1. Introduction
High-voltage direct-current (HVDC) systems have install and operated continuously to transfer constant or fluctuant power between power networks in recent years. Concretely, about 191,000 MW power is delivered through 172 HVDC system around the world after the HVDC system was operated first in 1954 [
1]. Although most HVDC projects have been utilized voltage-source converters (VSCs), a verified line-commutated converters (LCCs) are still installed and operated with higher capacities of HVDC system than current VSCs [
2]. For example, Korea Electric Power Corporation (KEPCO) have installed and utilized two LCC-based HVDC systems, i.e., 180-kV, 300-MW and 200-kV, 250-MW, to transfer electrical power from the Korean mainland to the Jeju Island [
3]. Moreover, the 200-kV LCC-based HVDC system installed by KEPCO has been used to transmit 300-MW electrical power from the Godduck substation to the Dangjin substation on the Korean mainland for improving stability and reliability of the Korea power grid against AC fault conditions [
4].
Before installing and operating the HVDC systems, it is essential to analyze the transient- and steady-state stabilities of HVDC-linked AC transmission grids. For this, several models of HVDC systems have been studied to analyze interactions between large-scale AC networks and the HVDC system against several AC network or HVDC system conditions [
5,
6,
7]. For example, in [
5], an LCC-based HVDC system was proposed using
dq-reference quantities of an connected AC network to calculate DC voltage and current. In [
6] and [
7], an LCC-based HVDC system in multi-infeed HVDC systems was linearized to analyze the small-signal and network stability, respectively. However, these models of HVDC systems may be difficult or required adaptations to represent the operating features of real-operated HVDC systems, which needs a lot of time and effort considering modeling complexity.
Considering the difficulties of HVDC system modeling, the conseil international des grands reseaux electriques (CIGRE) benchmark model have been utilized to simulate HVDC systems and AC grids for the dynamic and steady-state stabilities in the several papers. In [
8], comparative studies of the CIGRE benchmark model was conducted using different simulation tools. In [
9,
10], the responses of CIGRE benchmark model was explored when commutation failures occurred with respect to DC voltage variation and valve current variation, respectively. However, the CIGRE benchmark model may also require modifications to represent the operating characteristics of real HVDC systems. For example, in [
11], additional extinction angle and DC current controllers at the rectifier and the inverter, respectively, were implemented to the CIGRE benchmark model to represent the HVDC system in the Taiwan. In [
12], the Anshun-Zhaoqing HVDC system was modeled without consideration of the CIGRE benchmark model to represent the own operating characteristics of the system. Moreover, power systems computer aided design (PSCAD) and
Matlab/Simulink have been used as the simulation tools in [
8,
9,
10]. However, only simplified voltage sources and equivalent impedances were used to represent the AC network models in these studies due to limited capabilities of the simulation tools for modeling of large-scale AC grids. Therefore, modeling of the real AC networks, such as Korea and Jeju grids, are restricted by these simulators; i.e., real-time simulations of the HVDC systems will have computational burden.
Quasi-steady-state (QSS) simulators such as Power System Simulator for Engineering (PSS/E), Positive Sequence Load Flow (PSLF) or PowerWorld are suitable simulation tools to model large-scale AC networks including HVDC systems. In particular, PSS/E is an appropriate QSS simulator to study AC networks and associated controllers. It assists transmission planning and operation engineers in designing and operating reliable AC networks by a broad range of methods. Therefore, PSS/E have been utilized to analyze large-scale power grids by many electric utilities [
11,
13]. Moreover, real data of power grid can be utilized in PSS/E to demonstrate interactions between the HVDC system and AC power network. For this, PSS/E also provides generic HVDC models such as CDC4T, CDC6T, and CDC7T instead of the CIGRE benchmark model [
14]. In general, these HVDC models are used to represent real LCC-based HVDC systems when system operators analyze effects of the HVDC system on the AC power grid. For example, Western Electricity Coordination Council (WECC) have approved these HVDC models as generic models to simulate abnormal conditions, such as commutation failure or AC grid faults, for validating the real HVDC systems via PSS/E [
15]. However, these models require numerous parameters whose characteristics and differences are not described to demonstrate operations of the real HVDC system at the abnormal conditions. In addition, a few real HVDC systems may be restricted to depict operations via these models because of their own characteristics. Therefore, some grid operators or utility companies may request new PSS/E models of practical HVDC systems to analyze effects of the HVDC system on the AC power grid, for example we focus on the Jeju-Haenam HVDC system in Korea.
In the meantime, LCC-based HVDC systems are cautious to commutation failure under the abnormal operation due to AC line faults. This is because it is capable of interrupting power transfer or imposing stress on converter [
16]. Therefore, there have been several papers about cognizance of commutation failure caused by AC network faults [
17] and alleviation of commutation failure by modifying controllers [
18,
19] or by including supplement components [
13,
14]. In [
17], the maximum-allowable balanced voltage drop at an inverter bus was calculated to reduce commutation failure probability and to increase recovery speed of the DC system after the commutation failure. In [
18], A larger commutation margin was achieved by advancing the firing angle at the inverter side immediately when AC voltage disturbance was detected. It was described that a diminution of rectifier current order can reduce commutated DC current when AC voltage disturbances are detected in [
19]. In [
13], it was depicted that possibility of commutation failures and power factor can be reduced and improved, respectively, by a capacitor-commutated converters (CCC). In [
14], thyristor-based full-bridge module (TFBM) was used in the converter valve of LCC to improve commutation failure immunity. However, these papers discussed so far focused on the reduction of commutation failure possibilities caused by AC line-to-ground faults. The maximum DC voltage and current of HVDC systems during commutation failures due to the AC line-to-ground faults have not been investigated in these papers. In practice, the maximum fault current and voltage are major concerns for the HVDC systems as well as AC networks because parameters of converter valves, DC-line capacity, and protection relays are affected by these values [
20,
21,
22].
This paper investigates generic LCC-based HVDC system models and proposes a novel modeling method for an LCC-based HVDC system in the PSS/E simulation. In this paper, the characteristics and limitations as well as parameter investigations of generic HVDC models (e.g., CDC4T, CDC6T, and CDC7T) are conducted to indicate the maximum DC voltage and current of the HVDC systems in the abnormal condition, i.e., commutation failure due to AC line-to-ground faults. Moreover, the proposed modeling method, which composed of three modules, i.e., (a) AC/DC conversion; (b) controller selection; and (c) DC line model, is presented to calculate the maximum DC voltage and current of the HVDC system in the abnormal condition. Furthermore, the real HVDC system and the real power network are used as an example. The DC voltage and current of generic and proposed models are compared with measured data from the real-operated HVDC system to manifest differences between the generic and proposed models. The main contributions of this paper are summarized below:
Analyses of characteristics, limitations, and parameter for the generic HVDC models in PSS/E are conducted to describe dynamic DC current and voltage of HVDC systems when AC line-to-ground faults occur.
The HVDC system modeling method and procedure using PSS/E are proposed. The proposed modeling method calculates more precise maximum DC voltage and current of HVDC systems during the transient AC networks caused by AC grid faults.
This paper describes transient DC voltage and current profiles compared with measured data for a single-phase fault from a real-operated HVDC systems using the proposed HVDC systems in PSS/E. Moreover, the DC voltage and current profiles of generic and proposed models are compared with those of HVDC system model developed using PSCAD considering a three-phase line-to-ground fault.
Section 2 explains analyses and comparisons of generic HVDC models in PSS/E simulation. The proposed HVDC modeling method using the real-operated HVDC system is stated in
Section 3. The case studies for AC line-to-ground faults, e.g., single- and three-phase line-to-ground faults, are conducted in
Section 4.
Section 5 discusses conclusions.
2. Generic Models of HVDC System in PSS/E Simulation
PSS/E is one of the QSS-type simulation tools to simulate AC network at the fundamental grid frequency. It means that analyses of interaction between the HVDC systems and AC grid is more appropriate than analyses of detailed dynamics for converters using PSS/E. In particular, there are 12 examples of LCC-based HVDC system models in PSS/E for analyzing interaction between the HVDC system and AC transmission networks. Among these example models, 7 models (e.g., CDCABT, CEELT, CMDWAST, and etc.) represent actual operating HVDC models which have own additional controllers each, for example frequency or runback controllers. The other models, on the other hand, are generally utilized to represent several HVDC systems having fundamental controllers, such as DC voltage, DC current, and firing angle controllers. For example, CDC4T, CDC6T and CDC7T models belong to these models, and are called the generic models. Following sections will explain characteristics and parameter analyses for the system operators to analyze HVDC system under an abnormal condition AC line faults.
2.1. Generic HVDC Models—CDC4T & CDC6T
A schematic control diagram for the CDC4T and CDC6T models is presented in
Figure 1. The dc power reference
Pdc_ref or the dc current reference
Idc_ref can be selected for the both models as input variables including the dc voltage reference
Vdc_ref. When
Pdc_ref is selected as an input variable, the dc current reference from the dc power reference
IPdc_ref is chosen for the initial dc current reference
Iidcr_ref rather than
Idc_ref.
IPdc_ref is calculated by dividing
Pdc_ref by the inverter dc voltage
Vdci or rectifier dc voltage
Vdcr. Note that
Vdci or
Vdcr is chosen by measure point for the dc voltage of the HVDC system. The dc current reference from voltage-dependent current order limit (VDCOL) function,
IVdc_ref, is also calculated using
Vdci. The final dc current reference
Ifdc_ref is then selected either
Iidc_ref or
IVdc_ref by the minimum-select block. The final dc voltage reference
Vfdc_ref is calculated using
Vdc_ref,
Ifdc_ref and the compounding resistance
Rcomp.
Vdci and
Idc then calculated from
Vfdc_ref and
Ifdc_ref by the converter control block and transducer delay blocks, which have time constants
TVdc and
TIdc each. Note that
Vdcr can be calculated using
Vdci and
Idc because a dc line is modeled by the dc-line resistor,
Rdc, in the CDC4T and CDC6T models.
The primary aim of the converter control block is to obtain the Vdci and Idc of the HVDC system from final input variables Vfdc_ref and Ifdc_ref. Each converter control block is controlled by a simple feedback loop that adjusts firing delay to control the dc current to reference signal. The transfer function for the feedback loop depends on details of the bridge design. This feedback controller is able to force the dc current rapidly to the reference point by transient overadjustment of the rectifier dc voltage. This rapid forced response of the feedback control block is completed in a time that is generally shorter than the shortest time interval that can be recognized within the bandwidth of PSS/E simulation environment. This means that CDC4T and CDC6T models treat dc converter pairs as if they move instantaneously to their reference points when any of their input signals or ac feed voltages are changed. Therefore, these models are not concerned with the internal dynamic behavior of converters. The dc current and voltage from converter control block follows with transducer delay blocks which time constant determined by inductance of converter transformer and dc-link line.
The CDC4T and CDC6T models have 22 and 32 parameters which users can decide for investigation of interactions between HVDC systems and AC network. These parameters can be classified into two groups. One group is parameters given by manufacturers to represent their own individual HVDC characteristics. For example, the minimum alpha and gamma parameters (i.e., AFLDY and GAMDY) or the dc voltage and current transducer time constants (i.e., TVDC and TIDC) in CDC4T and CDC6T models are parameters given by manufacturer for representing their own HVDC system. These parameters are difficult for system operator to change. The other is parameters which can be changed by the system operators to validate HVDC system models against the real operating profiles for some network events, such as three-phase ground fault and dc-line block, or to modify HVDC models for making operating strategies of HVDC systems. For example, inverter dc bypassing voltage (VBYPAS), voltage recovery rate (VRAMP), and VDCOL parameters in CDC4T and CDC6T models are parameters can be included to this group.
Table 1 shows the parameters given by the manufacturers (i.e., Group A) and the parameters can be modified (i.e., Group B) of CDC4T and CDC6T models. Specially, example values of parameters for CDC4T model are also provided in the PSS/E manual [
23].
Both CDC4T and CDC6T models have block and bypass functions to protect against the abnormal condition of HVDC system due to AC grid faults. For example, when the ac voltage at the rectifier side falls below the setting value (i.e., VBLOCK), the rectifier and inverter are both blocked. The only inverter, on the other hand, is bypassed while the rectifier continues to maintain dc current at the scheduled value when the inverter dc voltage falls below the setting value (i.e., VBYPAS). Note that low DC voltage at the rectifier does not cause blocking of the HVDC system unless AC voltage at the rectifier is also low. Similarly, low AC voltage at the inverter does not cause blocking or bypassing unless DC voltage at the inverter is also low. If the HVDC system is blocked, the rectifier remains block for a minimum second (i.e., TBLOCK) and then restarts when the AC voltage at the rectifier rises to a value of VUNBL. In the same manner, if the HVDC system is bypassed, the inverter remains bypass for a minimum second (i.e., TBYPAS) and then reestablishes when the AC voltage at the inverter rises to a value of VUNBY.
Moreover, CDC6T model has additional 10 parameters for the block of bypass functions to protect the HVDC system in detail from the AC faults causing the commutation failure, as listed in
Table 2. This model allows for delayed automatic blocking of the HVDC system based on low AC voltage at the rectifier. For example, if the AC voltage at the rectifier is below the set value (i.e., VDEBLK) during the set seconds (i.e., TREBLK), the HVDC system is then blocked. Following this block, the HVDC system cannot restart until several seconds (i.e., TREBLK) after the AC voltage at the rectifier goes above the set value (i.e., VUNBY). Furthermore, the CDC6T model allows a low AC voltage at the inverter to send a signal via a communication channel to the rectifier for blocking the HVDC system. This function is modeled by the instantaneous AC voltage at the inverter for blocking and the time delay (i.e., VINBLK and TCOMB). The HVDC system will stay blocked until the set period (i.e., TINBLK) after the AC voltage at the inverter goes above VUNBY. Note that TINBLK should include the communication delay in getting the signal from the inverter to the rectifier. Besides, if the AC voltage at the inverter goes below the set value (i.e., VACBYP) during the set seconds (i.e., TDEBYP), the inverter is then bypassed. The inverter will clear the bypass the set time seconds later (i.e., TUNBY) when the AC voltage at the inverter goes above VUNBY.
Figure 2 shows differences of bypass and block functions between the CDC4T and CDC6T models.
2.2. Generic HVDC Model—CDC7T
The CDC7T model can simulate dynamics of DC line in the HVDC systems, which is a significant difference in other generic models, such as CDC4T or CDC6T models. The latter models assume that the HVDCs system have an instantaneous response to disturbance coming from the adjacent grid without internal dynamics of converters. These models also have block and bypass functions using some threshold AC and DC voltages to protect against the abnormal condition of HVDC system due to AC grid faults. The CDC7T model, on the other hand, can be utilized to analyze dynamic operations of the DC line and converter controllers. At the same time, the CDC7T model uses general converter controllers and typical configuration of DC line for modeling of several real-operated HVDC systems.
Figure 3 show a configuration of DC line circuit for the CDC7T model. The DC line of CDC7T model consists of overhand lines and cables from the rectifier to inverter. Both overhead lines and cables are represented by DC resistances and equivalent inductances. Note that the cable has also a capacitance and a small resistance to represent the cable damping which is place in series with the cable capacitance. The CDC7T model has no elements affected by frequencies for the overhead lines and cables. Therefore, a fundamental frequency is used for the equivalent inductances and capacitances in the DC line circuit. The CDC7T model also allows to simulate faults in the DC system by adding three fictitious shunt RL to the model as shown in
Figure 3. These shunt parameters for simulation of DC line fault should be set to large numbers to have almost zero current flowing through these shunt elements during the normal operation. It means that both inductance and resistance of the shunt elements should be declined for DC line fault simulations; faults on the (1) rectifier DC terminal, (2) inverter DC terminal, and (3) in the center of DC line. Note that L/R ratio for the DC line fault simulations should be 0.1 [
23].
The CDC7T model provides the following three major configurations of converter controls which numerous exiting HVDC systems have; (1) DC current and extinction angle (i.e., gamma) control at the rectifier and inverter, respectively, (2) DC current and voltage control at the rectifier and inverter, respectively, and (3) DC voltage and current control at the rectifier and inverter, respectively. Some real-operated HVDC systems, such as the first-operated and Jeju–Haenam HVDC systems, utilize the control configuration (1). The configuration (2) is general composition for present HVDC systems which have long overhead DC lines or relatively short cables. The control configuration (3) is more appropriate to the HVDC systems having long cables.
Figure 4 shows a control diagram of both converters in the CDC7T model, which includes three controllers; (1) DC current, (2) DC voltage, and (3) gamma controllers. The outputs from these three controllers enter the maximum and minimum selector for the rectifier and inverter side, respectively. The output of mode selector is utilized as an input signal for a PI controller, and then the final output is a firing angle order (i.e., an alpha order). In particular, the DC voltage and gamma controllers in the inverter have extra signal from the Current Error Control (CEC), which proportional to the DC current error to improve stability when AC voltages at the both sides vary. Note that CEC is look-up table composed of non-linear gains which determined to be advantageous to change-slope of the converter characteristic near the operating point. The CDC7T model also has the Voltage Dependent Current Order Limit (VDCOL) algorithm. The compounded DC voltage (i.e., Vdcomp) enters a lag controller which time constant determined by the DC voltage, and then multiplied by a non-linear gain. Note that the time constant of the lag controller is set to up and down value considering increment and reduction of DC voltage, respectively. The non-linear gain for the rectifier and inverter in the VDCOL is look-up table composed of the
Vd-
Id characteristics. Finally, a smaller value between the output of the VDCOL and the current order is selected as the input for the DC current controller.
The CDC7T model has 75 parameters which are much more than that of the CDC4T or CDC6T models. However, most of parameters are given by manufacturers for representing their own HVDC system, which is difficult to by modified by the system operator (i.e., Group A). For example, all parameters in the DC line circuit, which is shown in
Figure 3, are provided by the manufacturers.
Table 3 shows the parameters can be modified by the system operators to validate HVDC system models against the real operating profiles (i.e., Group B). Specifically, shunt inductances and resistances for simulation of DC system faults (i.e., LF1–RF3 in
Table 3) are determined by comparing DC current or voltage profiles of real operating HVDC system when DC faults are occurred using trial and error method. This is because these parameters are considerably affected by adjacent grids connected to the HVDC system. The 5 pairs of parameters for VDCOL in both-side converters and time constants for Vdcomp (i.e., Vd1–Id5 and VDCompeR–VDCompI in
Table 3) are decided by the HVDC system operation strategies at the abnormal conditions due to commutation failures or AC grid faults. In addition, parameters of DC current order change-rates for blocking and unblocking are set by the system operators based on the HVDC system operation strategies.
2.3. Comparisons with CDC4T & 6T and CDC7T
Table 4 lists functions implemented in the CDC4T, CDC6T, and CDC7T models to describe the HVDC system under the abnormal condition due to AC grid faults. The CDC6T model has delayed block and bypass functions considering communication delays as well as includes all functions of CDC4T. This enables the CDC6T model to block or bypass converter due to AC faults at the other converter side, which is not implemented in the CDC4T model. Both CDC4T and CDC6T models have the VDCOL function and can set the change-rates of DC voltage and current. Therefore, the system operators can describe recovery times of the DC voltage and current to the rated values, which similar to the those of real HVDC systems, after the AC faults are cleared using the both models. However, both models depict the DC voltage and current profiles briefly without oscillations under the abnormal operation (i.e., commutation failure) caused by the AC grid faults. This is because converter and DC line models are simplified without considering the dynamics for the abnormal operation of the HVDC system. In other words, it is difficult to describe oscillations of DC voltage or current and to identify the maximum DC voltage and current of the HVDC system under the abnormal operation using these models.
The CDC7T model, on the other hand, has a DC line model and converter controllers for DC current, DC voltage, and gamma via PI controllers. It means that the CDC7T model is capable to identify the maximum DC voltage and current of the HVDC system when AC faults occur. The CDC7T model can also simulate that both DC voltage and current are restored to the rated values gradually by modifying the change-rate of DC voltage and current as well as VDCOL. This means that the CDC7T model is more suitable for describing the DC voltage and current dynamics of the HVDC system under the abnormal condition due to AC faults than CDC4T or CDC6T models.
3. Proposed Model of HVDC System for Describing Dynamics of DC Voltage and Current
Figure 5 shows a flowchart of the proposed modeling procedure of the HVDC system to enhance calculation of DC voltage and current during the commutation failure caused by AC grid faults. It is integrated with the
Dynamic Simulation (DS) module in PSS/E. The state variables of various dynamic power devices, including not only the HVDC system but also thermal generators, wind turbines, and synchronous condensers, are initially set to the PSS/E data that are pre-determined based on their actual parameters and operating conditions. The AC power flow is then calculated in the
Power Flow Calculation (PFC) module using the initial values. The differential and algebraic equations characterizing the time-varying operations of the dynamic devices are solved for the period of ∆
tstep, based on the power flow calculation results. Specifically, the proposed model consists of the three modules for the AC/DC conversion, controller selection, and DC line model. The variation in the DC current ∆
Idc is calculated in the DC-line modeling module, based on the DC-line voltage
Vdc, the converter firing angle
α, and the AC voltage
Vac of the converter transformers. In addition,
α is updated to
αnew in the control-mode selection module using
Vdc and
Idc. In the equation conversion module,
Idc is updated to
Idc,new =
Idc + ∆
Idc, and
Vdc is calculated to
Vdc,new by using
Idc,new and
αnew. The algebraic equations are then solved to update the AC currents
Iac that are injected to the AC buses where the HVDC converters are connected. The variables are then used to update
Iac to
Iac,new for the AC power flow calculation. This iterative process continues until the total simulation time
tsimulation.
3.1. AC/DC Conversion Module
The main aim of AC/DC conversion module is to calculate the DC voltage of the HVDC system. This module also calculates the active and reactive AC power at the both-side converters to estimate injected AC current flowing into the AC network from the HVDC system during the normal and abnormal HVDC operations. This paper concentrates HVDC system on the abnormal operation caused by the commutation failure. The commutation failure can be occurred when the extinction angle
γ is smaller than
γmin or when
μ is larger than 60° [
22,
24]. If
μ is greater than 60°, the next commutation will commence prior to completion of the current commutation, which results in a short circuit as shown in
Figure 6a. In other words,
va and
vb are same to
ea and (
eb +
ec)/2, respectively, as shown in
Figure 6b. Therefore, the DC voltage and current can be expressed as Equations (1) and (2), respectively, during the abnormal operation of HVDC system. Note that
α is calculated by the controller selection module.
Vdc then can be obtained using Equation (3) by substituting Equation (2) into Equation (1). Moreover,
γ, power factor angle
ϕ, and the active power
Pac can be calculated using the updated
Vdc,
α, and
μ, expressed as Equations (4)–(6), respectively. The reactive AC power
Qac is also calculated by Equation (7) and the injected AC current from the HVDC system to AC grid, which utilized for power flow calculation (PFC), can be obtained using Equations (6) and (7). Using these equations, the proposed method can obtain more accurate DC voltage and current as well as injected AC current flowing from the HVDC system to the AC network during the abnormal HVDC operation cause by the commutation failure. It is noticeable that the generic models (i.e., CDC4T, CDC6T, and CDC7T) in PSS/E do not consider these equations.
3.2. Controller Selection Module
The controller selection module calculates
α for the HVDC converters, which can change from DC current control mode to DC voltage control mode, and vice versa, according to converter AC voltages. However, this module is difficult to be implemented using the CIGRE benchmark HVDC model or individual HVDC model having exclusive controllers because of several different
V-I characteristics of HVDC systems. Therefore, a simple and intuitive HVDC controller is developed to analyze dynamics of the DC voltage and current comfortably in this paper. Note that the proposed controller can be applied to other HVDC systems easily with slight modifications. For example, KEPCO has applied the controller to the Jeju-Jindo HVDC system model [
25].
Figure 7 shows a simplified schematic diagram of the proposed controller selection module at the rectifier and inverter side of the Jeju-Haenam HVDC system, as an example.
Figure 8 shows a
V-
I characteristic curve for the HVDC system. The proposed controller selection scheme decides the control mode which having the smallest difference between the reference and present DC voltage and current values. For example, in
Figure 7a, there are two PI controllers having restricted maximum and minimum output values at the rectifier. If the rectifier operates the DC voltage control mode under the normal operation (i.e., the point X in
Figure 8), then the operated DC voltage and current of the rectifier are quite close to
Vdcr = 1.0 pu and
Idcr = 0.5 pu, respectively. In the meantime, the DC voltage and current orders at the rectifier side are
Vdcr_order = 1.0 pu and
Idcr_order = 1.3 pu, respectively, as shown in
Figure 8. Therefore, the difference between
Vdcr_order and
Vdcr is small and the output value of the rectifier controller
αr_voltage is close to the current firing angle
αr. On the contrary, the DC current controller reduces the output value
αr_current so as to adjust
Idcr to
Idcr_order. This is because
Idcr is obtained from the difference between
Vdcr and the DC voltage at the middle of DC line. Note that
Vdcr is proportional to
cos αr. It means that
Idcr increases by reducing
αr which is same to increasing
Vdcr. Therefore, an updated
αr is same to
αr_voltage because the maximum selector chooses
αr_voltage, which is larger than
αr_current.
In addition, for the point Y in
Figure 8, the rectifier operates the DC current controller when the AC voltage is reduced. The rectifier DC voltage and current are close to
Vdcr = 0.55 pu and
Idcr = 1.3 pu, respectively.
Vdcr_order and
Idcr_order are then same to 1.0 and 1.3 pu, respectively, as discussed above. Therefore, the DC voltage controller decreases
αr_voltage so as to increase
Vdcr up to
Vdcr_order.
αr_current, on the other hand, is close to current
αr because difference between
Idcr_order and
Idcr is very small. Consequently,
αr_current from the DC current controller is selected to the updated
αr.
In particular, the DC voltages at the rectifier and inverter of the Jeju-Haenam HVDC system are controlled to be gradually restored to the nominal value of 1 pu (i.e.,
dVdcr/
dt ≈ 0.2 pu/s), after the AC line fault is cleared. This is to protect the Jeju AC grid from a sudden variation in the DC power flow during the time period when the HVDC system is recovering from the fault. Therefore, the proposed model includes an additional function for the VDCOL with a gradual restoration parameter (i.e.,
dVdcr/
dt) in the rectifier controller, as shown in
Figure 7a.
The controller selection of the inverter side is analogous to that of the rectifier side, besides the extra PI controller for the
γ selection, as shown in
Figure 7b. For the point X in
Figure 8, the inverter DC voltage and current are quite close to
Vdci = 1.0 pu and
Idci = 0.5 pu, respectively. In addition,
Vdci_order and
Idci_order are same to 1.2 pu and 0.5 pu, respectively. Therefore, the difference between
Idci_order and
Idcr is quite small that the output value of the inverter controller
αi_current is adjacent to the current inverter firing angle
αi. However, the output value
αi_voltage is increased by the DC voltage controller to increase
Vdci up to
Vdci_order;
Vdci is proportional to
cos (π-
αi). Therefore,
αi_voltage from the DC voltage controller is selected to the updated
αi by the minimum selector because
αi_voltage is smaller than
αi_current. Analogously, for the point Y in
Figure 8, the inverter controls the DC voltage. The supplementary
γ controller is not explained for brevity.
3.3. DC Line Model Module
In the DC line model module, the rectifier and inverter DC currents are obtained using the updated DC voltages (i.e., Equation (8)) during the abnormal operating conditions, as well as
αr and
αi for every time-step ∆
tstep.
Figure 9 shows a general schematic diagram of the proposed DC line model using
N π-sections.
The conventional DC-line model (i.e., T-equivalent model) have been used in previous papers [
26,
27] because of its simplicity. However, the model may lead to over-estimation of the fault current, particularly when a commutation failure occurs due to AC grid faults such as single- or three-phase line-to-ground faults. Specifically, in the conventional DC-line model, the DC voltages at the middle point
Vdm and
Vdci are used to calculate the fault current. In the proposed model, on the other hand, it is affected mainly by the difference between
Vdm(n-1) and
Vdmn, as shown in
Figure 9. The difference between
Vdm(n-1) and
Vdmn can result in more accurate fault current than that between
Vdm and
Vdci. This is because the actual DC line has a uniformly distributed resistance
R, inductance
L, and capacitance
C. Therefore, the DC voltage and current are affected by the several sections punctuated in the DC line.
However, as the number of π-sections increases, the number of differential equations for calculating
Idci also increases and, consequently, it makes it difficult to set the PI gains (e.g.,
Kp3 and
Ki3 in
Figure 7) in the both-sides controllers. Therefore, in this paper, three π-section lines (i.e.,
N = 3) was utilized considering both precision of DC line model and computational complication.
5. Conclusions
This paper described analyses of generic LCC-based HVDC system models and proposed a novel modeling method for an LCC-based HVDC system in the PSS/E simulation. In this paper, the characteristics and limitations as well as parameter investigations of generic HVDC models (e.g., CDC4T, CDC6T, and CDC7T) were conducted to indicate the maximum DC voltage and current of the HVDC system in the abnormal operation, i.e., commutation failure due to AC line-to-ground faults. The CDC6T model has additional protection schemes compared to the CDC4T model, and both CDC4T and CDC6T models are not concerned with the internal dynamic behavior of converters. The CDC7T model, on the other hand, can be utilized to analyze dynamic operations of the DC line and converter controllers. Furthermore, the proposed modeling method had three modules developed for the AC/DC conversion, controller selection, and DC line model. In particular, the AC/DC conversion module was developed considering the abnormal operation of HVDC system. The DC line was modeled using multiple π-sections for accurate estimation of the DC voltages and currents. The case study results showed that the specific generic HVDC models in PSS/E (i.e., CDC7T) can simulate the dynamics of the DC voltage and current after the fault, however, the maximum values of the DC voltage and current can be differed from the real-measured data. The case study results also showed that the proposed modeling method effectively improves the estimation of the DC voltage and current variations for single-phase and three-phase line-to-ground faults. In addition, the simulation results showed that the proposed model has a limitation for describing time delays of the firing controller in the converter due to restriction of simulation time-steps for PSS/E. Further work will focus on implementing various real-operated LCC-based HVDC systems which have different size and control types by using the proposed modeling method. Moreover, applications of the proposed method to VSC-based HVDC systems are required for the future work.