1. Introduction
The energy sector is a major source of greenhouse gas emissions that is committed to reaching net zero by 2050 [
1]. This means that the total greenhouse gas emissions emitted during power generation would be equal to the emissions removed from the atmosphere during power generation, aiming to limit global warming and climate change effects [
2]. The government aims to reduce all direct emissions from public sector buildings by 50% and 75% by 2032 and 2037, respectively [
3]. The drive for net zero is prompting a new push for cleaner and more sustainable forms of power generation, thus the switch from the switch of Synchronous Generators (SGs), which are fueled by fossil fuels, to Renewable Energy Sources (RES).
Figure 1 shows a continuous rise in RES while non-RES installation is on the decline.
In traditional power systems, SGs provide transient energy on the network in the form of inertia, which is required for network stability [
4]. The inertia support from SGs refers to the energy stored in the rotating mass within the generator to maintain system frequency during sudden changes in electrical load or disturbances in the power grid [
5]. The key component is the rotor, which rotates at a constant speed, synchronous with the frequency of the grid [
6]. This kinetic energy provides inertia support to the system, i.e., if there is an increase in load demand or a sudden loss of generation elsewhere in the system, the rotational speed of the SG will change to maintain the stability of the grid [
7]. Losing SG means the network is more susceptible to frequency variation as demand and supply changes, as the transient energy stored in the rotor is not slowly declining because of the switch to RES rather than SG.
Figure 1.
Global growth of RES from 2001 to 2021 [
8].
Figure 1.
Global growth of RES from 2001 to 2021 [
8].
Inertia support works in conjunction with other control mechanisms, such as governor action and automatic generation control (AGC), to stabilize system frequency when there is a sudden increase in load, for example, the speed of the generator’s rotor decreases momentarily because of the increased mechanical load. The energy stored in the rotating mass helps to resist this change, allowing time for other control mechanisms to adjust the output of the generator to match the new demand and restore the system frequency to its nominal value [
9].
The push for net zero presents both technical and economic challenges for the power systems. The technical challenge originates from the transition from SGs to RES. The nominal function of RES is to increase the green energy generation to offset carbon footprint, and thus, it is not designed to take part in frequency control. These RES can participate if the controllers are altered to respond to frequency fluctuation. Wind turbines (WTs) use pitch and speed control to contribute to inertia. RES energy production fluctuates constantly, as the output is determined by nature [
10]. The decline in SG generators on the electrical grid coupled with the installation of non-synchronous RES generation causes the grid to have faster oscillation. RES are designed for cheaper and more reliable energy, as such a solution is for the RES to provide inertia response. In this solution, the controller of the RES would need to be altered to participate in inertia control or frequency control [
11].
To address the technical challenges from RES, Energy Storage Systems (ESS) are included in the mix of generation, as the ESS can absorb excess energy produced from RES in the network by charging and discharging shortage/excess energy when required in times of high and low demand, respectively. The most popular form of ESS deployed globally is the Battery Energy Storage System (BESS). BESS technology has drawbacks, such as low energy density, high maintenance cost, and high installation cost [
12].
The adoption of RES can potentially increase the cost of balancing (COB) of the grid. The variability of RES means that grid operators need to balance the supply of electricity more frequently, which can lead to increased costs. In addition, the integration of RES can require significant upgrades to the existing grid infrastructures, which can also increase costs.
Figure 2 represents the increase in COB in the grid in the UK from the year 2020 to 2022. The total COB for the network for the year 2020 was GBP 1.7 B, and it increased to GBP 4.2 B in 2022, i.e., an increase of 247% within two years [
13].
In a power system with multiple types of energy generation, frequency control is critical to the system’s stability, and thus, it has been investigated in the literature. The majority of studies are on demand-side management. Demand-Side Response (DSR) is a measure used to manage the demand for electricity by incentivizing consumers to reduce their energy consumption during periods of high demand or low supply. This is accomplished by offering consumers financial incentives to reduce energy consumption during peak periods [
14]. In ref. [
15], a DSR constraint model was developed based on three flexible loads, namely Electric Vehicles, BESS, and air conditioning clusters, to reduce electricity costs and improve the cost of operation. The model considered day and night to schedule the flexible loads to shift loads where RES had a surplus generation, and as a result, the cost of energy was reduced. DSR can give customers the strategic opportunity to adjust electricity consumption to reduce electric costs, by reducing load at peak times [
16]. Two customer incentive plans are detailed in the literature, namely the Price-Based Demand Response (PBDR) and Incentive-Based Demand Response (IBDR). PBDR can shift the load distribution of users and has the effect of “cutting peaks and filling valleys”, while IBDR cannot shift the load distribution of users, but the effect of load reduction during the peak period of users is better than PBDR [
17].
Optimal scheduling of VPP operation considering the intermittent supply of RES forecast on the day-ahead and real-time scale using both the PBDR and IBDR to form a two-stage optimal scheduling of a VPP supporting DSR is presented in ref. [
18]. During the first stage, the impact of the PBDR and IBDR is studied with the objective of minimizing the cost of operation of the VPP. The next stage uses the regulation characteristics of IBDR and real-time power fluctuation of the VPP during operation to ensure stability in power flow on the VPP. The proposed VPP two-stage optimal scheduling model can effectively smooth out the power fluctuation caused by the day-ahead prediction error and ensure the reliability of system operation [
18].
A Multiple Linear Regression (MLR) model was built to estimate the effects of direct loads on customers’ average hourly demand [
19]. The average reduction in hourly demand from residential load with the use of smart meter data is utilized. The MLR model found, during the summer and winter seasons, that the controlled appliances could contribute to DSR. A real-time control-based method based on export limits was implemented on a roof-top PV system [
20]. The low-voltage feeder controller utilizes a two-stage decision-making process to reduce the assigned export from the PV on the LV feeders on the distribution network. The real-time control algorithm solves a minimization problem, to assign 5 min export limits for households while ensuring that network constraints are not violated.
Generation Export Management Scheme (GEMS) is a measure for the management of electricity generation by controlling the output of the generator [
21]. GEMS operates by reducing the output of RES during periods of low demand or high supply, which helps to avoid surplus generation on the grid and ensures that the supply of electricity matches the demand. GEMS can be used in conjunction with other measures, such as energy storage systems and demand response (DR) programs, to help balance the grid and ensure reliable and stable operation.
Despite the extensive body of research exploring Demand-Side Response (DSR) and its potential to address network instability and operational costs, significant gaps remain concerning the diverse energy generation types and their involvement in frequency control. Also, another shortcoming in the existing literature is the insufficient focus on COB. While many studies emphasize the operational cost reduction capabilities of DSR strategies, such as Price-Based Demand Response (PBDR) and Incentive-Based Demand Response (IBDR), they often fail to provide a comprehensive analysis of COB, especially in systems with high penetration of Renewable Energy Sources (RES). The balancing costs, which include expenditures on ancillary services to maintain system equilibrium amid variable RES output, are underexplored, limiting the understanding of DSR’s true economic impact.
This paper examines the integration of the Generation Export Management Scheme as a strategy for power system control to mitigate both the cost of balancing (COB) and the Rate of Change of Frequency (ROCOF). While numerous studies have concentrated on Demand-Side Response (DSR) as a remedy for network instability, this research addresses this gap by exploring generation control as an alternative approach to addressing instability and the increasing cost of balancing by proposing a load frequency control (LFC) simulation model and formulating the cost of balancing when GEMS is employed. Specifically, a Set-Point Control algorithm is proposed in the LFC model to assess the impact of GEMS on COB and ROCOF.
The novelty of the methodology lies in the unique introduction of the Setpoint Control to the Maximum Power Point Tracking (MPPT) Mode within the GEMS framework. This integration enhances the responsiveness of renewable energy sources and improves frequency stability, which has not been explored in previous studies. This study focuses on generation control and demand response at the same time, offering a fresh perspective that contributes to the development of more resilient and economically efficient power systems.
To demonstrate the benefits of this work, a case study of a mini-grid is presented with cross-comparisons between the traditional control method using the MPPT and the proposed Set-Point Control. The analysis reveals that the Set-Point Control significantly reduces COB and mitigates ROCOF more effectively than traditional control strategies. This research not only provides a viable alternative to existing solutions but also opens new avenues for integrating renewable energy sources more effectively into the grid.
The remaining part of this paper is organized as follows.
Section 2 presents the theoretical framework and methodology employed in this research, including the development of the LFC simulation model with the Set-Point Control algorithm.
Section 3 presents detailed descriptions of the mathematical models for energy not supplied (ENS) and COB of the grids.
Section 4 outlines a microgrid study with data sources, simulation environment, and experimental design utilized to evaluate the impact of GEMS on the cost of balancing (COB) and Rate of Change of Frequency (ROCOF). This section also discusses the results of the simulations, analyzing the effectiveness of GEMS and Set-Point Control in reducing COB and improving frequency stability.
Section 5 summarizes this work and provides recommendations for future research.
4. Results and Discussion
This section presents a mini-grid case study to compare the setpoint control to the base model that represents the current practice with SG and BESS. A mini-grid or microgrid is an aggregation of loads and one or more energy sources operating as a single system providing electric power independently or in synchronization with the main grid [
25]. The integration of RES and energy storage systems aims to provide reliable power to a designated community or area, enhancing energy access and resilience. The mini-grid supports both autonomous operation and grid-connected configurations, allowing for optimized energy management and improved stability in power supply [
26].
The proposed model with Set-Point Control is compared against a general benchmarking model, called the base model, which employs the SG with MPPT control mode [
23,
27]. It is noted that the MPPT control model in refs. [
23,
27] is mainly for the PV system, and in this research, we also extend this to the WT system to compare and demonstrate the effectiveness of the proposed setpoint control against the existing models in the literature.
In addition, to demonstrate that the proposed model operates under conditions that closely mirror real-world scenarios, the mini-grid case study utilizes real-life data for wind and solar energy input, generated from HOMER Pro 3.16.2 [
28], which is a widely used software in academia and industry, as it includes historical real-life data.
It is assumed that the microgrid is subject to excess supply and loss of supply from the RES.
Table 1 presents the specifications of the microgrid described in this paper.
4.1. Base Model Results
The primary method of providing frequency support in the base model is from the SG. The BESS was deployed as a secondary form of frequency regulation. The model has various operating conditions such as sudden shortages or surpluses in supply, due to the intermittent nature of the RES. The BESS charge and discharge is controlled by frequency magnitude; thus, the BESS will discharge to frequencies ranging from 49.5 Hz to 50 Hz, which indicates a loss of supply. However, frequencies ranging from 50.05 Hz to 50.5 Hz indicate an excess supply of electricity. In this situation, the BESS will charge to remove excess power from the network. This mode of operation will persist until the frequency exceeds the deadband threshold of 50 Hz.
See
Figure 6 for the visual depiction of the system dynamics from the base model. During the time interval from 0 to 5 s, the frequency experiences a decline to 49.8 Hz because of a reduction in the supply from the RES connected to the network. In order to offset this loss of supply, the BESS exports the stored energy into the grid. Excess supply and low demand conditions in the system lead to a sharp increase in frequency to 50.3 Hz within a time frame of 30–40 s. As a result, the BESS will import the excess power on the network. The total cost for network balancing is approximately GBP 18 k.
4.2. Setpoint Control Model Results and Comparison
This model is influenced by various operating conditions, such as loss and surplus generation produced by the intermittent nature of RES. The link between frequency and BESS power is inversely proportional. The BESS control system is designed to respond to frequencies within the range of 49.5 Hz to 50.05 Hz by exporting power, as this signifies a deficit in the power supply. On the other hand, frequencies ranging above 50.05 Hz to 50.5 Hz indicate a surplus of supply; thus, the BESS will charge to extract surplus power from the grid. This process persists until the frequency approaches the threshold of 50 Hz, known as the dead-band point. The setpoint frequency is set to 50.2 Hz, resulting in a reduction in the overall power output of the RES to about 0 kW. The difference may be observed in
Figure 7, particularly when comparing subplot 1 and subplot 2. The graphic in
Figure 7 depicts the switching of RES from MPPT mode to frequency control mode. Specifically, between 10 and 20 s, the controller restricts the power from the RES to 0 kW as the frequency has reached the setpoint of 50.2 Hz. The setpoint control is applied within the time of 30–40 s as the RES power is restricted to 0 kW, and subsequently, MPPT mode operation returns as the frequency drops to 49.8 Hz at 50 s.
The diagram in
Figure 7 illustrates the impact of the BESS when the frequency decreases to 49.8 Hz during the time frame of 0–5 s. During this period, there is a reduction in the power supply from the RES on the network. To offset this loss of supply, the BESS discharges energy into the network. The system encounters an excess of supply, resulting in a sudden increase in frequency to 50.2 Hz during the time of 30–40 s. Consequently, the Battery Energy Storage System (BESS) charges itself to absorb the extra power in the network. The base model depends exclusively on the BESS and SG for maintaining network equilibrium, whereas the SC model utilizes the RES to maintain frequency stability. The network balancing incurs a total cost of around GBP 18.07 k.
For a better interpretation of the setpoint control, see
Figure 8, where the established frequency threshold of 50.2 Hz serves as a critical operational boundary.
The top graph in
Figure 8 provides a detailed representation of grid frequency dynamics, fluctuating within the narrow range of 50.1995 Hz to 50.2005 Hz over a short temporal window. Notably, at approximately 13.6 s, the grid frequency breaches the 50.2 Hz threshold, marking a significant point. The bottom graph, depicting the total RES power output, exhibits a direct and immediate response to this frequency breach. Once the frequency exceeds 50.2 Hz, the RES power output undergoes a sharp curtailment, dropping to zero; this is the effect of the Setpoint Frequency control. This behavior strongly suggests the setpoint control mechanism designed to safeguard grid stability by curtailing renewable generation during over-frequency events. The coordinated response between grid frequency and RES output reflects a deliberate operational strategy aimed at mitigating the risks of frequency excursions, thus ensuring the system remains within secure operational limits.
Figure 9 provides a clear comparative analysis of the grid frequency behavior and total renewable energy source (RES) power output under the base case and the setpoint frequency control. This comparison presents a valuable insight into the operational differences and their implications on system stability.
In the upper graph of
Figure 9, the base case exhibits a gradual decline in frequency, starting just above 50.2 Hz and tapering toward 50 Hz. While this decline suggests a natural rebalancing of generation and load within the system, the base case is marked by inherent oscillations, which could potentially destabilize the grid under certain conditions. In contrast, the 50.2 Hz setpoint control imposes a more stringent regulation, maintaining the frequency within a narrower and more controlled range near the 50.2 Hz threshold. The comparison also demonstrates a frequency swing of 0.3 Hz between both cases. unlike the base case, where the frequency is allowed to fluctuate, the setpoint control effectively mitigates these deviations, thereby ensuring a more stable frequency profile. This behavior is critical in maintaining grid reliability and avoiding over-frequency conditions that can strain system components.
In the lower graph of
Figure 9, the total RES power output further illustrates the operational impact of the setpoint frequency control compared to the base case. Under the base case, RES output would likely continue to be curtailed, contributing to frequency oscillations and the risk of breaching acceptable operational limits. However, with the setpoint control active, RES output is drastically curtailed during the 30 to 40 s window, remaining close to zero. This sharp reduction in renewable power generation is a direct consequence of the setpoint control’s response to elevated frequencies, particularly as the frequency approaches the 50.2 Hz mark. This deliberate curtailment serves as a safeguard, preventing further contributions to frequency elevation from RES, which, in turn, assists in maintaining overall system stability. The coordinated response between the controlled reduction in RES power and the stabilization of grid frequency reflects the efficacy of the setpoint frequency control in managing over-frequency events.
4.3. Sensitivity Analysis
The setpoint control is applied to various frequency limits to estimate the COB and ENS if the control is applied to an electrical grid. The frequencies at which the setpoint control is tested vary from 49.5 Hz to 50.5 Hz as the nominal operation for the UK grid. See
Table 2 for the detailed sensitivity analysis results for the setpoint control.
From
Table 2, the frequency swing is constant at 49.5 Hz–49.7 Hz, which indicates the system experiences similar power exchanges, as the SC would not have been utilized, as the frequency did not go above the setpoint limit. However, from frequency 50.1 Hz to 50.5 Hz, the frequency swing increases to suppress the over-generation from RES because of the setpoint control. The effect of setpoint control is observed in that the frequency swing drops as the setpoint frequency control limit increases.
The setpoint control sensitivity analysis for the ENS gives a different perspective as to why the operational frequency band is between 49.5 Hz and 50.5 Hz. The ENS has an inverse relationship with frequency. In terms of the COB, it reduces as the setpoint frequency increases. However, the COB is constant for frequencies at 50.4 Hz and above. This is interesting, as it implies that there is a limit on the setpoint frequency control at which no benefit in terms of COB is obtained.
The sensitivity analysis for the COB indicates that the COB has a similar trend to the ENS, which indicates the direct relationship between ENS and COB. The ENS is less between 50 and 50.5 Hz, as the RES setpoint control is used less within these frequencies, as overgeneration from RES can be accommodated with the higher frequency band. In lower frequencies from 49.5 Hz to 49.9 Hz, both the ENS and COB are higher because the frequencies band is too tight, and as such, the setpoint control would be utilized to minimize frequency swing.
The comparative analysis of control strategies based on the metrics of frequency swing, ENS and COB, clearly demonstrates that the 50.5 Hz setpoint control strategy outperforms the 49.5 Hz setpoint control strategy and the base case. The 50.5 Hz setpoint control strategy exhibits a marked improvement in the frequency stability with a frequency of −0.6 Hz, which is significantly lower than the 0.6 Hz observed in the base case and the 0.5 Hz setpoint in the 49.5 Hz Setpoint Control. This indicates a superior capacity for frequency regulation, which is critical for the reliable operation of power systems, especially under high renewable energy penetration.
In relation to ENS, the 50.5 Hz Setpoint Control strategy achieves a reduction of 5 KWh in the ENS compared to 915 KWh seen in the 49.5 Hz Setpoint Control strategy scenario. The substantial decrease in ENS highlights the 50.5 Hz Setpoint Control strategy efficiency in aligning generation with demand, thereby minimizing frequency variation and enhancing system reliability. The significant reduction in the ENS underlines the strategic advantage of employing a higher setpoint control, as this method mitigates the negative impacts of supply–demand mismatch.
In terms of the COB metric, the 50.5 Hz Setpoint Control strategy is the most effective, with a COB of GBP 5.278/kWh, significantly outperforming both the base case (GBP 18/kWh) and the 49.5 Hz Setpoint Control strategy (GBP 42.74/kWh). This analysis indicates that the 50.5 Hz Setpoint Control strategy not only stabilizes system frequency more effectively but also reduces the COB of operating the microgrid. This ability to achieve lower balancing costs is a critical factor with more RES installed on the network.
Table 3 compares the worst- and best-case scenarios of the setpoint control sensitivity analysis against the base case of the microgrid considering three factors, namely the COB, frequency swing and ENS.
From
Table 3, the COB is estimated at GBP 42.74 k and GBP 5.278 k for the worst- and best-case scenarios for setpoint control; subsequently, these scenarios perform better than the base case system, which did not include control of the RES but solely relied on the SG and BESS for maintaining frequency within the operational limits. The difference between the cost of balancing is attributed to the ENS not being supplied in both models; the ENS is the difference between the RES operating in MPPT and FC mode, and thus, there is a direct relationship between the ENS and COB. However, the base case model does not have an ENS magnitude, as this model does not utilize the RES for frequency control.
5. Conclusions and Recommendations
This research presents the need to highlight a growing problem with RES integration from both the power system stability and economic perspectives. The cost of balancing the grid while considering generation management as an alternative method with DSR is investigated to improve the system stability. To achieve the results, a mathematical model for COB, ENS and network frequency is implemented on an LFC simulation model using setpoint control to consider these variables.
The relationship between setpoint frequency, Energy Not Supplied (ENS), cost of balancing (COB), and frequency swing (an indicator of the Rate of Change of Frequency, ROCOF) provides critical insights into optimizing power system performance, especially with high integration of Renewable Energy Sources (RES). The innovative aspect of this research lies in the strategic adjustment of setpoint frequencies and the dynamic switching between Maximum Power Point Tracking (MPPT) and modes—a method that extends beyond traditional approaches found in the existing literature.
From the case study results, the higher setpoint frequencies facilitate better accommodation of RES overgeneration, resulting in lower ENS and COB. Specifically, as the setpoint frequency increases from 49.5 Hz to 50.5 Hz, ENS decreases significantly, and COB reduces correspondingly. Additionally, the frequency swing decreases at higher setpoint frequencies, indicating improved frequency stability and reduced ROCOF.
In principle, the network balancing cost is influenced by the magnitude and duration of frequency deviations, the costs associated with using SG, BESS and RES for energy transactions during balancing actions. In the case study, the period of the balancing cost is a 60 s simulation duration, capturing the dynamic interactions between RES variability, demand fluctuations, and frequency control actions. The sensitivity analysis for the proposed setpoint control reveals that the setpoint frequency also influences the cost of balancing and it could significantly reduce the COB, as demonstrated in
Section 4.3.
This demonstrates that the innovative control strategy not only enhances economic outcomes but also strengthens system stability. The setpoint control strategy with frequency limit of 50.5 Hz demonstrates the best performance in terms of the COB while maintaining low-frequency swing and minimal ENS cost, making it the preferred choice for frequency management and cost-effective grid operation compared to the traditional model. By significantly enhancing frequency stability, reducing ENS, and minimizing COB, this strategy offers a robust solution for modern power systems challenged by the need for efficient integration of renewable energy sources and maintenance of grid stability. Our simulation results demonstrate that our proposed method offers significant enhancements over traditional LFC approaches. For instance,
Figure 2 and
Figure 3 show a reduction in frequency overshoot and a faster return to nominal frequency compared to the base scenario. This indicates improved system resilience and effectiveness of our control strategy. Finally, all the COB, ENS and frequency metrics for the setpoint control compared to the base scenario are detailed in
Table 3.
Future work should explore the scalability of this approach for real-world power grids with further economic evaluation and grid conditions and its integration with other grid management technologies to further enhance system resilience and operational efficiency. This work can also be further expanded to consider other factors such as the State of Charge for hybrid energy storage systems, and subsequently the use of machine learning to ensure that the best control strategy is utilized to achieve the lowest cost of balancing based on RES prediction.