1. Introduction
Belgium has a very extensive motorway system, which is one of the densest in the world, and is one of the busiest transit countries in Europe. Approximately 40% of the Belgian roads are made of non-reinforced and reinforced concrete [
1]. The quality and condition of road infrastructure differs from region to region. Most road construction and maintenance is observed in the north of Belgium in the Flemish Region (Flanders). Flanders invests 350 million euros in the maintenance of roads and bridges every year. The road infrastructure in the south of Belgium (Wallonia) and Brussels-Capital Region is in a quite poor condition where no maintenance is being carried out. Over the past five years there has been an increase of potholes [
2,
3] as a result of severe winter weather, primarily through the physical process of freeze–thaw and the ingress of water.
Concrete infrastructure elements should have adequate strength and durability in order to guarantee the proposed design life. The performance of both flexible and rigid pavements is significantly influenced by environmental conditions [
4]. The impact of freeze–thaw cycles plays a key role in defining the bounds of the environmental impact on the performance of the pavement. In Belgium, road engineering applications are regulated by the Standaard Bestek 250 (SB250) [
5]. In this code, the concrete composition restrictions are listed (water-to-cement ratio, choice of cement type and amount, minimal compressive strength, water absorption ratio and scaling/exfoliation), in order to come to a durable concrete application. In practice [
3], a lot of damage of the Belgian concrete roads is visible. According to Jones et al. [
2] freeze–thawing is the second main deterioration process affecting the concrete’s durability, besides steel corrosion in reinforced concrete elements. The main factors contributing to concrete failure are the impact of the environment, poor concrete quality, and insufficient handling and curing of the freshly cast concrete. During harsh Belgian winters under condition of negative temperatures, cycles of freezing and thawing, and in combination with the use of de-icing salts, concrete infrastructure (roads and bridges) suffers from scaling, which increases the roughness of the surface with following decrease of the thickness of the concrete pavement and internal mechanical degradation due to freeze–thaw attack [
6]. This exfoliation of the outer concrete layers results in a reduction of durability, comfort and safety of its practical application [
6]. Dooms et al. [
3] also mentioned that in the case where supplementary cementitious materials (SCMs) such as blast furnace slags and fly ashes are used, the effect of the curing duration and handling is of major importance in order to come to a durable and frost resistant concrete. In cases where de-icing salts are used, the impact of the freeze–thaw effect is worsened, mainly due to the scaling effect (chlorides lower the freezing point and the temperature gradient due to the de-icing effects leading to exfoliation of the outer concrete layer) and the osmotic pressure (due to salt concentration gradient).
In order to overcome internal mechanical degradation, concrete has to contain small cavities/pores in the concrete matrix which form a connecting network of pressure vessels. This network of pores can react to increasing pressure of the freezing water reducing the tension pressure in the upper and inner concrete layers. In SB250 [
5], the standard measure to overcome frost damage (with or without the use of de-icing salts), is the use of air entrainment agents (AEA) for a durable concrete. It is well known that inducing additional air into a concrete matrix leads to reduction of the tensile and compressive strength of the material (one percent induced air leads to a roughly five percent strength reduction) [
7]. In Belgium, in the case of traditional concrete, air entrainment agents (AEA) are added into concrete mix in order to increase resistance against freeze–thaw actions. In the case of heavy load bearing structures, addition of AEA into concrete mix is not desirable since it gives significant strength losses [
7]. An improvement in degradation resistance of concrete pavements can be obtained by modifying the composition of the considered pavement or its components. The use of fibers and/or polymer modified binders in asphalt has proven to be very efficient for concrete layers [
8]. A study conducted by [
9] mentioned the improvement of frost scaling resistance by replacing Ordinary Portland Cement (OPC) of the reference concrete mix with fly ash (FA) and/or silica fume (SF) (up to 15% by weight of cement). However, it was noted that scaling values of the FA specimens without SF were less than control specimens’ scaling, but they did not satisfy the capillary suction, se-icing agent and freeze–thaw-test (CDF) criterion. The obtained ternary concrete mix with 15% OPC replacement with 10% of fly ash and 5% of silica fume showed a significant reduction up to 50% of the scaling. This was also confirmed by Dooms et al. [
3] evaluating the scaling of concrete (W/C-ratio of 0.45, 340 kg of added cement) with various cement types. In the case where sufficient curing (56 days under water) of the specimens was applied, specimens containing blast furnace slag clearly performed better compared to the ones containing OPC. The difference between specimens that were cured in open air (relative humidity of 60%) was much smaller. In practice [
3], concrete infrastructure elements using blast furnace slag cements or other supplementary cementitious materials suffer severely from freeze–thaw actions, especially in cases where the curing time was insufficient.
As an alternative solution for the improvement of scaling resistance, the use of superabsorbent polymer materials (SAPs) can be recommended. SAPs are cross-linked hydrogel networks consisting of water-soluble polymers which generally are composed of ionic monomers and need a low cross-linking density in order to create a large fluid uptake capacity. SAPs can take up and hold aqueous solutions up to several hundred times their own weight while retaining it even under pressure [
10]. As the SAPs will release their water during hardening, they will leave behind air-filled pores. During freeze–thaw cycles, these voids can protect concrete in a similar way as by using air entrainment [
11]. With SAPs, the dimensions of the voids are fixed to the swollen state of the SAP during mixing, in contrast to regular air entrainment. Addition of SAPs does not necessarily need to affect the compressive strength [
12] and seems to be promising independent from local raw materials and production processes [
13].
The scope of this paper was to report an investigation under laboratory conditions on concrete durability by creating a size and shape-designed pore systems using SAP in concrete mixes, as an in alternative to AEA, in order to improve its durability, especially in terms of freeze–thaw resistance.
3. Results and Discussion
3.1. Fresh Properties
It was decided that in order to keep the total water content constant throughout the entire experimental program in order to maintain the prescribed consistency class S3–S4 of concrete mix, an additional amount of superplasticizer was needed (see
Table 3 and
Table 4). In the case of the coarser commercially available SAP
CT, the amount of superplasticizer was equal to that of the reference concrete mix. As a consequence, the slump value decreased by 47%. For the finer prototype SAP, doubling the amount of superabsorbent polymer led to a decrease in a slump by 20% (SAP0.26
PT vs. SAP0.13
PT). In order to get the same slump value, an additional amount (more than 50%) of superplasticizer was needed in case the amount of SAP was increased by 33% (SAP0.39
PT vs. SAP0.26
PT). By adding SAPs, the air content of the fresh concrete mix increased by 20%.
3.2. Mechanical Properties
All concrete mixes, except for the one containing AEA, have met the requirement of a minimal mean compressive strength of 50 MPa according to SB250 (see
Figure 6). It is evident that the amount of added SAPs influences the compressive strength.
By adding SAPs into the REF concrete mix the compressive strength evolution was noticed after 28 days in all cases (see
Figure 6, increase between 10% and 20%). This increase in strength is most likely due to the decrease in effective W/C-ratio due to the addition of the polymers during mixing. It is well known that strength of concrete increases when the W/C-ratio is lowered, e.g., by adding SAPs. However, at the age of 90 days, the strength only increased in the 0.13 and 0.26 wt % prototype polymer. Addition of the coarser commercially available SAPs or a higher amount of prototype polymer had a negative effect on the compressive strength. By adding 0.13 to 0.26 wt % prototype polymer, a higher 28-day and 90-day strength was obtained compared to the concrete mix with the same amount of commercially available polymer. The higher absorption capacity of the finer prototype SAP led to a higher reduction in effective W/C-ratio. By adding air entrainment agents, the strength was lowered significantly by 33% after 28 days.
It can be concluded that by increasing the amount of SAPs the strength develops slower, but in cases where finer SAPs are used in an optimal amount, the strength is higher compared the reference concrete mix without polymers. The optimal percentage of SAP in this experimental program is the range of 0.13–0.26 wt % (weight of dry SAP relative to the cement weight).
3.3. Evaluation of the Freeze–Thaw Resistance
The mean exfoliation of the reference concrete specimens after 28 consecutive freeze–thaw cycles is presented in
Figure 7. Scaling of 3.1 g/dm
2 was obtained which is less than the acceptance criterion of 10 g/dm
2 (according to SB250), mainly due to the perfect curing conditions preceding the casting.
For the commercially available polymer the resistance against scaling is lower: scaling of 4.1 g/dm2 was obtained after 28 cycles, which is an increase of 32%. By adding the coarse and commercially available superabsorbent polymers SAPCT the freeze–thaw resistance of the concrete was not ameliorated.
Addition of finer superabsorbent polymers SAPPT into the concrete mix had a positive effect on the freeze–thaw resistance: in the case of 0.13 wt %, 0.26 wt % or 0.39 wt % the exfoliation after 28 cycles decreased by 30%, 42% and 43%, respectively. This proved that the amount of added SAPs and the type (more specific: the grading and retention capacity) is a decisive factor for the improvement of the freeze–thaw resistance of concretes with W/C-ratio between 0.40 and 0.50.
It can be concluded that the optimal percentage of SAPs in this research study is quite close to the percentage of 0.26–0.39 wt % (weight of dry SAP relative to the cement weight). The size of the polymers has a decisive effect on the effectiveness: SAPs with mean particle size less than 100 μm have a positive effect, while SAPs with mean particle size greater than 500 μm have a negative effect. It must be mentioned that the obtained results in this study are applicable to the concrete mixes used in it, and cannot be generalized for all concrete types.
It has to be noted that by using AEA, the cumulated exfoliation was reduced significantly compared to the reference concrete mix. The cavities created by the polymers or the air entrainment agents compensated for the expanding freezing water, where for the dense reference concrete mixes less space was available, leading towards more scaling and internal cracking. Addition of AEA significantly reduced the strength which might be undesirable for infrastructure concrete for roads and bridges.
By comparing the freeze–thaw testing procedure (FT1 vs. FT2) it became clear that this has a major impact on the obtained results (see
Figure 8). The measured cumulated exfoliation is three times higher for the reference concrete mix in the case where the ISO/DIS 4846-2 method was used. The sudden temperature drop from +20 °C to −18 °C and the use of CaCl
2 instead of NaCl might explain the observed difference. For the concrete mixes AEA’ and SAP0.26-CT” the exfoliation was approximately four times higher (see
Figure 8). Especially after 5 to 10 freeze–thaw cycles, the concrete experience had quite high scaling.
3.4. Evaluation of Porosity and the Microstructure
3.4.1. The Water Absorption by Immersion
Small differences were noticeable in the obtained results of the water absorption of the specimens of the different concrete mixes, and all concrete mixes complied with the acceptance criterion of SB250 (absorption smaller than 6.3%). In the case of SAP
PT, the water absorption was decreased compared to the reference concrete mix, which is not the case for the commercially available polymer (see
Table 4). Addition of AEA increased the water absorption capacity of the concrete.
3.4.2. Scanning Electron Microscopy and Petrography on Thin Sections
By means of petrographic microscopy on thin sections the microstructure of concrete mixes REF, SAP0.26
CT and SAP0.26
PT were visualized (see
Figure 9).
For the reference concrete mix REF (see
Figure 9a) several air bubbles are noticeable with diameter in between 250 μm and 340 μm. Internal micro-cracking was observed most likely due to the self-desiccation of the matrix (e.g., autogenous shrinkage). SEM imaging (see
Figure 10a) confirms the micro-cracking. A very dense matrix was also noticeable, which is typically for concrete containing blast furnace slags. The spacing factor, i.e., the distance of the shortest travel path of expanding water, varies between 510 and 1760 μm. In the literature [
20], a distance factor of approximately 200–300 μm can be seen as effective. A SEM image of the AEA mix after 28 freeze–thaw cycles (see
Figure 10b) proves that this distance is necessary for effective improvement of the freeze–thaw resistance. It should be noticed that the cracks move towards the air bubbles. The higher factor of the reference concrete mix can be an explanation of the experienced scaling. By using the commercially available polymer in SAP0.26
CT (see
Figure 9b) the amount of air voids and its dimensions increases significantly: voids with size up to 1000 μm were found. The voids with irregular shape are created by the superabsorbent polymer. The spacing factor also varies from 500 to 880 μm, which is too high for effective freeze–thaw resisting concrete.
In concrete mix SAP0.26
PT with the finer prototype polymer (see
Figure 9c), several air bubbles and irregular structures can be identified. The shape and size of these air bubbles are more or less the same as the air bubbles shown in the previous two images (see
Figure 9a,b). However, these air voids are well scattered small irregular structures in this composition, with a spacing factor close to 200 μm. These cavities are the result of adding the prototype superabsorbent polymers: they have a smaller size than the pores created by adding commercially available type. This is the main reason why these compositions containing fine SAPs show a better freeze–thaw resistance in comparison to the reference composition.
The cavities formed by the SAPs are very recognizable due to their more irregular shape compared to air bubbles. During mixing, the superabsorbent polymer particles absorbed a part of the mixing water (pore fluid) but not at their full absorbing capacity due to the alkalinity of its environment. The absorbing capacity of pore solution was lower than the absorbing coefficient of pure water. During hardening and hydration of the cement in concrete, the minerals in the cement particles form CSH layers with the free mixing water. At a certain time, no more free water was available for the continuation of the hydration process and self-desiccation started, leading towards an under-pressure in the matrix, and autogenous shrinkage cracking in the case of the reference concrete mix. As a consequence, the water absorbed by the SAPs was gradually released and the hydration process continued in the close environment and in contact with the SAPs: small cavities between 190 μm up to 370 μm remained in the matrix. These cavities can serve as expansion vessels for expanding freezing water in the matrix.
4. Conclusions
Based on the reported research concerning the freeze–thaw resistance of concrete mixes used for infrastructure (road and bridges) applications, and the effect of superabsorbent polymers (SAPs) for the improvement and mitigation of its resistance as an alternative for the application of air entrainment agents (AEA), the following conclusions can be drawn:
Increasing the amount of SAPs in the concrete mix led to a small increase of compressive strength after 28 days of hardening, mainly as a result of the decrease of the effective W/C-ratio due to absorption of free water by the polymers during mixing. The difference decreased or even disappeared after 90 days of hardening where the amount of SAPs was too high or the size of the polymers was too large. Small cavities (between 190 μm up to 370 μm) were created in the matrix. Due to the absorbed water, self-desiccation during the hydration process was reduced, leading towards a higher ultimate degree of hydration, which clearly compensated the strength reduction due to the more porous matrix. By addition of an optimal percentage of SAPs in the range of 0.13–0.26 wt % (weight of dry SAP relative to the cement weight), there was a clear reduction of scaling. The particle size of the SAPs is a very important factor: polymers with mean size less than 100 μm had proven their effectiveness, while polymers with mean size up to 500 μm showed to be ineffective. The cumulated mass loss after 28 freeze–thaw cycles of the concrete mix can be less than 2 g/dm2 in the case of 0.26–0.39 wt % SAPs (relative to the cement weight) were added into the concrete mix.
By comparing the freeze–thaw testing procedure, it became evident that this has a major impact on the obtained results. The measured cumulated exfoliation is three to four times higher for the concrete mixes in the case where the ISO/DIS 4846-2 method is used. The sudden temperature drop from +20°C to −18°C and the use of CaCl2 in the case of NaCl might explain the observed difference.
It has to be noted that the obtained conclusions regarding dosage and size of SAPs to be added are only applicable for the concrete mixes mentioned in this experimental research study.