2.1. Fault Characteristic Analysis of PV Power Plants
Considering the ecological impact on underwater ecosystems, large-scale floating PV power stations have been designed with a floating layout. To enhance the system’s reliability and maintainability, a centralized inverter and transformer are typically employed to transmit the generated power. This overall structure is illustrated in
Figure 1. Consequently, the transmission lines for floating PV power stations are OHL–cable hybrid lines.
Since the fault current characteristics on the system’s side are primarily determined by the grid of synchronous generators, this section focuses on studying the fault current characteristics on the PV power station side and the operational performance of traditional directional elements. The fault current characteristics on the PV side are closely related to the control methods employed in the grid-connected inverters. Currently, the dual-vector control method is commonly used in engineering to achieve grid connection for PV systems. To achieve low-voltage ride-through, it is typically necessary to regulate and control the positive-sequence and negative-sequence current components within the current inner loop. The control block diagrams for positive-sequence and negative-sequence currents are illustrated in
Figure 2.
In the figure, id1, iq1, id2, and iq2 represent the current values in the forward and reverse synchronous rotating dq coordinate systems during the fault, respectively. i*d1, i*q1, i*d2, and i*q2 represent the current reference values in the forward and reverse synchronous rotating dq coordinate systems during the fault, respectively. ud1, uq1, ud2, and uq2 represent the voltage values of the grid voltage in the forward and reverse synchronous rotating dq coordinate systems, respectively; u*d1, u*q1, u*d2, and u*q2 represent the voltage vectors in the forward and reverse synchronous rotating dq coordinate systems under the dual-vector control strategy, respectively; u*α1, u*β1, u*α2, and u*β2 represent the reference voltage vectors in the stationary coordinate system under the dual-vector control strategy, respectively; and Sa, Sb, and Sc are the switching control signals of the PV grid-connected inverter.
In the case of an asymmetrical fault on the AC transmission line, the three-phase voltage on the PV plant side can be expressed as follows:
where
U represents the voltage magnitude;
δ represents the initial phase angle of the voltage; superscripts +, − and 0 are positive, negative, and zero sequence components, respectively;
η = a, b, c indicates the phase,
φa = 0,
φb = π2/3, and
φc = π4/3;
k0 indicates the grounding coefficient;
k0 = 1 indicates that the fault type is a grounding fault; and
k0 = 0 is a non-grounding fault
The dual-vector control method is commonly used in engineering. Consequently, the transient time of the fault current is only a few milliseconds. It can be considered that the fault current quickly follows its reference value. By combining Equation (1) and the basic formulas presented in reference [
19] for derivation and analysis, the expression for the fault current on the PV power station side of the transmission line can be derived as follows:
here:
Here,
kχ represents the control objective of the control strategy. When
kχ = 1, it suppresses active power fluctuations; when
kχ = 0, it suppresses negative sequence currents; and when
kχ = −1, it suppresses reactive power fluctuations [
20].
P* and
Q* represent the active and reactive power commands during the fault period in the PV array.
kρ =
U−/
U+ represents the voltage unbalance of the grid.
INm is the amplitude of the positive sequence current component of the fault current.
I0 and
φ0 represent the amplitude and initial phase angle of the zero-sequence current, respectively, which are determined by the zero-sequence voltage and the impedance in the zero-sequence network.
Based on Equations (2) and (3) and the vulnerability of power electronic devices (poor overcurrent capability), the following conclusions can be drawn:
- (1)
The fault current characteristics on the PV power station side are significantly different from those of traditional transmission line faults, influenced by various factors such as control objectives, active and reactive power references, and grid unbalance.
- (2)
Due to the limited overcurrent capability of power electronic devices and the controllability of grid-connected inverters, the maximum amplitudes of positive and negative sequence currents in the fault current generally do not exceed 1.5 times the rated value.
- (3)
If a grounded fault occurs, the fault current is dominated by the zero-sequence current; because of that, the following takes place: ① grid-connected transformer typically adopts a YNd11 connection; ② the PV power station exhibits weakly fed characteristics for positive and negative sequence components.
2.2. Adaptive Analysis of Traditional Directional Components
When a forward fault occurs in the transmission line, the criterion for judging the forward fault direction corresponding to the sequence fault component direction element is the following:
Here, j represents +, −, 0, which indicates the positive sequence, negative sequence, and zero sequences, respectively; α+, α−, and α0 represent the positive sequence impedance angle, negative sequence impedance angle, and zero sequence impedance angle, respectively; represents the voltage phasor of the corresponding sequence component; and represents the current phasor of the corresponding sequence component.
When a fault occurs, it may cause the phase jump of the grid voltage. However, under normal operating conditions, PV power plants usually operate at a unity power factor. Therefore, the positive sequence voltage and current of the PV power plant side should be in the same phase. The specific expressions for the positive sequence voltage and current phasors on the PV power plant side before and after the fault are as follows:
Here, ∆
δ represents the positive sequence voltage angle jump;
kλ represents the positive sequence voltage drop coefficient;
P0 represents the power of the PV power plant during normal operation;
and
represent the positive sequence voltage after and before the fault, respectively;
and
represent the positive sequence current after and before the fault, respectively;
φ[1] and
φ[0] represent the phase angles of the positive sequence current after and before the fault, respectively; and
δ[1] and
δ[0] represent the phase angles of the positive sequence voltage after and before the fault, respectively. Combining Equations (1)–(5), the following can be obtained:
According to Equations (3) and (6), α+ is related to variables such as ∆δ, P*, Q*, kχ, kρ, and kλ. However, when a fault occurs in the system, these variable factors are all fixed values. To facilitate subsequent analysis, the following assumptions are made for specific analysis:
- (1)
Reactive power command during the fault at 0 ≤ Q*(pu) ≤ 0.6;
- (2)
Positive sequence voltage drops at 0.3 < kλ < 0.7.
It can be assumed that P* = 0.7 pu, ∆δ ≈ π/9, kχ = 1, and kρ = 0.6, regardless of the variations in the reactive power command Q* and the positive sequence voltage drop kλ. Based on (6) and (7), it can be calculated that the range of the positive sequence incremental impedance angle α+ falls between −150° and 0°. These results do not satisfy the forward fault criterion described in Equation (4). Consequently, the positive sequence directional element fails to operate correctly. Similarly, the analysis process for the other two control objectives follows the same logic and is not elaborated upon further here.
When
kχ = 0, the PV power plants suppress the negative-sequence current. Therefore, there is no negative-sequence current in the transmission line, which causes the negative-sequence directional element to fail to work. When
kχ is 1 or −1, combining Equations (1)–(4) can lead to the following:
According to Equation (7), when kχ = 1, α−∈(0°,90°) under any fault condition; when kχ = −1, α−∈(−180°, −90°) under any fault condition. Therefore, the negative sequence directional element may fail to operate correctly.
The main transformer of a PV power plant typically adopts the YNd11 connection. When a ground fault occurs at the fault point, the zero-sequence impedance in the zero-sequence network is mainly composed of the transformer’s zero-sequence impedance and the line’s zero-sequence impedance. The impedance angle of the zero-sequence directional element is not affected by the PV power plant and can accurately judge the forward direction fault.
In summary, based on the analysis in this section, when a forward direction fault occurs at the fault point on the transmission line of a PV power plant, the positive-sequence fault component directional element on the side of the PV power station is related to factors such as active and reactive power commands, control objectives, and fault conditions. The traditional positive-sequence directional element’s judgment basis is no longer applicable to the directional element on the PV power station side.
Due to the weak-feed characteristics of PV inverters, among traditional directional elements, only the zero-sequence directional components remain unaffected.
With the expansion of PV development, the grid-connected voltage levels range from 10 to 220 kV, encompassing both neutral isolated systems and neutral grounded systems. This paper mainly focuses on neutral grounded systems. For the neutral isolated systems, despite the absence of a zero-sequence current path, the zero-sequence current generated by the distributed capacitance of the cables is sufficient to trigger the criterion.