Next Article in Journal
Evaluation of Lost Circulation Material Sealing for Geothermal Drilling
Previous Article in Journal
Second-Order Sliding-Mode Control Applied to Microgrids: DC & AC Buck Converters Powering Constant Power Loads
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Multi-Aspect Shaping of the Building’s Heat Balance

by
Aleksander Starakiewicz
1,
Przemysław Miąsik
1,
Joanna Krasoń
1,* and
Bożena Babiarz
2,*
1
Department of Building Engineering, The Faculty of Civil and Environmental Engineering and Architecture, Rzeszow University of Technology, Powstancow Warszawy Street 12, 35-959 Rzeszow, Poland
2
Department of Heat Engineering and Air Conditioning, The Faculty of Civil and Environmental Engineering and Architecture, Rzeszow University of Technology, Powstancow Warszawy Street 12, 35-959 Rzeszow, Poland
*
Authors to whom correspondence should be addressed.
Energies 2024, 17(11), 2702; https://doi.org/10.3390/en17112702
Submission received: 19 April 2024 / Revised: 24 May 2024 / Accepted: 30 May 2024 / Published: 2 June 2024
(This article belongs to the Special Issue Recent Developments in Heat Transfer: Towards Climate Neutrality)

Abstract

:
In the European Union, buildings account for 42% of the energy consumption and 36% of the direct and indirect energy-related greenhouse gas emissions. Reducing thermal power for heating purposes is crucial to achieve climate neutrality. The main purpose of this article is to identify the places in the building where it is possible to significantly improve energy efficiency through the use of appropriate construction and material solutions. This article contains a multi-aspect approach to the heat balance of a building. Solutions that have a direct impact on building energy consumption were analysed, taking into account architectural, technological, and material aspects. Particular attention was paid to energy-efficient design and material solutions for non-transparent and transparent external walls and thermal storage walls (Trombe walls). An analysis of heat transfer through building elements was carried out, along with the optimisation of energy-efficient solutions for non-transparent and transparent barriers. Two methods for determining the equivalent heat transfer coefficient Ue for solar active partitions are presented. The analysis presented in the work using the original method of the balanced heat transfer coefficient Ue is a testing ground for identifying unfavourable features of the building structure, as well as the most energy-efficient solutions that can be used in establishing standards for the construction and modernisation of buildings. The value of the Ue coefficient illustrates the actual heat transfer through the partition. Having Ue values for various structural solutions of building envelopes, the designer can easily select the most effective ones. The use of the presented methodology will allow for the optimisation of technical solutions for building elements to improve its energy efficiency.

1. Introduction

Energy efficiency measures in buildings are a priority to save energy and achieve zero emission and fully decarbonised buildings by 2050. In the European Union, 85% of buildings were built before 2000 and of these, 75% have poor energy performance. Buildings account for 42% of the energy consumed in the EU in 2021 and 36% of direct and indirect energy-related greenhouse gas emissions [1,2]. The burning of fossil fuels also causes air pollution, which has a negative impact on human health both directly, by penetrating the body and causing allergies and lung diseases, and indirectly, by being a carrier of heavy metals, microorganisms, and bacteria. The Directive 2008/50/CE of the European Union [3] determines the maximum daily allowed concentration of air pollutions. Therefore, it is important to monitor both the concentrations of pollutants in the air and to effectively control the amounts of pollutants emitted [4].
Every person living in a single-family or multifamily residential building has similar expectations about their property, primarily in terms of ensuring thermal comfort inside the apartment throughout the year and incurring minimal costs related to its operation [5,6]. Meeting these expectations is related to the issues taken into account when designing energy-sustainable buildings [7].
The energy efficiency of a building directly affects the level of energy consumption for various purposes, such as heating and cooling [8,9,10,11], preparation of domestic hot water [12], ventilation [13], and lighting. An effective way of using energy for these purposes should be implemented while ensuring the comfort of use of people staying in the building. Energy consumption depends on many external factors, such as climatic conditions, the method of using solar energy, etc. The applied construction and material solutions of building partitions also play an important role, affecting the dynamics of heat transfer [14] and the types and functioning of energy saving installations in the building, as well as the appropriate management of the heat supply [15].
The use of solar energy in a building depends, among others, on its location and terrain [16,17]. Flat land is a so-called neutral area for the location of a building, and is often devoid of many advantages, including diverse topography, occurrence of natural water reservoirs, and vegetation. Attractive areas in terms of construction include areas with a diversified topography, hills, and slopes towards the greatest amount of sunlight. The location of the building on the plot should be in its northern part. High greenery should be located on the north side and in the most frequently blowing winds, to protect the building against additional air infiltration and heat loss. The façade of the building with the largest area of transparent vertical partitions should be towards the south or with a slight deviation towards the east or west, and the building should not be shaded [18]. The least convenient location for plots is on northern slopes, on the tops of hills, in valleys, and with trees on the south side or around the building. In practice, there are many factors that prevent the selection of the optimal location. These include existing underground and above-ground infrastructure, buildings, and greenery in neighbouring plots.
The shape of the building also has an impact on its energy consumption [19]. When considering the shape of the building in terms of reducing heat losses, the shape of the building should be compact [20], similar to a cube or a hemisphere. If it is a rectangular building, the longer side of the building should face the greatest amount of sunlight [21]. The building should have the largest possible heated volume V with the smallest possible partition area limiting this volume A. Therefore, the shape factor of the building (A/V) should be as low as possible. A fragmented-shape building causes an increase value in the shape factor and, consequently, greater heat losses. Each fragmented building form (L-, T-, U-, E-shaped buildings; terraces above rooms; arcades) will generate higher heat losses throughout the life of the building compared to a compact shape. Buildings with an optimal shape are, for example, those built by the Eskimos (igloos).
Another factor influencing energy consumption is the functional arrangement of rooms [20]. It is considered in terms of its location in relation to the cardinal directions and the adjustment of the layout of the room in terms of internal temperature [22]. The rooms with the highest expected temperatures are mainly located on the eastern, southern, and western sides. The north side should generally be treated as a thermal buffer, where rooms with the lowest temperatures should be located. An example of room layout is shown in Figure 1.
The structural and material solutions of the building partitions also have a significant impact on the energy consumption of the building [23]. This mainly depends on the thermal insulation of the external elements of the heated zone of the building [24] and the related heat loss coefficient through penetration and ventilation H [W/K] of the entire building. The thickness of the thermal insulation of building envelopes has an impact on reducing energy demand, heating costs, and harmful emissions, as well as parameters that influence the thermal comfort of rooms [25]. Furthermore, to maintain their high insulation, building partitions should be operated continuously under dry conditions so that mould does not develop on their surface and condensation does not occur in the volume of the partition [26].
In addition to the appropriate insulation of external partitions, the structure of the wall itself also plays an important role. Increasing the capacity to accumulate heat, for example, in the masonry layer, stabilises the indoor air temperature and improves thermal comfort [27]. In the case of large glazing areas in the building, a massive partition during the transition period may contribute to reducing the heating demand in the building by approximately 40% [23].
When trying to reduce heat losses in a building, solutions in the form of passive solar systems integrated into the building envelope should be considered, along with highly insulating partitions. One of such solutions are various types of Trombe walls [28]. The use of solutions that use solar energy allows for an increase in heat gains, which in turn has a positive effect on the overall heating balance of the building [29].
To achieve a high level of energy efficiency in a building, at least several energy-saving solutions should be used, both in the architectural, construction, and installation areas. If all possible solutions are used, it is possible to achieve the highest level of energy efficiency, i.e., a building with a zero energy balance [10] or an energy-plus building, i.e., a building that generates more energy than it needs.
The purpose of this article is to present the possibilities of using various technological and material solutions for building partitions, which can have a positive impact on the thermal balance of the building, justifying their choice in the design and construction stage of the building.

2. Trends in the Changes in Thermal Insulation of Buildings

Changes in the thermal insulation of building envelopes in the European Union have evolved over the years. In Poland, the first requirements regarding thermal insulation of non-transparent building partitions were published on 1 July 1958. They underwent subsequent transformations, introducing increasingly higher requirements for thermal insulation for external building partitions. The history of subsequent legal acts regarding the heat transfer coefficient is presented in Table 1.

3. Analysis of Heat Loss for Traditional Structures

The currently applicable requirements (Table 1) with respect to partition insulation seem to be insufficient to meet the purpose of climate neutrality. This necessitates the search for other solutions for the construction of energy-efficient partitions that have a positive impact on the building’s heat balance.
This article focuses on a comparative analysis of masonry wall solutions. When designing the wall structure, the following is used: single-layer wall (L1); two-layer wall (L2); three-layer wall (L3). These structures are shown in Figure 2.
Each of these structures will generate different types of thermal bridges at the junction of the building partitions. Each thermal bridge of a given type has a specific value of the linear heat transfer coefficient Ψ [31]. Therefore, in the building envelope there is a total heat loss coefficient through penetration Htr [W/K], which is the sum of two coefficients: through flat elements Htr,1 [W/K] and through linear thermal bridges Htr,2 [W/K]. The values of the total coefficient of heat loss coefficient through penetration Htr for an exemplary single-family building, depending on the insulation of the partitions and the type of external wall construction (L1L3), are presented in Table 2 and Table 3. The tables show how the values of the heat loss coefficient change by penetration and what percentage of this coefficient is thermal bridges.
For the calculations, a single-family, two-story building with a basement and a flat roof with an attic was assumed. The external dimensions for the heated zone of the building are as follows: length 10.5 m, width 9.0 m, and height 5.75 m. The temperature reduction coefficient for the ceiling above the basement was assumed to be btr = 0.6.
Attention is drawn to the two-layer structure of the external wall, which generates the lowest values of thermal bridges and, as a result, the lowest values of the total heat loss coefficient through penetration Htr for the building.
In addition to the values for external walls, Table 2 and Table 3 include the values of the heat loss coefficient through penetration for the ceiling of the top floor and the flat roof. For technological reasons, these elements do not pose any major problems due to the thickness of the thermal insulation being installed and its type. Due to the natural upward flow of warm air, they require the thickest thermal insulation in the group of external partitions. In these partitions, it is worth using thermal insulation that is thicker than the standard requirements. Ceilings above the ground floor (basement) should have very good thermal insulation due to the differences in temperature between heated and unheated rooms.

4. Analysis of Passive Solar Systems

4.1. Transparent Partitions

The most important elements of a transparent partition include the type of material and the shape of the window frame profile, the type of insulating glass, and the type of spacer frame. The shape and division of the window itself should be taken into account during the building design process.
The thermal efficiency of the windows was assessed by the following:
  • Value of the window’s heat transfer coefficient Uw—estimation of heat loss through the window;
  • Equivalent window heat transfer coefficient Ue—estimation of the window’s potential heat balance.
In the first case, the calculation parameters are heat transfer coefficients of the cooperating elements of the window frame Uf and glass Ug, linear heat transfer coefficients (Ψg) and geometric dimensions (area, visible circumference of the glass in the window) of the structural elements. Depending on the profile of the window frame, the Uf coefficient varies in the range from 0.7 to 3.7 W/(m2K), for insulated glass, the Ug values range from 0.3 to 3.0 W/(m2K), while for thermal bridges at the profile–glass connection, the linear heat transfer coefficient Ψg varies from 0.024 to 0.2 W/(mK).
In the second case, the basis for the evaluation is the window heat balance, where the main calculation parameters are climatic data (Te, Ii); glass coefficient Cg ranging from 0.25 to 0.75 [-]; shading coefficient Z ranging from 0.45 to 1.0 [-]; transmittance coefficient of total solar radiation of insulating glass g varying in the range from 0.08 to 0.85 [-].
One of the principles of window design is the design of window surfaces in a building, which determines the minimum and maximum of their surface, the principle of “standard guidelines” [30]. This is the basic principle of window design in terms of size and number. Another principle of window design, based on heat balance and “standard guidelines”, is the “effective window selection method”. It allows you to select windows with the highest thermal efficiency for a given area and structure. The most favourable parameters are sought, such as the following:
  • Glazing coefficient;
  • Type of window profile;
  • Type of insulating glass;
  • Type of spacer frame.
The Cg values are significantly dependent on the type of window construction (number of sashes) and its surface. The Cg values for the available catalogue windows are summarised in Figure 3.
The influence of the spacer frame on the value of the heat transfer coefficient Uw of the windows is shown in Figure 4 and Figure 5. A significant reduction in the Uw value is visible when using a “warm” frame with a coefficient of Ψg = 0.03 compared to a classic frame with Ψg = 0.08.

4.2. Thermal Storage Walls (TSWs)

The thermal storage wall (Trombe wall) combines the functions of a collector (glazing) and heat accumulation (storage wall), creating a whole [32]. There are various material solutions for these elements for the thermal storage wall. The classic “solar wall” is a construction without any additional elements of heat distribution and regulation. The structure of the partition is shown in Figure 6. The collector consists of glazing, a frame, and an air void. The absorber is usually black external plaster and the structural wall is usually made of massive elements that allow for heat accumulation.
The parameters of the glazing and window profile in the collector affect the thermal efficiency of the Trombe wall and make it possible to determine an important value, which is the “collector parameter”—B. The analysis included two window profiles that have the following parameters:
  • Classic profile Bclasic: Uf = 1.6 W/(m2K), spacer with Ψg = 0.08 W/(mK);
  • Passive profile Bpassive: Uf = 0.79 W/(m2K), spacer frame with Ψg = 0.03 W/(mK).
The collector parameter B was calculated according to the following formulas:
B = a · g · C g · Z · R p + 1 U k o l R s i
U c o l = A g · U g + A f · U f + l g Ψ g A g + A f = C g · U g + 1 C g · U f + l g Ψ g A g + A f
C g = A g A g + A f
where:
a—absorption coefficient of the surface of the outer wall (absorber) [-] for which the value of 0.9 was assumed;
g—coefficient of solar radiation transmission through the glazing [-];
Cg—collector glass factor [-] for which the calculated value is 0.766;
Z—partition shading factor [-] for which the value is 1.0;
Rp—thermal resistance of the unventilated air layer (between the absorber and the glazing) (Table 2 in [33]) [m2K/W], assumed for a layer with a thickness of 3 cm;
Rsi—heat transfer resistance on the inner surface of the partition (Table 1 in [33]) [m2K/W];
Ucol—collector heat transfer coefficient, (calculated for a window according to [34] [W/(m2K)];
Ug—heat transfer coefficient of the glass in the collector [W/(m2K)];
Uf—heat transfer coefficient of the collector frame [W/(m2K)];
Ψg—linear heat transfer coefficient resulting from the combined thermal effects of the glass, the spacer frame, and the collector frame [W/(mK)];
Ag—surface area of glass in the collector [m2] with a calculated value of 2.934 m2;
Af—surface area of the collector frame [m2] with a calculated value of 0.896 m2;
lg—visible circumference of the collector glass at a given mating element [m] with a calculated value of 16.82 m.
Depending on the type of window profile and glazing, Table 4 presents the obtained values of the “collector parameter” B.
The higher the value of the collector parameter B, the more favourable it is for the TSW balance. It is visible that the passive profile is more energy-efficient than the classic profile for each of the analysed types of glazing (S1–S9).

5. Equivalent Heat Transfer Coefficient as a Measure of the Energy Efficiency of Passive Solar Systems

The thermal efficiency of a solar partition (passive system) determines how much thermal energy penetrates a specific surface, with a given thermal forcing in a specific time period. In conventional partitions, the heat flow flows towards a lower temperature and the thermal efficiency of this partition is equivalent to its thermal insulation and is usually expressed as the value of the heat transfer coefficient U.
In partitions using solar radiation energy, the direction of heat flow is variable, and depending on the thermal forcing, it may be directed outside or inside the room. The thermal efficiency of these partitions can be based on their heat balance QH, i.e., the difference between heat losses QT and heat gains Qsol, or expressed by the value of the equivalent heat transfer coefficient Ue. When preparing the energy characteristics of a building, it is important to know the heat gains and losses through such a partition.
The classically reported U value for the partitions only shows the amount of potential heat loss through the partition. The value of the Ue coefficient shows the actual heat flow through the partition (it takes into account both heat gains and losses). Based on the Ue coefficient values calculated for various configurations of building partitions, the designer can easily select the most effective ones under specific conditions.

5.1. Equivalent Heat Transfer Coefficient of the Window

The equivalent window heat transfer coefficient Ue [W/(m2K)] was calculated on the basis of three parameters: window heat transfer coefficient Uw; heating index Aind; and window efficiency parameter C, according to Equation (4):
U e m = U W A i n d , i ( m ) · C
The value of the helium heating index Aind,i was defined as the monthly sum of total solar radiation falling on the vertical plane with i-th orientation Ii divided by the number of degree hours of the month. The window efficiency parameter C is determined based on Equation (5):
C = g · C g · Z
where:
  • g—total solar energy transmittance factor [-];
  • Cg—glazing coefficient [-];
  • Z—shading coefficient [-].
Example values of the equivalent heat transfer coefficient Ue of three-leaf windows in the heating season (from 26 September to 5 May—222 days) for a typical meteorological year (TMY), for the Rzeszów-Jasionka meteorological station, are presented in Table 5. The windows are designed with elements with the following parameters: passive profile with Uf = 0.79 W/(m2K), double-chamber glass unit (S7) with Ug = 0.7 W/(m2K), spacer frame (so-called “warm edge”) with Ψg = 0.03 W/(mK), shading coefficient Z = 1.0, total solar energy transmittance factor g = 0.62.
Figure 7 shows the equivalent heat transfer coefficient Ue of a three-sash window (OW5) throughout the year for four orientations to the cardinal directions. Ue values were obtained on the basis of the adopted TMY.
As shown in Table 5 and Figure 7 Ue, they are lower than the Uw values of the windows presented in each month and for each orientation. The graph shows how the value of this coefficient changes each month in a given orientation. They take positive and negative values. Positive values mean that heat losses predominate over heat gains. However, negative values mean that heat gains prevail over heat losses.

5.2. Equivalent Heat Transfer Coefficient of the Thermal Storage Partition (Trombe Walls)

The equivalent heat transfer coefficient of the thermal storage wall Ue,TSW [W/m2K] was calculated on the basis of three parameters: heat transfer coefficient of the thermal storage wall UTSW; helioheating index; Aind and collector parameter B, according to Equation (6):
U e , T S W = U T S W · 1 A i n d , i · B W m 2 · K ,
where
U T S W = 1 R T = 1 R s i + R λ + R p + R k o l + R s e W m 2 · K
  • RT—total heat transfer resistance of the partition [m2K/W];
  • ΣRλ—sum of thermal resistances of homogeneous layers [m2K/W];
  • Rp—thermal resistance of the unventilated air layer (between the absorber and the glazing) [m2K/W];
  • Rkol—collector thermal resistance [m2K/W];
  • Rsi, Rse—heat transfer resistances on the inner and outer surfaces of the partition, respectively [m2K/W].
The equivalent heat transfer coefficient Ue,N [W/m2K] of north-orientated collector-storage partitions in December for TMY, for the city of Rzeszów, is presented in Table 6. Calculations were made for a masonry layer designed from various materials (M1–M7), which serves as a storage layer and for various insulating glass units S1–S9 (Table 4) placed in the collector. A collector made of the Bpassive profile was assumed for the calculations. The values of the equivalent heat transfer coefficient, lower than the current requirements for the heat transfer coefficient for external walls Umax ≤ 0.2 W/m2K, are marked in bold.
Table 6 assumes a modified ceramic block filled with two layers of phase change material (PCM) on the outside environment side and two layers of mineral wool on the inner environment side [35]. Using wall solutions modified with phase change materials, attention should be paid to their thermal safety. The main advantage of PCM is the improvement in the thermal stability of modified structural solutions. The disadvantage of these materials is their flammability; therefore, in future practical solutions, the phase change material should be modified using flame-retardant additives [36]. The bold values of the Ue,TSW coefficient presented in Table 6 are lower than the current requirements for the external wall heat transfer coefficient in Poland [30].
The values of the equivalent heat transfer coefficient Ue,TSW throughout the year for the eastern orientation Ue,TSW,E, southern Ue,TSW,S, western Ue,TSW,W, and northern Ue,TSW,N are presented in Table 7. Table 4 shows the profile adopted in the passive collector analysis (Bpassive), the accumulation layer made of concrete (M1), and the S9 insulating glass.
The vast majority of the values of the equivalent heat transfer coefficient Ue presented in Table 7 (87.5%) are negative, which means that heat gains prevail over heat losses in this partition (negative heat balance). The M1 material taken for the analysis is the most unfavourable material in terms of thermal insulation compared to all other materials (M2–M7). Each of the other materials analysed (M2–M7) achieves a more favourable heat balance than M1. Traditional building partition designs, even with the highest thermal insulation, generate only heat losses (positive heat balance).

6. Conclusions

Based on the analysis, the following conclusions were formulated:
  • An important task when constructing a building is the appropriate location and orientation on the plot. A “location study” of the building on the plot should be carried out in terms of the use of solar energy by the constructed facility.
  • The high insulation of the building partitions guarantees low heat losses through penetration during the building’s operation period. A passive building has the lowest value of the heat transfer coefficient through flat elements (Htr,1 = 57.66 W/K) and is more than 36% lower compared to a building with current thermal insulation requirements (U ≤ 0.2 W/m2K).
  • The optimal technological solution for external partitions is a two-layer structure (L2). Joints (nodes) of various building partitions generate the lowest value of the heat transfer coefficient through thermal bridges Htr,2 compared to single-layer (L1) and three-layer (L3) structures. For this structure, the share of thermal bridges in the total heat transfer coefficient Htr is 19.6%.
  • The connections of building partitions should be designed to eliminate thermal bridges to the greatest extent possible (the nodes should be as technologically simple as possible). In a passive building, thermal bridges only constitute 1.4% of the total thermal transfer coefficient of the building.
  • The windows in the building (regardless of the type of profile and the number of sashes) should have the highest possible values of the glazing coefficient Cg (recommended above 0.6).
  • The window heat transfer coefficient Uw is shaped by three heat transfer coefficients: the window profile Uf, the glass Ug, and the linear heat transfer coefficient Ψg. Each of these coefficients should have the lowest possible values in its category.
  • The values of the heat transfer coefficient of windows Uw are inversely proportional to their surface area. The greatest impact on reducing the Uw coefficient (approx. 15%) has the so-called warm spacers in insulating glass (parameter Ψg) compared to commonly used aluminium frames.
  • The thermal efficiency of windows (based on their heat balance) is determined by the so-called equivalent to the heat transfer coefficient Ue. This coefficient is always lower than the heat transfer coefficient of the window Uw. With appropriately selected parameters of the insulating glass (low glass heat transfer coefficient Ug and high total solar energy transmittance factor g) and the geographical orientation of the window, in many months of the year, the Ue coefficient becomes negative, which means that heat gains through the window are greater than heat losses.
  • An energy-efficient solution for the external walls of a building is thermal storage walls. The equivalent heat transfer coefficient of these partitions Ue is always lower than their heat transfer coefficient UTSW. With appropriately selected parameters of collector B and the material of the accumulating layer, in all months of the year, the Ue coefficient can obtain values lower than Umax = 0.2 W/m2K for external walls, and in many months of the year, the Ue coefficient reaches favourable values.
  • The author’s method of assessing the energy efficiency of partitions presented in the work based on the equivalent heat transfer coefficient allows for shaping the thermal balance of the building in any combination of construction and material solutions. The method can be used to optimise elements of the building structure to improve the heat balance.
  • The use of the presented methodology for calculating the equivalent heat transfer coefficient Ue in practice will allow for the optimisation of technical solutions of building elements to improve their energy efficiency.

Author Contributions

Conceptualisation, A.S., J.K., P.M. and B.B.; methodology, A.S. and B.B.; formal analysis, A.S., J.K., P.M. and B.B.; writing—original draft preparation, A.S.; writing—review and editing, A.S., J.K., P.M. and B.B.; visualisation, J.K. and P.M.; supervision, A.S. and B.B.; project administration, A.S., J.K., P.M. and B.B.; funding acquisition, B.B. All authors have read and agreed to the published version of the manuscript.

Funding

The research leading to these results has received funding from the commissioned task entitled “VIA CARPATIA Universities of Technology Network named after the President of the Republic of Poland Lech Kaczyński” under the special purpose grant from the Minister of Science, contract no. MEiN/2022/DPI/2578 action entitled “ISKRA—building inter-university research teams”.

Data Availability Statement

Data is contained within the article.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Directive (EU) 2023/1791 of the European Parliament and of the Council of 13 September 2023 on Energy Efficiency and Amending Regulation (EU) 2023/955. Available online: https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=OJ%3AJOL_2023_231_R_0001&qid=1695186598766 (accessed on 13 March 2024).
  2. Directive 2010/31/EU of The European Parliament and of the Council of 19 May 2010 on the Energy Performance of Buildings. Available online: https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX%3A02010L0031-20210101 (accessed on 13 March 2024).
  3. Directive 2008/50/EC of the European Parliament and of the Council of 21 May 2008 on Ambient Air Quality and Cleaner Air for Europe. Off. J. Eur. Union 2008, 29, 169–212. Available online: http://data.europa.eu/eli/dir/2008/50/oj (accessed on 12 June 2021).
  4. Křůmal, K.; Mikuška, P.; Horák, J.; Hopan, F.; Kuboňová, L. Influence of boiler output and type on gaseous and particulate emissions from the combustion of coal for residential heating. Chemosphere 2021, 278, 130402. [Google Scholar] [CrossRef] [PubMed]
  5. Krawczyk, D.A. Analysis of Energy Consumption for Heating in a Residential House in Poland. Energy Procedia 2016, 95, 216–222. [Google Scholar] [CrossRef]
  6. Shi, X.; Tian, Z.; Chen, W.; Si, B.; Jin, X. A review on building energy efficient design optimization room the perspective of architects. Renew. Sustain. Energy Rev. 2016, 65, 872–884. [Google Scholar] [CrossRef]
  7. Krawczyk, D.A. Sustainable Buildings. Development of Low Energy and Eco-Friendly Constructions; Publishing House of Bialystok University of Technology: Białystok, Poland, 2022. [Google Scholar]
  8. Staffell, I.; Pfenninger, S.; Johnson, N. A global model of hourly space heating and cooling demand at multiple spatial scales. Nat. Energy 2023, 8, 1328–1344. [Google Scholar] [CrossRef]
  9. Turski, M.; Sekret, R. Conceptual adsorption system of cooling and heating supplied by solar energy. Chem. Process Eng. 2016, 37, 293–304. [Google Scholar] [CrossRef]
  10. Kalús, D.; Cvíčela, M.; Janík, P.; Kubica, M. Combined Building-Energy Systems with Heat Transfer Control by Building Constructions using RES. IOP Conf. Ser. Mater. Sci. Eng. 2021, 1203, 032091. [Google Scholar] [CrossRef]
  11. Shahee, A.; Abdoos, M.; Aslani, A.; Zahedi, R. Reducing the energy consumption of buildings by implementing insulation scenarios and using renewable energies. Energy Inf. 2024, 7, 18. [Google Scholar] [CrossRef]
  12. Ratajczak, K.; Michalak, K.; Narojczyk, M.; Amanowicz, Ł. Real Domestic Hot Water Consumption in Residential Buildings and Its Impact on Buildings’ Energy Performance—Case Study in Poland. Energies 2021, 14, 5010. [Google Scholar] [CrossRef]
  13. Najjar, M.K.; De Araujo, L.O.C.; Oladimeji, O.; Khalas, M.; Figueiredo, K.V.; Boer, D.; Soares, C.A.P.; Haddad, A. Influence of Ventilation Openings on the Energy Efficiency of Metal Frame Modular Constructions in Brazil Using BIM. Eng 2023, 4, 1635–1654. [Google Scholar] [CrossRef]
  14. Wilson, M.; Luck, R.; Mago, P.J.; Cho, H. Building Energy Management Using Increased Thermal Capacitance and Thermal Storage Management. Buildings 2018, 8, 86. [Google Scholar] [CrossRef]
  15. Babiarz, B. Aspects of Heat Supply Security Management Using Elements of Decision Theory. Energies 2018, 11, 2764. [Google Scholar] [CrossRef]
  16. Rashad, M.; Żabnieńska-Góra, A.; Norman, L.; Jouhara, H. Analysis of energy demand in a residential building using TRNSYS. Energy 2022, 254, 124357. [Google Scholar] [CrossRef]
  17. Mikoś, J. Ecological Construction; Publishing House of Silesian University of Technology: Gliwice, Poland, 1996. (In Polish) [Google Scholar]
  18. Chwieduk, D. Solar Energy of the Building; Publishing Arkady: Warszawa, Poland, 2011. (In Polish) [Google Scholar]
  19. Geletka, V.; Sedláková, A. Shape of buildings and energy consumption. Czas. Tech. Bud. 2012, 2-B3, 123–129. [Google Scholar]
  20. Kaczmarzyk, M. Influence of building’s shape factor on its heat losses with respect to increasing requirements for building’s thermal insulation. J. Civ. Eng. Environ. Archit. JCEEA XXXIV 2017, 64, 45–54. (In Polish) [Google Scholar] [CrossRef]
  21. Zhang, H.; Pan, Y.; Wang, L. Influence of plan shapes on annual energy consumption of residential buildings. Int. J. Sustain. Dev. Plan. 2017, 12, 1178–1191. [Google Scholar] [CrossRef]
  22. Mousavi, S.N.; Gheibi, M.; Wacławek, S.; Smith, N.R.; Hajiaghaei-Keshteli, M.; Behzadian, K. Low-energy residential building optimisation for energy and comfort enhancement in semi-arid climate conditions. Energy Conv. Manag. 2016, 16, 23–33. [Google Scholar] [CrossRef]
  23. Dylewski, R.; Adamczyk, J. Economic and environmental benefits of thermal insulation of building external walls. Build. Environ. 2011, 46, 2615e2623. [Google Scholar] [CrossRef]
  24. Babiarz, B.; Szymański, W. Introduction to the Dynamics of Heat Transfer in Buildings. Energies 2020, 13, 6469. [Google Scholar] [CrossRef]
  25. Marincu, C.; Dan, D.; Moga, L. Investigating the influence of building shape and insulation thickness on energy efficiency of buildings. Energy Sustain. Dev. 2024, 79, 101384. [Google Scholar] [CrossRef]
  26. Wang, Y.; Liu, K.; Liu, Y.; Wang, D.; Liu, J. The impact of temperature and relative humidity dependent thermal conductivity of insulation materials on heat transfer through the building envelope. J. Build. Eng. 2022, 46, 103700. [Google Scholar] [CrossRef]
  27. Wang, D.; Hu, L.; Du, H.; Liu, Y.; Huang, J.; Xu, Y.; Liu, J. Classification, experimental assessment, modeling methods and evaluation metrics of Trombe walls. Renew. Sustain. Energy Rev. 2020, 124, 109772. [Google Scholar] [CrossRef]
  28. Żelazna, A.; Lichołai, L.; Krasoń, J.; Miąsik, P.; Mikušová, D. The Effects of Using a Trombe Wall Modified with a phase Change Material, from the Perspective of a Building’s Life Cycle. Energies 2023, 16, 7689. [Google Scholar] [CrossRef]
  29. Bevilacqua, P.; Bruno, R.; Szyszka, J.; Cirone, D.; Rollo, A. Summer and winter performance of an innovative concept of Trombe wall for residential buildings. Energy 2022, 258, 124798. [Google Scholar] [CrossRef]
  30. Regulation of the Minister of Infrastructure of April 12, 2002, on the Technical Conditions to Be Met by Buildings and Their Location (In Polish). Journal of Laws No. 75, Item 690, as Amended. Available online: https://sip.lex.pl/akty-prawne/dzu-dziennik-ustaw/warunki-techniczne-jakim-powinny-odpowiadac-budynki-i-ich-usytuowanie-16964625 (accessed on 13 March 2024).
  31. PN-EN ISO 14683:2017-09; Thermal Bridges in Building Construction—Linear Thermal Transmittance—Simplified Methods and Default Values. International Organization for Standardization: Geneva, Switzerland, 2017.
  32. Quesada, G.; Rousse, D.; Dutil, Y.; Badache, M.; Hallé, S. A comprehensive review of solar facades. Opaque solar facades. Renew. Sustain. Energy Rev. 2012, 16, 2820–2832. [Google Scholar] [CrossRef]
  33. PN-EN ISO 6946:2017-10; Building Components and Building Elements—Thermal Resistance and Thermal Transmittance—Calculation Methods. International Organization for Standardization: Geneva, Switzerland, 2017.
  34. PN-EN ISO 10077-1:2017-10; Thermal Performance of Windows, Doors and Shutters—Calculation of Thermal Transmittance. Part 1: General. International Organization for Standardization: Geneva, Switzerland, 2017.
  35. Krasoń, J.; Miąsik, P.; Lichołai, L.; Dębska, B.; Starakiewicz, A. Analysis of the Thermal Characteristics of a Composite Ceramic Product Filled with Phase Change Material. Buildings 2019, 9, 217. [Google Scholar] [CrossRef]
  36. Weng, J.; Huang, Q.; Li, X.; Zhang, G.; Ouyang, D.; Chen, M.; Yuen, A.C.Y.; Li, A.; Lee, E.W.M.; Yang, W.; et al. Safety issue on PCM-based battery thermal management: Material thermal stability and system hazard mitigation. Energy Storage Mater. 2022, 53, 580–612. [Google Scholar] [CrossRef]
Figure 1. Sample arrangement of rooms relative to cardinal directions.
Figure 1. Sample arrangement of rooms relative to cardinal directions.
Energies 17 02702 g001
Figure 2. Traditional solutions for the construction of external masonry walls: (a) one-layer wall (L1); (b) three-layer wall (L3); (c) two-layer wall (L2); (d) three-layer wall with hollow core (L3).
Figure 2. Traditional solutions for the construction of external masonry walls: (a) one-layer wall (L1); (b) three-layer wall (L3); (c) two-layer wall (L2); (d) three-layer wall with hollow core (L3).
Energies 17 02702 g002
Figure 3. Glazing coefficient (Cg) of the catalogue windows available on the market.
Figure 3. Glazing coefficient (Cg) of the catalogue windows available on the market.
Energies 17 02702 g003
Figure 4. Uw coefficient of windows of various designs for a classic spacer frame with coefficient Ψg = 0.08.
Figure 4. Uw coefficient of windows of various designs for a classic spacer frame with coefficient Ψg = 0.08.
Energies 17 02702 g004
Figure 5. Uw coefficient of windows of various designs for a “warm” spacer with coefficient Ψg = 0.03.
Figure 5. Uw coefficient of windows of various designs for a “warm” spacer with coefficient Ψg = 0.03.
Energies 17 02702 g005
Figure 6. Construction of the thermal storage wall.
Figure 6. Construction of the thermal storage wall.
Energies 17 02702 g006
Figure 7. Equivalent heat transfer coefficient Ue of the OW5 window for four orientations.
Figure 7. Equivalent heat transfer coefficient Ue of the OW5 window for four orientations.
Energies 17 02702 g007
Table 1. History of the permissible values of heat transfer coefficient of building barriers according to laws [30].
Table 1. History of the permissible values of heat transfer coefficient of building barriers according to laws [30].
Duration of the Legal ActUmax [W/m2K]
External WallFlat RoofCeiling under the AtticCeiling above the BasementFloor on the GroundWindows/Roof Windows/External Doors
1.07.1958–31.12.19671.42 (1)
1.16 (2)
0.871.16 (1)
1.05 (2)
1.16--
1.01.1968–31.06.19761.47 (3)
1.16 (2)
0.871.16 (3)
1.05 (2)
1.16--
1.07.1976–31.12.19821.160.700.931.16--
1.01.1983–31.12.19910.750.450.401.00-2.0 (4); 2.6 (2)/-/-
1.01.1992–27.04.19980.550300.300.60-2.0 (4); 2.6 (2)/-/-
28.04.1998–31.12.20080.3–0.50.300.300.60-2.0 (4); 2.6 (2)/-/-
1.01.2009–31.12.20130.300.250.250.45-1.7 (4); 1.8 (2)/-/-
1.01.2014–31.12.20160.250.200.200.250.301.3/1.5/1.7
1.01.2017–30.12.20200.230.180.180.250.301.1/1.3/1.5
31.12.2020–to the present 0.200.150.150.250.300.9/1.1/1.3
Passive buildings0.150.150.150.150.150.8/0.8/0.8
(1) In climate zone I; (2) In the remaining climate zones; (3) In climate zones I and II; (4) In climate zones IV and V.
Table 2. Heat loss coefficient through flat elements of the building, (Htr,1).
Table 2. Heat loss coefficient through flat elements of the building, (Htr,1).
Type of BuildingExistingSince 2014Since 2017Since 2021Passive
BarrierAibtr,iUiHtr,1UiHtr,1UiHtr,1UiHtr,1UiHtr,1
-m2-W/m2KW/KW/m2KW/KW/m2KW/KW/m2KW/KW/m2KW/K
External walls199.561.00.599.780.2549.890.2345.900.239.910.1529.93
Flat roof94.501.00.2523.630.218.900.1817.010.1514.180.1514.18
Ceiling above the unheated basement94.500.60.4022.680.2514.180.2514.180.2514.180.158.51
Windows 22.801.01.65837.801.329.641.125.080.920.520.818.24
External doors1.891.02.03.781.73.211.52.841.32.460.81.51
Total413.25-0.49187.67-115.82-105.00-91.24-72.37
Table 3. Heat loss coefficient through linear thermal bridges (Htr,2) and the total heat loss coefficient through transmission (Htr) for the building and the share of thermal bridges for various wall structures.
Table 3. Heat loss coefficient through linear thermal bridges (Htr,2) and the total heat loss coefficient through transmission (Htr) for the building and the share of thermal bridges for various wall structures.
Type of Thermal BridgeThermal Bridge LengthThermal Bridge Type *Heat Loss Coefficient, Htr,2
-leL1L2L3L2
Passive
L1L2L3L2
Passive
-m----W/KW/KW/KW/K
Corner23.00C4C1C2C1−3.45−1.15−2.3−1.15
Wall/flat roof39.00R12R5R6R115.8523.419.51.95
Wall/ceiling39.00IF4IF1IF5IF127.3023.40.00
Ceiling above the basement39.00IF4IF1IF5IF116.38014.040.00
Internal wall/external wall23.00IW4IW1IW5IW10000.00
Internal wall/flat roof19.50IW6IW6IW6IW60000.00
Lintel19.25W10W1W8W11.93019.250.00
Jambs44.30W10W1W11W14.43000.00
Σ Htr,2 246.05----52.4422.2573.890.80
Htr.1 for buildings from 2021-----91.2491.2491.2472.37
Htr (Htr,1+ Htr,2)-----143.68113.49165.1373.17
Thermal bridge share [%]-----36.519.644.71.1
* Designations of thermal bridges according to [31].
Table 4. Parameters of the collector made of different variants.
Table 4. Parameters of the collector made of different variants.
Type of GlazingSymbolGlazing StructureUgUcol,classicUcol,passivegBclassicBpassive
---[W/m2K][W/m2K][W/m2K]-[m2K/W][m2K/W]
One-chamber,
ordinary glass
S14/12/43.03.022.610.740.1940.221
One-chamber, ordinary and low-emissivity glassS24/12/4T1.92.181.770.720.2520.305
One-chamber, ordinary and low-emissivity glass plus ArgonS34/16Ar/4T1.51.871.470.720.2900.364
One-chamber, ordinary and low-emissivity glass plus ArgonS44/15Ar/4TP1.11.571.160.620.2940.390
One-chamber, ordinary glass plus ArgonS54/16Ar/42.62.722.310.830.2390.277
Two-chamber, ordinary glass plus ArgonS64/14Ar/4/
14Ar/4
1.72.031.620.760.2850.350
Two-chamber, ordinary and low-emissivity glass plus ArgonS74TRIIIE/16Ar/4/
16Ar/4TRIIIE
0.71.260.850.620.3600.523
Two-chamber, ordinary and low-emissivity glass plus ArgonS84LE/16Ar/4/
16Ar/33.1LE
0.61.190.780.50.3080.461
Two-chamber, low-emissivity glass plus KryptonS94Ew/12Kr/4Ew/
12Kr/4Ew
0.61.190.780.660.4070.609
Table 5. Equivalent heat transfer coefficient (Ue) of three-sash windows in the heating season for four orientations.
Table 5. Equivalent heat transfer coefficient (Ue) of three-sash windows in the heating season for four orientations.
Catalogue Symbol *We *He *CgCUwUe,SUe,WUe,NUe,E
- mm--W/m2KW/m2KW/m2KW/m2KW/m2K
OW12.080.850.5150.3200.857−1.29−0.81−0.52−0.84
OW41.781.150.5260.3260.858−1.34−0.86−0.56−0.88
OW52.081.150.5650.3510.845−1.51−1.00−0.67−1.02
OW62.381.150.5950.3690.836−1.64−1.10−0.76−1.12
OW81.781.450.5530.3430.853−1.46−0.95−0.64−0.98
OW92.081.450.5950.3690.839−1.65−1.10−0.76−1.13
OW102.381.450.6260.3880.828−1.79−1.21−0.85−1.24
OW121.781.650.5660.3510.850−1.52−1.00−0.68−1.02
OW132.081.650.6080.3770.835−1.71−1.15−0.80−1.18
OW142.381.650.6400.3970.825−1.85−1.26−0.90−1.29
* The designations OW1–OW14 are catalogue symbols of selected three-leaf windows, We—external window width, He—external window height.
Table 6. Equivalent heat transfer coefficient of thermal storage walls Ue,TSW [W/m2K] with a northern orientation in December.
Table 6. Equivalent heat transfer coefficient of thermal storage walls Ue,TSW [W/m2K] with a northern orientation in December.
Type of Construction MaterialWall ThicknessConductivity CoefficientSymbolType of Glazing—Symbol
[m][W/(mK)]S1S2S3S4S5S6S7S8S9
Concrete0.251.7M10.990.680.540.430.840.590.240.260.15 *
Silicate bricks0.380.9M20.720.530.420.350.620.460.200.230.13
Solid ceramic bricks0.380.77M30.680.500.400.330.580.430.190.220.13
Hollowed ceramic blocks0.380.32M40.410.320.270.230.360.280.140.160.09
Autoclaved aerated concrete blocks0.360.21M50.320.250.210.190.280.230.120.140.08
Porous ceramic blocks0.380.143M60.220.180.160.140.200.160.090.100.06
Porous ceramic blocks filled with PCM and mineral wool0.260.132M70.280.230.190.170.250.200.110.120.07
* The bold indicates values below Umax ≤ 0.2 W/m2K.
Table 7. Equivalent heat transfer coefficient Ue,TSW [W/m2K] of the thermal storage wall for four orientations.
Table 7. Equivalent heat transfer coefficient Ue,TSW [W/m2K] of the thermal storage wall for four orientations.
MonthsUe,TSW,EUe,TSW,SUe,TSW,WUe,TSW,N
-[W/m2K][W/m2K][W/m2K][W/m2K]
January0.07−0.380.100.152
February−0.39−0.97−0.33−0.19
March−1.08−1.51−0.98−0.73
April−3.32−3.69−3.19−2.46
May−6.16−5.93−6.32−4.67
June−8.41−7.89−8.29−6.27
July−7.62−7.17−7.37−6.01
August−6.71−6.93−6.43−4.77
September−4.20−4.96−4.03−3.32
October−1.16−1.94−1.18−0.90
November−0.09−0.66−0.15−0.02
December0.12−0.330.090.15
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Starakiewicz, A.; Miąsik, P.; Krasoń, J.; Babiarz, B. Multi-Aspect Shaping of the Building’s Heat Balance. Energies 2024, 17, 2702. https://doi.org/10.3390/en17112702

AMA Style

Starakiewicz A, Miąsik P, Krasoń J, Babiarz B. Multi-Aspect Shaping of the Building’s Heat Balance. Energies. 2024; 17(11):2702. https://doi.org/10.3390/en17112702

Chicago/Turabian Style

Starakiewicz, Aleksander, Przemysław Miąsik, Joanna Krasoń, and Bożena Babiarz. 2024. "Multi-Aspect Shaping of the Building’s Heat Balance" Energies 17, no. 11: 2702. https://doi.org/10.3390/en17112702

APA Style

Starakiewicz, A., Miąsik, P., Krasoń, J., & Babiarz, B. (2024). Multi-Aspect Shaping of the Building’s Heat Balance. Energies, 17(11), 2702. https://doi.org/10.3390/en17112702

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop