A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors
Abstract
:1. Introduction
2. Materials and Methods
2.1. Equivalent Circuit
2.2. Inter-Turn Short-Circuit Fault When
2.2.1. ISCF Occurring in Different Coils within the Same Encapsulate
2.2.2. ISCF Occurring in Different Encapsulates
2.3. Local Inter-Turn Short-Circuit Fault When
2.3.1. ISCF Detection Method
2.3.2. The Impact of Noise Signals on Fault Detection Reliability
3. Results
4. Conclusions
- (1)
- For different coils within the same encapsulate of dry-type air-core reactors, the equivalent resistance and active power of a global ISCF at the same height show almost no change. As the fault moves outside the encapsulate, both the equivalent resistance and active power increase initially and then decrease. Moving from the middle to the end of the fault height results in a decreasing trend.
- (2)
- The equivalent resistance and active power experience significant increments in the presence of an ISCF, reaching up to 50 and 60 times the rated values, respectively, without accounting for insulation resistance.
- (3)
- At the initial stage of a local ISCF with one turn, the insulation resistance is relatively high, making it challenging to detect the fault. A larger exponent ‘a’ in the FDF has better sensitivity in detecting ISCFs under the aforementioned condition without considering the noise signal.
- (4)
- The FDF applied with an MAF can improve the reliability of the proposed method by reducing the fluctuation amplitude of the FDF to reduce the misjudgment likelihood in ISCF detection while guaranteeing the sensitivity of the detection proposed method when the signal noise in the monitoring system is considered.
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
References
- Sun, Y.; Zou, L.; Liu, Q.; Dai, L.; Zhang, L.; Zhao, T. Research on five-loop simplified scaling model for dry-type air-core reactors with inter-turn short circuit fault. IEEE Access 2021, 9, 163707–163715. [Google Scholar] [CrossRef]
- Nie, H.; Liu, X.; Wang, Y.; Yao, Y.; Gu, Z.; Zhang, C. Breaking overvoltage of dry-type air-core shunt reactors and its cumulative effect on the interturn insulation. IEEE Access 2019, 7, 55707–55720. [Google Scholar] [CrossRef]
- Das, S.; Sidhu, T.; Zadeh, M.D.; Zhang, Z. A novel hybrid differential algorithm for turn to turn fault detection in shunt reactors. IEEE Trans. Power Deliv. 2017, 32, 2537–2545. [Google Scholar] [CrossRef]
- Vázquez, E.; Andrade, M.A.; Esponda, H.; Ávila, J. A new differential protection algorithm for power reactors based on the second central moment. Electr. Power Energy Syst. 2020, 118, 10579. [Google Scholar] [CrossRef]
- Li, Y.Q. Operation analysis and operation and maintenance method of 35 kV dry-type air-core shunt reactor. Electr. Eng. 2018, 18, 39–40+53. [Google Scholar]
- Jiang, J.Q.; Shi, W.F.; Liu, Y.H.; Xie, J.L. Early Warning of Interturn Short Circuit Fault of Stator Winding of Ship Generator. CSU-EPSA. [CrossRef]
- Li, Q.; Wang, Z.; Zhao, H.B.; Dong, J.P.; Shen, Z.Y.; Zhang, X.Y.; Zhang, Z.; Hu, E.; Xing, Y. Interturn fault detection algorithm for shunt reactors based on leakage magnetic field. In Proceedings of the 2019 IEEE 3rd Conference on Energy Internet and Energy System Integration, Changsha, China, 8–10 November 2019. [Google Scholar] [CrossRef]
- Zhou, D.Z.; Xv, M.K.; Du, X.M.; Fu, Z.Y.; Lv, X.P.; Kang, Q.K.; Song, H. Study for spatial magnetic field distribution of inter-turn short-circuit fault degree in dry air-core reactors. In Proceedings of the 2018 13th IEEE Conference on Industrial Electronics and Applications, Wuhan, China, 31 May 2018–2 June 2018. [Google Scholar] [CrossRef]
- Tian, Y.F. Research of fault detection method of dry-type power reactor at substations. South. Power Syst. Technol. 2010, 4 (Suppl. S1), 60–63. [Google Scholar] [CrossRef]
- He, L.; Huang, Z. Fault diagnosis of dry-type air-core reactor based on temperature field with multi-component normal distributions. In Proceedings of the 2020 Chinese Control and Decision Conference, Hefei, China, 22–24 August 2020. [Google Scholar] [CrossRef]
- Yang, H.; Lu, G.; Ji, S.; Zhu, L. Detection method of turn to turn insulation short circuit fault of dry-type air-core reactor using vibration characteristics based on machine learning. In Proceedings of the 2019 IEEE 8th International Conference on Advanced Power System Automation and Protection, Xi’an, China, 21–24 October 2019. [Google Scholar] [CrossRef]
- Zhu, L.; Du, Y.; Gao, L.; Zhuang, Z.; Ji, S. Vibration Distribution Detection Method for Turn-to-Turn Short-Circuit Fault of Dry-Type Air-Core Filter Reactors. IEEE Trans. Power Deliv. 2022, 37, 4474–4476. [Google Scholar] [CrossRef]
- Guo, Z.; Guo, Z.G.; Jia, G.M.; Lang, Q.; Liu, X.; Luo, F. Three-stage characteristic analysis on inter-turn fault and comprehensive protection method for air-core shun reactor. Autom. Electr. Power Syst. 2020, 44, 149–156. [Google Scholar] [CrossRef]
- Gao, Z.W.; Zhu, X.C.; Wang, Y.H.; Zhuang, Y. Study on turn-to-turn short circuit on-line monitoring system for dry-type air-core reactor. J. Harbin Univ. Sci. Technol. 2017, 22, 67–71. [Google Scholar] [CrossRef]
- He, L.; Zhengyi, H. Fault diagnosis of dry-type air-core reactor based on hierarchical neural networks. In Proceedings of the 2020 Chinese Control and Decision Conference, Hefei, China, 22–24 August 2020. [Google Scholar] [CrossRef]
- Qin, R.S.; Wang, W.L.; Wang, B. Research on the modeling method and turn-to-turn short circuit monitoring method for the dry-type air-core reactor. In Proceedings of the 2018 2nd IEEE Conference on Energy Internet and Energy System Integration, Beijing, China, 20–22 October 2018. [Google Scholar] [CrossRef]
- Li, N.; Zhang, X.; Yao, C.H.; Ran, B.; Mi, Y.; Cheng, J.C. Research on inter-turn short circuit fault detection method of dry-type air-core reactor based on IFRA magnetic coupling. Electr. Eng. 2022, 15, 83–87+91. [Google Scholar] [CrossRef]
- Wang, J.; Zhang, G.Z.; Zhao, X.Z.; Zhang, L.; Liang, N.F.; Yao, C.G. Online detection investigation of the high voltage shunt reactor winding deformation based on coupling injection of pulses. High Volt. Eng. 2017, 43, 872–878. [Google Scholar] [CrossRef]
- Zhuang, Y.; Wang, Y.; Zhang, Q. Study on turn-to-turn insulation fault condition monitoring method for dry-type air-core reactor. In Proceedings of the 2015 IEEE 11th International Conference on the Properties and Applications of Dielectric Materials, Sydney, Australia, 19–22 July 2015. [Google Scholar] [CrossRef]
- Zhuang, Y.; Wang, Y. A monitoring method of inter-turn insulation fault for dry-type air-core shunt reactor. In Proceedings of the 2018 12th International Conference on the Properties and Applications of Dielectric Materials, Xi’an, China, 20–24 May 2018. [Google Scholar] [CrossRef]
- Ma, C.; Zhang, B.; Yan, Z.; Li, J. Detection of metallic turn-turn short circuit of dry air core reactor based on digital twin current method. In Proceedings of the 2nd International Conference on Electronic Materials and Information Engineering, Hangzhou, China, 15–17 April 2022. [Google Scholar] [CrossRef]
- Solak, K.; Mieske, F.; Schneider, S. Modeling and detection of turn-to-turn faults in shunt reactors. IEEE Access 2021, 10, 1386–1400. [Google Scholar] [CrossRef]
- Zhu, Y.; Xue, Z.; Zhou, Y.; Hu, J.; Liu, J.; Li, Z. Research and application of on-line monitoring device for dry-type air-core reactor. In Proceedings of the 2019 IEEE International Conference on Electron Devices and Solid-State Circuits, Xi’an, China, 12–14 June 2019. [Google Scholar] [CrossRef]
- Huang, S.P.; Aggarwal, A.; Strangas, E.G.; Li, K.; Niu, F.; Huang, X.Y. Robust stator winding fault detection in PMSMs with respect to current controller bandwidth. IEEE Trans. Power Electron. 2021, 36, 5032–5042. [Google Scholar] [CrossRef]
- Moon, S.; Jeong, H.; Lee, H.; Sang, W.K. Interturn short fault diagnosis in a PMSM by voltage and current residual analysis with the faulty winding model. IEEE Trans. Energy Convers. 2018, 33, 190–198. [Google Scholar] [CrossRef]
- Wu, J.; Luo, R.; Zhang, M.; Peng, Y.M.; Jing, S.; Huang, Q. A New Method to Detect the Inter-Turn Short Circuit Fault of Dry-Type Air-Core Shunt Reactor. In Proceedings of the 2022 4th International Conference on Power and Energy Technology, Xining, China, 28–31 July 2022. [Google Scholar] [CrossRef]
- Zhao, C.M.; Wang, Y.H.; Ao, M.; Zhuang, Y. Electric parameter variation of dry-type air-core shunt reactor with interturn short-circuit fault. Transformer 2019, 56, 31–36. [Google Scholar] [CrossRef]
- Chen, J.; Li, J.; Ge, N. Study on variation law of electrical parameters in dry hollow reactor inter-turn short circuit fault. In Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, Xi’an, China, 20–24 May 2018. [Google Scholar] [CrossRef]
- Wei, X.L.; Zhu, B.; Nie, H.Y.; Yu, C.L.; Liang, J.Q.; Zhang, H.D. Relationship between electrical parameters and turn-to-turn insulation fault position of dry-type air-core reactor. Electr. Mach. Control. 2020, 24, 71–79. [Google Scholar] [CrossRef]
- Zhu, B.J.; Liu, X.H.; Xie, T.P.; Xian, R.C.; Lu, Y.; Wang, L.Q. Analysis of electrical characteristics of series reactor winding inter-turn short-circuit fault. Transformer 2021, 58, 30–32. [Google Scholar] [CrossRef]
Parameters | Value | Parameters | Value |
---|---|---|---|
Rated capacity (kVar) | 20,000 | Rated current (A) | 989.7 |
Rated voltage (kV) | 20.21 | Height (mm) | 1990 |
Number of encapsulates | 13 | Outer radius (mm) | 2807.1 |
Number of coils | 44 | Equivalent reactance (Ω) | 20.42 |
Rated frequency (Hz) | 50 | Equivalent resistance (Ω) | 0.051 |
Encapsulate | Coil | Equivalent Resistance Ratio | Active Power Ratio |
---|---|---|---|
1 | 1 | 15.982 | 16.176 |
2 | 16.117 | 16.317 | |
3 | 16.260 | 16.463 | |
4 | 16.394 | 16.600 | |
5 | 16.535 | 16.744 | |
3 | 1 | 26.506 | 27.299 |
2 | 26.693 | 27.499 | |
3 | 26.878 | 27.695 | |
4 | 27.077 | 27.905 | |
11 | 1 | 53.580 | 60.194 |
2 | 53.485 | 60.078 | |
3 | 53.420 | 59.988 |
Parameters | Value | Parameter | Value |
---|---|---|---|
Rated capacity (kVar) | 20,000 | Rated current (A) | 989.7 |
Rated voltage (kV) | 20.21 | Height (mm) | 2540 |
Number of encapsulates | 14 | Outer radius (mm) | 3024 |
Number of coils | 44 | Equivalent reactance (Ω) | 20.65 |
Rated frequency (Hz) | 50 | Equivalent resistance (Ω) | 0.039 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Wu, J.; Zhen, W.; Chang, Z.; Zhang, M.; Peng, Y.; Liu, Y.; Huang, Q. A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors. Energies 2024, 17, 1709. https://doi.org/10.3390/en17071709
Wu J, Zhen W, Chang Z, Zhang M, Peng Y, Liu Y, Huang Q. A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors. Energies. 2024; 17(7):1709. https://doi.org/10.3390/en17071709
Chicago/Turabian StyleWu, Jie, Wei Zhen, Zhengwei Chang, Man Zhang, Yumin Peng, Ying Liu, and Qi Huang. 2024. "A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors" Energies 17, no. 7: 1709. https://doi.org/10.3390/en17071709
APA StyleWu, J., Zhen, W., Chang, Z., Zhang, M., Peng, Y., Liu, Y., & Huang, Q. (2024). A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors. Energies, 17(7), 1709. https://doi.org/10.3390/en17071709