Next Article in Journal
An Optimal Wavelet Packets Basis Method for Cascade Hydro-PV-Pumped Storage Generation Systems to Smooth Photovoltaic Power Fluctuations
Previous Article in Journal
Quantification of Efficiency Improvements from Integration of Battery Energy Storage Systems and Renewable Energy Sources into Domestic Distribution Networks
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Compatibility between C6F12O–N2 Gas Mixture and Metal Used in Medium-Voltage Switchgears

1
Electric Power Research Institute, China Southern Power Grid, Guangzhou 510623, China
2
State Key Laboratory of HVDC, Electric Power Research Institute, CSG, Guangzhou 510663, China
3
School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China
4
Pingdingshan Power Supply Company, State Grid Corporation of China, Pingdingshan 467001, China
*
Author to whom correspondence should be addressed.
Energies 2019, 12(24), 4639; https://doi.org/10.3390/en12244639
Submission received: 4 November 2019 / Revised: 19 November 2019 / Accepted: 1 December 2019 / Published: 6 December 2019
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
C6F12O has been introduced as the potential alternative gas to SF6 because of its excellent insulation properties and great eco-friendly performance. Considering that C6F12O may react with the internal materials of switchgears in practical applications, its compatibility with metal materials must be tested to evaluate its long-term application possibilities. In this work, the compatibility of C6F12O–N2 gas mixtures with aluminum and copper was tested at different temperatures by setting up a heat-aging reaction platform between the gas and each metal. The metal surface morphology and gas composition before and after the reaction were compared and analyzed. The results show that the surface color of the copper sheet changed considerably, and the corrosion degree of the surface deepened with the increase of temperature. The decomposition of C6F12O was also promoted. In contrast, aluminum did not react severely with the gas mixture. The compatibility of the gas mixture with aluminum was generally better than that of copper.

Graphical Abstract

1. Introduction

SF6 has been widely used in the power industry, especially in high-voltage (HV) and medium-voltage (MV) gas-insulated switchgears (GIS), since the early 1980s due to its excellent technical performance and small footprint [1,2]. Approximately 80% of the global production of SF6 is used in HV and MV gas-insulated equipment [3,4]. However, SF6 has a high global warming potential (GWP) of 23,500 and a long atmospheric lifetime of 3200 years [5,6]. These characteristics indicate that the unrestricted emission of SF6 would cause great harm to the atmospheric environment. Actually, the atmospheric content of SF6 increases rapidly. The global annual mean concentration of SF6 in 2011 was 7.29 ppt, which is 1.65 ppt higher than the value in 2005 [7]. Thus, the Kyoto Protocol in 1997 and the Paris Agreement in 2015 were proposed to implement measures for controlling SF6 growth [8,9], and several countries have begun to take action. For example, Slovenia and Spain have levied SF6 emission taxes [10]. Therefore, the use of SF6 should be urgently reduced or limited, and an environmental-friendly gas must be identified to replace SF6.
The gases currently used in switchgears mainly include CO2, N2, dry air, SF6, and their gas mixtures. However, due to the limited insulation strength of traditional gases (up to approximately 30%–40% of that of SF6) [11], the filling pressure or dimension must be increased when these gases are used as the insulating or arc extinguishing medium in the equipment. This condition entails security risks and increased equipment cost [12].
In addition to the traditional gases mentioned above, potential alternatives to SF6 that have been considered in recent years include perfluorocarbons (PFCs), trifluoroiodomethane (CF3I), HFO-1234zeE, fluoronitrile (C4F7N), and fluoroketones (C5-PFK and C6-PFK). The GWP of PFCs is high (e.g., c-C4F8 and C2F6 have GWPs of 8700 and 12,200, respectively); thus, there is no significant reduction in GWP [13,14,15]. CF3I is classified as a type 3 mutagen and presents disadvantages such as iodine I2 (acute toxicity) precipitation after repeated discharges. Therefore, it is not conducive for long-term safe equipment operation [16,17]. HFO-1234zeE will precipitate carbon deposits on the solid after a flashover and have a risk of flammability [3,18]. C4F7N demonstrates excellent insulation performance, but its toxicity is relatively high, and the risks of large-scale engineering application still require further study [19,20,21]. The application prospect of fluoroketones in electrical equipment has been widely optimistic in the past few years, and related research has mainly focused on C5-PFK and C6-PFK gas mixtures. Table 1 shows a comparison of several of the main characteristics of C5-PFK, C6-PFK, and SF6 [22,23,24,25]. It can be seen that C6-PFK is less toxic than C5-PFK.
Currently, C6F12O is only used as a fire-extinguishing agent and covering gas for magnesium treatment as well as two-phase immersion cooling systems, which is safe to use and relatively low in cost [26]. Furthermore, research on C6F12O as a gas-insulating medium has just started [27,28,29,30]. However, due to its high boiling point, C6F12O cannot be used as an insulating medium alone; that is, it must be mixed with a buffer gas, such as N2 or CO2. Moreover, since the dielectric strength of pure C6-PFK can reach about 2.5 times that of SF6, a gas mixture with a small percentage of C6-PFK can also achieve a relatively high insulation strength. Relevant results demonstrate that C6F12O gas mixtures have the potential to be used in MV switchgears, such as cubicle gas-insulated switchgears (C-GIS) [31].
In addition, in-depth studies of the long-term compatibility between gas-insulating medium and materials must be conducted. Given that C6F12O gas is not as inert as SF6, chemical reactions might exist between the gas components and materials, resulting in changes in the properties of materials and jeopardizing the normal operation of gas-insulated equipment. Thus, material compatibility must be tested before engineering application to avoid any negative effect of the interaction between the materials and the C6F12O–N2 gas mixture.
In this study, considering that the advantage of CO2 is its arc-extinguishing ability and that the C6F12O gas mixtures are mainly used in non-arcing applications, the N2 with an extremely low boiling point was chosen as the carrier gas to reduce the liquefaction temperature of the gas mixture. The compatibility of C6F12O–N2 gas mixtures with copper and aluminum, which are normally used in medium-voltage switchgears (e.g., C-GIS) as conductors, was studied by aging tests. The surface morphology of the metals and the composition of the gas mixtures after thermal aging were determined and analyzed via scanning electron microscopy (SEM) and gas chromatography-mass spectrometry (GCMS). The interaction mechanism between the gas mixture and metallic surface was also discussed. Relevant results could provide guidance for the engineering application of C6F12O–N2 gas mixtures.

2. Experimental Device and Methods

The experimental device, experimental methods, and analytical methods used in this paper are described in detail as follows.

2.1. Experimental Device

The schematic of the compatibility test device is shown in Figure 1.
The test device mainly consisted of a gas chamber, heating device, temperature feedback unit, and control system. The heating device was composed of a heating element and a metal sleeve. The metal sleeve was used to expand the contact area with the C6F12O–N2 gas mixture, and the outer surface of the metal sleeve served as the reaction interface with the gas mixture. The metal sleeve and heating element were kept in close contact to achieve even heat conduction. Moreover, two 100 mm × 5 mm × 0.2 mm metal sheets were bundled on the metal sleeve to participate in the thermal aging test. The metal sleeves and sheets were composed of copper or aluminum according to the experimental requirements. The feedback unit detected the surface temperature of the metal sleeve through a temperature sensor (K-type thermocouple) mounted on the metal sleeve surface. The temperature control system adjusted the output power of the heating element to ensure that the surface temperature of the metal sleeve remained at the set value during the tests. The main body and the upper cover of the gas chamber are welded and machined with 304 stainless steel (due to its great corrosion resistance performance), as well as polished inside and outside. The chamber can withstand a pressure of 0.7 MPa, and its volume is about 2 L.

2.2. Experimental and Analytical Methods

Prior to the experiment, the gas chamber, metal sleeve, and metal sheet were carefully cleaned using absolute alcohol, and the metal sheet was fixed to the metal sleeve. The gas chamber was vacuumed and then filled with N2 three times to dispel the gas impurity. Finally, the gas mixture was charged into the gas chamber. The volume fraction was determined by a partial pressure ratio based on the Dalton partial pressure law. When inflating, the C6F12O was charged first, followed by the buffer gas. The N2 is supplied by Wuhan Newred Special Gas Co., Ltd. with a purity of 99.999%. The C6F12O gas is supplied by Zhengzhou Alfachem Co., Ltd. with a purity of 99%.
Given the working pressure and liquefaction temperature requirements (−5 °C) of MV switchgears [32], the total gas pressure and content of C6F12O in the experiment were fixed to 0.2 MPa and 5%, respectively. The breakdown voltage of 5% C6F12O–95% N2 gas mixture at 0.2 MPa is about 1.05 times that of 10% SF6–90% N2 [29]. Considering the temperature rise effect of the current-carrying metal inside the equipment under the rated working condition and the local overheating faults caused by the poor contact of the contacts, the experimental temperature was set to 150 °C, 200 °C, and 250 °C. Each set of experiments was heated for 8 h.
The gas in the chamber was collected for GC-MS analysis after each group of tests. When the gas is scanned by GC-MS, the range of the mass-to-charge ratios (m/z) is set to 45–350 to remove the damage of the detector by the oversaturation of N2 and the interference of H2O and CO2 in the air. The surface morphology of the metal sheets before and after thermal aging was observed and recorded with optical and scanning electron microscopes.

3. Results of Compatibility between C6F12O–N2 Gas Mixture and Cooper

In order to comprehensively analyze the compatibility between the C6F12O–N2 gas mixture and copper, the surface morphology of the copper sheets and the gas composition before and after the reaction were analyzed by optical microscope, SEM.

3.1. Surface Morphology

Figure 2 shows surface morphology photos of the copper sheet before and after thermal aging for 8 h.
It can be found that several areas of the copper sheet changed to red and green after an 8 h test at 150 °C. The surface color of the copper sheet deepened as the temperature increased. The copper surface turned bright orange at 200 °C, and most of the area turned purple–red at 250 °C, indicating that a significant chemical reaction occurred between the copper and the gas mixture. Meanwhile, the optical microscope showed that the grain structure on the copper sheet gradually became less clear as the temperature increased. These phenomena indicate that the material compatibility between copper and the C6F12O–N2 gas mixture was not very good, and the reactions resulted in a significant surface change.
In order to facilitate comparative analysis with SF6, the copper sheets exposed to a 220 °C SF6 environment for 8 h were also tested, and it was found that there is no significant change in the color of the copper surface. The relevant results confirm that the compatibility between copper and SF6 is superior to that between copper and the C6F12O–N2 gas mixture.
Actually, when the C6F12O gas mixture is in contact with the heated copper surface, the thermal motion of C6F12O molecules and Cu atoms is intensified, which causes the intensification of the chemical bond vibration inside the molecule and the deterioration of the structure stability, eventually leading to a chemical reaction between the gas molecule and the heated copper surface. As the temperature increases, the reaction rate is further accelerated, causing the decomposition of gas molecules and severe corrosion of the copper surface.

3.2. SEM Analysis

SEM was used to observe the surface morphology and further analyze the microscopic morphology of the copper sheet. The observation results are shown in Figure 3. The surface shape of the copper sheet before the reaction was clear, and the structure was flat and compact. Fewer corrosion spots were observed at 150 °C, and the texture was not damaged. As the temperature increased further, the surface of the copper sheet became uneven, indicating that serious corrosion occurs at this stage.

3.3. GC-MS Analysis

Qualitative analysis of the gas mixture after the aging test was performed in accordance with the National Institute of Standards and Technology’s (NIST 14.0) standard chromatographic database [33]. Given that the gas composition after the experiment was unknown, the gas could only be qualitatively analyzed using the SCAN mode. Figure 4 shows the gas chromatogram of the C6F12O–N2 gas mixtures before and after the experiment.
It can be seen from Figure 4 that the C6F12O–N2 gas mixture decomposed at 150 °C, and the main decomposition products included C4F8O, C3F6, and C2F5H. With the increase in temperature, the peak areas of C3F6 and C2F5H increased considerably. This result indicates that the macromolecular product decomposed further with the increase in temperature. The production of C2F5H may be related to trace moisture.
According to the surface morphology change of the copper sheet and the composition change of the C6F12O–N2 gas mixtures before and after the reaction, the C6F12O–N2 gas mixtures interacted with the copper sheet at 150 °C and above, and the surface structure of the copper sheet exhibited certain corrosion. The gas mixtures decomposed to produce decomposition products, such as C2F5H and C3F6. The compatibility of the C6F12O–N2 gas mixtures with copper was not very good, and the mutual reaction between them may pose a potential threat to gas-insulated equipment.

4. Results of Compatibility between C6F12O–N2 Gas Mixtures and Aluminum

Similarly, the results of analysis by optical microscope, SEM, and GC-MS before and after the reaction are as follows.

4.1. Surface Morphology

Figure 5 shows surface morphology photos of the aluminum sheet before and after the high-temperature 8 h aging test.
After the high-temperature reaction of the aluminum sheet and C6F12O–N2 gas mixture, the surface color of the aluminum did not change considerably. The aluminum surface stayed white and silver, and the gloss was bright. The main reason for this phenomenon is that aluminum is more active and easily oxidized in air to form a dense Al2O3 protective film, which is extremely resistant to corrosion and therefore forms an effective protection of the internal aluminum.
The results of optical microscopy show that the surface grain structure of the aluminum sheet was maintained with the increasing temperature, and no corrosion changes occurred. These phenomena indicate that the material compatibility between aluminum and the gas mixtures was great, and the reaction between the gas mixtures and aluminum sheet did not change the surface of the sheet.

4.2. SEM Analysis

Figure 6 shows the SEM of the aluminum sheet before and after tests. The surface morphology of the aluminum was flat and tight, and no change was observed at all temperature conditions. No corrosion spots were observed.

4.3. GC-MS Analysis

Figure 7 shows the gas chromatogram of the C6F12O–N2 gas mixtures after heat aging with aluminum for 8 h at different temperatures.
The chromatogram results show that the decomposition components of the C6F12O–N2 gas mixture that interacted with aluminum were similar to those of copper. C2F5H, C3F6, and C4F8O were detected after the test. These results, together with the characterization results in Section 3.2, indicate that the surface structure of the aluminum sheet was not destroyed, so the appearance of this decomposition product is presumed to be a slight decomposition of C6F12O gas after heating.
Overall, the C6F12O–N2 gas mixture could interact with copper and aluminum at temperatures higher than 150 °C. The corrosion degree of the copper sheet was more serious than that of aluminum. The compatibility of the C6F12O–N2 gas mixture with aluminum is better than that of copper.
Thus, it is necessary to consider the reaction of the C6F12O–N2 gas mixture with copper materials used inside gas-insulated switchgears for engineering application, which would lead to internal insulation failure of the electrical equipment and pose safety hazards during normal long-term operation of the equipment.

5. Discussion

In fact, the reason why the material compatibility of the C6F12O–N2 gas mixtures with aluminum was better than with copper may be attributed to the difference in the activity of these two metal surfaces.
As we know, aluminum is more active and easily oxidized in air to form a dense Al2O3 protective film, which is extremely resistant to corrosion and therefore forms an effective protection of the internal aluminum. The existence of Al2O3 could effectively inhibit the interaction between aluminum and C6F12O–N2 gas mixtures.
In contrast, the chemical reactivity of copper is quite strong. When a C6F12O gas molecule interacts with the copper surface, the interaction between the gas molecule and the metal surface occurs along with charge transfer process. The structure of the gas molecule will change and the weaker chemical bonds in the C6F12O molecule will dissociate to form some particles. Finally, the reaction between the particles could result in the formation of gaseous by-products.
The possible reactions between the metal surface and C6F12O can be summarized as shown in Figure 8.

6. Conclusions

In this work, the material compatibility of a potential SF6 substitute gas, C6F12O, with copper and aluminum was studied. Thermal aging test results at different temperatures were analyzed. The compatibility of the gas mixtures with copper and aluminum was evaluated by comparing the surface morphology of the metal materials and the composition of the C6F12O–N2 gas mixture before and after the reaction. The following relevant conclusions were obtained.
(1) The C6F12O–N2 gas mixture could react with hot copper higher than 150 °C. The surface structure of the copper sheet was corroded to some extent, the color change was evident, and the gas mixture decomposed to produce by-products including C2F5H, C3F6, and C4F8O.
(2) The interaction of the C6F12O–N2 gas mixtures with aluminum under high-temperature conditions did not cause corrosion of aluminum surface, while the gas mixture also decomposed to produce C3F6, C2F5H, and C4F8O.
(3) The compatibility of the C6F12O–N2 gas mixture with aluminum was better than that of copper. It is necessary to consider the reaction of the gas mixture with the copper used inside gas-insulated switchgears to avoid potential hazards during the normal long-term operation of the equipment.

Author Contributions

Q.C. conceived and designed the research, R.Z. performed the research and wrote this manuscript, while M.F., D.W., J.T., J.H. and Y.J. helped analyze the data.

Funding

This research was funded by China Southern Power Grid, grant number ZBKJXM20170090.

Conflicts of Interest

The authors declare no competing interests.

References

  1. Hyrenbach, M.; Zache, S. Alternative insulation gas for medium-voltage switchgear. In Proceedings of the 2016 Petroleum and Chemical Industry Conference Europe (PCIC EUROPE), Berlin, Germany, 14 June–16 July 2016. [Google Scholar]
  2. Li, Y.; Zhang, X.; Zhang, J.; Tang, J.; Xie, C.; Shao, X.; Wang, Z.; Chen, D.; Xiao, S. Study on the thermal decomposition characteristics of C4F7N-CO2 mixture as eco-friendly gas insulating medium. High. Volt. 2019. [Google Scholar] [CrossRef]
  3. Beroual, A.; Haddad, A. Recent advances in the quest for a new insulation gas with a low impact on the environment to replace sulfur hexafluoride (SF6) gas in high-voltage power network applications. Energies 2017, 10, 1216. [Google Scholar] [CrossRef] [Green Version]
  4. Li, Y.; Zhang, X.; Xiao, S.; Chen, Q.; Tang, J.; Chen, D.; Wang, D. Decomposition properties of C4F7N/N2 gas mixture: An environmentally friendly gas to replace SF6. Ind. Eng. Chem. Res. 2018, 57, 5173–5182. [Google Scholar] [CrossRef]
  5. Zhang, X.; Xiao, H.; Tang, J.; Cui, Z.; Zhang, Y. Recent advances in decomposition of the most potent greenhouse gas SF6. Crit. Rev. Environ. Sci. Technol. 2017, 47, 1763–1782. [Google Scholar] [CrossRef]
  6. Owens, J. Greenhouse gas emission reductions through use of a sustainable alternative to SF6. In Proceedings of the 2016 IEEE Electrical Insulation Conference (EIC), Montreal, QB, Canada, 19–22 June 2016; pp. 535–538. [Google Scholar]
  7. IPCC. Climate Change 2013: The Physical Science Basis. Contribution of Working Group I to the Fifth Assessment Report of the Intergovernmental Panel on Climate Change; Stocker, T.F., Qin, D., Plattner, G.-K., Tignor, M., Allen, S.K., Boschung, J., Nauels, A., Xia, Y., Bex, V., Midgley, P.M., Eds.; Cambridge University Press: Cambridge, UK; New York, NY, USA, 2013; p. 1535. [Google Scholar]
  8. Li, Y.; Zhang, X.; Zhang, J.; Fu, M.; Zhuo, R.; Luo, Y.; Chen, D.; Xiao, S. Experimental study on the partial discharge and AC breakdown properties of C4F7N/CO2 mixture. High Volt. 2019, 4, 12–17. [Google Scholar] [CrossRef]
  9. Rogelj, J.; den Elzen, M.; Hohne, N.; Fransen, T.; Fekete, H.; Winkler, H.; Chaeffer, R.S.; Ha, F.; Riahi, K.; Meinshausen, M. Paris Agreement climate proposals need a boost to keep warming well below 2 °C. Nature 2016, 534, 631. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  10. Li, Y.; Zhang, X.; Chen, D.; Li, Y.; Zhang, J.; Cui, Z.; Xiao, S.; Tang, J. Theoretical study on the interaction between C5-PFK and Al (1 1 1), Ag (1 1 1): A comparative study. Appl. Surf. Sci. 2019, 464, 586–596. [Google Scholar] [CrossRef]
  11. Romero, A.; Racz, L.; Matrai, A.; Bokor, T.; Cselko, R. A review of sulfur-hexafluoride reduction by dielectric coatings and alternative gases. In Proceedings of the 2017 6th International Youth Conference on Energy (IYCE), Budapest, Hungary, 21–24 June 2017. [Google Scholar]
  12. Kieffel, Y.; Biquez, F.; Ponchon, P. Alternative gas to SF6 for use in high voltage switchgears: g3. In Proceedings of the 23rd International Conference on Electricity Distribution, Lyon, France, 15–18 June 2015; p. 0230. [Google Scholar]
  13. De Urquijo, J.; Castrejon-Pita, A.A.; Hernandez-Avila, J.L.; Basurto, E. Electron transport and effective ionization coefficients in C2F6, C2F6–Ar and C2F6–N2 mixtures. J. Phys. D Appl. Phys. 2004, 37, 1774. [Google Scholar] [CrossRef]
  14. Yamamoto, O.; Takuma, T.; Hamada, S.; Yamakawa, Y.; Yashima, M. Applying a gas mixture containing c-C4F8 as an insulation medium. IEEE Trans. Dielectr. Electr. Insul. 2001, 8, 1075–1081. [Google Scholar] [CrossRef]
  15. Wada, J.; Ueta, G.; Okabe, S.; Hikita, M. Dielectric properties of gas mixtures with per-fluorocarbon gas and gas with low liquefaction temperature. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 838–847. [Google Scholar] [CrossRef]
  16. Xiao, S.; Zhang, X.; Han, Y.; Dai, Q. AC breakdown characteristics of CF3I/N2 in a non-uniform electric field. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 2649–2656. [Google Scholar] [CrossRef]
  17. Kieffel, Y.; Biquez, F.; Ponchon, P.; Irwin, T. SF6 alternative development for high voltage Switchgears. In Proceedings of the IEEE Power & Energy Society General Meeting, Denver, CO, USA, 26–30 July 2015. [Google Scholar]
  18. Preve, C.; Piccoz, D.; Maladen, R. Application of HFO1234zeE in MV switchgear AS SF6 alternative gas. CIRED-Open Access Proc. J. 2017, 2017, 42–45. [Google Scholar] [CrossRef]
  19. Li, Y.; Zhang, X.; Zhang, J.; Xiao, S.; Xie, B.J.; Chen, D.C.; Gao, Y.D.; Tang, J. Assessment on the toxicity and application risk of C4F7N: A new SF6 alternative gas. J. Hazard. Mater. 2019, 368, 653–660. [Google Scholar] [CrossRef] [PubMed]
  20. Preve, C.; Piccoz, D.; Maladen, R. Validation Protocol of Potential SF6 Alternatives; MATPOST: Lyon, France, 2015. [Google Scholar]
  21. Li, Y.; Zhang, X.; Chen, Q.; Zhang, J.; Li, Y.; Xiao, S.; Tang, J. Influence of oxygen on dielectric and decomposition properties of C4F7N-N2-O2 mixture. IEEE Trans. Dielectr. Electr. Insul. 2019, 26, 1279–1286. [Google Scholar] [CrossRef]
  22. Linteris, G.; Babushok, V.; Sunderland, P.; Takahashi, F.; Katta, V.; Meier, O. Unwanted combustion enhancement by C6F12O fire suppressant. Proc. Combust. Inst. 2013, 34, 2683–2690. [Google Scholar] [CrossRef]
  23. Zhang, X.; Li, Y.; Tian, S.; Xiao, S.; Chen, D.; Tang, J.; Zhuo, R. Decomposition mechanism of the C5-PFK/CO2 gas mixture as an alternative gas for SF6. Chem. Eng. J. 2018, 336, 38–46. [Google Scholar] [CrossRef]
  24. Simka, P.; Ranjan, N. Dielectric strength of C5 Perfluoroketone. In Proceedings of the 19th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, 23–28 August 2015; pp. 23–28. [Google Scholar]
  25. Preve, C.; Maladen, R.; Piccoz, D. Method for validation of new eco-friendly insulating gases for medium voltage equipment. In Proceedings of the 2016 IEEE International Conference on Dielectrics (ICD), Montpellier, France, 3–7 July 2016; pp. 235–240. [Google Scholar]
  26. Tuma, P.E. Fluoroketone C2F5C(O)CF(CF3)2, as a Heat Transfer Fluid for Passive and Pumped 2-Phase Applications. In Proceedings of the 2008 Twenty-Fourth Annual IEEE Semiconductor Thermal Measurement and Management Symposium, San Jose, CA, USA, 16–20 March 2008. [Google Scholar]
  27. Li, Y.; Zhang, X.; Tian, S.; Xiao, S.; Li, Y.; Chen, D. Insight into the decomposition mechanism of C6F12O-CO2 gas mixture. Chem. Eng. J. 2019, 360, 929–940. [Google Scholar] [CrossRef]
  28. Xu, W.; Jiang, Y.; Ren, X. Combustion promotion and extinction of premixed counterflow methane/air flames by C6F12O fire suppressant. J. Fire Sci. 2016, 34, 289–304. [Google Scholar] [CrossRef]
  29. Tian, S.; Zhang, X.; Xiao, S.; Deng, Z.; Li, Y.; Tang, J. Experimental research on insulation properties of C6F12O/N2 and C6F12O/CO2 gas mixtures. IET Gener. Transm. Distrib. 2018, 13, 417–422. [Google Scholar] [CrossRef]
  30. Mantilla, J.; Gariboldi, N.; Grob, S.; Claessens, M. Investigation of the insulation performance of a new gas mixture with extremely low GWP. In Proceedings of the 2014 Electrical Insulation Conference (EIC), Philadelphia, PA, USA, 8–11 June 2014; pp. 469–473. [Google Scholar]
  31. Li, Y.; Zhang, X.; Tian, S.; Xiao, S.; Chen, Q.; Chen, D.; Cui, Z.; Tang, J. Insight into the compatibility between C6F12O and metal materials: Experiment and theory. IEEE Access 2018, 6, 58154–58160. [Google Scholar] [CrossRef]
  32. Tian, S.; Zhang, X.; Xiao, S.; Chen, Q.; Li, Y. Application of C6F12O/CO2 mixture in 10 kV medium-voltage switchgear. IET Sci. Meas. Technol. 2019, 13, 1225–1230. [Google Scholar] [CrossRef]
  33. Yogeswari, S.; Ramalakshmi, S.; Neelavathy, R.; Johnpaul, M. Identification and comparative studies of different volatile fractions from Monochaetia kansensis by GCMS. Glob. J. Pharmacol. 2012, 6, 65–71. [Google Scholar]
Figure 1. Schematic of the compatibility test device.
Figure 1. Schematic of the compatibility test device.
Energies 12 04639 g001
Figure 2. Surface morphology photos of the copper sheet before and after thermal aging. (a) Before the test; (b) 150 °C; (c) 200 °C; (d) 250 °C.
Figure 2. Surface morphology photos of the copper sheet before and after thermal aging. (a) Before the test; (b) 150 °C; (c) 200 °C; (d) 250 °C.
Energies 12 04639 g002
Figure 3. Surface morphology photos of the copper sheet before and after thermal aging at 3000 times magnification. (a) Before the test; (b) 150 °C; (c) 200 °C; and (d) 250 °C.
Figure 3. Surface morphology photos of the copper sheet before and after thermal aging at 3000 times magnification. (a) Before the test; (b) 150 °C; (c) 200 °C; and (d) 250 °C.
Energies 12 04639 g003
Figure 4. Gas chromatography of the C6F12O–N2 gas mixtures.
Figure 4. Gas chromatography of the C6F12O–N2 gas mixtures.
Energies 12 04639 g004
Figure 5. Surface morphology photos of the aluminum sheet before and after the high-temperature 8 h aging test. (a) Before the test; (b) 150 °C; (c) 200 °C; and (d) 250 °C.
Figure 5. Surface morphology photos of the aluminum sheet before and after the high-temperature 8 h aging test. (a) Before the test; (b) 150 °C; (c) 200 °C; and (d) 250 °C.
Energies 12 04639 g005
Figure 6. Surface morphology photos of the aluminum sheet before and after thermal aging at 3000 times magnification. (a) before the test; (b) 150 °C; (c) 200 °C; and (d) 250 °C.
Figure 6. Surface morphology photos of the aluminum sheet before and after thermal aging at 3000 times magnification. (a) before the test; (b) 150 °C; (c) 200 °C; and (d) 250 °C.
Energies 12 04639 g006
Figure 7. Gas chromatography of the C6F12O–N2 gas mixtures after thermal aging.
Figure 7. Gas chromatography of the C6F12O–N2 gas mixtures after thermal aging.
Energies 12 04639 g007
Figure 8. Interaction mechanism between C6F12O and copper.
Figure 8. Interaction mechanism between C6F12O and copper.
Energies 12 04639 g008
Table 1. Comparison of C5-PFK, C6-PFK, and SF6 GWP: global warming potential.
Table 1. Comparison of C5-PFK, C6-PFK, and SF6 GWP: global warming potential.
NameC5-PFKC6-PFKSF6
Chemical formulaC5F10OC6F12OSF6
GWP<1<123500
Atmospheric lifetime (years)0.040.0193200
Ozone depletion potential000
Boiling point at 0.1 MPa (°C)2449.2−64
Relative dielectric strength to SF622.51
Flammabilitynon-flammablenon-flammablenon-flammable
Toxicity (LC50, ppmv)>20000>100000>100000

Share and Cite

MDPI and ACS Style

Zhuo, R.; Chen, Q.; Wang, D.; Fu, M.; Tang, J.; Hu, J.; Jiang, Y. Compatibility between C6F12O–N2 Gas Mixture and Metal Used in Medium-Voltage Switchgears. Energies 2019, 12, 4639. https://doi.org/10.3390/en12244639

AMA Style

Zhuo R, Chen Q, Wang D, Fu M, Tang J, Hu J, Jiang Y. Compatibility between C6F12O–N2 Gas Mixture and Metal Used in Medium-Voltage Switchgears. Energies. 2019; 12(24):4639. https://doi.org/10.3390/en12244639

Chicago/Turabian Style

Zhuo, Ran, Qi Chen, Dibo Wang, Mingli Fu, Ju Tang, Juntai Hu, and Yanlei Jiang. 2019. "Compatibility between C6F12O–N2 Gas Mixture and Metal Used in Medium-Voltage Switchgears" Energies 12, no. 24: 4639. https://doi.org/10.3390/en12244639

APA Style

Zhuo, R., Chen, Q., Wang, D., Fu, M., Tang, J., Hu, J., & Jiang, Y. (2019). Compatibility between C6F12O–N2 Gas Mixture and Metal Used in Medium-Voltage Switchgears. Energies, 12(24), 4639. https://doi.org/10.3390/en12244639

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop