Numerical Investigation of the Seismic Performance of Steel Frames with Energy-Dissipating Composite Walls
Abstract
:1. Introduction
2. Steel Frame with EDCWs
2.1. Structural Composition
2.2. Composition of the EDCW
2.3. Structural Composition of the Steel Frame
3. Numerical Tests
3.1. Calculation Models
3.2. Loading Method
- (1)
- Loading method for the EDCW
- (2)
- Loading method for the frame structure
3.3. Yield Model
- (1)
- Plastic yield model of concrete
- (2)
- Yield model of the steel structure
4. Results and Discussion
4.1. Seismic Performance of the EDCW
- (1)
- Process and characteristics of deformation and failure
- (2)
- Hysteresis curves and the skeleton curve
4.2. Seismic Performance of the Steel Frame Structure with EDCWs
4.2.1. Simulation Scheme
4.2.2. Seismic Performance of the Frames
- (1)
- Structural failure mode
- (2)
- Hysteresis curves and skeleton curves
4.2.3. Effects of Structural Design Parameters on the Seismic Performance of Frames
- (1)
- Effect of the span ratio of the steel frame to the EDCW on seismic performance
- (2)
- Effect of the installation location of the EDCW on the seismic performance of the steel frame
- (3)
- Effect of steel frame stiffness on seismic performance
4.3. Discussion
- (1)
- An energy-dissipating composite wall (EDCW) was designed to improve the seismic performance of steel frame buildings.
- (2)
- The EDCW was installed in a two-storey steel frame, and the seismic performance of the steel frame was analysed using the FEM. The results showed that the EDCW dissipated most of the seismic energy and thus substantially improved the seismic performance of the frame.
5. Conclusions
- (1)
- A preliminary finite element model was developed to test the seismic performance of an energy-dissipating composite wall (EDCW), and the hysteretic curves obtained by numerical simulation were compared with the experimental hysteretic curves. The curves fit each other, and the development pattern was consistent, verifying the reliability of the finite element analysis;
- (2)
- An EDCW that was assembled from concrete-filled steel tubular columns (CFSTCs) and concrete sheet walls were designed to improve the seismic performance of steel frame houses in rural areas. The seismic performance of the EDCW was obtained by reproducing the cyclic loading test on the EDCW using numerical simulations. The EDCW had a butterfly-shaped hysteresis curve. Before the concrete wall failed, the wall and frame worked together, resulting in a steep hysteresis curve; after failure of the concrete wall, the CFSTCs resisted the seismic load, leading to a gentle hysteresis curve;
- (3)
- The seismic performance of a two-storey steel frame installed with EDCWs was analysed by using the finite element method to obtain the deformation and failure characteristics, hysteresis curves, and skeleton curves. The numerical simulation results showed that the EDCWs dissipated most of the seismic energy during earthquakes, and hence, the seismic performance of the steel frame was substantially improved by the installation of the EDCWs;
- (4)
- The seismic performances of 16 frames were compared to investigate the effects of the span ratio of the steel frame to the EDCW, the installation location of the EDCW, and the stiffness of the steel frame on the seismic performance of the frame. With the increase in the span ratio, the extent of damage to the EDCW decreased, as did its seismic effectiveness. The farther the installation location of the EDCW was from the side column of the frame, the more energy was dissipated by the EDCW, and the best seismic performance was achieved when the EDCW was in the middle of the frame. As the stiffness of the steel frame increased, the extent of damage to the EDCW increased, as did its energy dissipation capacity;
- (5)
- According to the seismic performance analysis of 16 trusses of frames, the component proposed in this paper could improve the overall stiffness of the frame and absorb most of the seismic energy under the seismic load, thus reducing the damage of the external frame to within a negligible range. Since the overall structure could still perform its original function, the cost of reconstruction after an earthquake could be reduced by replacing only the most severely stressed concrete wall sheet or replacing the whole internal component to keep the structure in use.
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
References
- Wang, Y.; Cao, S.; Zhang, X. Lessons from the Wenchuan Earthquake//Earthquakes and Their Impact on Society; Springer: Berlin/Heidelberg, Germany, 2015; pp. 449–458. [Google Scholar]
- Cimellaro, G.P.; Renschler, C.; Reinhorn, A.M.; Arendt, L. Peoples: A framework for evaluating resilience. J. Struct. Eng. 2016, 142, 04016063. [Google Scholar] [CrossRef]
- Zhong, C.; Binder, J.; Kwon, O.S.; Christopoulos, C. Full-Scale Experimental Testing and Postfracture Simulations of Cast-Steel Yielding Connectors. J. Struct. Eng. 2020, 146, 04020261. [Google Scholar] [CrossRef]
- Fischer, E.C.; Varma, A.H.; Agarwal, A. Performance-Based Structural Fire Engineering of Steel Building Structures: Design-Basis Compartment Fires. J. Struct. Eng. 2019, 145, 04019090. [Google Scholar] [CrossRef]
- Zhang, G.; Fan, Q.; Lu, Z. Experimental and numerical study on the seismic performance of rocking steel frames with different joints under earthquake excitation. Eng. Struct. 2020, 220, 110974. [Google Scholar] [CrossRef]
- Zhang, A.; Ye, Q. Design and testing of prefabricated steel frame with an innovative re-centering energy dissipative brace. Eng. Struct. 2019, 201, 109791. [Google Scholar] [CrossRef]
- Jia, J. Seismic Rehabilitation for Structures. Modern Earthquake Engineering; Springer: Berlin/Heidelberg, Germany, 2017; Volume 10, pp. 815–836. [Google Scholar]
- Saberi, V.; Gerami, M.; Kheyroddin, A. Seismic rehabilitation of bolted end plate connections using post-tensioned tendons. Eng. Struct. 2016, 129, 18–30. [Google Scholar] [CrossRef]
- Nurchasanah, Y.; Ujianto, M.; Rochman, A. Diagonal reinforcement as strengthening to increase the stiffness and strength of concrete frame. In Proceedings of the 4th International Conference on Rehabilitation and Maintenance in Civil Engineering, Solo Baru, Indonesia, 11–12 July 2018. [Google Scholar]
- Arafa, M.; Alqedra, M.A.; Salim, R. Performance of RC Beams with Embedded Steel Trusses Using Nonlinear FEM Analysis. Adv. Civ. Eng. 2018, 2018, 9079818. [Google Scholar] [CrossRef]
- Chalioris, C.E.; Bantilas, K.E. Shear strength of reinforced concrete beam-column joints with crossed inclined bars. Eng. Struct. 2017, 140, 241–255. [Google Scholar] [CrossRef]
- Sen, A.D.; Swatosh, M.A.; Ballard, R.; Sloat, D.; Johnson, M.M.; Roeder, C.W.; Berman, J.W. Development and Evaluation of Seismic Retrofit Alternatives for Older Concentrically Braced Frames. J. Struct. Eng. 2017, 143, 04016232. [Google Scholar] [CrossRef]
- Lu, X.L.; Yang, B.Y.; Zhao, B. Shake-table testing of a self-centering precast reinforced concrete frame with shear walls. Earthq. Eng. Eng. Vib. 2018, 17, 221–233. [Google Scholar] [CrossRef]
- Zhang, H.; Su, M.; Lian, M. Experimental and numerical study on the seismic behavior of high-strength steel framed-tube structures with end-plate-connected replaceable shear links. Eng. Struct. 2020, 223, 111172. [Google Scholar] [CrossRef]
- Lu, X.; Cui, Y.; Liu, J.; Gao, W. Shaking table test and numerical simulation of a 1/2-scale self-centering reinforced concrete frame. Earthq. Eng. Struct. Dyn. 2015, 44, 1899–1917. [Google Scholar] [CrossRef]
- Di Sarno, L.; Elnashai, A.S. Innovative strategies for seismic retrofitting of steel and composite structures. Prog. Struct. Eng. Mater. 2005, 7, 115–135. [Google Scholar] [CrossRef]
- Di Sarno, L.; Elnashai, A.S. Bracing systems for seismic retrofitting of steel frames. J. Constr. Steel Res. 2009, 65, 452–465. [Google Scholar] [CrossRef]
- Cui, Y.; Lu, X.L.; Jiang, C. Experimental investigation of tri-axial self-centering reinforced concrete frame structures through shaking table tests. Eng. Struct. 2017, 13, 684–694. (In Chinese) [Google Scholar] [CrossRef]
- Lu, X.; Chen, C.; Chen, Y.; Shan, J. Application of replaceable coupling beams to RC structures: Application of Replaceable Coupling Beams. Struct. Des. Tall Spec. Build. 2016, 25, 947–966. [Google Scholar] [CrossRef]
- Ji, X.; Liu, D.; Sun, Y.; Molina Hutt, C. Seismic performance assessment of a hybrid coupled wall system with replaceable steel coupling beams versus traditional RC coupling beams. Earthq. Eng. Struct. Dyn. 2017, 46, 517–535. [Google Scholar] [CrossRef]
- Ji, X.; Wang, Y.; Ma, Q.; Okazaki, T. Cyclic behavior of very short steel shear links. J. Struct. Eng. 2016, 142, 04015114. [Google Scholar] [CrossRef]
- Ji, X.; Wang, Y.; Ma, Q.; Okazaki, T. Cyclic behavior of replaceable steel coupling beams. J. Struct. Eng. 2017, 143, 97–99. (In Chinese) [Google Scholar] [CrossRef]
- Shen, Y.; Christopoulos, C.; Mansour, N.; Tremblay, R. Seismic design and performance of steel moment resisting frames with nonlinear replaceable links. J. Struct. Eng. 2011, 137, 1107–1117. [Google Scholar] [CrossRef]
- Mansour, N.; Christopoulos, C.; Tremblay, R. Experimental validation of replaceable shear links for eccentrically braced steel frames. J. Struct. Eng. 2011, 137, 1141–1152. [Google Scholar] [CrossRef]
- Fortney, P.J.; Shahrooz, B.M.; Rassati, G.A. Large-scale testing of a replaceable steel coupling beam. J. Struct. Eng. 2007, 133, 1801–1807. [Google Scholar] [CrossRef]
- Lyons, R.M.; Christopoulos, C.; Montgomery, M.S. Enhancing the seismic performance of RC coupled wall high rise buildings with viscoelastic coupling dampers. In Proceedings of the 15 WCEE, Lisbon, Portugal, 24–28 September 2012; p. 1573. [Google Scholar]
- Christopoulos, C.; Montgomery, M.S. Viscoelastic coupling dampers (VCDs) for enhanced wind and seismic performance of high-rise buildings. Earthq. Eng. Struct. Dyn. 2013, 42, 2217–2233. [Google Scholar] [CrossRef]
- Wang, T.; Guo, X.; He, X.; Duan, C.; Du, Y. Experimental study on replaceable hybrid coupling beams. Appl. Mech. Mater. 2012, 166–169, 1779–1784. [Google Scholar] [CrossRef]
- Zhu, B.J.; Wang, T.; Zhang, L.X. 2018. Quasi-static test of assembled steel shear panel dampers with optimized shapes. Earthq. Eng. Struct. Dyn. 2013, 42, 2217–2233. [Google Scholar]
- Volynkin, D.; Clifton, G.C.; Dusicka, P. Cyclic performance of shear links with contact stiffeners. In Proceedings of the 16th World Conference on Earthquake Engineering, Santiago, Chile, 9–13 January 2017; p. 3312. [Google Scholar]
- Liu, Q.Z.; Jiang, H.J. Study on a new type of earthquake resilient shear wall. In Proceedings of the 16th World Conference on Earthquake Engineering, Santiago, Chile, 9–13 January 2017; p. 524. [Google Scholar]
- Lu, X.; Dang, X.; Qian, J.; Zhou, Y.; Jiang, H. Experimental study of self-centering shear walls with horizontal bottom slits. J. Struct. Eng. 2017, 143, 04016183. [Google Scholar] [CrossRef]
- Cortés, G.; Liu, J. Experimental evaluation of steel slit panel-frames for seismic resistance. J. Constr. Steel Res. 2011, 67, 181–191. [Google Scholar] [CrossRef]
- Lin, C.H.; Tsai, K.C.; Qu, B.; Bruneau, M. Sub-structural pseudo-dynamic performance of two full-scale two-story steel plate shear walls. J. Constr. Steel Res. 2010, 66, 1467–1482. [Google Scholar] [CrossRef]
- Jia, S.; Cao, W.; Zhang, Y. Low reversed cyclic loading tests for integrated precast structure of lightweight wall with single-row reinforcement under a lightweight steel frame. R. Soc. Open Sci. 2018, 5, 180321. [Google Scholar] [CrossRef] [Green Version]
- Dassault Systèmes, Dassault Systèmes Simulia Corp. ABAQUS Analysis User’s Manual 6.14-EF; Dassault Systems Simulia Corp.: Providence, RI, USA, 2014. [Google Scholar]
Steel Type | Steel Specifications | Yield Strength fy (MPa) | Ultimate Strength fu (MPa) | Elongation Δ (%) | Elastic Modulus E (MPa) | Thickness of the Steel Plate (mm) |
---|---|---|---|---|---|---|
Distribution rebar | Φ5 | 680 | 786 | 5.50 | 2.09 × 105 | - |
Steel plate strip | 40 | 309 | 467 | 25.27 | 2.11 × 105 | 4 |
Steel boundary component | 100 × 100 | 375 | 477 | 23.23 | 2.18 × 105 | 4 |
Concrete Grade | Components Cement, Water, Fine Aggregate, Coarse Aggregate, Fly Ash, Mineral Powder | Compressive Strength fcu (MPa) | Elastic Modulus Ec (MPa) |
---|---|---|---|
C40 | 1:0.49:2.28:2.28:0.21:0.21 | 41.15 | 3.15 × 104 |
Steel Type | Section Dimensions (mm) | Yield Strength fy (MPa) | Ultimate Strength fu (MPa) | Elongation δ (%) | Elastic Modulus Es (MPa) |
---|---|---|---|---|---|
I-beam | 350 × 200 × 6 × 8 | 375 | 477 | 23.23 | 2.18 × 105 |
Square steel tube | 200 × 200 × 8 | 375 | 477 | 23.23 | 2.18 × 105 |
No. | Frame Span (m) | Frame Beam Section Dimensions (mm) | Frame Column Section Dimensions (mm) | EDCW Span (mm) | Distance from the Midpoint of the EDCW to Left Column (mm) | Span Ratio (Frame Span/EDCW Span) |
---|---|---|---|---|---|---|
F1 | 3840 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 1920 | 2.4 |
F2 | 4800 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 2400 | 3.0 |
F3 | 5760 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 2880 | 3.6 |
F4 | 6720 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 3360 | 4.2 |
F5 | 7680 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 3840 | 4.8 |
F6 | 4800 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 800 | 3.0 |
F7 | 4800 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 1000 | 3.0 |
F8 | 4800 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 1920 | 3.0 |
F9 | 4800 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 3040 | 3.0 |
F10 | 4800 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 2840 | 3.0 |
F11 | 3840 | 350 × 160 × 5 × 7 | 160 × 160 × 8 | 1600 | 1920 | 3.0 |
F12 | 3840 | 350 × 200 × 6 × 8 | 240 × 240 × 8 | 1600 | 1920 | 2.4 |
F13 | 3840 | 350 × 200 × 6 × 8 | 200 × 200 × 8 | 1600 | 1920 | 2.4 |
F14 | 3840 | 350 × 240 × 7 × 10 | 300 × 300 × 8 | 1600 | 1920 | 2.4 |
F15 | 3840 | 350 × 300 × 9 × 12 | 360 × 360 × 8 | 1600 | 1920 | 2.4 |
F16 | 4800 | 350 × 360 × 10 × 14 | 200 × 200 × 8 | - | - | - |
Frame ID | Span Ratio | Dissipated Energy (kN·mm) | Ratio to That of F5 |
---|---|---|---|
F1 | 0.8 L | 13.2451 × 104 | 16.1415 |
F2 | L | 9.0388 × 104 | 11.0154 |
F3 | 1.2 L | 6.2363 × 104 | 7.60001 |
F4 | 1.5 L | 2.9012 × 104 | 3.5356 |
F5 | 2 L | 0.8205 × 104 | 1.0000 |
Frame ID | Distance L from the Centreline of the EDCW to the Left Column of the Frame (mm) | Dissipated Energy (kN·mm) | Ratio to That of F6 |
---|---|---|---|
F6 | 820 | 4.4595 × 104 | 1.0000 |
F7 | 1215 | 5.5622 × 104 | 1.2473 |
F8 | 1610 | 7.4544 × 104 | 1.6716 |
F9 | 2005 | 8.6705 × 104 | 1.9443 |
F10 | 2400 | 9.0388 × 104 | 2.0269 |
Frame ID | Cross-Sectional Expansion Multiplier | Dissipated Energy (kN·mm) | Ratio to That of F11 |
---|---|---|---|
F11 | 0.8 | 9.8993 × 104 | 1.0000 |
F12 | 1 | 13.2451 × 104 | 1.3380 |
F13 | 1.2 | 16.3053 × 104 | 1.6471 |
F14 | 1.5 | 26.6152 × 104 | 2.6886 |
F15 | 1.8 | 38.0334 × 104 | 3.8420 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Wei, D.; Suizi, J. Numerical Investigation of the Seismic Performance of Steel Frames with Energy-Dissipating Composite Walls. Materials 2022, 15, 828. https://doi.org/10.3390/ma15030828
Wei D, Suizi J. Numerical Investigation of the Seismic Performance of Steel Frames with Energy-Dissipating Composite Walls. Materials. 2022; 15(3):828. https://doi.org/10.3390/ma15030828
Chicago/Turabian StyleWei, Ding, and Jia Suizi. 2022. "Numerical Investigation of the Seismic Performance of Steel Frames with Energy-Dissipating Composite Walls" Materials 15, no. 3: 828. https://doi.org/10.3390/ma15030828
APA StyleWei, D., & Suizi, J. (2022). Numerical Investigation of the Seismic Performance of Steel Frames with Energy-Dissipating Composite Walls. Materials, 15(3), 828. https://doi.org/10.3390/ma15030828