Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System
Abstract
:1. Introduction
- Electrical parameters and characteristics were evaluated using a model based on actual data from the PEA 22 kV distribution system in Thailand.
- The process of selecting DG size and placement location in the distribution system to address the voltage drop issue was presented.
- The impact of DG placement at the proposed location in terms of fault occurrence was evaluated to determine the system characteristics under fault conditions.
- This method provides a sustainable way to maintain voltage regulation in distribution systems with renewable energy.
2. Research Methodologies and Configuration of the Distribution System
2.1. Research Methodologies
2.2. System Description
2.3. Distribution System with DG Placement
3. Single DG Placement along the Length of the Distribution Line
4. Single DG Placement between the Substation and the Critical Load
4.1. Voltage Drop Improvement in the Case of DG Placement between the STA Substation and the Critical Load
4.2. Voltage Drop Improvement in the Case of DG Placement between the SWA Substation and the Critical Load
5. Single DG Placement under Fault Occurrence
6. Conclusions
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Acknowledgments
Conflicts of Interest
References
- Khator, S.K.; Leung, L.C. Power distribution planning: A review of models and issues. IEEE Trans. Power Syst. 1997, 12, 1151–1159. [Google Scholar] [CrossRef]
- IEEE Std 141-1993; IEEE Recommended Practice for Electric Power Distribution for Industrial Plants. IEEE: New York, NY, USA, 1994.
- Osahenvemwen, O.A.; Omorogiuwa, O. Parametric Modeling of Voltage Drop in Power Distribution Networks. Int. J. Tech. Res. Appl. 2015, 3, 356–359. [Google Scholar]
- Hasan, K.N.; Muttaqi, K.M.; Borboa, P.; Scira, J.; Zhang, Z.; Leishman, M. Distribution network voltage analysis with data-driven electric vehicle load profiles. Sustain. Energy Grids Netw. 2023, 36, 101216. [Google Scholar] [CrossRef]
- Nunoo, S.; Attachie, J.C.; Duah, F.N. An Investigation into the Causes and Effects of Voltage Drops on an 11 kV Feeder. Can. J. Electr. Electron. Eng. 2012, 3, 40–47. [Google Scholar]
- Priyank, S.; Rabab, H.; Vineet, J.N.; Venkatesh, V.; Anuradha, M.A.; Anurag, K.S. Voltage regulation in distribution grids A survey. Annu. Rev. Control 2023, 55, 165–181. [Google Scholar]
- AlAhmad, O.; AlDahmi, M. Voltage Profile Improvement Analysis of 11 kV Feeders Using Capacitor Banks. In Proceedings of the 2021 International Conference on Electrotechnical Complexes and Systems (ICOECS), Ufa, Russia, 16–18 November 2021; pp. 83–87. [Google Scholar]
- Hakim, M.F.; Saputra, M.; Ananto, R.A.; Harijanto, P.S.; Santoso, A.H. Voltage Improvement on the Feeder Using the Load Breaking Method. Int. J. Electr. Eng. Appl. Sci. 2023, 6, 1–7. [Google Scholar]
- Mehigan, L.; Deane, J.P.; Gallachóir, B.P.Ó.; Bertsch, V. A review of the role of distributed generation (DG) in future electricity systems. Energy 2018, 163, 822–836. [Google Scholar] [CrossRef]
- Razmjoo; Gakenia, K.L.; Vaziri, R.M.A.; Marzband, M.; Davarpanah, A.; Denai, M.A. Technical analysis investigating energy sustainability utilizing reliable renewable energy sources to reduce CO2 emissions in a high potential area. Renew. Energy 2021, 164, 46–57. [Google Scholar] [CrossRef]
- Ministry of Energy. Alternative Energy Development Plan 2018–2037 (AEDP 2018); Ministry of Energy: Bangkok, Thailand, 2020. [Google Scholar]
- Ministry of Energy. Power Development Plan (PDP 2018 Revision 1); Ministry of Energy: Bangkok, Thailand, 2019. [Google Scholar]
- Chu, D.I.; Samuel, G.; Emmanuel, T.; Eric, E. Distributed Generation and Renewable Energy Integration into the Grid Prerequisites, Push Factors, Practical Options, Issues and Merits. Energies 2021, 14, 5375. [Google Scholar] [CrossRef]
- Song, Y.; Zheng, Y.; Liu, T.; Lei, S.; Hill, D.J. A New Formulation of Distribution Network Reconfiguration for Reducing the Voltage Volatility Induced by Distributed Generation. IEEE Trans. Power Syst. 2020, 35, 496–507. [Google Scholar] [CrossRef]
- Bajaj, M.; Singh, A.K.; Alowaidi, M.; Sharma, N.K.; Sharma, S.K.; Mishra, S. Power Quality Assessment of Distorted Distribution Networks Incorporating Renewable Distributed Generation Systems Based on the Analytic Hierarchy Process. IEEE Access 2020, 8, 145713–145737. [Google Scholar] [CrossRef]
- Robi, K.; Ardiansyah, N.; Arnawan, H.; Muzamir, I.; Muskan, G.; Shrikant, V.B. The Effect of Distributed Generator Injection with Different Number of Unit Power Quality in the Electric Power System. J. Renew. Energy Electr. Comput. Eng. 2021, 1, 71–78. [Google Scholar]
- Mohammad-Ali, H.; Farzaneh, B. Optimal planning of distributed generation and battery energy storage systems simultaneously in distribution networks for loss reduction and reliability improvement. J. Energy Storage 2022, 46, 101216. [Google Scholar]
- Chiradeja, P.; Ngaopitakkul, A. The impacts of electrical power losses due to distributed generation integration to distribution system. In Proceedings of the 2013 International Conference on Electrical Machines and Systems (ICEMS), Busan, Republic of Korea, 26–29 October 2013; pp. 1330–1333. [Google Scholar]
- Niazi, Y.; Golshan, M.E.H.; Alhelou, H.H. Combined Firm and Renewable Distributed Generation and Reactive Power Planning. IEEE Access 2021, 9, 133735–133745. [Google Scholar] [CrossRef]
- Aguila, T.; Lopez, G.; Isaac, I.; Gonzalez, J.W. Optimal reactive power compensation in electrical distribution systems with distributed resources. Heliyon 2018, 4, e00746. [Google Scholar] [CrossRef]
- Chiradeja, P.; Ngaopitakkul, A. The impact of capacity and location of multidistributed generator integrated in the distribution system on electrical line losses, reliability, and interruption cost. Environ. Prog. Sustain. Energy 2015, 34, 1763–1773. [Google Scholar] [CrossRef]
- Prakash, R.; Lokeshgupta, B.; Sivasubramani, S.; Kobaku, T.; Agarwal, V. Optimal DG Planning Incorporating Energy Management for an Economical and Resilient Smart Distribution System. IEEE Trans. Ind. Appl. 2024, 60, 1890–1901. [Google Scholar] [CrossRef]
- Karngala, K.; Singh, C. Reliability Assessment Framework for the Distribution System Including Distributed Energy Resources. IEEE Trans. Sustain. Energy 2021, 12, 1539–1548. [Google Scholar] [CrossRef]
- Muqthiar, S.; Padma, L.M.; Visali, N. Enhancement of Voltage Profile in the Distribution system by Reconfiguring with DG placement using Equilibrium Optimizer. Alex. Eng. J. 2022, 61, 4081–4093. [Google Scholar]
- Hasibuan; Dani, F.; Asran; Nrartha, I.M.A. Simulation and Analysis of Distributed Generation Installation on a 20 kV Distribution System Using ETAP 19.0. Bull. Comput. Sci. Electr. Eng. 2022, 3, 18–29. [Google Scholar]
- Yousaf, M.; Muttaqi, K.M.; Sutanto, D. An Investigative Analysis of the Protection Performance of Unbalanced Distribution Networks with Higher Concentration of Distributed Energy Resources. IEEE Trans. Ind. Appl. 2022, 58, 1771–1782. [Google Scholar] [CrossRef]
- Ngamroo; Kotesakha, W.; Yoomak, S.; Ngaopitakkul, A. Characteristic Evaluation of Wind Power Distributed Generation Sizing in Distribution System. Sustainability 2023, 15, 5581. [Google Scholar] [CrossRef]
- Hongchun, S.; Yaqi, D.; Pulin, C.; Tingyi, D.J.H.; Guangxue, W. A novel fault location scheme for transmission lines connected to wind farm based on variational iteration method. IET Gener. Transm. Distrib. 2022, 16, 3748–3759. [Google Scholar]
- Patcharoen, T.; Ngaopitakkul, A. Fault classifications in distribution systems consisting of wind power as distributed generation using discrete wavelet transforms. Sustainability 2019, 11, 7209. [Google Scholar] [CrossRef]
- Lim, S.-H.; Park, M.-K. Analysis on Protection Coordination of OCRs Using Voltage Components for the Application of SFCL in a Power Distribution System with DG. IEEE Trans. Appl. Supercond. 2021, 31, 5602106. [Google Scholar] [CrossRef]
- Jin, W.; Zhang, S.; Li, J.; Feng, M.; Feng, S.; Lu, Y. A Novel Differential Protection Scheme for Distribution Lines under Weak Synchronization Conditions Considering DG Characteristics. IEEE Access 2023, 11, 86561–86574. [Google Scholar] [CrossRef]
- Surakit, T.; Atthapol, N.; Wikorn, K.; Monthon, L.; Chaichan, P.; Suntiti, Y. An approach for voltage drop improvement in 22 kV PEA distribution system based on high voltage capacitor placement. Energy Rep. 2023, 9, 48–54. [Google Scholar]
- Manual Book: “Control and Operation of the Power Distribution Procedure for the Power Distribution Commander Center of Thailand”. PEA Command Center, May 2016.
Parameter | Value Setting |
---|---|
1. System Voltage | 23 kV |
2. Boundary voltage | 20.9–23.1 kV |
3. Cable type | Space Aerial Cable |
4. Conductor style | Solid core |
5. Sizing cable | 185 mm2 |
6. Number conductor | 3 conductors |
7. Outer radius | 0.00799 m. |
8. DC Resistance | 0.164 Ω |
9. Total load of feeder | 40.87 MVA |
Load No. | Load Capacity (MVA) | Power Factor (p.f.) | Length (Load-Load) (km) |
---|---|---|---|
1 | 1.49 | 0.95 | 5.5 |
2 | 8.15 | 0.95 | 4.5 |
3 | 4.42 | 0.95 | 4.5 |
4 | 10.42 | 0.95 | 3.0 |
5 | 5.15 | 0.95 | 2.5 |
6 | 1.67 | 0.95 | 6.0 |
7 | 4.11 | 0.95 | 4.5 |
8 | 5.11 | 0.95 | 3.0 |
9 | 0.31 | 0.95 | 4.0 |
Total | 40.87 | - | 43.0 |
Item | Descriptions | Specifications |
---|---|---|
1 | Turbine model type | GHFD87-2000/II |
2 | Manufacturer | Geoho |
3 | Rated power | 2 MW |
4 | Rotor diameter | 87 m |
5 | Blade quantity | 3 blades |
6 | Wind speed | 7–13 m/s |
7 | Generator type | Synchronous |
8 | Rated power | 2 MVA |
9 | Rated voltage | 690 V |
10 | Rated current | 1840 A |
DG Locations | PEA Std. | Without DG | 1/3 Line | 1/2 Line | 2/3 Line |
---|---|---|---|---|---|
STA | 20.900 | 23.000 | 23.000 | 23.000 | 23.000 |
Load 1 | 20.900 | 21.705 | 22.243 | 22.103 | 21.922 |
Load 2 | 20.900 | 20.766 | 21.601 | 21.484 | 21.146 |
Load 3 | 20.900 | 20.213 | 21.325 | 21.276 | 20.764 |
Load 4 | 20.900 | 19.967 | 20.953 | 21.283 | 20.651 |
Load 5 | 20.900 | 20.017 | 20.910 | 21.551 | 20.812 |
Load 6 | 20.900 | 20.433 | 21.068 | 21.732 | 21.511 |
Load 7 | 20.900 | 20.821 | 21.277 | 21.756 | 21.746 |
Load 8 | 20.900 | 21.203 | 21.555 | 21.903 | 21.904 |
Load9 | 20.900 | 21.939 | 22.142 | 22.339 | 22.344 |
SWA | 20.900 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.705 | 21.997 | 22.243 | 22.262 | 22.385 | 22.509 | 22.622 | 22.736219 |
2 | 20.766 | 21.283 | 21.601 | 21.772 | 22.000 | 22.228 | 22.444 | 22.660486 |
3 | 20.213 | 20.941 | 21.325 | 21.646 | 21.975 | 22.304 | 22.618 | 22.932569 |
4 | 19.967 | 20.612 | 20.953 | 21.224 | 21.513 | 21.802 | 22.075 | 22.349410 |
5 | 20.017 | 20.590 | 20.910 | 21.141 | 21.401 | 21.660 | 21.897 | 22.133517 |
6 | 20.433 | 20.845 | 21.068 | 21.244 | 21.431 | 21.619 | 21.795 | 21.971349 |
7 | 20.821 | 21.122 | 21.277 | 21.407 | 21.543 | 21.679 | 21.804 | 21.928803 |
8 | 21.203 | 21.436 | 21.555 | 21.651 | 21.753 | 21.854 | 21.948 | 22.042515 |
9 | 21.939 | 22.074 | 22.142 | 22.196 | 22.254 | 22.312 | 22.367 | 22.422310 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.705 | 21.856 | 21.922 | 21.988 | 22.048 | 22.109 | 22.164 | 22.219574 |
2 | 20.766 | 21.025 | 21.146 | 21.266 | 21.379 | 21.492 | 21.595 | 21.698174 |
3 | 20.213 | 20.583 | 20.764 | 20.944 | 21.111 | 21.279 | 21.438 | 21.597143 |
4 | 19.967 | 20.431 | 20.651 | 20.870 | 21.079 | 21.288 | 21.481 | 21.674618 |
5 | 20.017 | 20.557 | 20.812 | 21.066 | 21.304 | 21.543 | 21.771 | 22.000575 |
6 | 20.433 | 21.163 | 21.511 | 21.859 | 22.184 | 22.510 | 22.812 | 23.114537 |
7 | 20.821 | 21.447 | 21.746 | 22.045 | 22.322 | 22.599 | 22.860 | 23.120848 |
8 | 21.203 | 21.682 | 21.904 | 22.125 | 22.334 | 22.542 | 22.742 | 22.942699 |
9 | 21.939 | 22.215 | 22.344 | 22.472 | 22.593 | 22.713 | 22.825 | 22.937549 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
DG Locations | PEA Std. | Without DG | 1/3 Line | 1/2 Line | 2/3 Line |
---|---|---|---|---|---|
STA | 20.900 | 23.000 | 23.000 | 23.000 | 23.000 |
Load 1 | 20.900 | 21.705 | 22.485 | 22.358 | 22.225 |
Load 2 | 20.900 | 20.766 | 21.420 | 21.752 | 21.573 |
Load 3 | 20.900 | 20.213 | 20.752 | 21.038 | 21.324 |
Load 4 | 20.900 | 19.967 | 20.445 | 20.697 | 20.946 |
Load 5 | 20.900 | 20.017 | 20.444 | 20.662 | 20.892 |
Load 6 | 20.900 | 20.433 | 20.740 | 20.902 | 21.065 |
Load 7 | 20.900 | 20.821 | 21.048 | 21.160 | 21.277 |
Load 8 | 20.900 | 21.203 | 21.373 | 21.457 | 21.545 |
Load9 | 20.900 | 21.939 | 22.037 | 22.085 | 22.136 |
SWA | 20.900 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.705 | 22.118 | 22.311 | 22.505 | 22.692 | 22.880 | 23.060 | 23.241 |
2 | 20.766 | 21.109 | 21.273 | 21.437 | 21.595 | 21.753 | 21.906 | 22.059 |
3 | 20.213 | 20.492 | 20.629 | 20.766 | 20.898 | 21.031 | 21.158 | 21.286 |
4 | 19.967 | 20.219 | 20.339 | 20.458 | 20.574 | 20.690 | 20.802 | 20.913 |
5 | 20.017 | 20.242 | 20.349 | 20.456 | 20.559 | 20.663 | 20.762 | 20.862 |
6 | 20.433 | 20.594 | 20.672 | 20.750 | 20.825 | 20.900 | 20.972 | 21.044 |
7 | 20.821 | 20.944 | 21.000 | 21.056 | 21.110 | 21.164 | 21.216 | 21.268 |
8 | 21.203 | 21.295 | 21.337 | 21.379 | 21.420 | 21.461 | 21.500 | 21.539 |
9 | 21.939 | 21.992 | 22.016 | 22.041 | 22.064 | 22.087 | 22.110 | 22.132 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.706 | 22.095 | 22.240 | 22.384 | 22.539 | 22.694 | 22.840 | 22.985 |
2 | 20.767 | 21.291 | 21.539 | 21.788 | 22.021 | 22.254 | 22.480 | 22.705 |
3 | 20.213 | 20.645 | 20.852 | 21.059 | 21.257 | 21.454 | 21.635 | 21.816 |
4 | 19.967 | 20.350 | 20.550 | 20.750 | 20.900 | 21.049 | 21.221 | 21.392 |
5 | 20.017 | 20.360 | 20.551 | 20.743 | 20.865 | 20.986 | 21.139 | 21.291 |
6 | 20.434 | 20.680 | 20.798 | 20.915 | 21.029 | 21.143 | 21.245 | 21.347 |
7 | 20.821 | 21.003 | 21.088 | 21.172 | 21.252 | 21.332 | 21.410 | 21.488 |
8 | 21.203 | 21.339 | 21.403 | 21.466 | 21.528 | 21.589 | 21.646 | 21.703 |
9 | 21.939 | 22.018 | 22.055 | 22.091 | 22.126 | 22.162 | 22.194 | 22.227 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.706 | 22.150 | 22.225 | 22.374 | 22.453 | 22.592 | 22.725 | 22.857 |
2 | 20.767 | 21.566 | 21.573 | 21.980 | 22.127 | 22.382 | 22.618 | 22.854 |
3 | 20.213 | 21.044 | 21.324 | 21.477 | 21.630 | 21.901 | 22.155 | 22.409 |
4 | 19.967 | 20.701 | 20.946 | 21.079 | 21.213 | 21.448 | 21.662 | 21.876 |
5 | 20.017 | 20.674 | 20.892 | 21.011 | 21.130 | 21.339 | 21.535 | 21.730 |
6 | 20.434 | 20.905 | 21.065 | 21.152 | 21.240 | 21.392 | 21.532 | 21.672 |
7 | 20.821 | 21.162 | 21.278 | 21.342 | 21.407 | 21.514 | 21.615 | 21.716 |
8 | 21.203 | 21.460 | 21.546 | 21.594 | 21.642 | 21.721 | 21.800 | 21.878 |
9 | 21.939 | 22.087 | 22.136 | 22.164 | 22.192 | 22.238 | 22.283 | 22.328 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
DG Locations | PEA Std. | Without DG | 1/3 Line | 1/2 Line | 2/3 Line |
---|---|---|---|---|---|
STA | 20.900 | 23.000 | 23.000 | 23.000 | 23.000 |
Load 1 | 20.900 | 21.706 | 21.882 | 21.929 | 22.045 |
Load 2 | 20.900 | 20.767 | 21.073 | 21.160 | 21.307 |
Load 3 | 20.900 | 20.213 | 20.659 | 20.790 | 20.994 |
Load 4 | 20.900 | 19.967 | 20.524 | 20.677 | 20.942 |
Load 5 | 20.900 | 20.017 | 20.665 | 20.851 | 21.154 |
Load 6 | 20.900 | 20.434 | 21.308 | 21.039 | 21.973 |
Load 7 | 20.900 | 20.821 | 21.879 | 22.121 | 21.944 |
Load 8 | 20.900 | 21.203 | 22.381 | 22.118 | 22.036 |
Load9 | 20.900 | 21.939 | 22.616 | 22.504 | 22.417 |
SWA | 20.900 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.706 | 21.806 | 21.848 | 21.889 | 21.928 | 21.968 | 22.005 | 22.042 |
2 | 20.767 | 20.932 | 21.008 | 21.085 | 21.157 | 21.230 | 21.298 | 21.367 |
3 | 20.213 | 20.448 | 20.561 | 20.675 | 20.782 | 20.890 | 20.991 | 21.093 |
4 | 19.967 | 20.264 | 20.402 | 20.541 | 20.673 | 20.805 | 20.929 | 21.054 |
5 | 20.017 | 20.361 | 20.523 | 20.685 | 20.838 | 20.992 | 21.137 | 21.283 |
6 | 20.434 | 20.894 | 21.114 | 21.333 | 21.542 | 21.750 | 21.947 | 22.144 |
7 | 20.821 | 21.381 | 21.645 | 21.909 | 22.159 | 22.410 | 22.647 | 22.885 |
8 | 21.203 | 21.825 | 22.119 | 22.414 | 22.694 | 22.974 | 23.238 | 23.503 |
9 | 21.939 | 22.298 | 22.467 | 22.637 | 22.798 | 22.959 | 23.112 | 23.264 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
Locations | Without DG | 2 MW | 3 MW | 4 MW | 5 MW | 6 MW | 7 MW | 8 MW |
---|---|---|---|---|---|---|---|---|
STA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
1 | 21.706 | 21.833 | 21.886 | 21.939 | 21.988 | 22.036 | 22.085 | 22.133 |
2 | 20.767 | 20.981 | 21.079 | 21.178 | 21.268 | 21.358 | 21.444 | 21.530 |
3 | 20.213 | 20.520 | 20.667 | 20.814 | 20.950 | 21.087 | 21.219 | 21.351 |
4 | 19.967 | 20.348 | 20.527 | 20.705 | 20.906 | 21.027 | 21.193 | 21.360 |
5 | 20.017 | 20.485 | 20.682 | 20.879 | 21.065 | 21.251 | 21.443 | 21.635 |
6 | 20.434 | 21.023 | 21.312 | 21.601 | 21.861 | 22.120 | 22.369 | 22.618 |
7 | 20.821 | 21.517 | 21.842 | 22.167 | 22.475 | 22.783 | 23.069 | 23.355 |
8 | 21.203 | 21.727 | 21.973 | 22.218 | 22.454 | 22.690 | 22.909 | 23.128 |
9 | 21.939 | 22.241 | 22.384 | 22.528 | 22.660 | 22.792 | 22.916 | 23.040 |
SWA | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 | 23.000 |
Fault Locations (Measured from STA Substation) | Fault Types | Load Locations (kA) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
STA (S1) | Load No. 1 | Load No. 2 | Load No. 3 | Load No. 4 | Load No. 5 | Load No. 6 | Load No. 7 | Load No. 8 | Load No. 9 | SWA (S2) | ||
3 MW (Normal condition) | 0.468 | 0.036 | 0.189 | 0.101 | 0.238 | 0.119 | 0.040 | 0.098 | 0.123 | 0.008 | 0.363 | |
L1, or 5.5 km | 1Φ | 3.368 | 3.859 | 0.048 | 0.038 | 0.114 | 0.066 | 0.028 | 0.078 | 0.104 | 0.007 | 0.521 |
3Φ | 6.914 | 7.929 | 0.040 | 0.028 | 0.088 | 0.053 | 0.025 | 0.072 | 0.098 | 0.007 | 0.988 | |
L2, or 10 km | 1Φ | 1.987 | 0.019 | 2.613 | 0.027 | 0.083 | 0.052 | 0.025 | 0.072 | 0.099 | 0.007 | 0.598 |
3Φ | 3.812 | 0.017 | 5.016 | 0.023 | 0.065 | 0.043 | 0.023 | 0.068 | 0.094 | 0.007 | 1.096 | |
L3, or 17.5 km | 1Φ | 1.234 | 0.026 | 0.092 | 0.032 | 2.100 | 0.031 | 0.017 | 0.058 | 0.086 | 0.006 | 0.755 |
3Φ | 2.215 | 0.026 | 0.087 | 0.032 | 3.824 | 0.034 | 0.016 | 0.056 | 0.083 | 0.006 | 1.425 | |
L4, or 21.5 km | 1Φ | 1.012 | 0.028 | 0.115 | 0.040 | 0.065 | 0.041 | 0.012 | 0.047 | 0.076 | 0.006 | 0.916 |
3Φ | 1.842 | 0.027 | 0.106 | 0.035 | 0.048 | 0.036 | 0.010 | 0.044 | 0.072 | 0.006 | 1.775 | |
L5, or 33.5 km | 1Φ | 0.716 | 0.032 | 0.150 | 0.069 | 0.141 | 0.061 | 0.012 | 0.026 | 0.054 | 0.004 | 1.867 |
3Φ | 1.264 | 0.031 | 0.138 | 0.061 | 0.119 | 0.050 | 0.010 | 0.027 | 0.046 | 0.004 | 3.813 | |
L6, or 37.5 km | 1Φ | 0.650 | 0.033 | 0.157 | 0.075 | 0.159 | 0.071 | 0.017 | 0.029 | 0.031 | 3.815 | 3.255 |
3Φ | 1.135 | 0.031 | 0.146 | 0.067 | 0.139 | 0.062 | 0.015 | 0.025 | 0.031 | 8.039 | 6.906 |
Fault Locations (Measured from STA Substation) | Fault Types | Load Locations (kA) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
STA (S1) | Load No. 1 | Load No. 2 | Load No. 3 | Load No. 4 | Load No. 5 | Load No. 6 | Load No. 7 | Load No. 8 | Load No. 9 | SWA (S2) | ||
3 MW (Normal condition) | 0.468 | 0.036 | 0.189 | 0.101 | 0.238 | 0.119 | 0.040 | 0.098 | 0.123 | 0.008 | 0.363 | |
L1, or 5.5 km | 1Φ | 3.368 | 3.859 | 0.048 | 0.038 | 0.114 | 0.066 | 0.028 | 0.078 | 0.104 | 0.007 | 0.521 |
3Φ | 6.914 | 7.929 | 0.040 | 0.028 | 0.088 | 0.053 | 0.025 | 0.072 | 0.098 | 0.007 | 0.988 | |
L2, or 10 km | 1Φ | 1.987 | 0.019 | 2.613 | 0.027 | 0.083 | 0.052 | 0.025 | 0.072 | 0.099 | 0.007 | 0.598 |
3Φ | 3.812 | 0.017 | 5.016 | 0.023 | 0.065 | 0.043 | 0.023 | 0.068 | 0.094 | 0.007 | 1.096 | |
L3, or 17.5 km | 1Φ | 1.234 | 0.026 | 0.092 | 0.032 | 2.100 | 0.031 | 0.017 | 0.058 | 0.086 | 0.006 | 0.755 |
3Φ | 2.215 | 0.026 | 0.087 | 0.032 | 3.824 | 0.034 | 0.016 | 0.056 | 0.083 | 0.006 | 1.425 | |
L4, or 21.5 km | 1Φ | 1.012 | 0.028 | 0.115 | 0.040 | 0.065 | 0.041 | 0.012 | 0.047 | 0.076 | 0.006 | 0.916 |
3Φ | 1.842 | 0.027 | 0.106 | 0.035 | 0.048 | 0.036 | 0.010 | 0.044 | 0.072 | 0.006 | 1.775 | |
L5, or 33.5 km | 1Φ | 0.716 | 0.032 | 0.150 | 0.069 | 0.141 | 0.061 | 0.012 | 0.026 | 0.054 | 0.004 | 1.867 |
3Φ | 1.264 | 0.031 | 0.138 | 0.061 | 0.119 | 0.050 | 0.010 | 0.027 | 0.046 | 0.004 | 3.813 | |
L6, or 37.5 km | 1Φ | 0.650 | 0.033 | 0.157 | 0.075 | 0.159 | 0.071 | 0.017 | 0.029 | 0.031 | 3.815 | 3.255 |
3Φ | 1.135 | 0.031 | 0.146 | 0.067 | 0.139 | 0.062 | 0.015 | 0.025 | 0.031 | 8.039 | 6.906 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Ananwattanaporn, S.; Thongsuk, S.; Lertwanitrot, P.; Yoomak, S.; Ngamroo, I. Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System. Sustainability 2024, 16, 4295. https://doi.org/10.3390/su16104295
Ananwattanaporn S, Thongsuk S, Lertwanitrot P, Yoomak S, Ngamroo I. Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System. Sustainability. 2024; 16(10):4295. https://doi.org/10.3390/su16104295
Chicago/Turabian StyleAnanwattanaporn, Santipont, Surakit Thongsuk, Praikanok Lertwanitrot, Suntiti Yoomak, and Issarachai Ngamroo. 2024. "Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System" Sustainability 16, no. 10: 4295. https://doi.org/10.3390/su16104295
APA StyleAnanwattanaporn, S., Thongsuk, S., Lertwanitrot, P., Yoomak, S., & Ngamroo, I. (2024). Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System. Sustainability, 16(10), 4295. https://doi.org/10.3390/su16104295