Finite element analysis enables the visualization of the transient spatial distribution and waveform of sound waves, thereby facilitating better data analysis and providing improved parameter references for research on transformer fault diagnosis and other related studies.
5.1. Spatial Distribution of Sound Waves
Figure 12 shows the spatial propagation iso-surface of the ultrasonic wave signal over time when the PD source S
1 emits a sound wave signal in an oil-immersed transformer. As seen in
Figure 12a, the ultrasonic signal mainly spreads in the form of spherical waves in the surrounding insulation oil, with the highest sound pressure values near the sound source, represented by the red regions in this figure. Upon reaching the winding or iron core, the sound wave signal first undergoes refraction and absorption. The refracted signal and the new signal overlap, resulting in higher sound pressure values. The parts that cancel each other out are shown in lighter colors in this figure. Consequently, there are some red areas and lighter color areas in the simulation results of the transformer core and winding, indicating that the acoustic pressure value is not completely uniform.
Figure 12 shows that after a period of time following PD, the acoustic wave signal rapidly propagated in the insulating oil, and approximately 800 µs after the acoustic wave signal, it nearly filled the entire inner wall of the oil tank. The figure displays the spatial acoustic equal value distribution at time intervals of 100 µs, 150 µs, 200 µs, 300 µs, 500 µs, and 800 µs after the emission of the acoustic wave from the PD discharge source. The diffusion behavior of the acoustic wave in space can be observed from the color difference, gradually attenuating with the distance from the PD source. The amplitude of the acoustic wave also gradually reduced, verifying the diffusion and attenuation principle of the sound source or spherical wave. Under the condition of the constant total energy of the sound source, the energy of the acoustic wave per unit area is inversely proportional to the square of the distance from the sound source, which can be calculated as follows:
where
E0 represents the point sound source intensity,
Er denotes the energy per unit area at a distance r from the sound source, and
r indicates the distance from the sound source.
During the propagation of sound waves inside a transformer toward the detection point, the waves pass through the iron core and winding sections in most cases. After removing the refraction and reflection of sound waves, the theoretical propagation speed of the waves through the iron core and windings is expected to be faster than in the oil. Therefore, when reaching the detection point, the leading part of the waveform will be accompanied by a certain amount of reverberation. A preliminary explanation is provided in
Figure 11.
5.2. PD Source Location Calculation
The five-element cross-coordinate system designates the center of the bottom surface of the transformer oil tank as the origin. The coordinates for the positions of the six sound wave sensors are as follows: S0 (0, 0, 0), S1 (−d, 0, 0), S2 (0, d, 0), S3 (d, 0, 0), S4 (0, −d, 0), and S5 (0, 0, h), where d represents an appropriate distance ensuring the equidistance of sensors S1 to S4 from the source point, and h represents the symmetric point with respect to the midpoint of the transformer’s height.
The specific distribution is illustrated in
Figure 13, depicting the positional relationships between the sensors and the PD sources. These four PD sources were located within the low-voltage winding, high-voltage winding, and yoke.
Figure 13 provides a schematic overview of the positional relationship between the sensors and the PD sources. Finally, the coordinates of the discharge sources were calculated, and the accuracy of the simulation was validated using error calculation methods.
Based on the array of six-element cross sensors,
Figure 14 shows the detected sound waveforms at each detection point when the PD discharge source at position S
1 emits different types of discharges.
Figure 14 shows that the time at which the sound wave first reaches each sensor is different. Therefore, this paper leveraged a direct solution method based on time differences to calculate the location of the PD source. For each plane in three-dimensional space, obtaining n sound wave equations through measurements yields
(n − 1) time delay equations. Therefore, a minimum of four detection points is necessary for three-dimensional space to obtain 3-time delay equations and determine the three-dimensional spatial coordinates of the PD source. Although the method of locating the sound source with four detection points can be used as a tetrahedral array, the accuracy of the calculation is much lower than that of the five-element cross array. The equation for sound source localization is shown in Equation (14).
where
xpd,
ypd, and
zpd represent the coordinates of the PD source, and
d denotes the appropriate size of the transformer. Here, the length of d was set to 0.6 m, and
d = 0.5 h.
Ri indicates the distance between the PD source and the corresponding sensor. Using sound wave propagation Equation (6), we can obtain:
where
co represents the speed of sound in the transformer insulating oil.
In the positional location calculation of the discharge source PD1, the coordinates of the PD source can be calculated using the formula by selecting four detection points: S0, S1, S2, and S5. Among these, sensor S0, with the shortest arrival time, served as the reference detection point for position calculation. Utilizing signals with minimal distortion allows for more accurate calculation results. Furthermore, selecting detection points S1 and S2, which exhibited significantly larger arrival time differences from S0, enhanced the distinctiveness of the time differences in the calculation equations, thereby improving the calculation accuracy.
The signal-to-noise ratio of the detected acoustic wave signals at the detection points is a crucial factor in acoustic analysis. The signal-to-noise ratio represents the ratio of the pure acoustic wave signal emitted by the sound source to other white noise. In normal operation, three-phase AC transformers exhibit a large number of different sizes and shapes of magnetic domains inside the core that constantly change with the AC voltage, resulting in the generation of pulse acoustic waves within the core, known as magnetostriction noise. This type of noise can reach up to several kHz in some cases, thereby affecting the measurement data of acoustic waves. Magnetostriction noise can be eliminated and attenuated using bandpass filters to ensure more accurate measurement results. The positions of different types of PD sources can be calculated using the selected detection points and corresponding calculation methods, as shown in
Table 4.
Table 4 displays the calculated coordinates corresponding to different discharge types. Since the discharge source PD
1 can only occur as corona discharge,
Table 4 only includes the calculated coordinates for corona discharge positions in this paper. During the operation of a transformer, losses such as those in the iron core and windings generate a significant amount of heat, leading to an increase in the internal temperature of the transformer. As a result, the physical properties of the insulating oil may change, affecting the speed of sound propagation. In oil-immersed transformers, the temperature of the upper layer of oil typically exceeds 313.15 K during normal operation. For higher loads, the oil temperature can continue to rise, reaching temperatures of over 373.15 K. According to the simulation results in
Figure 3, the speed of sound in oil at a temperature of 313.15 K is approximately 1350 m/s. Compared to the speed at room temperature, the percentage difference in speed change ranged from 5% to 17%. Such significant variations in sound velocity can introduce errors in ultrasonic localization technology.
Therefore, in this study, various material parameter characteristics were adjusted at different temperatures to simulate partial discharges of the same type, using tip discharge faults as an example, and conducted localization based on these adjustments. The specific localization coordinates are presented in
Table 5.
5.3. Error Calculation
The coordinates of each discharge source were calculated using the method of time difference of arrival by a new type of sensor array. The positioning of these sources on the transformer diagram is shown in
Figure 15, where the difference between the calculated positions and the actual positions can be visually observed. Pre-processing of fault diagnosis was performed around the calculated discharge source positions to reduce the occurrence rate of partial discharge, and the sensors in the five-element cross array were located in the same plane, affecting the accuracy of the z-axis coordinate when locating the PD source.
In this study, the sensors were positioned symmetrically with respect to the origin to provide a reference for the z-axis. As a result, the error in the z-component of the calculated results was minimal. This approach enhances the accuracy of determining the coordinates of each PD source.
Figure 15 illustrates the localization results of PD. In this figure, the red marks indicate the actual set positions of the discharge sources, while the black marks represent the calculated positions under the new sensor array. The following equation can be used to compute the distance between the two PD sources.
where Δ
R represents the straight-line distance between the calculated and actual centers of the discharge sources, and
x′ and
x denote the calculated and actual abscissae of the discharge sources, respectively. The errors of each PD source, obtained through calculation, are shown in
Table 6 and
Table 7.
From the statistical analysis of the table, the average error in the overall measurement data between the two centroids was approximately 5 cm. In the simulated measurements, the maximum average error in the calculation of air-gap discharge was around 7.27 cm, while the minimum average error was 2.78 cm. In the simulation of air-gap discharge, the shape of the PD source model was similar to a spherical shape. After removing the 1 cm radius of the actual and simulated discharge spheres, the boundary distance between the two discharge sources was approximately 0.78 cm. As mentioned in
Table 1, in a transformer oil tank with internal dimensions of 3 m × 2 m × 1.5 m, the error accounted for 0.5% of the total transformer volume, which sufficiently reflects the accuracy of the new array positioning.
From the calculation table data on errors in positioning research under different temperatures, it can be seen that in this simulation, the highest calculation accuracy was achieved for 293.15 K and 363.15 K. The average error between the calculated coordinates and the actual coordinates was around 4–5 cm. In contrast, the calculation errors for temperatures of 313.15 K and 343.15 K were relatively larger, at approximately 5–6 cm.
5.4. Local Partial Discharge Source Positioning Method Based on Dynamic Distance Difference Correction, and Error Iteration Algorithm
Due to the fact that the liquid materials added in the simulation model were all in the ideal transformer oil state, the coordinates of PD calculated by the method of time difference were assumed to be uniformly propagated along a straight-line path by acoustic waves. In reality, however, acoustic waves propagate nonlinearly and non-uniformly. The distances d′i1 between the calculated PD source and the sensors were referenced on the assumption of linear acoustic wave propagation. In practice, there exists a certain error between the actual ultrasonic propagation path di1 and d′i1, resulting in significant errors in local partial discharge source localization. Therefore, it is necessary to correct d′i1 to make it as close as possible to the distance of the actual propagation path.
Let the actual coordinates of the PD discharge source be (
x,
y,
z), and the computed coordinates be (
x′,
y′,
z′). When the acoustic impedance distribution is uniform, the difference between the straight-line distance from sensor i to the PD and the straight-line distance from sensor 1 to the PD is:
where
di is the linear distance between the
i-th sensor and the local power supply.
Therefore, the distance difference obtained by the simulation calculation is:
where
v represents the constant speed of sound in the oil, and
t′
i1 is the time difference of the acoustic waves between sensor i and sensor 1. Based on the previous calculation, the straight-line distance from the
i-th sensor to the coordinates of the local discharge source is:
where
str represents the physical parameter in the case of linear propagation.
For the actual propagation path of the acoustic waves, it will curve based on the internal structure of the transformer. The main propagation path is divided into N segments, with each segment assumed to have uniform acoustic impedance and no significant angle abrupt changes. Therefore, the distance of the main route can be expressed as:
where
main represents the physical parameters of the main propagation path, and
tmain is the propagation time between the local discharge source and the sensors along the main propagation path, expressed as:
where
D represents the distance from the localization calculation of the PD location to the
i-th sensor in the main path of segment n, and
vi,n represents the propagation path of ultrasound in segment n. The error between the main acoustic propagation path distance and the straight-line distance is:
In order to calculate the PD source location more accurately, the value of
dstr,i should be brought as close as possible to the value of
dmain,i. Therefore, by using the method of analogizing distances with the same properties, these two physical quantities were used to determine the approximate error. Subsequently, the corrected error distance
d′
str,i can be obtained by subtracting the main path and error Δ
di.
Substitute this into the formula to obtain:
where
d′
i represents the initial calculated distance. Therefore, the above equation can also be simplified as:
According to the corrected distance difference
d′
i1, a new set of local power source coordinates with less error can be obtained. The initial coordinates of the local power supply are iterated, and the number of iterations is k.
where
f () represents the nonlinear functional relationship of the time difference equations. Therefore, the
k-th iteration of sound wave propagation time in the main line can also be expressed as:
The corrected distance can therefore be expressed as:
Similarly, a new set of local discharge source coordinates can be obtained for
d′
i1(
k).
Based on the results of multiple calculations, it can be concluded that when the number of iterations reaches around 10 times, the results of the PD source localization tend to stabilize within a small range of oscillation. Therefore, to improve the accuracy and efficiency of the calculations, this study set the total number of iterations to be around 30 to 40 times. The final output result was obtained by averaging the results of the last 10 iterations, and the final expression is as follows:
The overall process flowchart is shown in
Figure 16.
Through iterative calculations at different numbers of iterations, it was found that the error was reduced by 26.49% after the first iteration, and decreased to only 25.17% of the original error after the 40th iteration. A significant reduction in calculation error was observed in the first iteration, and as the number of iterations increased, the error was reduced to a quarter of the original value. The average error data from iterations 31 to 40 are shown in
Table 8 and
Table 9.
Based on the table, it is apparent that the average calculation error after iteration was approximately 1.3 cm, with a maximum error of 3.11 cm. This correction method optimized the propagation path of sound waves by correcting the model simulation data based on the relationship between the main propagation path and the straight-line path. Subsequently, by combining the corrected propagation characteristics with the iterative method, further improvement in the accuracy of localization was achieved.
In the study of partial discharge acoustic signal localization within transformers, various scholars have established models with different sizes and parameters by using different algorithms to achieve localization results with varying degrees of accuracy. The results are shown in
Table 10. In comparison, the method adopted in this paper, which combined TDOA and iterative algorithms with model parameters, achieved relatively accurate PD calculation results under comprehensive conditions considering different types and temperatures. The error was also relatively significant compared to many other studies, demonstrating the feasibility of our research method.
Current research widely uses acoustic localization to determine transformer partial discharge locations. Compared to traditional UHF techniques, acoustic methods offer stronger EMI resistance and higher sensitivity, making them valuable for precise calculations. Our study combined models and algorithms, using TDOA as the foundational method. By integrating dynamic distance differences and error iteration algorithms, we achieved more accurate results.