1. Introduction
The widespread adoption of solar photovoltaic (PV) systems is increasingly being recognized as a transformative solution to address global energy crises while simultaneously mitigating greenhouse gas emissions [
1]. As of 2023, the cumulative global installed capacity of solar PV systems exceeded 1400 GW, reflecting a tenfold increase from just over 100 GW in 2012 [
2]. This remarkable growth has been driven by advancements in technology, which have reduced solar module prices by approximately 85% since 2010, coupled with supportive policy frameworks such as feed-in tariffs and renewable energy subsidies [
3]. In comparison to other renewable energy sources such as wind or hydropower, solar PV systems offer distinct advantages, including scalability, versatility in installation on urban rooftops or rural landscapes, and the absence of location-specific constraints like consistent wind speeds or water availability. These unique attributes make solar PV systems particularly well suited for decentralized energy generation, empowering regions with limited access to traditional grid infrastructure [
4].
In line with this global trend, the development of solar PV systems and their associated legal frameworks is expanding beyond highly developed countries to include developing nations [
5]. Mongolia, for example, has made significant progress in this area, with several solar power plants of megawatt capacities commissioned over the past decade [
6]. Additionally, a large number of small-scale solar PV systems have been successfully connected to the power distribution grid, as reported by the Ulaanbaatar Electricity Distribution Network (UBEDN) state-owned company. To support this growth, Mongolia approved regulations for the interconnection of consumer renewable energy systems to the grid in August 2020, with an updated version released in 2024 [
7]. Furthermore, extensive research efforts are being conducted by academic institutions in Mongolia to further advance solar PV systems and their operation [
8,
9,
10,
11]. As a result of these developments, the number of households, organizations, and enterprises interested in installing solar photovoltaic systems continues to rise steadily.
The integration of solar PV systems into existing power grids, in addition to addressing energy crises and reducing greenhouse gas emissions, has been a focal point of extensive research. A number of studies have explored the impact of solar PV integration on power distribution grids [
12,
13,
14,
15,
16].
One of the major concerns associated with increased solar PV penetration is its potential effect on voltage quality within the distribution grid. Solar PV generation typically peaks during daylight hours, which can lead to overvoltage when generation surpasses local consumption. This imbalance can result in undesirable consequences such as voltage fluctuations, reverse power flow into the grid, and increased system losses. Several studies have identified these challenges and proposed mitigation strategies to address them [
12,
13].
For instance, a study using an IEEE 13-bus test case examined the impact of solar PV integration on the distribution grid. By simulating different scenarios with varying levels of PV penetration in the Open Distribution System Simulator (OpenDSS) and interfacing with MATLAB, the study found that higher penetration levels led to more frequent voltage issues and higher system losses. These outcomes necessitated the implementation of corrective actions, such as deploying voltage regulation devices and optimizing inverter settings to mitigate power quality problems [
12].
Similarly, an analysis of a real distribution feeder in South Australia revealed that while increasing PV penetration helped reduce instances of undervoltage, it simultaneously caused a significant rise in overvoltage occurrences. This overvoltage led to inverter shutdowns when voltage levels exceeded the maximum limits for inverters. The study also quantified the financial losses resulting from PV curtailment due to overvoltage-induced shutdowns, underlining the importance of considering these financial impacts when planning for greater PV hosting capacity in distribution networks [
13].
In addition to voltage issues, the integration of solar PV systems can affect the reliability of distribution systems. A Monte Carlo simulation conducted on the RBTS Bus 2 system assessed how different levels of solar PV integration influence Energy Not Supplied (ENS) during system outages. The results demonstrated that solar PV can significantly reduce ENS, particularly during the day when solar generation is at its peak. This highlights the potential for solar PV to improve the reliability of distribution grids by mitigating energy shortages during outages [
14].
Moreover, high levels of rooftop PV penetration can interfere with the operation of voltage-regulating devices, such as tap-changing transformers and reactive power compensators. These devices are designed to maintain voltage levels within acceptable bounds, but the reverse power flow caused by excess PV generation can disrupt their function. The literature suggests that one solution to these challenges is the adoption of smart inverters. These inverters can adjust their output dynamically in response to grid conditions, alleviating many of the voltage-related problems associated with high PV penetration. A review of the impacts of rooftop PV systems highlighted the crucial role of smart inverters in enabling higher levels of PV integration. By providing voltage control and reactive power support, smart inverters reduce the burden on traditional voltage-regulating devices, facilitating smoother integration of solar PV into the distribution grid [
15]. Additionally, the complexity of managing solar PV generation is increasing, as it presents more challenges than conventional electricity sources [
16].
The high number of households in ger districts, coupled with their sparse distribution, necessitates the construction of extensive power distribution grids. This design leads to issues such as overload and undervoltage, particularly at the end of the lines, as well as higher-than-normal power losses. These challenges are unique to areas like the Ulaanbaatar ger district and may not be fully represented in studies that use more conventional or simplified grid models, such as the 13-bus system or low-voltage systems. Consequently, it is essential to study the impact of solar PV systems on the power distribution grid in these districts in detail. Such research can help address power quality issues in Mongolia, particularly in Ulaanbaatar and other densely populated areas, while also reducing power and electricity losses in distribution lines and substations. Furthermore, understanding the optimal use of small-scale solar PV systems, in compliance with existing regulations, can facilitate the injection of energy into the grid from distributed renewable energy sources owned by consumers. By considering the specific characteristics of overloaded feeders with unevenly distributed loads, this study contributes to optimizing the integration of solar PV systems in areas facing unique grid infrastructure challenges, which are often overlooked in broader studies.
This study examines the impact of solar PV systems on the power distribution grid by analyzing changes in power losses and voltage deviations under various scenarios. Two primary factors are considered in the assessment: the installed capacity of the solar PV systems and the location of their connection to the grid. Among three heavily loaded feeders in the Ulaanbaatar area, the Dambadarjaa feeder with the highest load was selected for detailed analysis. The robustness of the methodology was assessed by evaluating eight distinct scenarios, with solar PV systems connected at four primary locations: the beginning, middle, end, and evenly distributed throughout the grid. The installed capacities of the solar PV systems range from 25% to 80% of the feeder’s highest daily load. The results consistently demonstrated that power loss reduction is most significant when the total installed capacity of the solar PV systems is 75% of the feeder’s highest daily load and the systems are connected at the end of the power distribution grid. While additional scenarios with slight variations could be considered, the differences in outcomes are expected to be minimal due to the comprehensive nature of the analyzed cases. This consistency across multiple scenarios highlights the robustness of the methodology, ensuring its reliability under varying operating conditions.
This study demonstrates that strategic placement and sizing of solar PV systems can significantly enhance grid reliability, reduce power losses, and support higher penetration levels of solar PV systems within acceptable ranges. These insights not only inform grid policy and planning but also contribute to the development of a more sustainable and efficient energy infrastructure.
3. Solar PV Systems Connected to Power Distribution Line
In order to assess the impact on voltage deviation and transmission losses when solar PV systems are connected to the Dambadarjaa feeder of the Selbe substation, four different connection points of solar PV systems were studied. The impact of connecting solar PV systems with a capacity of 25 to 80 percent of the feeder’s daily load was studied at each connection point. PowerFactory simulation software V.15.1.7 was used in this study. The NU-RC300 solar PV module was chosen for all simulations conducted in this study. The design parameters of the selected PV module are detailed in
Table 1.
Figure 4 shows a developed scheme of the Dambadarjaa feeder on the worksheet of the simulation software. The length of the Dambadarjaa feeder line is 6.81 km, and the total length is 11.42 km. In total, 36 units of 10/0.4 kV transformers with different rated powers are connected to the Dambadarjaa feeder. The location of each unit is shown in
Figure 5a and the specifications of each unit are listed in
Table 2.
Based on the measurement results, the seasonal load conditions of the selected feeder were determined.
Table 3 shows the seasonal lowest and highest loads of the selected feeder, which has a distribution capacity of 2.2 MW. In winter, the lowest and highest loads were equal to 116.89% and 157.47% of the installed capacity of the selected feeder, respectively. It can be seen that the feeder is continuously overloaded during the winter season, resulting in a high temperature and reduced lifetime of the equipment. While the lowest load of the selected feeder was 27.56%, and the highest load was 70.72% in summer. Thus, it can be seen as the load conditions of the power distribution grid strongly depend on the season.
3.1. Solar PV Systems Connected at the Beginning of the Power Distribution Line
The power distribution line is divided into three sections: beginning, middle, and end. There are seven transformers connected at the beginning of the power distribution line. These transformers have rated powers of 1 × 30 kVA, 1 × 100 kVA, 1 × 160 kVA, 1 × 250 kVA, and 3 × 400 kVA. The total installed capacity of the solar PV systems was selected to be 25% to 80% of the highest daily load of the feeder, while the installed capacity of each solar PV system was chosen to be up to 75% of the highest load measured on the connected transformer.
Figure 5b shows the location of each substation and solar PV system connected at the beginning of the power distribution line. According to the results obtained from the simulation using the PowerFactory software, the daily power losses of the Dambadarjaa feeder were 4319 kWh when there no solar PV systems were connected. This could be reduced by 90 kWh by installing the solar PV systems at the beginning of the feeder. In this case, the total capacity was equal to 25% of the highest daily load of the feeder. The power loss reduction of 90 kWh accounts for 2% of the daily power losses.
Then, the total capacity of the solar PV systems was increased to 50% and 80% of the feeder’s highest daily load. The corresponding energy losses were reduced by 3.5% and 4.1%, respectively.
3.2. Solar PV Systems Connected in the Middle of the Power Distribution Line
There are eight transformers connected in the middle of the power distribution line. Their rated powers are 1 × 40 kVA, 1 × 63 kVA, 4 × 250 kVA, and 2 × 400 kVA. The total installed capacity of the solar PV systems was decided in the same way that was used in the previous scenario.
Figure 5c shows the location of each transformer and solar PV system connected in the middle of the power distribution line. The losses of the Dambadarjaa feeder were reduced by 224 kWh by installing solar PV systems with a total capacity equal to 25% of the highest daily load of the feeder—the power loss reduction of 224 kWh accounts for 5.1% of the daily power losses.
Like the previous simulation, the total capacity of the solar PV systems was increased to 50% and 80% of the feeder’s highest daily load. The corresponding energy losses were reduced by 9.4% and 11.5%, respectively. Thus, it can be seen that the losses could be reduced more when solar PV systems are installed in the middle of the power distribution line.
3.3. Solar PV Systems Connected at the End of the Power Distribution Line
There are also eight transformers connected at the end of the power distribution line. Their rated powers are 1 × 50 kVA, 1 × 160 kVA, 5 × 250 kVA, and 1 × 400 kVA. The sizing of the solar PV systems was completed in the same way as the previous two scenarios.
Figure 5d shows the location of each substation and solar PV system at the end of the power distribution line. The losses of the Dambadarjaa feeder were reduced by 258 kWh by installing solar PV systems with a total capacity equal to 25% of the highest daily load of the feeder—the loss reduction of 258 kWh accounts for about 6% of the daily power losses.
As with the previous simulation, the total capacity of the solar PV systems was increased to 50% and 80% of the feeder’s highest daily load. The corresponding energy losses were reduced by 10.7% and 12.9%, respectively. The reduction rates of power losses were increased while connecting the solar PV systems at the end of the power distribution line.
3.4. Solar PV Systems Evenly Distributed Along the Power Distribution Line
To assess the effects based on different connection points, solar PV systems distributed evenly along the power distribution line were also examined. Several transformers were systematically chosen along the line until their total installed capacity reached 80% of the feeder’s highest daily load. Subsequently, the sizing of the solar PV systems was determined for each selected transformer, varying between 25% and 80% of the feeder’s peak daily load.
The simulation results from the PowerFactory software showed that the daily power losses of the Dambadarjaa feeder were 4319 kWh when no solar PV systems were connected. With this connection scenario, power losses were reduced by 5%, with the total system capacity set to 25% of the feeder’s peak load. As the total capacity of the solar PV systems was increased to 50% and 80% of the feeder’s highest daily load, energy losses decreased by 9.5% and 13.2%, respectively.
4. Analyses of Energy Loss Reductions and Voltage Deviations
Figure 6 summarizes energy losses on the feeder depending on the solar PV systems’ total installed capacity and connection points. The vertical axis represents energy losses on the feeder. The horizontal axis indicates the ratio of the total installed capacity of the solar PV system and the feeder load by percentage. In order to clearly show the reduction rates of the energy losses, the scenario with no solar PV systems has been added to the existing four scenarios with different connection points. The energy loss has a constant value of 4319 kWh in the scenario with no solar PV systems shown by the light-blue line. The scenarios with solar PV systems connected at the power distribution line’s beginning, middle, and end are shown in orange, gray, and amber, respectively. From the comparison shown in
Figure 6, it is clear that the associated energy losses could be reduced by the highest percentage when the solar PV systems were connected at the end of the power distribution line until the installed capacity reached 70%. Afterward, the evenly distributed solar PV systems showed lower energy losses when the total installed capacity exceeded 75% of the feeder’s highest daily load (for more information, please see the numerical data at the bottom part of
Figure 6).
Figure 7 shows the costs associated with daily energy losses. The costs of daily energy losses are calculated based on the measured energy losses presented in
Figure 6. To estimate these costs, the electricity tariff set by the Energy Regulatory Commission of Mongolia in November 2024 was used. The analysis reveals that the largest cost arises from the scenario without any solar PV systems, while the cost of energy losses is significantly reduced in scenarios where solar PV systems are connected to the end of the power distribution grid. This reduction highlights the potential benefits of integrating solar PV systems into the grid, particularly at strategic locations, to minimize energy losses and associated costs.
In order to analyze the voltage deviations on the selected feeder, voltage probes were placed at the beginning, middle, and end of the power distribution line. As a result of the simulation with no solar PV systems, the probed voltages at the beginning, middle, and end of the power distribution line reached 0.9935 p.u., 0.96368 p.u., and 0.94846 p.u., respectively.
Figure 8 shows the probed voltage deviations at the beginning of the power distribution line depending on the installed location of solar PV systems, where the vertical, primary horizontal, and secondary horizontal axes illustrate the voltage per unit, time in hours, and total installed capacity in the percentage of the highest daily load of the feeder. By installing the solar PV systems at the beginning, middle, and end of, or evenly distributed throughout, the power distribution line, the voltage could be increased to 0.99961 p.u., 0.99961 p.u., 0.99962 p.u., and 0.99961 p.u., respectively. In this case, the closest value to the rated voltage can be obtained with the installation of solar PV systems at the end of the power distribution lines.
Figure 9 shows the probed voltage deviations in the middle of the power distribution line depending on the installed location of the solar PV systems. The voltage increases to 0.97240 p.u., 0.98481 p.u., 0.98572 p.u., and 0.98158 p.u. when the solar PV systems are installed at the beginning, middle, and end, or evenly distributed throughout the power distribution line, respectively. In this scenario, the closest value to the rated voltage is achieved when the solar PV systems are also installed at the end of the distribution lines.
Figure 10 shows the probed voltage deviations at the end of the power distribution line depending on the installed location of solar PV systems. In the scenario with solar PV systems connected at the end of the power distribution line, the voltages increased to 0.95731 p.u., 0.97254 p.u., 0.98632 p.u., and 0.97393 p.u.
Overall, the voltage at the beginning of the power distribution line does not have a noticeable increase regarding the installed location of the solar PV systems, whereas there are significant differences in the voltage in the middle and end of the power distribution line due to the installed locations. This can be seen in the voltage at the end of the power distribution line, which was increased to the highest value when the solar PV systems were installed at the end of the power distribution line.
6. Conclusions
In this study, an impact assessment of the grid-connected solar PV systems on the overloaded feeder in Ulaanbaatar ger district was carried out considering the total installed capacity and installation locations. Solar PV systems show the best effect on the undervoltage of the power distribution line when they are connected at the end of the line.
In terms of the loss reduction rate, solar PV systems with a total installed capacity equal to 25% of the daily load of the selected feeder can reduce the associated loss by 2% to 6%, depending on the connection point. The total installed capacity of the solar PV systems was then increased to 50% of the daily load of the selected feeder, resulting in a loss reduction of 3.4% to 9.7%. Afterward, the total installed capacity was increased to 75% of the daily load of the selected feeder. With this capacity specification, the associated loss could be reduced by 4% to 11.4%, suggesting that this scenario is the best one.
In other words, the energy losses are reduced most significantly when solar PV systems are installed at the end of the distribution line, particularly for installed capacities up to 70% of the feeder’s highest daily load. This is because end-of-line installations provide localized electricity generation for households farthest from the feeder’s source, thereby minimizing the need for long-distance power transmission and reducing resistive losses. However, when the total installed capacity exceeds 75% of the feeder’s highest daily load, scenarios with evenly distributed solar PV systems result in lower energy losses. However, the performance on the reduction of the voltage deviation with the evenly distributed solar PV systems could not overcome the scenario when the solar PV systems were installed at the end of the power distribution line.
The findings of this study are primarily based on the power distribution grid in the Ulaanbaatar ger district, where the grid structure is characterized by long feeder lines with high resistance and an uneven distribution of load centers. However, the observed results and underlying principles are applicable to other ger districts or areas with similar power distribution grid structures. In particular, the reduction in energy losses and voltage deviations when solar PV systems are installed at the end of the distribution line is primarily due to localized electricity generation near the households at the feeder’s farthest points, which minimizes long-distance power transmission and reduces resistive losses. This behavior is expected to be consistent in other ger districts due to their similar characteristics.
It is entirely feasible to address undervoltage and other technical challenges through the integration of battery energy storage systems with solar PV installations. The findings of this study provide a solid foundation for developing a methodology to determine the optimal installed capacity of solar PV systems at any point along the power distribution line. This methodology will be presented in forthcoming research.