1. Introduction
A recuperator is a device used, among others, for supplying and extracting air from rooms as part of ventilation systems with heat recovery (recuperation systems). Connected to a properly executed ventilation system, it recovers heat (energy) from air, reducing the building’s energy demand. The most important part of any recuperator, which determines heat recovery parameters, is the heat exchanger located centrally in the recuperator. There are many recuperator types, including those discussed in monographs [
1,
2] and presented on numerous websites, e.g., [
3]. The exhaust air flows in the heat exchanger without mixing with the supply air. Energy is exchanged between the air fluxes. It enables the recovery of heat or cold (depending on the season). Numerous publications discussing heat exchanger types are known.
The paper discusses plate heat exchangers. A heat exchanger of this type is composed of many metal plates, and heat is transferred by the liquids flowing through them. The exchanger, made mainly of weather-resistant aluminium, deserves particular attention due to its unique design, which ensures the highest known efficiency, with a 100% share of fresh air. When one of the exchanger’s sections takes heat from the exhaust air, the other gives off the stored heat to the cold supply air.
Another important feature is frost resistance. In the vertical positions, the upper part is cold, and the bottom part is warm. Condensate drops fall down to the warmer part, from where they are routed to the sewerage system. This direction of the condensate flow excludes the possibility of condensate getting into the cold part, preventing it from freezing. The main advantage is undoubtedly self-cleaning, which is ensured by a two-way air flow. For this reason, the effectiveness of two types of exchangers was analysed in order to optimise the design parameters.
Plate heat exchangers are among the most efficient heat transfer devices. However, the main limitation of plate heat exchangers is the fact that they can only be used in a relatively low pressure and temperature, [
4]. Therefore, only heat exchangers operating under a small temperature difference (up to 50–60 °C) between the room from which the air is extracted and the outside area will be considered.
In a parallel flow exchanger, the air can be exchanged in two ways: (a) first, used air is exhausted from the room; then, fresh air is supplied from outside, or (b) used air is exhausted from the room, and at the same time, fresh air is supplied (counter-flow exchanger). In both cases, the heat collected during air exhaust is released by the panel to the fresh air supplied from the outside.
The literature does not focus on modelling the heat flow itself through a heat exchanger with parallel plates. In a number of studies, a model and a computational grid were developed to simulate a heat exchanger, and then fluid dynamics (CFD) computation software was launched. When assembling the heat exchanger, complicated and irregular narrow channels were created. For example, in [
5] and [
6], the authors dealt with heat exchangers and their different geometries. In [
7], the authors presented a comparison of various grids for a plate heat exchanger modelled by a tetrahedral mesh. The influence of oblique waves on the heat transfer surface was investigated in [
8]. Heat transfer in a channel with parallel plates was studied in [
9] using Dissipative Particle Dynamics with energy conservation (eDPD). In [
10], the design of a new plate heat exchanger and its cost were compared to heat exchangers available on the market. The production of heat exchangers (the medium is a liquid) with the use of 3D printing was discussed in [
11]. The heat transfer was modelled by the Boltzmann mesh method. In the report [
12], the application of a quasi 1-D code (Phyton) for the design of heat exchangers was described. The heat transfer was modelled by the balance of thermal energy and by empirical heat transfer correlations. A series of quasi-counter-flow parallel membrane channels was used for the construction of an air dryer in [
13]. In addition, in [
14], a numerical model simulating the operation of a drying system based on a parallel membrane system was considered.
Heat flow and transfer in a recuperative air-to-air counter-flow heat exchanger was studied numerically in [
15]. The results therein indicate that the lowest possible material thickness is crucial for developing the most effective recuperative air-to-air counter-flow heat exchanger with high efficiency and low-pressure losses, the properties of the material itself being irrelevant.
The authors of [
16] demonstrated that larger heat exchangers offer better efficiency and lower pressure drop with the same velocity.
A uniform air stream is very often applied as an inlet boundary condition of a heat exchanger in studies using computational fluid dynamics software. However, in actual applications, the inlet flow conditions are not uniform. The effect of non-uniformities on the thermal performance characterised in a wind tunnel for a commercially available plate water/air heat exchanger was investigated in [
17].
To the authors’ best knowledge, the problem of temperature distribution in time in the heat exchanger plate during the exhaust/supply air has not been the subject of any research yet.
This paper focuses on the heat distribution within an exchanger plate. As the plate is heated/cooled by air, the obtained plate temperatures at the air inlet and outlet correspond to the supply or exhaust air temperatures. The thermal conductivity equation based on Fourier’s law was used to describe the heat flow through the plate. Boundary conditions describing the effect of air on the plate for both heat exchangers were formulated. For the sake of simplicity, the effects associated with air moisture or air contamination were omitted. By applying the Trefftz method, as described in
Section 3, approximate solutions of heat conduction equations for both exchangers were obtained and discussed.
For the calculations, the assumed room temperature was 21 °C, while the outside temperatures were simulated as follows: frosty winter (−19 °C), early spring and later autumn (+1 °C), and hot summer (+31 °C). In [
15], where a recuperative counter-current air-to-air plate heat exchanger was tested numerically using the Fluent software, it was found that the thinnest possible material is crucial for creating the most efficient air-to-air recuperative heat exchanger with low efficiency and low-pressure losses, and the properties of the material itself do not matter. The presented research confirmed the conclusions from the cited paper.
Mathematical description of the heat transfer issues for both types of exchangers is formulated in
Section 2. In
Section 3, the Trefftz method is discussed. An approximation of solutions for both exchangers using a linear combination of the Trefftz function (T-functions) is presented. Moreover, objective functionals are built. Minimization of the functionals leads to a system of algebraic equations for the coefficients of these linear combinations. Calculation results are presented in the form of graphs and tables in
Section 4. In
Section 5, results for both types of exchangers are compared, and further types of counter-flow steel plate exchangers are discussed. The conclusions summarize the results obtained.
2. Formulation of Equations and Conditions for Both Tested Heat Exchangers
A heat exchanger structure is made up of subsequent plate layers separated with successive air layers, which means it is a geometrically repeatable structure (the top and bottom plates are omitted). As a result, in the case of the “supply first from one side, then the other” operation, it is sufficient to take into consideration only one-half of the plate thickness with one-half of the air layer and assume the zeroing heat flux at the plate centreline with respect to y, (comp.
Figure 1). In the case of supply from both sides (over the plate in one direction, and below in the opposite), the entire plate cross-section has to be considered, as shown in
Figure 2. The shorter cross-sectional edges of the exchanger plate are hereinafter referred to as inner or left and outer or right.
Disregarding the heat generated per unit of volume, we get an equation that will constitute a base for the computations, namely, [
18,
19],
where
(K) describes temperature,
is the so-called thermal diffusivity coefficient,
(W/(mK)) is the thermal conductivity coefficient,
ρ (kg/m
3) stands for density,
c (J/(kg K)) is specific heat,
t (s) stands for time, and
is the gradient operator.
The problem is two-dimensional. Spatial coordinates will be denoted as x and y.
Heat exchange between the inner heat exchanger plates and the air supplied by the exchanger can follow two ways.
As mentioned in the Introduction, the heat exchange between the internal plates of the exchanger and the air supplied by the exchanger can take place in two ways: (a) first exhaust from the room, then supply from the outside; (b) simultaneous exhaust above the plate and supply air below it (counter-flow supply).
The air moves between the plates at a speed (m/s). After the time , (l, (m), being the length of the plate), it will reach the opposite end of the plate. The time is very short in relation to the total time of the supply (exhaust) operation; therefore, its potential impact on the thermal process is ignored.
The following dimensionless variables are introduced:
where
α is the heat transfer coefficient.
In both considered exchangers, the heat transfer coefficient
will be different for heat penetration on shorter edges (
and
), where it is assumed that air is immobile, and different on longer edges (
), where it moves at a velocity of
. The coefficient
is defined as falling within a range of 5–37
, [
20]. The relationship between
and laminar flow velocity,
, is determined by the equation [
21,
22].
The kinematic viscosity
for air within a range of –20 to 30 °C changes in the range 11.8 to 16 mm
2/s. For the maximum air velocity,
m/s (parallel to the longer cross-section edge), the Reynolds number
will change within a range of 457 to 338. It means that laminar flow occurs between the plates, because for air flowing over the flat layer (
h = 0.0012 m—air duct height, adopted as plate thickness), the bottom critical Reynolds number is
[
23,
24,
25].
On the shorter plate edges, it is assumed that the air velocity is zero, i.e., the heat transfer coefficient is W/(m2 K). On the longer edges m/s and W/(m2 K), (comp.(2.3), Biot numbers will be accordingly marked with and .
Equation (1) in dimensionless coordinates takes the form
Initial and boundary conditions for variant (a) are presented below. A heat exchanger plate cross-section with marked central surface and boundary conditions when air is exhausted from the room, variant (a1), or from outside, variant (a2), is shown at
Figure 1.
Variant (a1)
Variant (a2)
where
is the end moment of the supply (exhaust) process,
, stands for the end temperature in variant (a1), and
is the initial temperature in the variant (a2);
Variant (b)—counter-flow exchanger (comp.
Figure 2)
The initial condition takes the Equation (5). Boundary conditions are as follows:
4. Computation Results
The following data were adopted for the computations:
°C (room or inside temperature),
°C (outside temperature), 1 °C, 31 °C,
1.2 m (plate section length),
0.0006 m (plate section half height),
0.5 m/s and 4.5 m/s,
,
,
tend = 300 s
(66 T-functions), (, respectively, comp. Equation (19)).
Calculations were conducted for copper, aluminium, and steel. Their thermophysical data are presented in
Table 2. The temperature of plate surface,
, was studied for
and
.
4.1. Results for Variant (a)
For the temperature calculation in variants (a1) and (a2), the objective functionals
and
were used (cf. Equations (21) and (22)). First, the copper plate was considered. The temperature distribution for the case for
°C,
0.5 m/s is presented in
Figure 3 for time is given in seconds and distance in meters.
On the left side in
Figure 3, one can see the initial temperature for air exhaust from the room changing linearly from
°C to
°C, variant (a1). In the same Figure, above the axis describing time
t, one can see a change of the right plate end temperature, from
°C to ca.
°C for air velocity of
0.5 m/s and to ca.
°C, when
4.5 m/s.
When supplying air from the outside into the room, variant (a2), as seen in the graphs on the right side, it can be seen how an air temperature of °C changes, using heat of air exhausting out of the room. At air velocity 0.5 m/s, the right end of the plate cools down after 5 min from ca. °C to ca. °C. At velocity of 4.5 m/s, this temperature changes from °C to °C. In the case of the inlet into the room, with air velocity 0.5 m/s, the air temperature reaches °C after 5 min. For a velocity 4.5 m/s, this value is ca. °C.
For aluminium and steel and for other values of external temperatures, the temperature distributions are similar to those presented in
Figure 3. The temperature values for copper, aluminium, and steel plates are presented in
Table 3.
The analysis of data in
Table 3 indicates that the best plate material is steel, and the air velocity should be around 0.5 m/s, since in the case of such heat transfer combination, the supplied air temperature in high frosts is not too low, and in the case of high positive temperatures, it does not significantly deviate from room temperature. This is indicated by the values in column
(inside) showing that the temperature of the air supplied to the room is relatively highest in frosty winter and lowest in hot summer.
Copper plates give slightly higher temperature values than aluminium plates. However, copper is more expensive than aluminium or steel (steel is USD 1.84/lb, aluminium is USD 2.87/lb, while copper is USD 4.27/lb, [
31,
32]) and is therefore omitted in further discussion concerning the exhaust-supply heat exchanger.
4.2. Results for Variant (b)
For the temperature calculation in variants (b), the objective functional
was used (cf. Equation (23)). The temperature graphs, when air from the room flows above a plate, and the air into the room flows under the plate are shown and discussed below, again, for copper, aluminium, and steel. Plate surface temperature,
, was studied for
and
.
Figure 4 shows an example of the temperature distribution in the plate as a function of time. Since the plate thickness is very small compared to its length, for
and
, its temperature turns out to be virtually the same. As before, the copper plate was considered first.
The temperature distributions for aluminium and steel and for other values of external temperatures are similar to those presented in
Figure 4.
Table 4 focuses on the temperatures for
, since they are lowest in the frosty winter (highest in the hot summer) throughout the entire process of supplying air into the room.
The analysis of data in
Table 4 indicates that the best plate material for the counter-flow heat exchanger is also steel, and the air velocity should be around 0.5 m/s or slightly higher. It should be noted that in the case of severe frosts and at a supply velocity of 0.5 m/s, the plate temperature on the air inlet into the room falls from the initial value of 21 to 13 °C after 300 s, while in the case of high positive temperatures, it increases above 21 °C but does not exceed 23 °C.
Again, copper plates give slightly higher temperature values than aluminium plates. However, for the reasons mentioned above, for counter-flow heat exchangers, copper plates are also omitted in the further discussion.
5. Discussion
The analysis of the results presented in
Section 4 shows that the use of a counter-flow exchanger is a better method of air exchange, and the best material of the heat exchanger plates is steel. This is illustrated in
Table 5. In the case of a counter-flow heat exchanger, the temperature of the air supplied into the room is relatively highest when it is cold outside and lowest when it is hot.
The analysis in
Section 4 was applied to a situation when air transfer inside the room lasted 300 (exhaust) + 300 (supply) seconds or with a counter-flow process lasting 300 s.
Table 6,
Table 7 and
Table 8 show the supply and exhaust temperatures
in exchangers made of 0.8 m, 1.0 m, and 1.2 m long plates, after a heat transfer time of 300, 600, and 900 s, in the counter-flow mode.
As indicated by the data from
Table 6, when the exchanger operation time is 300 s, with plates 0.8 m long and air velocity 0.5 m/s, the temperature difference between air supply in frost conditions and hot weather is about 10.5 degrees, with the outside temperature difference reaching 50 degrees. When high heat transfer velocity (4.5 m/s) takes place, this difference is almost twice as high (ca. 19 degrees).
A longer operation time of the counter-flow plate heat exchanger, at the air velocity of 0.5 m/s, lowers the supply air temperature for x = 0 in severe frosts even to 8.1 °C after 600 s and to 5.4 °C after 900 s. In the case of high supply velocity of 4.5 m/s, the final supply temperatures are significantly lower than for a supply velocity of 0.5 m/s. In addition, the equalization of the supply and exhaust temperature over time on both plate ends is visible.
This indicates that exchangers with 0.8 m long plates should be used at low air flow velocities.
Table 7 indicates that the extension of exchanger plates from 0.8 to 1.0 m slightly increases the supply temperatures in severe frosts. A longer heat exchanger operation time leads to a reduced difference between supply and exhaust temperatures, just like for an exchanger that is 0.8 m long.
Table 8 shows that further extension of exchanger plates improves temperature but only slightly. It follows that the best exchanger plate length is 1 m.
As mentioned in the Introduction, exchangers are built mainly of the weather-resistant aluminium. However, the presented computations indicate that steel would be a material better in terms of heat dissipation when supplying fresh air into a room. It is obvious that a steel plate can be much thinner than that adopted for the purposes of this paper. The presented research shows that the thinner the plate, the less the supply air heats up, although the differences are slight. The differences in the final air temperatures are greater only in severe frosts, as presented in
Table 9.
As can be seen in
Table 9, the final air inlet temperature
, at approximately 1 °C, is lower by ca. 0.5 °C for 0.8 mm thick steel plates than for 150% thicker aluminium plates; however, in the case of air supply during a hot summer day, this difference is only 0.2 °C. Only during a harsh winter, the difference in the final temperatures is ca. 2 °C. Therefore, a heat exchanger with 0.8 mm thick steel plates will exhibit similar performance to a heat exchanger with aluminium plates. It should be noted that it is much cheaper, although it is a little heavier. For steel plates ca 0.4 mm thick, the final air inlet temperatures are less favourable than for aluminium plates that are 1.2 mm thick (almost 5 °C for a harsh winter, more than 2 °C for the spring–autumn period, and approximately 1 °C for a hot summer). However, at the same time, the weight of a heat exchanger made of 0.4 mm thick steel plates is a bit lower than the weight of that made of aluminium plates, and with the exchanger operation time less than 300 s, the final air inlet temperatures will be similar to the temperatures achieved in an aluminium-plate exchanger.
It should be noted that the temperatures achieved for steel plates with a thickness of 0.4 mm and 0.8 mm, and a supply velocity of 0.5 m/s are very similar to temperatures at a supply velocity of 4.5 m/s but for plates that are thicker by 0.4 mm.
As mentioned in the Introduction, exchangers are mainly made of the weather-resistant aluminium. However, the presented computations indicate that steel would be a better material in terms of heat dissipation when supplying fresh air into a room.
Consider the temperature transfer efficiency of aluminium and steel exhaust/supply and counter-flow heat exchangers. The efficiency is calculated from the formula, [
33],
where
stands for supply air temperature, and
and
are outside and room temperature, respectively. The average of
and
for
= 0.5 m/s is taken as
(see
Table 3 for exhaust/supply and
Table 4 for counter-flow exchangers). When comparing the temperature transfer efficiency for the considered heat exchangers, its value is calculated for
°C and
°C. For the counter-flow exchanger, we get
0.825,
0.9, and for the exhaust/supply,
0.7075,
0.815. The advantage of the counter-flow heat exchanger over the exhaust-supply heat exchanger and steel over aluminium is evident. In addition, steel is cheaper than aluminium (steel is USD 1.84/lb, aluminium is USD 2.87/lb). However, steel plate heat exchangers are heavier. The use of thinner steel plates can reduce the weight.
6. Conclusions
The Trefftz functions have been adopted as the baseline for the approximate solution of the problem. As shown in
Table 1, it is sufficient to use the first several dozen T-functions in order to achieve an approximate solution that describes the temperature field in the exchanger plate with adequate accuracy, approximating the fulfilment of the boundary conditions by means of the least squares method.
As could be expected, the plate thickness (1.2 mm) in relation to the length means that although the equation has been solved for x, y, t (dimensionless ξ, η, τ), the results practically depend only on x and t. It follows that the plate section of the heat exchanger can be considered one-dimensional.
The results clearly show how temperature distribution depends on air velocity. It is obvious that lower air velocities are more favourable in terms of recovering heat from the supplied heat that is transferred with the air during extraction. In numerical terms, this is described in
Table 3,
Table 4,
Table 5,
Table 6,
Table 7 and
Table 8.
The presented analysis indicates that counter-flow exchangers are more effective than those operating in the exhaust–supply mode. If we consider plates that are 0.8 m, 1.0 m, and 1.2 m long, their length is of secondary significance; it seems that the best results in relation to the potential production costs are obtained for the length m. The comparison of the three considered materials for the heat exchanger plates shows that steel is the best.
The exchanger operation time is significant to the temperature of air supplied to the room. In the case of cold periods, this time should be shorter. In the case of positive temperatures, the exchanger operation time can be longer, and the computation results indicate that 300 s is the best option.
Air humidity and pollution are not included in the analysis. However, the results obtained with the simplifications applied are in line with the practice of designing and using heat exchangers/recuperators.