Flowing Blow-Offs: A Solution to Maintain Adequate Disinfectant Residuals of Dead-End Nodes in WDNs †

1
Department of Civil Engineering and Architecture, University of Pavia, Via Ferrata 3, 27100 Pavia, Italy
2
Department DICDEA, University of Campania Luigi Vanvitelli, via Roma 29, 81031 Aversa, Italy
3
Bentley Systems, 3 Brian’s Place, Nanticoke, PA 18634, USA
*
Author to whom correspondence should be addressed.
Presented at the 4th International Electronic Conference on Water Sciences, 13–29 November 2019; Available online: https://ecws-4.sciforum.net/.
Proceedings 2020, 48(1), 20; https://doi.org/10.3390/ECWS-4-06443
Published: 12 November 2019
(This article belongs to the Proceedings of The 4th International Electronic Conference on Water Sciences)

Abstract

:
Flushing plans within a water distribution network (WDN) provide a tool for improving disinfectant residuals and removing stagnant water. The problem of low disinfectant residuals occurs in areas of a WDN such as dead-end nodes, in which low flow conditions and long residence times lead to excessive decay of the disinfectant upstream from users. Here, a methodology is presented to maintain adequate disinfectant residuals in WDNs that have numerous dead-end nodes. The slight increase in nodal outflows at these sites, which can be obtained through the opening of a blow-off at the hydrant site, can help in tackling this problem. The methodology is based on the combined use of optimization and of flow routing/water quality modelling. The concentration of disinfectant at the source(s) and the values of nodal emitter coefficients at the critical dead-end nodes are the decisional variables to be optimized. Two objective functions are considered in the optimization, namely the total volume of water delivered in the network and the total mass of disinfectant injected into the network. The effectiveness of the methodology is proven on a real WDN, yielding an insight into the economic feasibility of the solution.

1. Introduction

Disinfection within the water distribution network (WDN) is necessary to prevent drinking water from being harmful to our health. As disinfectant travels through the pipes in a distribution system, it can react with a variety of materials both within the bulk water and from the pipe wall [1]. However, in some terminal nodes of the WDN, disinfectant concentrations may become lower than the minimum values necessary to guarantee users’ protection from contaminations (as prescribed by technical guidelines) [2]. The problem of low disinfectant concentrations occurs in areas such as dead-end nodes, in which low flow conditions lead to long residence times and to excessive decay of the disinfectant upstream from users. A solution to this problem may be to increase the concentration of disinfectant fed at the treatment plant. Although this is done in some cases, it may create excessive disinfectant residuals near the feeding point, resulting in taste and odor problems, as well as in the formation of carcinogenic disinfection by-products (DBPs) [3]. Another possible solution to the problem lies in the use of additional disinfectant booster stations [4,5,6,7]. However, these solutions cause an increase in installation and operational costs for water utility managers. Furthermore, when critical nodes are scattered over the WDN, it may be infeasible to serve all critical dead-end nodes with a reasonable number of booster stations.
This paper presents a solution to the problem of low disinfectant residual in water systems that have numerous dead-end nodes and water circulation problems. The solution proposed is based on the slight increase in nodal outflows all day long, through the opening of a blow-off at a dead-end node, to obtain a continuous flow. This increase can be obtained by proposing incentives to users, to encourage them to store water in household tanks at remote nodes, to be used for instance for irrigation purposes. Otherwise, a tap can be slightly opened at the hydrant-site in proximity of the generic critical dead-end node. The opening degree of these devices must be modulated in such a way so as to obtain the smallest increase in pipe flow that enables meeting the minimum concentrations of disinfectant at downstream critical nodes of 0.2 mg/L as prescribed by the current regulation. Obviously, nodal pressure deficits must also be prevented when outflows are increased.

2. Methods

The plan of nodal blow-offs to prevent low disinfectant concentrations in WDN can be developed by making use of models that simulate WDN behavior in terms of both flow routing and water quality (disinfectant decay), such as EPANET [8] or WaterGEMS® [9].
In these pieces of software, flow through an open hydrant is simulated as an emitter, with pressure-driven demand Q given by Equation (1):
Q = e   P n
where Q is the flow through the hydrant (m3 s−1), e is the emitter coefficient (m3−n s−1), P is the pressure upstream of the hydrant (m) and n is the emitter exponent (equal to 0.5). Using the emitter object, the flushing outflow rate in the considered node depends on the value of the pressure in each time step.
The modulation of nodal outflows can be tackled as an optimization problem, in which compromise solutions are sought for between two objective functions (f1 and f2) to be minimized.
The first objective function f1 is to minimize the total volume of water delivered in the network Vol (m3), given by Equation (2):
f 1 =Vol = j=1 N Δt i=1 n n q i,j Δt
where qij is the flow rate delivered at the i-th node (m3 s−1), nn is the total number of nodes, Δt the j-th time step(s) and NΔt the total number of steps of the simulation. The variable Vol includes all nodal outflows (leakage from WDN pipes + standard outflow + additional outflow considered for fixing disinfectant residuals).
The second objective function f2 is to minimize the total mass of chlorine fed into the network W (kg), given by Equation (3):
f 2 =W= C cl j=1 N Δt i=1 n n q i,j Δt
where Ccl is the concentration of disinfectant imposed on supply (kg m−3). Indeed, f2 can be simply assessed by multiplying f1 = Vol by Ccl.
The decision variables are Ccl and the values of the emitter coefficients e at the nn critical nodes of the network. These emitters can be considered as elements of a vector e = (e1, e2, …, enn).
Two constraints were considered in the methodology:
(1)
a minimal residual pressure hmin ≥ 12 + 10 = 22 m (12 m is the height of the average building in the network while 10 m is the surplus of head pressure as prescribed by the Italian guidelines), and
(2)
the minimum residual chlorine concentration Ccl,min = 0.2 mg/L, as prescribed by the current regulation.
A heuristic procedure was set up in this work to obtain this Pareto front, using the EPANET 2.0 solver in MATLAB environment [10].

3. Application

The network model considered in this work is shown in Figure 1 [11]. It includes 623 demand nodes, 678 pipes and 1 source node, with total head ranging from 38.00 to 42.00 m.
The network hydraulics are periodic on a 24 h cycle. To represent the daily variation in the users’ demand in the system a pattern was used for the hourly demand with multiplier values ranging from 0.500 to 1.335. The total system demand is 68.54 L/s. WDN emitters were tuned in such a way so as to obtain a percentage of leakage around 20%, consistently with the real WDN.
For water quality simulations, chlorine was chosen as disinfectant. In the chlorine decay simulation, bulk and wall reactions are both first-order. The bulk decay constant (kb) was assumed to be 1.0 d−1 from literature for all the links and the wall decay constant (kw) was assumed negligible because network pipes are made of plastic material (smooth surface of pipes’ internal wall) [1,12,13]. The simulations were run for 10 days of WDN operation using a time step of 1 h, to make sure that chlorine injected close to the reservoir had enough time to reach the final nodes of the network, and to reach well-established cyclical operating conditions in the last day of simulation. The initial chlorine concentration was set at 0 at all WDN nodes.
In an initial exploratory simulation with EPANET, chlorine was injected into the source node with a constant concentration of Ccl = 1.0 mg/L, typical low value used at WDN sources. The software was used to identify the critical nodes, with a residual chlorine concentration below the minimum constraint of Ccl,min = 0.2 mg/L in the last day of WDN operation.
Specifically, 24 nodes were identified with minimum chlorine concentration below 0.2 mg/L. These critical nodes are scattered in the WDN and they are located at various dead ends.
A viable option to correct violations lies in increasing flows constantly at dead-end nodes by opening blow-offs at the critical terminal nodes. To this end, the procedure presented above was applied to the WDN for the following eight values of Ccl = 1, 1.1, 1.2, 1.4, 1.6, 2, 3, 4 mg/L.

4. Results

As a result of the optimization problem, the approximated Pareto front of optimal solutions is shown in Figure 2. In the graph, the total mass W of chlorine injected at the source is plotted against the total volume Vol of water delivered in the network (including supply, leakage and additional outflow considered for fixing chlorine residuals).
As expected, the graph highlights that higher values of W are associated with lower values of Vol and vice versa. This contrast is because, when there is no additional outflow (minimum value of Vol), it is necessary to impose high concentrations of chlorine at the source with high W value, to meet chlorine residual requirements even at dead-end nodes. On the other hand, by imposing some additional outflows (high values of Vol) near identified critical nodes, it is possible to obtain the satisfaction of the minimum concentrations of chlorine with low values of W.
Each solution of Figure 2, featuring certain values of Vol and W associated with a single value of Ccl, can be postprocessed for cost analysis, as is shown in Table 1. The economic analysis was carried out considering a chlorine unit cost of 4.89 €/kg and various values of water unit cost cw.
The calculations reported in Table 1 point out that, for the various values cw considered, the lowest values of Ctot are obtained for low values of chlorine concentration Ccl at the source (≤1.4 mg/L). This corresponds to solutions with lower values of W and slightly larger values of Vol.
The additional nodal blow-offs can be considered as another kind of water loss, besides leakage along WDN pipes. In Table 1, the percentage of leakage plus additional nodal blow-off, calculated with reference to the total outflow from the source, only slightly increases compared to the no-dripping scenario (20%). In fact, the maximum value of this percentage is 20.51% (see third column in Table 1). This means that the slight opening blow-offs for improving water quality at dead-end nodes worsen water losses in the WDN only slightly. However, it must be remarked that the small value of nodal outflows may make the results of this methodology difficult to apply rigorously in the field. It is likely that the opening of hydrants or faucets in the field may cause larger outflows than those required by the methodology.

5. Discussion

Additional simulations were carried out to perform a sensitivity analysis of different parameters. In this context, a single value Ccl = 1 mg/L was considered for the chlorine concentration at the source since the effects of this parameter were considered above. A range of variation [0.75, 1.25] was considered for both the demand multiplier and the bulk decay constant to analyze the effects of demand seasonality and chlorine decay conditions. Table 2 shows the number of opened hydrants and the total daily additional outflow that correct chlorine deficits in five different scenarios.
As expected, the decrease in demand and the growth of the bulk decay constant cause the increase in the number of hydrants to open and in the hydrant outflows.
Finally, other simulations were performed to investigate if hydrants running with larger outflow (e.g., 5–10 L/s) can be flowed for a short period instead of dripping hydrants to fix chlorine residuals. However, these simulations proved that hydrants with larger outflow are ineffective at solving the problem of low disinfectant concentrations at some sites, besides causing larger head-losses in the WDN. Therefore, the use of dripping faucets and hydrants should be preferred.

Author Contributions

S.A. and E.C. wrote the paper, E.C. developed the coding, S.A. performed the analysis, C.G., T.W., S.T. and A.D.N. revised the paper. All authors have read and agreed to the published version of the manuscript.

Acknowledgments

This research was conducted within the EU project Wat-Qual (Grant Agreement No. 778136).

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Rossman, L.A.; Clark, R.M.; Grayman, W.M. Modeling chlorine residuals in drinking water distribution systems. J. Environ. Eng. 1994, 120, 803–820. [Google Scholar] [CrossRef]
  2. World Health Organization. Guidelines for Drinking Water Quality, 4th ed.; WHO: Geneva, Switzerland, 2011. [Google Scholar]
  3. Morris, R.D.; Audet, A.M.; Angelillo, I.F.; Chalmers, T.C.; Mosteller, F. Chlorination, chlorination by-products, and cancer: A meta-analysis. Am. J. Public Health 1992, 82, 955–963. [Google Scholar] [CrossRef] [PubMed]
  4. Boccelli, D.L.; Tryby, M.E.; Uber, J.G.; Rossman, L.A.; Zierolf, M.L.; Polycarpou, M. Optimal scheduling of booster disinfection in water distribution systems. J. Water Resour. Plan. Manag. 1998, 124, 99–111. [Google Scholar] [CrossRef]
  5. Tryby, M.E.; Bocelli, D.L.; Uber, J.G.; Rossman, L.A. Facility location model for booster disinfection of water supply networks. J. Water Resour. Plan. Manag. 2002, 128, 322–333. [Google Scholar] [CrossRef]
  6. Propato, M.; Uber, J.G. Linear least-squares formulation for operation of booster disinfection systems. J. Water Resour. Plan. Manag. 2004, 130, 53–62. [Google Scholar] [CrossRef]
  7. Carrico, B.; Singer, P.C. Impact of booster chlorination on chlorine decay and THM production: Simulated analysis. J. Environ. Eng. 2009, 135, 928–935. [Google Scholar] [CrossRef]
  8. Rossman, L.A. EPANET 2 User’s Manual; United States Environmental Protection Agency: Cincinnati, OH, USA, 2000. [Google Scholar]
  9. WaterGEMS® [Computer Software v. 10.02.00.43]; Bentley Systems, Inc.: Exton, PA, USA, 2018.
  10. MATLAB 2018b; The MathWorks, Inc.: Natick, MA, USA, 2018.
  11. Creaco, E.; Franchini, M. A new algorithm for real-time pressure control in water distribution networks. Water Sci. Technol. Water Supply 2013, 13, 875–882. [Google Scholar] [CrossRef]
  12. Powell, J.C.; Hallam, N.B.; West, J.R.; Forster, C.F.; Simms, J. Factors which control bulk chlorine decay rates. Water Res. 2000, 34, 117–126. [Google Scholar] [CrossRef]
  13. Boccelli, D.L.; Tryby, M.E.; Uber, J.G.; Scott Summers, R. A reactive species model for chlorine decay and THM formation under rechlorination conditions. Water Res. 2003, 37, 2654–2666. [Google Scholar] [CrossRef]
Figure 1. Water distribution network layout. Grey numbers and nodes indicate critical nodes where hydrants may be opened for chlorine concentrations at the source Ccl larger than or equal to 1 mg/L.
Figure 1. Water distribution network layout. Grey numbers and nodes indicate critical nodes where hydrants may be opened for chlorine concentrations at the source Ccl larger than or equal to 1 mg/L.
Proceedings 48 00020 g001
Figure 2. Pareto front of optimal solutions in the trade-off between total volume and total mass dosage.
Figure 2. Pareto front of optimal solutions in the trade-off between total volume and total mass dosage.
Proceedings 48 00020 g002
Table 1. Economic analysis for the solutions in the Pareto front.
Table 1. Economic analysis for the solutions in the Pareto front.
ChlorineVolLeakageWChlorineCtot (€)Ctot (€)Ctot (€)Ctot (€)Ctot (€)Ctot (€)Ctot (€)
Conc. (mg/L)(m3)(%)(Kg)cost (€)cw = 0.005 €/m3cw = 0.0275 €/m3cw = 0.05 €/m3cw = 0.275 €/m3cw = 0.5 €/m3cw = 0.75 €/m3cw = 1 €/m3
1729320.517.2936722364002041368255057329
1.1728220.398.0139762394032042368055017321
1.2727520.328.7343792434062043368054997318
1.4726620.2210.1750862504132048368354997316
1.6726120.1611.6257932564202054368755037318
2725620.1114.51711072704342066369955137327
3725220.0621.761061433064692101373255457359
4725120.0529.001421783415042136376755807392
Table 2. Number of opened hydrants and total additional outflow in five operational scenarios.
Table 2. Number of opened hydrants and total additional outflow in five operational scenarios.
Demand MultiplierBulk Decay Constant (d−1)Number of Opened HydrantsTotal Additional Outflow (L/d)
0.75133102,081
112670,800
1.2512353,798
10.751215,819
11.2539209,058
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Avvedimento, S.; Todeschini, S.; Giudicianni, C.; Nardo, A.D.; Walski, T.; Creaco, E. Flowing Blow-Offs: A Solution to Maintain Adequate Disinfectant Residuals of Dead-End Nodes in WDNs. Proceedings 2020, 48, 20. https://doi.org/10.3390/ECWS-4-06443

AMA Style

Avvedimento S, Todeschini S, Giudicianni C, Nardo AD, Walski T, Creaco E. Flowing Blow-Offs: A Solution to Maintain Adequate Disinfectant Residuals of Dead-End Nodes in WDNs. Proceedings. 2020; 48(1):20. https://doi.org/10.3390/ECWS-4-06443

Chicago/Turabian Style

Avvedimento, Stefania, Sara Todeschini, Carlo Giudicianni, Armando Di Nardo, Tom Walski, and Enrico Creaco. 2020. "Flowing Blow-Offs: A Solution to Maintain Adequate Disinfectant Residuals of Dead-End Nodes in WDNs" Proceedings 48, no. 1: 20. https://doi.org/10.3390/ECWS-4-06443

APA Style

Avvedimento, S., Todeschini, S., Giudicianni, C., Nardo, A. D., Walski, T., & Creaco, E. (2020). Flowing Blow-Offs: A Solution to Maintain Adequate Disinfectant Residuals of Dead-End Nodes in WDNs. Proceedings, 48(1), 20. https://doi.org/10.3390/ECWS-4-06443

Article Metrics

Back to TopTop