The Energy-Saving Potential of Chilled Ceilings Combined with Personalized Ventilation
Abstract
:1. Introduction
2. Materials and Methods
2.1. Zone Description
2.2. Internal Heat Gains and Occupancy
2.3. Simulated Cases
- (1)
- CCPV26-3K–the system maintained a maximum room temperature of 26 °C. The supply air temperature was controlled based on the room air temperature (equal to the return air temperature), as shown in Figure 2. When the room air temperature was less than or equal to 20 °C, the supply air temperature was kept at 20 °C. As the room air temperature increased, the supply air temperature was linearly increased to the design temperature difference of 3 K (between room setpoint temperature and supply air temperature). If the room temperature exceeded 26 °C, then the supply air temperature was kept at 23 °C;
- (2)
- CCPV28-3K–the maximum room temperature was increased to 28 °C with the design supply temperature difference of 3 K. The supply air temperature was controlled in the range from 20 to 25 °C as shown in Figure 2;
- (3)
- CCPV28-6K–the maximum room temperature was 28 °C. The designed temperature difference between room air temperature and supply air temperature was increased to 6 K. The supply air temperature was controlled in the range from 20 to 22 °C as shown in Figure 2.
2.4. Description of HVAC Systems
2.4.1. Chilled Ceiling (CC)
2.4.2. Personalized Ventilation (PV)
2.4.3. CAV and VAV Mixing Ventilation (MV)
2.4.4. Zone Heating
3. Results
3.1. Temperate Climate (Katowice)
3.1.1. Energy Use
3.1.2. Delivered Energy
3.1.3. Thermal Environment Quality in Room
3.2. Hot and Humid Climate (Singapore)
3.2.1. Energy Use
3.2.2. Delivered Energy
3.2.3. Thermal Environment Quality in the Room
3.3. Hot and Dry Climate (Dubai)
3.3.1. Energy Use
3.3.2. Delivered Energy
3.3.3. Thermal Environment Quality in Room
4. Discussion
5. Conclusions
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
Nomenclature
Abbreviations | |
AHU | air handling unit |
CC | chilled ceiling |
CAV | constant air volume |
CTRL | control macro for cooling water temperature of CC |
HVAC | heating, ventilation and air-conditioning |
MV | mixing ventilation |
OT | room temperature control based on operative temperature |
PAQ | perceived air quality |
PV | personalized ventilation |
SBS | sick building syndrome |
VAV | variable air volume |
Symbols | |
A | surface area, m2 |
d | thickness of wall layer, m |
g | solar heat gain coefficient (SHGC) |
q | flow rate, L/s |
RH | relative humidity, % |
T | light transmittance |
Tv | visible light transmittance (VLT) |
ta | air temperature, °C |
to | operative temperature, °C |
tw | cooling water temperature, °C |
U | heat transfer coefficient, W/(m2∙K) |
λ | thermal conductivity, W/(m∙K) |
Subscripts | |
B | pollution source from the building |
P | pollution source from people |
References
- Lipczynska, A.; Kaczmarczyk, J.; Melikov, A.K. Thermal Environment and Air Quality in Office with Personalized Ventilation Combined with Chilled Ceiling. Build. Environ. 2015, 92, 603–614. [Google Scholar] [CrossRef]
- American Society of Heating, Refrigerating and Air-Conditioning Engineers. ANSI/ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy; American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.: Atlanta, GA, USA, 2017. [Google Scholar]
- European Committee for Standardization. EN ISO 7730 Ergonomics of the Thermal Environment—Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria; European Committee for Standardization: Brussels, Belgium, 2005. [Google Scholar]
- European Committee for Standardization. EN 16798-1 Energy Performance of Buildings—Ventilation for Buildings—Part 1: Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics—Module M1-6; European Committee for Standardization: Brussels, Belgium, 2019. [Google Scholar]
- Dalewski, M.; Melikov, A.K.; Vesely, M. Performance of Ductless Personalized Ventilation in Conjunction with Displacement Ventilation: Physical Environment and Human Response. Build. Environ. 2014, 81, 354–364. [Google Scholar] [CrossRef]
- Melikov, A.; Skwarczynski, M.; Kaczmarczyk, J.; Zabecky, J. Use of Personalized Ventilation for Improving Health, Comfort, and Performance at High Room Temperature and Humidity. Indoor Air 2013, 23, 250–263. [Google Scholar] [CrossRef] [PubMed]
- Lipczynska, A.; Kaczmarczyk, J.; Marcol, B.; Melikov, A.K.; Kierat, W. Human Response to Personalized Ventilation Combined with Chilled Ceiling. In Proceedings of the 13th SCANVAC International Conference on Air Distribution in Rooms, São Paulo, Brazil, 19–22 October 2014. [Google Scholar]
- Sekhar, S.; Gong, N.; Tham, K.; Cheong, K.; Melikov, A.; Wyon, D.; Fanger, P. Findings of Personalized Ventilation Studies in a Hot and Humid Climate. HVACR Res. 2005, 11, 603–620. [Google Scholar] [CrossRef]
- Schiavon, S.; Melikov, A.; Sekhar, C. Energy Analysis of the Personalized Ventilation System in Hot and Humid Climates. Energy Build. 2010, 42, 699–707. [Google Scholar] [CrossRef]
- Skwarczyński, M. Impact of Personalized Ventilation on Perceived Indoor Environmental Quality, Work Performance and Energy Consumption. Ph.D. Thesis, Lublin University of Technology, Lublin, Poland, 2012. [Google Scholar]
- Schiavon, S.; Melikov, A. Energy-Saving Strategies with Personalized Ventilation in Cold Climates. Energy Build. 2009, 41, 543–550. [Google Scholar] [CrossRef] [Green Version]
- Novoselac, A.; Srebric, J. A Critical Review on the Performance and Design of Combined Cooled Ceiling and Displacement Ventilation Systems. Energy Build. 2002, 34, 497–509. [Google Scholar] [CrossRef]
- Bahman, A.; Saade, R.; Chakroun, W.; Ghali, K.; Ghaddar, N. Performance Comparison of Conventional and Chilled Ceiling/Displacement Ventilation Systems in Kuwait. Ashrae Trans. 2009, 115 Pt 1, 587–594. [Google Scholar]
- Chakroun, W.; Ghali, K.; Ghaddar, N. Energy Saving Using Mixed Air in Rooms Conditioned by Chilled Ceiling Displacement Ventilation System. Ashrae Trans. 2011, 117 Pt 2, 67–75. [Google Scholar]
- Chakroun, W.; Ghali, K.; Ghaddar, N. Air Quality in Rooms Conditioned by Chilled Ceiling and Mixed Displacement Ventilation for Energy Saving. Energy Build. 2011, 43, 2684–2695. [Google Scholar] [CrossRef]
- Chakroun, W.; Ghaddar, N.; Ghali, K. Chilled Ceiling and Displacement Ventilation Aided with Personalized Evaporative Cooler. Energy Build. 2011, 43, 3250–3257. [Google Scholar] [CrossRef]
- Niu, J.; Zhang, L.; Zuo, H. Energy Savings Potential of Chilled-Ceiling Combined with Desiccant Cooling in Hot and Humid Climates. Energy Build. 2002, 34, 487–495. [Google Scholar] [CrossRef]
- Niu, J.; Kooki, J.; Ree, H. Energy Savings Possibilities with Cooled-Ceiling Systems. Energy Build. 1995, 23, 147–158. [Google Scholar] [CrossRef]
- Sodec, F. Economic Viability of Cooling Ceiling Systems. Energy Build. 1999, 30, 195–201. [Google Scholar] [CrossRef]
- Liu, S.; Schulz, U.W.; Sapar, M.H.; Qian, S. Evaluation of the Environmental Performance of the Chilled Ceiling System Using Life Cycle Assessment (LCA): A Case Study in Singapore. Build. Environ. 2016, 102, 207–216. [Google Scholar] [CrossRef]
- Tian, Z.; Love, J. Energy Performance Optimization of Radiant Slab Cooling Using Building Simulation and Field Measurements. Energy Build. 2009, 41, 320–330. [Google Scholar] [CrossRef]
- Talami, R.; Jakubiec, J.A. Early-Design Sensitivity of Radiant Cooled Office Buildings in the Tropics for Building Performance. Energy Build. 2020, 223, 110177. [Google Scholar] [CrossRef]
- Bauman, F.; Feng, J.; Schiavon, S. Cooling Load Calculations for Radiant Systems Are They the Same as Traditional Methods? ASHRAE J. 2013, 55, 20–27. [Google Scholar]
- Feng, J.; Bauman, F.; Schiavon, S. Experimental Comparison of Zone Cooling Load between Radiant and Air Systems. Energy Build. 2014, 84, 152–159. [Google Scholar] [CrossRef] [Green Version]
- Ghaddar, N.; Ghali, K.; Saadeh, R.; Keblawi, A. Ashrae Design Charts for Combined Chilled Ceiling Displacement Ventilation System. ASHRAE Trans. 2008, 114, 574–587. [Google Scholar]
- Kropf, S.; Zweifel, G. Validation of the Building Simulation Program IDA-ICE According to CEN 13791 “Thermal Performance of Buildings–Calculation of Internal Temperatures of a Room in Summer Without Mechanical Cooling–General Criteria and Validation Procedures”; Hochschule Technik + Architektur Luzern, HLK Engineering: Horw, Switzerland, 2001. [Google Scholar]
- EQUA. Validation of IDA Indoor Climate and Energy 4.0 with Respect to CEN Standards EN 15255-2007 and EN 15265-2007; EQUA: Solna, Sweden, 2010. [Google Scholar]
- EQUA. Validation of IDA Indoor Climate and Energy 4.0 Build 4 with Respect to ANSI/ASHRAE Standard 140-2004; EQUA: Solna, Sweden, 2010. [Google Scholar]
- Achermann, M.; Zweifel, G. RADTEST—Radiant Heating and Cooling Test Cases. A Report of Task 22, Subtask C, Building Energy Analysis Tools Comparative Evaluation Tests; International Energy Agency: Paris, France, 2003. [Google Scholar]
- International Energy Agency. Empirical Validation of EDF ETNA and GENEC Test-Cell Models. A Report of Task 22 Building Energy Analysis Tools; International Energy Agency: Paris, France, 1999. [Google Scholar]
- Bring, A.; Sahlin, P.; Vuolle, M. Models for Building Indoor Climate and Energy Simulation. A Report of Task 22 Building Energy Analysis Tools; International Energy Agency: Paris, France, 1999. [Google Scholar]
- Cornaro, C.; Pierro, M.; Roncarati, D.; Puggioni, V. Validation of a PCM Simulation Tool in IDA ICE Dynamic Building Simulation Software Using Experimental Data from Solar Test Boxes. In Proceedings of the Building Simulation Applications BSA 2017, Bolzano, Italy, 8–10 February 2017. [Google Scholar]
- Salvalai, G. Implementation and Validation of Simplified Heat Pump Model in IDA-ICE Energy Simulation Environment. Energy Build. 2012, 49, 132–141. [Google Scholar] [CrossRef]
- Hilliaho, K.; Lahdensivu, J.; Vinha, J. Glazed Space Thermal Simulation with IDA-ICE 4.61 Software—Suitability Analysis with Case Study. Energy Build. 2015, 89, 132–141. [Google Scholar] [CrossRef]
- Kaczmarczyk, J.; Melikov, A.; Fanger, P. Human Response to Personalized Ventilation and Mixing Ventilation. Indoor Air 2004, 14, 17–29. [Google Scholar] [CrossRef]
- Melikov, A.; Knudsen, G. Human Response to an Individually Controlled Microenvironment. HVACR Res. 2007, 13, 645–660. [Google Scholar] [CrossRef]
- Humphreys, M.A.; Nicol, J.F. The Validity of ISO-PMV for Predicting Comfort Votes in Every-Day Thermal Environments. Energy Build. 2002, 34, 667–684. [Google Scholar] [CrossRef]
- Humphreys, M.A.; Hancock, M. Do People like to Feel ‘Neutral’?: Exploring the Variation of the Desired Thermal Sensation on the ASHRAE Scale. Energy Build. 2007, 39, 867–874. [Google Scholar] [CrossRef]
Building Envelope | Area (m2) | U (W/(m2∙K)) | U∙A (W/K) | % of Total |
---|---|---|---|---|
Wall: gypsum d = 0.026 m; λ = 0.220 W/(m∙K) concrete d = 0.150 m; λ = 1.700 W/(m∙K) light insulation d = 0.180 m; λ = 0.036 W/(m∙K) concrete d = 0.080 m; λ = 1.700 W/(m∙K) gypsum d = 0.026 m; λ = 0.220 W/(m∙K) | 5.82 | 0.18 | 1.05 | 11.36 |
Windows: glazing: Pilkington Insulight 6-15Ar-S(3)4 (2-glass) with outer glass Optifloat Clear, cavity width 15 mm argon, inner glass Pilkington Optitherm S3. g = 0.59, T = 0.52, Tv = 0.79, U = 1.1 W/(m2∙K) frame: U = 2.0 W/(m2∙K) | 6.36 | 1.19 | 7.57 | 81.85 |
Thermal bridges | 0.63 | 6.79 | ||
Total | 12.18 | 0.76 | 9.25 | 100.00 |
Case | Room Temperature | Ventilation System | Room Cooling Units | Window Shading Blinds | |||
---|---|---|---|---|---|---|---|
Setpoints | Control Sensor | Type | Supply Airflows | Type | Supervisory Control | ||
VAV | Min.: 20 °C Max.: 26 °C | ta | VAV MV const. 16°C | Minimum: qB = 12 L/s or qB + 2∙qP = 26 L/s (during occupancy) Maximum: depending on the cooling demand | - | - | None |
VAV (ext blind) | External horizontal | ||||||
VAV (int blind) | Internal vertical | ||||||
CCMV | Min.: 20 °C Max.: 26 °C | ta | CAV MV const. 16 °C | Constant: qB = 12 L/s At occupied hours: qB + 2∙qP = 26 L/s | CC 1700 W | None | None |
CCMV Ctrl | ta | Dew-point | None | ||||
CCMV Ctrl OT | to | Dew-point | None | ||||
CCMV Ctrl (ext blind) | ta | Dew-point | External horizontal | ||||
CCMV Ctrl (int blind) | ta | Dew-point | Internal vertical | ||||
CCPV26-3K | Min.: 20 °C Max.: 26 °C | ta | PV Δt = 3 K | Constant: qB = 12 L/s Additional due to occupancy: qP = 7 L/s per person when present | CC 1700 W | None | None |
CCPV26-3K Ctrl | ta | Dew-point | None | ||||
CCPV26-3K Ctrl OT | to | Dew-point | None | ||||
CCPV26-3K Ctrl (ext blind) | ta | Dew-point | External horizontal | ||||
CCPV26-3K Ctrl (int blind) | ta | Dew-point | Internal vertical | ||||
CCPV28-3K | Min.: 20 °C Max.: 28 °C | ta | PV Δt = 3 K | Constant: qB = 12 L/s Additional due to occupancy: qP = 7 L/s per person when present | CC 1700 W | None | None |
CCPV28-3K Ctrl | ta | Dew-point | None | ||||
CCPV28-3K Ctrl OT | to | Dew-point | None | ||||
CCPV28-3K Ctrl (ext blind) | ta | Dew-point | External horizontal | ||||
CCPV28-3K Ctrl (int blind) | ta | Dew-point | Internal vertical | ||||
CCPV28-6K | Min.: 20 °C Max.: 28 °C | ta | PV Δt = 6 K | Constant: qB = 12 L/s Additional due to occupancy: qP = 7 L/s per person when present | CC 1700 W | None | None |
CCPV28-6K Ctrl | ta | Dew-point | None | ||||
CCPV28-6K Ctrl OT | to | Dew-point | None | ||||
CCPV28-6K Ctrl (ext blind) | ta | Dew-point | External horizontal | ||||
CCPV28-6K Ctrl (int blind) | ta | Dew-point | Internal vertical |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Lipczynska, A.; Kaczmarczyk, J.; Melikov, A. The Energy-Saving Potential of Chilled Ceilings Combined with Personalized Ventilation. Energies 2021, 14, 1133. https://doi.org/10.3390/en14041133
Lipczynska A, Kaczmarczyk J, Melikov A. The Energy-Saving Potential of Chilled Ceilings Combined with Personalized Ventilation. Energies. 2021; 14(4):1133. https://doi.org/10.3390/en14041133
Chicago/Turabian StyleLipczynska, Aleksandra, Jan Kaczmarczyk, and Arsen Melikov. 2021. "The Energy-Saving Potential of Chilled Ceilings Combined with Personalized Ventilation" Energies 14, no. 4: 1133. https://doi.org/10.3390/en14041133
APA StyleLipczynska, A., Kaczmarczyk, J., & Melikov, A. (2021). The Energy-Saving Potential of Chilled Ceilings Combined with Personalized Ventilation. Energies, 14(4), 1133. https://doi.org/10.3390/en14041133