltaic station and IGPSm).
- The zero-sequence current flowing through the installation of non-fault collector line protection is the zero-sequence capacitive current to the ground of this line.
- The zero-sequence current flowing through the whole tie line MNi connected to non-fault IGPSi (i =1, 2,…, m − 1) is the zero-sequence capacitive current I0i of the cable in the station.
- Zero-sequence current I0M flowing through the whole superior tie line MNm of fault collector line M-NM is the sum of resistance current I0R and zero-sequence capacitive current of all non-fault collector line of IGPSs, as shown in Equation (19).
3. Blocking Zero-Sequence Pilot Protection
3.1. Protection Algorithm
- When the power station is in normal operation, there is no zero-sequence current in the collection system, I1 and I2 are not started, then the four and-gates of PM and PN on both sides have no output, and the protection does not start.
- When the ground fault occurs at any point K” of the adjacent collector line outside the area, the zero-sequence current flowing through the whole tie line MNm is the zero-sequence capacitive current I0m of its subordinate IGPSm. So I1 start, I2 do not. “and-gate 1” on PM side has instantaneous action, start the transmitter, send locking signal, and lock protection on both sides. I2 on the PN side does not start and outputs 1 through the not gate, but it is sent to “the and gate 3” after t2 delay. Therefore, “the and gate 3” also outputs 1 before t2, and the starting transmitter sends a locking signal to close the trip circuit of “the and gate 4” on the local side. After t2, “the and gate 3” returns and stops sending signal, but the receiver has received the locking signal from PM side, locking “the and gate 4” tripping circuit. To sum up, when there is a fault on the adjacent collector line outside the area, both sides of the protection can be reliably locked, will not miss-operate.
- When the fault occurs on other tie lines outside the zone, the zero-sequence current flowing through the whole tie line MNm of the non-fault tie line is still the zero-sequence capacitive current I0m, and the subsequent protection work is the same as that of (2).
- When the ground fault occurs at any point K” of the subordinate collector line outside the area, the zero-sequence current flowing through the whole tie line MNm is shown as Equation (20), which is the vector sum of the zero-sequence resistance current I0R and the zero-sequence capacitive current of all non-fault capacitive branches. Therefore, the starting elements I1 and I2 on both sides of the protection are in action. “the and gates 1 and 3” are instantaneously started by I1 before t2, and the transmitter sends a blocking signal. After t2, “the and gate 1” returns, and the transmitter on PM side stops sending. However, after “the and gate 3” receives the 1 output by I2 through the nor gate, the PN side transmitter continues to send the message and sends the locking signal to lock the protection on both sides. To sum up, when there is a fault on the outside subordinate collector line, both sides of the protection can be reliably locked, will not miss-operate.
- 5.
- When the grounding fault occurs at the point K on the fault tie line MNm in the area, the zero-sequence current flowing through the M side of the fault line is the vector sum of the zero-sequence resistance current I0R and the zero-sequence capacitive current, as shown in Equation (7). Therefore, both I1 and I2 of PM protection operate, and the zero-sequence current flowing through the Nm side of the fault tie line is zero-sequence capacitive current I0m. PN protection only operates I1 and I2 does not start. Both “the and gates 1 and 3” are instantaneously started by I1 before t2, and the transmitter sends a locking signal. After t2, PM’s I2 outputs 1, starts the tripping circuit of “and 2”, “the and gate 1” returns, and the transmitter stops. PN’s I2 does not start and output 1 through the nor gate, start “the and gate 4” trip circuit, “the and gate 3” returns and the transmitter stops, both sides of the protection action trip.
3.2. Comparison with Traditional Zero-Sequence Current Differential Protection
4. The Example Analysis
4.1. Fault Characteristic Analysis of Tie Line
- (1)
- Longitudinal trend: As the neutral point resistance Rg gradually increases, the capacitive current gradually increases.
- (2)
- Cross-sectional trend: as the point K moves from M to N, both and gradually decrease when Rg is small, and both and gradually increase when Rg is large. As discussed separately below.
- (a)
- when Rg is small:
- (b)
- When Rg is large:
4.2. Fault Characteristic Analysis of Outside Tie Line
4.2.1. The Fault of Adjacent Outside Collector Line
4.2.2. The Fault of Subordinate Outside Collector Line
4.3. Blocking Zero-Sequence Pilot Protection Setting and Verification of Tie Line
- 1.
- When Rg = 20 Ω and the fault of the end tie line MN2 occurs, the resistance current and capacitive current are taken to calculate the protection fixed value as follows:
- 2.
- When Rg = 150 Ω and the fault of the head of tie line MN2 occurs, the resistance current and capacitive current are taken to calculate the protection fixed value as follows:
5. Conclusions
- We established a fault analysis model of large-scale centralized IGPS collection system with ground capacitance. By analyzing the characteristics of single-phase grounding fault on different lines, we proposed a blocking zero-sequence pilot protection scheme with economic characteristics. The protection scheme only uses the current to constitute the protection criterion without the measurement of voltage, and the protection on both sides does not need synchronous sampling data, only needs to transmit logic information, which can save the investment cost of engineering construction.
- The influence of neutral resistance on different components of zero-sequence current is analyzed. When the neutral resistance is small, the zero-sequence equivalent impedance of short-circuit point is mainly resistive, and the zero-sequence current is mainly resistive and inductive, and the influence of ground capacitance on fault current is small. When the resistance of the neutral point is large, the zero-sequence equivalent impedance of the short-circuit point is mainly characterized by resistance and capacitance, and the zero-sequence current is mainly characterized by resistance and capacitance.
- Through the quantitative protection setting calculation and verification process, it is verified that the proposed protection scheme can reliably judge the in-zone and out-zone faults, and can give consideration to the protection selectivity and rapidity when the value of neutral point resistance is low or high.
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
Appendix A
- System parameters: short-circuit capacity of 110 kV system is 3000 MVA.
- Line parameters: The 10 km long overhead line LGJ-240 is adopted for the tie line MN2. Positive and negative sequence unit parameters are the same, R (1) + jX (1) is 0.132 + J0.386 Ω/km and zero-sequence unit parameter is 3 times of positive and negative sequence unit parameters, i.e., 3R (1) + j3X (1) is 0.396 + J1.158 Ω/km.
- 3.
- Transformer parameters: The rated capacity of T1 is 80MVA, and the impedance voltage of T1 is UKT1=10.75%, The rated capacity of photovoltaic grid-connected transformer is 1MVA, and the impedabce voltage UKTPV = 6%.
- 4.
- The capacity of IGPS1 is 50 MW, the capacity of IGPS2 is 20 MW.
References
- Li, H.; Liu, D.; Yao, D.Y. Analysis and reflection on the development of power system towards the goal of carbon emission peak and carbon neutrality. Proc. CSEE 2021, 41, 6245–6259. [Google Scholar]
- Jin, S.D.; Song, Y.Q.; Fan, C.J.; Jiang, S.; Li, X. Calculation of Current Protection Setting Based on Inverter Generation Control Strategy. Power Syst. Technol. 2021, 45, 3690–3699. [Google Scholar]
- Memari, M.; Karimi, A.; Hashemi-Dezaki, H. Reliability evaluation of smart grid using various classic and metaheuristic clustering algorithms considering system uncertainties. Int. Trans. Electr. Energy Syst. 2021, 31, e12902. [Google Scholar] [CrossRef]
- Fereidouni, A.R.; Nafisi, H.; Garmrudi, M.; Hashemi-Dezaki, H. The effect of distributed generation in distribution network on coordination of protective devices. Int. Rev. Model. Simul. 2011, 4, 1773–1779. [Google Scholar]
- Hosseini, S.A.; Sadeghi, S.H.H.; Askarian-Abyaneh, A.; Nasiri, A. Optimal placement and sizing of distributed generation sources considering network parameters and protection issues. In Proceedings of the IEEE 2014 International Conference on Renewable Energy Research and Application (ICRERA), Milwaukee, WI, USA, 19–22 October 2014; pp. 922–926. [Google Scholar]
- Jia, K.; Gu, C.J.; Bi, T.S.; Chen, Y.R.; Ren, Z.F. Research on the Compressive Sensing Based Fault Location Within the Collection System of a Large-scale Photovoltaic Power Plant. Proc. CSEE 2017, 37, 3480–3489+3676. [Google Scholar]
- State Grid Corporation of China. Technical Rule for Photovoltaic Power Station Connected to Power Grid:Q-GDW 617-2015; China Electric Power Press: Beijing, China, 2015. [Google Scholar]
- Xi, W.; Zhang, Z.; Chen, W.; Zhang, Z.W.; Liu, L. Analysis of short-circuit characteristics of photovoltaic inverters. Power Syst. Prot. Control 2015, 43, 70–75. [Google Scholar]
- Shi, X.; Zhang, H.; Wei, C.; Li, Z.; Chen, S. Fault modelling of IIDG considering inverter’s detailed characteristics. IEEE Access 2020, 8, 183401–183410. [Google Scholar] [CrossRef]
- Haddadi, A.; Zhao, M.; Kocar, I.; Karaagac, U.; Chan, K.W.; Farantatos, E. Impact of inverter-based resources on negative sequence quantities-based protection elements. IEEE Trans. Power Deliv. 2020, 36, 289–298. [Google Scholar] [CrossRef]
- Jia, K.; Yang, Z.; Fang, Y.; Bi, T.; Sumner, M. Influence of inverter-interfaced renewable energy generators on directional relay and an improved scheme. IEEE Trans. Power Electron. 2020, 34, 11843–11855. [Google Scholar] [CrossRef]
- Zheng, L.M.; Jia, K.; Bi, T.S.; Ren, L.F.; Yang, Z. Comprehensive criteria of pilot protection based on structural similarity and square error for outgoing line from renewable power plants. Power Syst. Technol. 2020, 44, 1788–1795. [Google Scholar]
- Wang, H.Y.; Zhang, L.Z. Analysis of the influence of distributed power access on relay protection of distribution network. Electr. Equip. Econ. 2018, 5, 41–44. [Google Scholar]
- Chen, X.L.; Li, Y.L.; Tan, H.Z.; Zhao, M.Y.; Wen, A.; Liu, N. An adaptive instantaneous trip protection based on positive-sequence current for distribution network with IBDG. Autom. Electr. Power Syst. 2015, 39, 107–112. [Google Scholar]
- Zeng, D.H.; Wang, G.; Guo, J.M.; Sun, X.L. Aadaptive current protection scheme for distribution network with inverter-interfaced distributed generators. Autom. Electr. Power Syst. 2017, 41, 86–92. [Google Scholar]
- Wu, H.; Sun, J.L.; Qiao, L.W.; Qiao, Y.; Lu, Z.X.; Ruan, J.X. Short Circuit Current Characteristics and Calculation of Current Protection Setting of Feeder Lines in Wind Farms Considering LVRT. Power Syst. Technol. 2016, 40, 3019–3028. [Google Scholar]
- Song, G.B.; Tao, R.; Li, B.; Hu, J.B.; Wang, C.Q. Survey of Fault Analysis and Protection for Power System with Large Scale Power Electronic Equipments. Autom. Electr. Power Syst. 2017, 41, 2–12. [Google Scholar]
- Li, Z.; Lu, J.; Liu, J.; Zhu, Y.; He, Q. Resistance selection and control strategy considering the coordination of protection performance and low voltage ride-through of a large-scale photovoltaic power station. IEEE Access 2020, 8, 143746–143758. [Google Scholar] [CrossRef]
- Liu, X.J.; Wang, K.L.; Guo, D. Current differential protection scheme for distribution feeders with high penetration of PV. Acta Energ. Sol. Sin. 2016, 37, 1805–1812. [Google Scholar]
- Xu, S.X.; Lu, Y.P. The current phase variation pilot protection method. Trans. China Electrotech. Soc. 2016, 31, 198–206. [Google Scholar]
- He, J.H.; Li, W.l.; Zhang, D.H.; Zhang, Q.F. Differential protection scheme based on current amplitude of branch node for distribution network with DG. Power Syst. Technol. 2018, 38, 1–9. [Google Scholar]
- Han, B.W.; Wang, G.; Li, H.F.; Zeng, D.H. Novel pilot protection scheme for distribution network with inverter-interfaced distributed generators. High Volt. Eng. 2017, 43, 3453–3462. [Google Scholar]
- Sun, L.L.; Wang, N.; Jia, Q.Q.; Zhang, G. Protection method of active distribution network considering low voltage ride-through of distributed PV generation. Electr. Power Autom. Equip. 2018, 38, 79–86. [Google Scholar]
- He, M.; Xu, G.F.; Yi, Y.; Yu, Q.B.; Zhu, H.B. A practical protection scheme for distribution network with high penetration of DG. Power Syst. Prot. Control 2017, 45, 136–143. [Google Scholar]
- Li, J.; Gao, H.L.; Zhu, G.F. Inverse-time current differential protection in active distribution network considering characteristics of inverter-interfaced distributed generations. Trans. China Electrotech. Soc. 2016, 31, 74–83. [Google Scholar]
Requirement | The Traditional Zero-Sequence Current Differential Protection | The Proposed Zero-Sequence Current Differential Protection |
---|---|---|
Synchronous sampling | Necessary | Unnecessary |
Real time transmission | Necessary | Unnecessary |
Communication channel | High | Low |
Investment | High | Low |
Rg (Ω) | Zero-Sequence Resistance Current I0R.S When Point K Is at the Head (A) | Zero-Sequence Resistance Current I0R.m When Point K Is at the Midpoint (A) | Zero-Sequence Resistance Current I0R.E When Point K Is at the End (A) |
---|---|---|---|
10 | 740.74∠−5.66° | 595.50∠−25.54° | 477.72∠−36.82° |
15 | 496.41∠−2.57° | 443.46∠−17.68° | 387.44∠−28.29° |
20 | 372.92∠−1.00° | 350.25∠−13.02° | 321.75∠−22.45° |
50 | 149.35∠1.83° | 151.81∠−3.33° | 152.94∠−8.25° |
100 | 74.67∠2.77° | 77.55∠0.26° | 80.20∠−2.30° |
150 | 49.78∠3.09° | 52.03∠1.49° | 54.22∠−0.18° |
200 | 37.33∠3.25° | 39.14∠2.11° | 40.94∠0.90° |
Rg (Ω) | Zero-Sequence Capacitive Current I01.S When Point K Is at the Head (A) | Zero-Sequence Capacitive Current I01.m When Point K Is at the Mmidpoint (A) | Zero-Sequence Capacitive Current I01.E When Point K Is at the End (A) |
---|---|---|---|
10 | 16.33∠85.48° | 13.13∠65.61° | 10.53∠54.32° |
15 | 16.41∠88.20° | 14.66∠73.08° | 12.81∠62.48° |
20 | 16.44∠89.57° | 15.44∠77.55° | 14.19∠68.12° |
50 | 16.46∠92.06° | 16.73∠86.90° | 16.86∠81.98° |
100 | 16.46∠92.89° | 17.09∠90.37° | 17.68∠87.82° |
150 | 16.46∠93.16° | 17.20∠91.57° | 17.93∠89.89° |
200 | 16.46∠93.30° | 17.26∠92.17° | 18.05∠90.96° |
Rg (Ω) | Zero-Sequence Capacitive Current I02.S When Point K Is at the Head (A) | Zero-Sequence Capacitive Current I02.m When Point K Is at the Midpoint (A) | Zero-Sequence Capacitive Current I02.E When Point K Is at the End (A) |
10 | 6.53∠85.49° | 5.97∠80.38° | 5.60∠80.14° |
15 | 6.57∠88.20° | 6.33∠83.45° | 6.10∠81.54° |
20 | 6.58∠89.57° | 6.52∠85.53° | 6.40∠83.17° |
50 | 6.58∠92.06° | 6.80∠90.29° | 6.97∠88.65° |
100 | 6.58∠92.89° | 6.87∠92.15° | 7.14∠91.35° |
150 | 6.58∠93.16° | 6.88∠92.80° | 7.18∠92.35° |
200 | 6.58∠93.30° | 6.89∠93.13° | 7.20∠92.87° |
Rg (Ω) | Zero-Sequence Current Is at the Head (A) | Zero-Sequence Current Is at the Midpoint (A) | Zero-Sequence Current Is at the End (A) |
---|---|---|---|
10 | 740.59 | 595.37 | 477.62 |
15 | 496.46 | 443.50 | 387.48 |
20 | 373.11 | 350.43 | 321.91 |
30 | 249.29 | 245.19 | 237.35 |
50 | 150.19 | 152.65 | 153.80 |
100 | 76.43 | 79.37 | 82.09 |
150 | 52.41 | 54.78 | 57.09 |
200 | 40.78 | 42.76 | 44.72 |
Rg (Ω) | Zero-Sequence Current Is at the Head (A) | Zero-Sequence Current Is at the Midpoint (A) | Zero-Sequence Current Is at the End (A) |
---|---|---|---|
10 | 6.44 | 6.03 | 5.66 |
15 | 6.52 | 6.24 | 5.98 |
20 | 6.55 | 6.34 | 6.14 |
30 | 6.58 | 6.44 | 6.31 |
50 | 6.60 | 6.52 | 6.45 |
100 | 6.61 | 6.58 | 6.55 |
150 | 6.62 | 6.60 | 6.58 |
200 | 6.62 | 6.61 | 6.60 |
Rg (Ω) | Zero-Sequence Current Is at the Head (A) | Zero-Sequence Current Is at the Midpoint (A) | Zero-Sequence Current Is at the Rnd (A) |
---|---|---|---|
10 | 475.22 | 472.59 | 469.32 |
15 | 385.40 | 384.33 | 382.27 |
20 | 321.22 | 319.90 | 318.57 |
30 | 237.04 | 236.44 | 235.84 |
50 | 153.72 | 153.57 | 153.41 |
100 | 82.10 | 82.12 | 82.14 |
150 | 57.10 | 57.14 | 57.18 |
200 | 44.74 | 44.78 | 44.82 |
Current Location | Minimum Current Amplitude (A) | Start Setting of I1 (A) | Start Setting of I2 (A) | Element Action Result |
---|---|---|---|---|
PM | 965.73 | 12.80 | 643.50 | I1, “1” I2, “1” |
PN | 19.20 | 12.80 | 643.50 | I1, “1” I2, “0” |
Current Location | Minimum Current Amplitude (A) | Start Setting of I1 (A) | Start Setting of I2 (A) | Element Action Result |
---|---|---|---|---|
PM | 18.42 | 12.80 | 643.50 | I1, “1” I2, “0” |
PN | 18.42 | 12.80 | 643.50 | I1, “1” I2, “0” |
Current Location | Minimum Current Amplitude (A) | Start Setting of I1 (A) | Start Setting of I2 (A) | Element Action Result |
---|---|---|---|---|
PM | 955.71 | 12.80 | 643.50 | I1, “1” I2, “1” |
PN | 955.71 | 12.80 | 643.50 | I1, “1” I2, “1” |
Current Location | Minimum Current Amplitude (A) | Start Setting of I1 (A) | Start Setting of I2 (A) | Element Action Result |
---|---|---|---|---|
PM | 157.23 | 13.16 | 99.56 | I1, “1” I2, “1” |
PN | 19.74 | 13.16 | 99.56 | I1, “1” I2, “0” |
Current Location | Minimum Current Amplitude (A) | Start Setting of I1 (A) | Start Setting of I2 (A) | Element Action Result |
---|---|---|---|---|
PM | 19.74 | 13.16 | 99.56 | I1, “1” I2, “0” |
PN | 19.74 | 13.16 | 99.56 | I1, “1” I2, “0” |
Current Location | Minimum Current Amplitude (A) | Start Setting of I1 (A) | Start Setting of I2 (A) | Element Action Result |
---|---|---|---|---|
PM | 171.30 | 13.16 | 99.56 | I1, “1” I2, “1” |
PN | 171.30 | 13.16 | 99.56 | I1, “1” I2, “1” |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
He, Q.; He, G.; Li, Z.; Lin, M.; Zhang, G.; Li, X. Pilot Protection Based on Zero-Sequence Current Resistance-Capacitance Component for Large-Scale Inverter-Interfaced Power Stations. Sustainability 2022, 14, 13268. https://doi.org/10.3390/su142013268
He Q, He G, Li Z, Lin M, Zhang G, Li X. Pilot Protection Based on Zero-Sequence Current Resistance-Capacitance Component for Large-Scale Inverter-Interfaced Power Stations. Sustainability. 2022; 14(20):13268. https://doi.org/10.3390/su142013268
Chicago/Turabian StyleHe, Qian, Gong He, Zheng Li, Meichen Lin, Gexiang Zhang, and Xuedong Li. 2022. "Pilot Protection Based on Zero-Sequence Current Resistance-Capacitance Component for Large-Scale Inverter-Interfaced Power Stations" Sustainability 14, no. 20: 13268. https://doi.org/10.3390/su142013268
APA StyleHe, Q., He, G., Li, Z., Lin, M., Zhang, G., & Li, X. (2022). Pilot Protection Based on Zero-Sequence Current Resistance-Capacitance Component for Large-Scale Inverter-Interfaced Power Stations. Sustainability, 14(20), 13268. https://doi.org/10.3390/su142013268