1. Introduction
There are obvious and growing efforts worldwide to increase and expand RES contributions to the generation mix, replacing the conventional power stations that rely on fossil fuels [
1]. However, SOs, technology developers and RES farms operators are still facing the fundamental challenge of maintaining power system stability subject to potential risks caused by the variable nature of RES output (except hydropower plants), which depend on meteorological conditions, e.g., wind speed, tides, solar irradiation, etc. [
2].
The literature covers many aspects of the grid-friendly operation of RESs, which includes the provision of frequency support [
3,
4] and voltage support [
5], among other types of ancillary services. Significant attention has been given to the provision of frequency support by wind turbines and wind farms (WFs), where supplementary controllers are integrated into the controls of Type 3 (double-fed induction generator) and Type 4 (full rated synchronous generator) wind turbine generators (WTGs) to be capable of providing a regulated active power increment during frequency excursions. The two most common concepts are pitch-deloading and kinetic energy extraction [
6]. The two concepts have been extensively implemented in the literature through different controller designs, which usually require the system frequency, WTG pitch angle and speed or available power as input signals; meanwhile, the output signal is an amended reference torque or power signal as well as reference pitch angle. It is worth noting that this paper already considers this technology in the developed HPP model, as explained in
Section 2.
Voltage support by RES is another active field of research and technology developments. Many papers have proposed various control methods to enable wind turbines and PV systems to provide reactive power compensation during voltage dips and overvoltage events. This is mainly focused on the integration of supplementary controllers into the
d-q currents control loops to regulate active and reactive power during faults. The challenge in this field is more limited in comparison to frequency support as there is no need to sustain certain amounts of active power for relatively long intervals. In addition, the presence of the power electronics interface, i.e., back-to-back converters, facilitates the implementation of these controls, making them very responsive and grid-compliant [
7].
The combination of multiple power sources and generation technologies in one entity has received special interest from stakeholders, and they are often referred to as HPPs. They rely on a variety of power generation and energy sources, hence, the use of the word ‘hybrid’. Some research also uses the term ‘virtual power plants’ [
8]. However, this expression might not be an accurate description of the developed energy system in this paper, as all the elements should be physically available. One of the common examples of virtual power plants is WFs, which are controlled to behave as a typical synchronous generator, i.e., virtual synchronous generator; however, this is outside the paper scope.
The authors of [
9] aim to validate simplified simulation models of the various energy sources that can be parts of hybrid power plants. However, they do not offer specialized control methods to provide ancillary services or improve the ability of the HPP output dispatch as seen from the SOs viewpoint. The study is also more focused on grid-forming control of WTGs in small microgrids. The authors of [
10] developed sensitivity studies to exploit various energy storage technologies, where they examined lead-acid battery packs along with reversible polymer electrolyte fuel cells. They have also included a diesel generator as a backup energy source which compromises the ‘green’ nature of the HPP, leading to CO2 emissions. The review article [
11] provides a high-level comprehensive discussion on two main aspects, the optimization techniques to size the generation units forming an HPP, and the different approaches implemented to design control methods of HPPs. It is mentioned that the offered control methods in the literature can consider either economic challenges or technical challenges, and this manuscript is focused on the technical challenges related to the coordinated provision of ancillary services by the power units forming the HPP. The research presented in [
12] provides an overview of the various generation technologies that can contribute to HPPs, including wind and hydro power. It also presents the advancement in probabilistic algorithms used to estimate the capacity factor of renewable energy, with some real case studies for solar power plants in the US. However, they do not discuss modeling of HPPs and the corresponding holistic controls to enable further functionalities, including ancillary services provision. This paper considers the feasibility of providing frequency support services from more than one power source, i.e., the BESS and the wind farm, while the third power source, i.e., PV farm, does not sacrifice any of its generated power to maintain a reserve margin. In addition, the proposed control utilizes the online HPP capacity factor as a key driver for the HPP’s dispatchability and control of the integrated BESS.
Energy storage systems have been widely investigated in the literature as pivotal elements in the increase of RESs share in the generation mix. There are various technologies that can be used to sustain power generation and provide ancillary services; however, the most common are hydro-pumped storage (more than 98% of grid-scale energy storage worldwide) and battery energy storage [
13]. Even though hydro-pumped storage is the most common, it has special geographic requirements and huge capital investments, whilst also being less responsive compared to BESS. However, BESSs are still facing a higher levelized cost of energy compared to other power-generation technologies. In addition to the essential cooling systems, which represent a major challenge for warm countries, BESSs are still a relatively expensive option.
The key roles of BESSs can be categorized into four areas: concurrent provision of grid services, e.g., frequency and voltage support [
14]; optimal BESS operation under various constraints and lifetime boundaries [
15]; special controls of the power electronic interface in the case of a weak grid, e.g., grid-forming controls [
16]; and coordinated operation with RES. Authors in [
13] propose a control method for BESSs to provide both energy and frequency control services. In [
17], the BESS is sized according to the seasonal historical generation of a WF, and then a frequency support method is proposed, which relies on a certain droop profile. The authors of [
18] implemented predictive control to make the distribution feeder dispatchable within a 5 min time window considering the operational constraints of the integrated BESS.
In the light of this literature review, and to the authors’ best knowledge, the operation and modeling of detailed HPPs is an active topic that requires further contributions. This paper proposes the design and control methods of a complete HPP, where the incorporated BESSs power generation/demand is managed according to the WF and PV farm (PVF) generation. The BESS has two control modes; first, it can stabilize the HPP output at a predefined capacity factor (CF), and second, provide active power support during frequency drops. The priority is always given to mode 2: frequency support, where the provided increment in active power is regulated to comply with a certain generic grid code. Moreover, and to exploit further capabilities of such HPPs, the WTGs are equipped with a supplementary frequency support control, which relies on the pitch deloading concept to provide additional security to the interconnected power system during frequency events. The support from the WF can also be seen as a backup when the state of charge (SOC) of the BESS falls below its minimum threshold; hence, the BESS will not be able to provide active power support in the case of frequency drops. The presence of the BESS should compensate both technically and economically for the wasted electrical energy due to deloading the WF at normal operation (i.e., when the frequency is within the safe deadband), where the BESS acts as a buffer absorbing excess/injecting deficit power to maintain a certain CF, fulfilling the promised power rating of the HPP. It is worth mentioning that The HPP research can be focused on either the technical and/or the economic aspects [
11]. The presented study and the developed models and control methods are focused on the technical operation and coordination between the power sources forming the HPP. The sizes of the WF, PVF and the BESS are prerequisites to the proposed operation method.
The rest of the paper is organized as follows:
Section 2 explains the developed BESS controls and their coordination with PVF and WF instantaneous generation.
Section 3 describes the controls of the three power sources, the implemented test system, the corresponding simulation model, and the applied case studies.
Section 4 presents the results obtained and the corresponding technical explanations. Finally,
Section 5 provides a brief discussion that includes the main findings and conclusions.
3. Test System and Case Studies
This section explains the implemented test system to demonstrate the application of the proposed control method. It also describes the various case studies that have been designed to examine the system response under different operating conditions, during and after some system events.
3.1. HPP Model and the Interconnected Network
The HPP encompasses three power sources: a WF, PV installation (PVF) and a BESS, as illustrated in
Figure 5 Every WTG inside the WF, as well as the PV installation, is coupled to the network through a power electronics interface.
3.1.1. The Wind Farm
The WF is modeled as an aggregate WTG, which includes the turbine, drive train, synchronous generator and full-rated back-to-back converter models as well as their controllers. The mathematical modeling and explanation of Type 4 WTG has been vastly investigated in the literature [
21]. The WTG controls are amended, as explained earlier in
Section 2, to integrate the pitch-deloading frequency support controller. The harnessed wind power (
Pw) is calculated using the well-known Equations (7)–(9):
where
Cp is the performance coefficient,
λ is the tip speed ratio and both are dimensionless.
β is the pitch angle in degrees, A is the rotor swept area in m
2 and
is the air density in kg/m
3. The WTGs apply the conventional maximum power tracking (MPT) approach, which relies on adjusting the rotor speed through a tracking function based on the output power of the WTG (
) in per unit of the WTG rated power, as in Equation (10).
The deviation between the optimum reference rotor speed and the actual speed is fed into the duty cycle controller of the machine side converter, as illustrated in
Figure 6. Further explanations of the WTG benchmark can be found in MATLAB documentation. The rated power of the WF is 80 MW, i.e., 40 × 2 MW Type 4 WTGs.
3.1.2. The PV Farm
The PVF is modeled as an aggregation of 20 groups, each of 400 kW rated power, where the combined power of the farm is 8 MW at 1-Sun. Each group is formed of 128 parallel strings; each string includes 20 series modules. The PV modules are controlled using the conventional Perturb and Observe control approach to adjust the modules currents, achieving maximum power tracking according to the incident solar irradiation [
22]. The PVF is connected to the grid via a DC boost converter that regulates the DC link voltage, then an inverter to convert the DC power into AC power, which is fed into the grid. The temperature is kept constant at an average value of 30 °C.
3.1.3. The Battery Storage System
The MATLAB benchmark model of the Li-Ion cell is the fundamental component of the BESS, whose design is inspired by the commercial BESS in [
23]. The BESSs’ power size was estimated upon the average output power of the WF, where the applied variable wind speed is considered as a reference. The BESS power capacity is assumed to be 15% of the HPP-rated power, i.e., WF plus PVF rated power. The BESS reference value of the total charging/discharging current is calculated using the controller, explained in
Section 2. The main characteristics of the three power sources are summarized in
Table 3. The common technical characetersics of the four identical synchronous power plants are in
Table 4.
3.1.4. The Interconnected Network
The implemented two-area benchmark was modified to reduce the conventional generation capacity, i.e., the combined ratings of the generators 1 to 4, i.e., G1 to G4, as illustrated in
Figure 7. Hence, the loads in the two areas are also scaled down to match the total generation capacity of the grid. The total synchronous generation is 1440 MVA, and they are loaded by about 85% to feed the connected loads. This should be considered as a challenging scenario of a weak grid. Further details about the two-area model are available in [
24] and MATLAB documentation.
3.2. Case Studies
The variable wind speed and solar irradiation profiles which are implemenetd in all case studies is shown in
Figure 8 and
Figure 9 respectively. This is realistic wind speed data represent a typical wind speed profile. The applied simulation time span is relevant to the nature of the study and the objectives of the control method, which are focused on active power control and its impact on frequency dynamics. The presented study applies randomly changing insolation within the range of 700–1000 W/m
2 to reflect realistic and moderate variations at average weather conditions.
Case study 1 (base case)—A sudden increase in load with 88 MW occurs in Area 1 at t = 8 s. All the special controls are OFF, including the CF tracking. This should be the base case, which is used as a reference to observe the impact of various scenarios and control methods on both the power source dynamics as well as the system response.
Case study 2—variable wind/gull support: both the WF frequency support and the BESS functionalities (CF tracking and frequency support are ON). The system is subject to the same load event of Case study 1.
Case study 3—variable wind/WF support OFF: similar to Case study 2, but the frequency support by WF is turned OFF, i.e., no deloading.
Case study 4—constant wind/no support: this is a second base case but at a constant wind speed of 9.4 m/s applying the same load event of Case 1.
Case study 5—constant wind/full support: similar to Case study 2, full support from both WF and the BESS, but at a constant wind speed of 9.4 m/s.
The constant wind speed in Case studies 4 and 5 was selected to this value as an average of the variable wind speed profile applied in the first three case studies.
4. Results
The results of the five case studies are thoroughly discussed where some reflective signals are discussed separately in this section; meanwhile, the combined observations are explained in the next section. All cases are always compared to Case study 2, as it represents a realistic scenario of variable wind speed with a reasonable average; meanwhile, the other cases mainly reveal and separate the various effects of the implemented controls. The BESS cell reference current is displayed in
Figure 10, where the current is maintained at zero before the CF tracking is activated at t = 1 s, where the current increases in the positive direction, i.e., BESS charging, to reduce the CF until it reaches the target value at normal operation. This is clear in both Cases 3 and 5; however, in the case of constant wind speed, the current is almost constant according to the constant nature of the WF output. On the other hand, the current fluctuates in Case studies 2 and 3, following the continuous variations in WF output due to the variable wind speed. The BESS current is always higher in Case study 3 compared to Case 2, where the WF output is not deloaded in Case study 3 (frequency support is off; hence, pitch deloading is deactivated during normal operation). The conventional generation of both the WF and PVF are displayed in
Figure 11 to provide a wider picture of the generation mix during the simulation time span. It can also be observed that under the given wind and solar irradiation conditions, the PVF contribution into the HPP generation mix is about 20%; meanwhile, its installed capacity compared to the WF capacity is 10%. This also reflects the capability of the proposed control method to track
CFo using the integrated BESS, with the presence of two green power sources, which rely on two different types of input energy (i.e., solar irradiation and wind).
The higher WF output in Case study 3 requires the BESS to charge more, keeping the CF within the targeted value. At t = 9 s, the frequency events occur; hence, the BESS should respond in an opposite way to the cause of the frequency event. In this case, there is a frequency drop caused by a sudden increase in load; hence, more active power should promptly be injected into the power system. Since the BESS was in charging mode just before the event, it has to switch discharging mode, i.e., negative current, to comply with the frequency support requirements, as explained earlier in
Section 2. Similar outcomes are deduced based on the in/output power of the BESS shown in
Figure 12.
The successful operation of the CF tracking functionality is demonstrated through the behavior of the CF displayed in
Figure 13, where the CF drops to the target value within a very short time from CF tracking activation. The designed PI control and the selected input signal enabled such a smooth and fast tracking in spite of the variable nature of wind speed at 1 s time resolution. At constant wind speed in
Figure 13b, the CF maintained an almost flat line because of the constant wind speed; however, once the frequency excursion occurs, the CF increases rapidly as the HPP injects more active power to arrest the frequency nadir and mitigate the consequences of the sudden increase in load. The impact of WF deloading can also be seen on the CF, which has some slight fluctuations in Case study 3 compared to Case study 2.
The system frequency shows an expected behavior in the examined case studies as in
Figure 14, where the frequency drops very slightly once the CF tracking is activated at t = 1 s; however, the frequency deviation is still within the safe margin, which is ±0.05 Hz in this research work. The frequency is less than the nominal value on this occasion, as the BESS will activate the charging mode to reduce the CF to the target value.
The contribution of HPP to frequency support during the event does not clearly impact either the RoCoF or the worst frequency deviation, i.e., nadir, due to the limited HPP capacity compared to the aggregate capacity of the four synchronous generators, as they dominate the generation mix. There was no clear impact of wind speed variability due to the domination of conventional generation mix as well as the activation of CF tracking, which maintained an almost constant HPP output, as discussed previously. It is worth mentioning that the authors will investigate further scenarios and implement the proposed methods and model of the HPP with a larger capacity which achieves higher penetration into the generation mix in their future research.
The WTG pitch angle dynamics reflect the influence of the output deloading where the pitch is always higher than zero in Case 2 of full support in
Figure 15a, where its value is changing continuously according to the incident wind speed. The pitch angle is almost constant in Case 5 with constant wind speed (
Figure 15b), then it drops quickly to almost zero at the frequency event following the controller response, which is explained in
Section 2.2.
5. Discussion
The proposed active power control of the HPP power sources considered two main functions: improving the ability of HPP output dispatch, i.e., keeping a constant and predetermined CF as possible using the BESS as a buffer and the provision of synthetic inertia and primary response using the BESS as a sustainable power reserve. The implemented test system and case studies prove the successful application of the proposed control method. The BESS charging/discharging strategy provides a reasonable balance between the mitigation of uncertainty of HPP power output and the capability of frequency support. This includes the capability of CF tracking if it requires the same operation mode which is necessary for frequency support, not just to simply switch between the two functionalities simultaneously. The incorporation of a second reserve, which is the margin between the optimum and deloaded output of the WF, should reduce the stress on the BESS; however, it can reduce the HPP revenue due to the unsold amounts of energy. The included low-pass filter in the CF tracking control should also reduce the minor negative influence of continuous fluctuation in cell current. In addition, the nature of wind speed fluctuations should also suppress this influence, as the wind speed is always fluctuating around a certain average, which does not change steeply within very short intervals, similar to the profile applied in the presented case studies. Hence, the cell current does not change its direction (charging/discharging).
The size of the BESS, i.e., power rating and energy capacity, can be accurately calculated using probabilistic or deterministic methods offered in the literature. In particular, the HPP research is usually focused on either the technical and/or the economic aspects [
11]. The presented study and the developed models and control methods are focused on the technical operation and coordination between the power sources forming the HPP. Therefore, the presented research considers the capacities of the wind farm, the PV farm and the BESS as prerequisites to the proposed operation methods. The sizing optimization can be developed to consider the best sharing of the HPP primary reserve between the contributions of the BESS and the WF deloaded output.