Article

Impacts of Occupant Behavior on Building Energy Consumption and Energy Savings Analysis of Upgrading ASHRAE 90.1 Energy Efficiency Standards

1
College of Civil Engineering, Hunan University, Changsha 410082, China
2
Key Laboratory of Building Safety and Energy Efficiency of Ministry of Education, Hunan University, Changsha 410082, China
*
Author to whom correspondence should be addressed.
Buildings 2022, 12(8), 1108; https://doi.org/10.3390/buildings12081108
Submission received: 29 May 2022 / Revised: 18 July 2022 / Accepted: 21 July 2022 / Published: 27 July 2022
(This article belongs to the Special Issue Advanced Studies in Building Energy Efficiency and Occupant Behavior)

Abstract

:
Commercial prototype building models were developed by the United States Department of Energy (DOE) to analyze the energy savings of the ASHRAE 90.1 standard. However, in the DOE models, occupant behavior inputs were deterministic and the stochasticity of occupant behavior was not fully characterized. This study evaluated the impacts of stochastic occupant behavior on building energy consumption and energy savings analysis from upgrading the ASHRAE 90.1-2016 to 2019 in sixteen climate zones in the United States (U.S.). Three occupant behavior styles (austerity, normal, and wasteful) were defined to represent the different levels of energy consciousness. The DOE medium office prototype models were used as the baseline (normal behavior style). The occupant behavior functional mock-up unit (obFMU) was used to model the stochastic occupant behavior models (austerity and wasteful). The EnergyPlus medium office prototype models were modified to co-simulate with the obFMU models. The results of 16 climate zones were aggregated by the relative construction volume of each climate zone. The results showed that the weighted national annual source energy use intensity (EUI) of the austerity, normal, and wasteful behavior styles were 203.81 kWh/m2, 287.15 kWh/m2, and 388.33 kWh/m2 for ASHRAE 90.1-2016, and 192.43 kWh/m2, 273.48 kWh/m2, and 371.28 kWh/m2 for ASHRAE 90.1-2019, respectively. Compared to the normal behavior style, the austerity behavior style consumed 29% less source energy, while the wasteful behavior style consumed 36% more source energy. From upgrading the ASHRAE 90.1-2016 to 2019, the energy saving percentages based on the austerity, normal, and wasteful behavior styles were 5.59%, 4.78%, and 4.42%, respectively. The stochastic occupant behavior significantly impacted the building energy consumption, and their impacts on the energy savings analysis of upgrading ASHRAE 90.1 were also not negligible.

1. Introduction

With the rapid development of the global economy, building energy consumption has increased and is responsible for approximately 30% of global energy usage [1,2]. Building energy efficiency regulations have been developed for energy conservation and emission reduction in buildings [1]. For example, in 1975, the United States (U.S.) published and implemented the building energy efficiency standard, ASHRAE 90.1. As energy prices and technology began to evolve rapidly, the ASHRAE Board of Directors voted in 1999 to place the standard on continuous maintenance. As of the 2001 edition, the standard is published in its entirety during the fall of every third year, continuing to the 2019 edition. The standard parameters are revised every three years, presenting minimum performance characteristic values for all of the parameters related to the building envelope, air conditioning system requirements, lighting power density, and similar considerations [3].
As ASHRAE 90.1 evolved, the Pacific Northwest National Laboratory (PNNL) modified the suite of commercial prototype building models [4]. The suite of commercial prototype buildings covers 75% of the commercial building floor area in the U.S. for new construction including both commercial buildings and mid-to high-rise residential buildings, and across all U.S. climate zones. These commercial prototype building models derived from the commercial reference building models developed by the Department of Energy (DOE) [5]. The input parameters for the DOE commercial prototype building models were determined from the ASHRAE Standard 90.1, ASHRAE Standard 62.1, and as well as some studies of the data and standard practices. These models represent reasonably realistic building characteristics and construction practices [6]. They were used to determine the energy-saving potential of the different versions of the ASHRAE 90.1 standards.
People spend most of their time indoors [7]. Occupants and their behaviors (movement behavior and interaction behavior) are one of the driving factors of building energy consumption [8,9,10,11,12,13]. However, in many building performance simulation (BPS) studies (including DOE prototype building models), the occupant behavior inputs were deterministic [5,14,15] and lacked dynamic, stochasticity, and diversity. For example, the occupancy schedule of each thermal zone and the switching state of the lighting, equipment, and heating, ventilating, and air conditioning (HVAC) systems were consistent.
Occupancy information could determine the heating, ventilation, and lighting requirements [16]. The deterministic occupancy cannot reflect the load demand caused by the dynamic change in the number of people. Ahmed et al. [17] developed a new occupant hourly schedule for an office building and evaluated the impact of occupant behavior on the peak cooling load by energy simulation. The results illustrated that the peak cooling load in an office room was increased by a factor of 1.1–1.3 compared to the use of constant average value. Norouziasl et al. [18] investigated the performance of lighting occupancy sensors (represented the stochastic occupancy) in a simulated office. The results revealed that installing lighting occupancy sensors could reduce the annual lighting energy consumption by approximately 33%–55% compared to the sensor-free simulation.
Moreover, people have different energy-saving awareness, and the use habits of lighting, equipment, and HVAC systems differ from person to person. The deterministic occupant behavior inputs cannot depict this difference. Sun and Hong [19] employed BPS to evaluate the impact of three typical occupant behaviors (austerity, normal, and wasteful) on the energy use of an office building, and the simulation results demonstrated that compared to the normal workstyle, the austerity workstyle consumed up to 17.8–32.1% less energy, while the wasteful workstyle consumed up to 27.8–47.8% more energy. Jami et al. [20] identified the effect of occupant energy behavior scenarios (austerity, normal, energy spender) on the energy retrofit of a student dormitory via BPS. They found that energy conservation measures (ECMs) could improve energy efficiency by 32%, 56%, and 60% with the energy spender, normal, and austere occupant behavior models, respectively. He et al. [21] estimated the energy-saving potential of occupant behavior improvement by BPS based on a case study with a nationwide survey in Singapore and found that the building energy consumption could be reduced by up to 9.5% with moderate behavior improvement and up to 21.0% with aggressive behavior improvement. These studies all found that the stochastic behavior models had different impacts on the building energy consumption than the deterministic behavior models. Building prototypes (such as DOE commercial prototype building models) are regularly used in building performance analysis [22]. If stochastic occupant behavior models are integrated into DOE building models, it will be very helpful for researchers to evaluate the building energy performance by BPS tools (EnergyPlus, DeST 3.0 [23], etc.).
In terms of simulating the stochastic occupant movement behavior (e.g., arrival, departure, short-term leave, and from one office to another et al.) in an office building, Reinhart [24] used the cumulated probability statistics to simulate the status transition event (e.g., arrival, departure, and short-term leave). Wang et al. [25] used the Markov chain to simulate the random movement event (e.g., from one office to another). Goldstein et al. [26] used the occupant activity simulation to simulate the chronological sequence of detailed activities with attributes of a task (e.g., meeting event). Chen et al. [27] developed a web-based stochastic occupancy simulator, Occupancy Simulator, which simulated the presence and movement of each occupant by three types of events including: (1) the random movement event with Wang’s [25] homogeneous Markov chain model; (2) the status transition event with Reinhart’s [24] cumulated probability statistics model; and (3) the meeting events with a new stochastic model. In terms of modeling the stochastic occupant interaction behaviors (e.g., the control of lighting, window, HVAC, and other building energy systems), the interaction behaviors between the occupants and energy systems have often been fitted to the probabilistic distribution function of indoor environmental parameters. Hunt [28], Reinhart [24], and Wang [29] all proposed a light-on probability model with work plane daylight illuminance as the independent variable. Nicol [30] proposed a heating-on probability model with outdoor dry bulb temperature as the independent variable. Haldi and Robinson [31], Yun and Steemers [32], and Zhang and Barrett [33] all proposed the window-open or window-close probability model with indoor or outdoor air temperature as the independent variable. The occupant behavior functional mock-up unit (obFMU) developed by Lawrence Berkeley National Laboratory can model both the occupant movement and interaction behaviors [34]. obFMU was selected in this study to co-simulate with EnergyPlus via the functional mock-up interface (FMI) to implement the occupant behavior models.
This study evaluated the impacts of stochastic occupant behavior on building energy consumption and energy savings analysis from upgrading the ASHRAE 90.1-2016 [35] to 2019 [36] based on the DOE medium office prototype models across sixteen U.S. climate zones. For the convenience of simulation, the DOE medium office building models grouped rooms on each floor into five zones, including one core zone and four perimeter zones. The five zones in each floor were served by a packaged rooftop air conditioner with a variable air volume (VAV) system. Each zone was occupied by more than 10 persons based on the occupancy density. Those zones, therefore, were defined as open-plan office spaces in this study. The HVAC systems were kept running during office hours all year round. Thus, the HVAC zonal on/off control behavior and window zonal open/close behavior were not considered in this study. This paper, therefore, focused on the stochastic light switch behavior, appliance use behavior, and thermostat setpoint behavior. Other occupant behavior inputs were the same as the DOE prototype models. The main components of this study were as follows:
  • Three occupant behavior styles (austerity, normal, and wasteful) were defined based on the energy consciousness levels of the occupants regarding their interactions with the lighting, equipment, and heating/cooling setpoint systems. The DOE medium office prototype models were used as the baseline case (with normal behavior style). The obFMU was used to model the stochastic occupant behaviors, including the occupant movement and two interaction behavior styles (austerity and wasteful).
  • The EnergyPlus medium office prototype models for the 2016 and 2019 editions across sixteen U.S. climate zones were modified to co-simulate with the obFMU models.
  • After verifying the effectiveness of the occupant behavior models, the impacts of the stochastic occupant behavior on the building energy consumption and the energy savings analysis from upgrading the ASHRAE 90.1-2016 to 2019 were analyzed.

2. Methodology

2.1. Framework Overview

Figure 1 shows the proposed framework with its three major steps. The first step was to define three occupant behavior styles (austerity, normal, and wasteful). The DOE medium office prototype models, where occupant behavior inputs were deterministic, were used as the baseline case (with normal behavior style). The obFMU was used to model the stochastic occupant behaviors, including movement and two interaction behaviors (austerity and wasteful behavior styles). An occupant behavior modeling program, occupant behavior eXtensible Markup Language-generator (obXML-generator), was developed to generate the occupant behavior model file, which was used as the input file for the obFMU model. The second step was to modify the EnergyPlus medium office prototype models (in EnergyPlus™ Version 9.0) for the 2016 and 2019 editions across sixteen U.S. climate zones to co-simulate with the obFMU models. Moreover, the normal behavior style was only simulated by EnergyPlus. The final step was to verify the effectiveness of the occupant behavior models and analyze the impacts of the stochastic occupant behavior on the building energy consumption and the energy savings analysis from upgrading the ASHRAE 90.1-2016 to 2019.

2.2. DOE Medium Office Building Models

Commercial prototype building models [4] include 16 commercial building types in 19 climate zones (16 in the U.S.) for recent editions of ASHRAE 90.1. Figure 2 shows the basic situation of the DOE medium office building model. This building has three above-ground floors, a floor-to-floor height of 3.96 m, and a total floor area of 4983 m2. Each floor has the same layout, consisting of one core zone and four perimeter zones, and each zone has a uniform space type, defined as the “office”. The occupant density is 0.053 person/m2, and the equipment power density is 8.07 W/m2. The lighting power density was 8.50 W/m2 in 2016 and 6.89 W/m2 in 2019. Figure 2c shows the occupant behavior schedules in 15 zones, including the occupancy, interior lighting schedule, interior equipment schedule, and thermostat setpoint. These schedules were deterministic. This study focused on defining the stochastic occupant behavior models and analyzing the impacts of the stochastic occupant behaviors on building energy performance.
The Oak Ridge National Laboratory (ORNL) [37] updated the DOE medium office building model to include more space types such as open-plan office, enclosed office, corridor, etc. The ORNL’s models are more detailed than the DOE’s. However, this study wanted to briefly analyze the impacts of occupant behavior on the energy savings analysis of upgrading ASHRAE 90.1. The DOE’s models have often been used to evaluate the energy saving potential of ASHRAE 90.1 [38,39], and no official statement has been made that the ORNL’s models could replace the DOE’s. This study still used the DOE’s models. Table 1 lists the characteristics of the sixteen cities and climate zones in the U.S., which are described in ASHRAE Standard 169-2013 [40].

2.3. Occupant Behavior Models

2.3.1. obXML

To solve the problem of the existing data-driven behavior model’s low standardization and consistency, Hong et al. [41] developed the obXML schema to describe the occupant behaviors quantitatively. The obXML is a key tool for defining the stochastic occupant behavior models in the obFMU. The algorithm and solver of the Occupancy Simulator were implemented in obFMU by Hong et al. Users can define the movement model of each occupant by three types of events [27]: (1) the random movement event; (2) the status transition event; and (3) the meeting events. The obXML schema describes the stochastic occupant interaction behavior by implementing a framework of the Driver-Need-Action-System (DNAS) [41]. D represents the environmental factors that stimulate the occupants to fulfill a physical, physiological, or psychological need. N represents the occupant’s physical and non-physical requirements that must be met to ensure satisfaction with their environment. A represents the interactions with the energy systems that occupants can perform to achieve environmental comfort. S represents the equipment in the building.

2.3.2. Occupant Movement Model

For the convenience of simulation, the DOE medium office building models grouped rooms with the same setup parameters and set them to a unified thermal zone. The room type of each zone was defined as the “office”. The lighting, equipment, and other energy systems in 15 zones were uniformly controlled. In this study, each thermal zone was split into some subspaces by obFMU, allowing the lighting and equipment system of each space to be under independent control. The control style of the thermostat setpoint was unchanged, and future studies would achieve independent control of the HVAC system. Each subspace was a four-person space, common in office buildings. Generally speaking, there are seven room types in the office building: office, corridor, meeting room, copy room, lobby, restrooms, and mechanical/electrical room [42]. Occupants mainly stay in the “office” for a long time and stay in the other six room types for a short time. Therefore, the room type was redefined as the office, meeting room, and other types, which took about 72%, 4%, and 24% of the total floor area, respectively. The area fraction of each room type defined in this study referred to the Database for Energy Efficient Resources (DEER) prototype building models [42]. The floor area of each subspace was approximately 66.5 m2. The occupant density (0.053 person/m2) did not change. Because there are no permanent occupants in the meeting room and other rooms, the number of people in these rooms was defined as 0. The original occupant type (only “staff”) was redefined as staff, manager, and administrator types. See the details of each thermal zone in Figure 3 and its movement behavior in Table 2, Table 3 and Table 4. The definition of the random movement and status transition events in Table 3 referred to He’s study [21] and the DOE’s model (see Figure 2c). The definition of meeting events in Table 4 referred to Chen’s study [27].

2.3.3. Occupant Interaction Models

Table 5 shows the definition of three behavior styles. The normal behavior style indicates the average energy consciousness level, which refers to the deterministic occupant behavior in the DOE medium office building models. The austerity behavior style represents that the occupant actively saves energy. The wasteful behavior style means that the person did not care about energy consumption but cared about their own comfort. This study defined the occupant interaction models according to the main driving factors for their actions, divided into environmental factors (such as illuminance levels) and time-related stimuli (arrivals or departures et al.) [43]. After finishing the definition of the stochastic occupant behavior models (austerity and wasteful behavior styles), obXML was used to model the occupant behavior models.
  • Interior lighting model
The interior lighting model implemented by the wasteful behavior style only related to the occupancy. The interior lighting model implemented by the austerity behavior style were affected by the occupancy and the work plane daylight illuminance. Sun’s model [44], a three-parameter Weibull distribution, was used to describe the probability of turning on/off the lights when people stayed in the room in our austerity behavior model. The functions can be defined as Equations (1) and (2). The function shape is shown in Figure 4.
P = { 1 e Δ τ ( x u L ) k ,       x u 0 ,   x > u     ,     t u r n   o n   w h e n   f e e l i n g   d a r k ;
P = { 1 e Δ τ ( x u L ) k ,       x u 0 ,   x < u     ,     t u r n   o f f   w h e n   f e e l i n g   b r i g h t   e n o u g h .
where P is the probability of turning on/off the lights; Δ τ is the time step, min; x is the work plane illumination, lux; u is the threshold for the uncomfortable domain that controls when the action will begin; L describes the range for the functional variable; and k describes the shape.
2.
Interior equipment model
To define the interior equipment model for the austerity and wasteful behavior styles, this study made a measurement in a four-person office with the size of 4.2 m × 3.0 m × 3.9 m. The working hours were 9:00–17:00, and lunchtime was 12:00–13:00. Therefore, the total working time of the building was 8 h, and the total time people stayed in the building was 7 h (except for lunchtime). The on power and standby power of each type of equipment were measured separately for each behavior style, and the measurement duration was six hours. There were four computers, eight monitors (it was assumed that four monitors were used under the condition of austerity behavior style and eight monitors were used under the condition of wasteful behavior style), one water heater, and other equipment in the office. All equipment was turned on during working hours and on standby after people left work for the wasteful behavior style, and the computers were in high-performance mode. For the austerity behavior style, all equipment was turned on when people used it, on standby when people left for a short time, and turned off after they left work. The computers were on energy saving mode, and the monitors went dormant after 1 min if monitors were not used.
Table 6 shows the mean power of all equipment calculated by the measurement results (see Figure 5). The equipment power density in the DOE medium office building models was 8.07 W/m2, and the total design power was 536 W per subspace. Aside from the monitors, computers, and water heater, there were other types of equipment whose total power was assumed to be 92 W. The austerity workers would turn on 48% of the total plug loads during working hours and put 8% of the total plug loads on standby after leaving work; the 48% was calculated by Equation (3). Wasteful workers always turned on all equipment during working hours and put 61% of the total plug loads on standby after leaving work. The probability (0.9) of turning on plug loads and plug loads on standby referred to Wang’s study [45].
P e r c e n t a g e   o f   t u r n i n g   o n   t h e   p l u g   l o a d = ( A 1 B 1 + A 2 B 2 + A 3 B 3 ) / τ
where A1, A2, and A3 are the percentages of power for the austerity workers to stay in their own office, leave their own office for less than one hour, and leave their own office for more than one hour, respectively (see Table 6). B1, B2, and B3 are the percentages of time for the austerity workers to stay in their own office, leave their own office for less than one hour, and leave their own office for more than one hour (including lunch event (1 h) and meeting event). The time percent that people stayed in their own office and conducted meetings was 66% and 20% (see Table 3) of the time they stayed in the building (7 h), respectively. Thus B1, B3, and B2 were 4.62 h, 2.4 h, and 0.98 h, respectively. τ is the total working hours, 8 h.
Suppose the hot water consumption for each person was 1 L per day, the   using   power   Q w   (38 W) could be calculated by Equation (4). The water heater was turned on only when people drank for the austerity behavior style. Hence, the mean power of the water heater for the austerity behavior style was 38 W, and there was no water heater line for the austerity behavior in Figure 5a. The mean power (98 W) of the water heater during working hours for the wasteful behavior style included standby power (60 W) and use power (38 W).
Q w = n · C w m Δ t τ
where n is the number of people, n = 4; C w is the specific heat capacity of water, 4.2 × 103 J/(kg·°C); m is the water consumption, 1 kg; Δ t is the temperature difference that water is boiled from normal temperature, 65 °C; τ is the total working hours, 8 h.
3.
Thermostat setpoint model
The setpoints of the austerity behavior style mainly met the building energy saving requirements; thus, the temperature range was wider (a higher cooling setpoint and a lower heating setpoint), and the setpoints of the wasteful behavior style mainly met the occupant’s comfort requirements. As a result, the temperature range was narrower (a lower cooling setpoint and a higher heating setpoint). As shown in Table 5, based on the heating/cooling temperature setpoint of the DOE medium office building models, the setpoint was adjusted by 2 °C for the austerity behavior style. If the setpoint was adjusted by 2 °C for the wasteful behavior style, the heating setpoint temperature (23 °C) was higher than the cooling setpoint temperature (22 °C), which was unsuitable. Therefore, the setpoint was adjusted by 1 °C for the wasteful behavior style. The temperature ranges of the austerity and the wasteful behavior in Sun’s study [19] were referred to. The operation schedule of HVAC still followed the setup of the DOE medium office building models. The HVAC system was turned on from 7:00 a.m. to 10:00 p.m. on weekdays and from 7:00 a.m. to 6:00 p.m. on Saturdays. The HVAC system was turned off on Sundays and holidays.

2.4. The Development of the obXML-Generator

There were 264 occupants in the medium office building model. When establishing the stochastic occupant behavior model (such as the obXML.xml file), it was unrealistic to manually establish them one by one, as this process was time-consuming and error-prone. Therefore, this study used the Ruby language to develop a computer program, obXML-generator, that could quickly generate an obXML.xml file, as shown in Figure 6. First, based on the obXML schema (obxml_v1.4.xsd), the occupant behavior model parameters, including behaviors, holidays, meeting events, seasons, etc., were input in the “data” folder. Second, the building parameters, including basic information about each thermal zone, the building energy systems, behaviors, etc., were input into the “inputs.xlsx” file. Finally, the obXML-generator program was run to output the occupant behavior models.

2.5. The Co-Simulation between EnergyPlus and obFMU

After the stochastic occupant behavior models (austerity and wasteful behavior styles) were established, the co-simulation between obFMU and EnergyPlus could be run through the FMI. In Figure 7, obXML.xml and a co-simulation information file (obCoSim.xml) were used by obFMU as inputs. The building energy models, which were added to the co-simulation information, were used by EnergyPlus as inputs. EnergyPlus managed the co-simulation with the obFMU via FMI. The obFMU could simulate the occupant behaviors at each timestep based on the occupant behavior models and the environmental parameters obtained from EnergyPlus.
Moreover, the deterministic occupant behavior model (normal behavior style) was simulated only by EnergyPlus. The TMY3 weather data were used in the simulation. Finally, the operation schedules and building energy consumption in sixteen climate zones in the U.S. were outputted.

3. Results

3.1. Simulation Repetition

As the austerity and wasteful occupant behavior models were stochastic, the building energy consumption results of each simulation may be different. Thus, simulation repetition was required to calculate the mean value. Numerous studies showed that a repetition of ten times was adequate to determine the mean results [19,46]. There were few changes in the annual total source energy and total site energy among 20 times simulations for each occupant behavior model for the 2016 and 2019 editions across 16 climate zones. Therefore, a repetition of 20 times was adequate to determine the mean results.

3.2. Model Verification

The simulation results of a typical week for three occupant behavior models in Seattle in 2019 were analyzed. Because this study focused only on the impacts of stochastic occupant interaction behaviors on the ASHRAE 90.1 energy performance, the co-simulation model’s occupancy should be consistent with that of the prototype model. Then, the energy use results of the three occupant interaction models were varied to ensure that the occupant interaction models were well-implemented.

3.2.1. The Verification of the Occupant Movement Model

Figure 8 shows the occupancy of the co-simulation model and prototype model during a typical week in Seattle in 2019. In particular, the CVRMSE and the normalized mean bias error (NMBE) were used to evaluate the effectiveness of the occupant movement model. The CVRMSE (calculated using Equation (5)) measured the variation in the deviation between the co-simulation model’s occupancy and the prototype model’s occupancy. The NMBE (calculated using Equation (6)) measured the prediction error percentage between the co-simulation model’s occupancy and the prototype model’s occupancy. A smaller value of the CVRMSE indicated a smaller variation in deviations between the occupancy of two models and, consequently, a smaller prediction error. A smaller value of the NMBE (absolute value) indicated a higher prediction accuracy of the co-simulation model. According to ASHRAE Guideline 14-2014 [47], it can be considered acceptable when CVRMSE is less than or equal to 30% and NMBE is less than or equal to 10% for hourly intervals. The CVRMSE (26.51%) and NMBE (2.72%) of the occupancy of the co-simulation model at the building level were acceptable, which indicates that the occupancy of the co-simulation model was consistent with that of the prototype model at the building level (see Figure 8a), and the occupant movement model was suitable. From the comparison of the occupancy schedules in typical zones (see Figure 8b,c), unlike the occupancy schedule of the prototype model, the occupancy schedules of the co-simulation model in the two offices were different, so the defined occupant movement model could reflect the stochasticity, dynamics, and diversity of the occupancy.
C V R M S E = 100 × [ Σ ( y i y ^ i ) 2 / ( n 1 ) ] 1 2 y ¯
N M B E = 100 × Σ ( y i y ^ i ) ( n 1 ) × y ¯
where y i is the hourly occupancy of the prototype model; y ¯ is the hourly occupancy average of the prototype model; y ^ i is the hourly occupancy of the co-simulation model; n is the total number of the data samples, which was 8760.

3.2.2. The Verification of the Occupant Interaction Model

If the austerity behavior style consumes less energy use than the normal behavior style, and the normal behavior style consumes less energy use than the wasteful behavior style, the defined interaction models are suitable. The building energy use was reported after the simulation. The source energy was calculated as an indicator of the building energy consumption, including the source energy of electricity for the HVAC (heating, cooling, fans, and pumps), interior lighting, interior equipment, and the source energy of the natural gas for heating. The indicator is calculated as follows:
S o u r c e   e n e r g y   ( GJ ) = 3.167 × E l e c t r i c i t y   ( GJ ) + 1.084 × N a t u r a l   g a s   ( GJ )
where 3.167 and 1.084 are the site-to-source energy conversion factors, referring to the standard value in the DOE commercial prototype building models. Site energy refers to the energy consumed at the building site, and source energy refers to the energy required to generate and deliver energy to the site [48].
Figure 9 shows the energy use results of the three models during a week in Seattle in 2019. One may observe that the austerity behavior style consumed less energy than the normal behavior style for all energy systems. The wasteful behavior style consumed more energy than the normal behavior style for all energy systems. This indicates that the defined occupant interaction models met the requirements.

3.3. Results Analysis

The quantitative energy saving analysis was built on the method of the weighted national annual energy use intensity (EUI) statistics, which were DOE developed to assess the energy performance of new editions of ASHRAE Standard 90.1 [48]. The weighting factors by 16 climate zones allowed for aggregation of the energy impact from each climate zone level to the national level. The construction volume for the medium office buildings in the 16 climate zones accounted for 0.21%, 0.85%, 0.29%, 0.83%, 0.72%, 0.14%, 1.16%, 0.04%, 0.19%, 1.00%, 0.35%, 0.01%, 0.21%, 0.03%, 0.02%, and 0.01% of the total construction volume for all buildings in the U.S., respectively. Therefore, the weighting factor of the medium office buildings for each climate zone can be calculated (see Table 7, Table 8 and Table 9).
The EUI (kWh/m2) can be calculated using Equation (8).
E U I = a n n u a l   t o t a l   s o u r c e   e n e r g y   o f   b u i l d i n g   t o t a l   f l o o r   a r e a   o f   b u i l d i n g
The energy saving percentage from upgrading the ASHRAE 90.1-2016 to 2019 is calculated in Equation (9).
E n e r g y   s a v i n g   p e r c e n t a g e   ( % ) = ( E 1 E 2 ) / E 1 × 100 %
where E1 is the EUI for each behavior style in 2016, kWh/m2 and E2 is the EUI for each behavior style in 2019, kWh/m2.
Table 7, Table 8 and Table 9 and Figure 10 show the energy results for the three behavior styles in the 16 climate zones. The results were aggregated at a national level based on the weighting factors. The results indicated that the weighted national annual site EUI was 71.66 kWh/m2, 96.11 kWh/m2, and 126.83 kWh/m2 for the austerity, normal, and wasteful behavior styles, respectively, in 2016. The weighted national annual site EUI was 68.76 kWh/m2, 92.67 kWh/m2, and 122.27 kWh/m2 for the austerity, normal, and wasteful behavior styles, respectively, in 2019. Compared to the normal behavior style, the austerity behavior style consumed 25% less site EUI, while the wasteful behavior style consumed 32% more site EUI. The weighted national annual source EUI was 203.81 kWh/m2, 287.15 kWh/m2, and 388.33 kWh/m2 for the austerity, normal, and wasteful behavior styles, respectively, in 2016. The weighted national annual source EUI was 192.43 kWh/m2, 273.48 kWh/m2, and 371.28 kWh/m2 for the austerity, normal, and wasteful behavior styles, respectively, in 2019. Compared to the normal behavior style, the austerity behavior style consumed 29% less source EUI, while the wasteful behavior style consumed 36% more source EUI. Compared to the normal behavior style, the site EUI and source EUI for the austerity behavior style had decreased, but the site EUI and source EUI for the wasteful behavior style had increased in each climate zone. In 2016 and 2019, the site EUI and source EUI for the wasteful behavior style were more than 1.5~2.1 times that for the austerity behavior style. From upgrading the ASHRAE 90.1-2016 to 2019, the site energy saving percentages for the austerity, normal, and wasteful behavior styles were 4.05%, 3.58%, and 3.60%, respectively. The source energy saving percentages for the austerity, normal, and wasteful behavior styles were 5.59%, 4.78%, and 4.42%, respectively. These findings show that the occupant behavior significantly impacted the building energy consumption, and their impacts on the energy savings analysis of upgrading ASHRAE 90.1 were also not negligible. Although the impacts of the stochastic occupant behaviors on the energy savings of DOE medium office models were slight, it will also be conducive to the energy conservation of high energy-consuming buildings to a certain extent.

4. Discussion

This study evaluated the impacts of stochastic occupant behaviors on the building energy performance from upgrading the ASHRAE 90.1-2016 to 2019. The novelty of the proposed methodology included two aspects. (1) The obFMU was updated to allow each thermal zone in the DOE medium office to be split into some subspaces by users. Users could also redefine the room type and the number of people in each room to achieve independent control of the lighting and equipment systems. (2) This study used the Ruby language to develop a computer program, obXML-generator, that could quickly and accurately generate an occupant behavior model (obXML.xml file) based on the behavior and building parameter inputs. There are several aspects worth discussing or improving:
  • This study focused on the impacts of stochastic occupant behaviors on building energy performance. The stochastic occupant behavior models (austerity, normal, and wasteful) were defined, and the impacts of each occupant behavior model on the building energy performance were analyzed. However, there are many important parameters that significantly impact the building energy performance, such as the air infiltrations [49], the coefficient of performance (COP) of the VAV direct expansion (DX) cooling coil, and the conductance and the solar heat gain coefficient (SHGC) of windows [50], and so on. Many of these parameters were well-considered in the existing prototype building models in sixteen climate zones in the U.S. and thus were not discussed in this study. Table 10 presents the design parameters of the DOE medium office building models in Seattle for different editions of ASHRAE 90.1.
  • Occupancy and their behaviors all had significant impacts on the building energy consumption. However, it is very difficult to define the low-occupancy and high-occupancy cases, as it will bring more questions than the problem solved. Thus, this study focused only on the impacts of different occupant interaction behaviors with the stochastic and same occupancy.
  • This study only considered the occupant activities in the building operation stage. More comprehensive factors such as socio-economic characteristics, geographical location, subjective values, individual and collective adaptive action, and the optimization control of building energy systems [51] are needed to be integrated into occupant behavior models; therefore, more representative, synthetic occupants [52,53] can be generated.
  • This study only divided each thermal zone into four-person rooms to improve the DOE medium office building models. A field survey of room types in office buildings will be conducted to add more room types in the future study. Moreover, ORNL’s building models have significant meaning in defining the space type of the DOE building models and occupant behavior models. We will refine our study if the ORNL’s building models replace the DOE’s.
  • The five zones in each floor in the DOE medium office building models were served by an air conditioner system. These zones, therefore, were defined as open-plan office spaces in this study. The HVAC systems were kept running during office hours all year round, so this study did not consider the HVAC zonal on/off control and window zonal open/close behaviors. Private offices will be considered in the prototype building models, and the occupant behavior models will be improved in the next work.
  • The use of shade systems can impact the use of artificial lighting, thus affecting the building energy consumption [54,55]. The shading control behaviors in the open-plan offices were more complex than in the private offices. There were more manually-operated shade behavior models that could be referred to in private offices than in open-plan offices [55,56,57]. Therefore, this study did not consider the stochastic shading control behaviors. We are collecting parameters such as the work plane illumination and occupancy schedule in the office buildings through measurement and expect to construct shade control behavior models in the future.

5. Conclusions

This study evaluated the impacts of stochastic occupant behavior on building energy consumption and the energy savings analysis from upgrading the ASHRAE 90.1-2016 to 2019 in sixteen climate zones in the U.S. Three occupant behavior styles (austerity, normal, and wasteful) were defined to represent the different levels of energy consciousness of occupants regarding their interactions with the building energy systems (lighting, equipment, and heating/cooling setpoint). The DOE medium office prototype models for the 2016 and 2019 editions, where occupant behavior inputs were deterministic, were used as the baseline (with normal behavior style). The obFMU was used to model the stochastic occupant behaviors, including movement and two interaction behavior styles (austerity and wasteful). Then, the DOE medium office prototype models were modified to co-simulate with the obFMU models. Next, the impacts of the occupant behaviors on the building energy performance were analyzed. The main conclusions from this study were as follows:
  • The occupancy of the co-simulation model (with stochastic occupant movement behavior) was consistent with that of the DOE prototype model (with deterministic occupant movement behavior) at the building level.
  • The stochastic occupant behavior significantly impacted the building energy use. Compared with the normal behavior style in 2016 and 2019, the austerity behavior style consumed 25% less site energy and 29% less source energy, while the wasteful behavior style consumed 32% more site energy and 36% more source energy.
  • The impacts of the stochastic occupant behaviors on the energy savings from upgrading ASHRAE 90.1 were also not negligible. The different occupant behavior styles had different impacts on the ASHRAE 90.1 energy savings. From upgrading the ASHRAE 90.1-2016 to 2019, the source energy savings were 5.59%, 4.78%, and 4.42% for the austerity, normal, and wasteful behavior styles. Although the impacts of the stochastic occupant behaviors on the energy savings of the DOE medium office models were slight, it will also be conducive to the energy conservation of high energy-consuming buildings to a certain extent. In summary, it is necessary to consider the diversity, stochasticity, and dynamics of occupant behavior when updating the building energy efficiency standards.
This study also recommends some future work: (1) extending the study to other building types such as residential buildings and large office buildings; (2) evaluating the combined effect of stochastic occupancy and their behaviors on building energy performance; and (3) collecting data such as HVAC energy consumption, occupancy, and indoor and outdoor air temperature through large scale measurements to develop more open and realistic occupant behavior models.

Author Contributions

Data curation, Y.H. and Z.D.; Investigation, Z.C. and Y.Y.; Methodology, Z.D.; Project administration, Y.Y.; Resources, Z.C.; Software, Y.C. and Y.Y.; Supervision, Yixing Chen; Writing—original draft, Y.H.; Writing—review & editing, Y.C. All authors have read and agreed to the published version of the manuscript.

Funding

This study was supported by the National Natural Science Foundation of China (NSFC) through Grant No. 51908204 and the Natural Science Foundation of Hunan Province of China through Grant No. 2020JJ3008.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Xue, Q.; Wang, Z.; Chen, Q. Multi-Objective Optimization of Building Design for Life Cycle Cost and CO2 Emissions: A Case Study of a Low-Energy Residential Building in a Severe Cold Climate. Build. Simul. 2022, 15, 83–98. [Google Scholar] [CrossRef]
  2. Skea, J.; Shukla, P.R.; Reisinger, A.; Slade, R.; Pathak, M.; Khourdajie, A.A.; Diemen, R.V.; Abdulla, A.; Akimoto, K.; Babiker, M.; et al. Climate Change 2022: Mitigation of Climate Change. Contribution of Working Group III to the Sixth Assessment Report of the Intergovernmental Panel on Climate Change; Intergovernmental Panel on Climate Change (IPCC): Cambridge, UK, 2022. [Google Scholar]
  3. Melo, A.P.; Sorgato, M.J.; Lamberts, R. Building Energy Performance Assessment: Comparison between ASHRAE Standard 90.1 and Brazilian Regulation. Energy Build. 2014, 70, 372–383. [Google Scholar] [CrossRef]
  4. Prototype Building Models. Available online: https://www.energycodes.gov/prototype-building-models (accessed on 6 July 2022).
  5. Commercial Reference Buildings. Available online: https://www.energy.gov/eere/buildings/commercial-reference-buildings (accessed on 6 July 2022).
  6. Deru, M.; Field, K.; Studer, D.; Benne, K.; Griffith, B.; Torcellini, P.; Liu, B.; Halverson, M.; Winiarski, D.; Rosenberg, M.; et al. US Department of Energy Commercial Reference Building Models of the National Building Stock; National Renewable Energy Laboratory: Cole Boulevard Golden, CO, USA, 2011. [Google Scholar]
  7. Hormigos-Jimenez, S.; Padilla-Marcos, M.A.; Meiss, A.; Gonzalez-Lezcano, R.A.; Feijó-MuÑoz, J. Experimental Validation of the Age-of-the-Air CFD Analysis: A Case Study. Sci. Technol. Built Environ. 2018, 24, 994–1003. [Google Scholar] [CrossRef]
  8. Yoshino, H.; Hong, T.; Nord, N. IEA EBC Annex 53: Total Energy Use in Buildings—Analysis and Evaluation Methods. Energy Build. 2017, 152, 124–136. [Google Scholar] [CrossRef] [Green Version]
  9. Nisiforou, O.A.; Poullis, S.; Charalambides, A.G. Behaviour, Attitudes and Opinion of Large Enterprise Employees with Regard to Their Energy Usage Habits and Adoption of Energy Saving Measures. Energy Build. 2012, 55, 299–311. [Google Scholar] [CrossRef]
  10. Uddin, M.N.; Wei, H.-H.; Chi, H.L.; Ni, M. Influence of Occupant Behavior for Building Energy Conservation: A Systematic Review Study of Diverse Modeling. Buildings 2021, 11, 41. [Google Scholar] [CrossRef]
  11. Yfanti, S.; Sakkas, N.; Karapidakis, E. An Event-Driven Approach for Changing User Behaviour towards an Enhanced Building’s Energy Efficiency. Buildings 2020, 10, 183. [Google Scholar] [CrossRef]
  12. Jia, M.; Srinivasan, R.; Ries, R.J.; Bharathy, G.; Weyer, N. Investigating the Impact of Actual and Modeled Occupant Behavior Information Input to Building Performance Simulation. Buildings 2021, 11, 32. [Google Scholar] [CrossRef]
  13. Lu, X.; Feng, F.; Pang, Z.; Yang, T.; O’Neill, Z. Extracting Typical Occupancy Schedules from Social Media (TOSSM) and Its Integration with Building Energy Modeling. Build. Simul. 2021, 14, 25–41. [Google Scholar] [CrossRef]
  14. Deng, Z.; Chen, Y.; Yang, J.; Chen, Z. Archetype Identification and Urban Building Energy Modeling for City-Scale Buildings Based on GIS Datasets. Build. Simul. 2022, 15, 1547–1559. [Google Scholar] [CrossRef]
  15. Chen, Y.; Yang, C.; Pan, X.; Yan, D. Design and Operation Optimization of Multi-Chiller Plants Based on Energy Performance Simulation. Energy Build. 2020, 222, 110100. [Google Scholar] [CrossRef]
  16. Chen, Z.; Masood, M.K.; Soh, Y.C. A Fusion Framework for Occupancy Estimation in Office Buildings Based on Environmental Sensor Data. Energy Build. 2016, 133, 790–798. [Google Scholar] [CrossRef]
  17. Ahmed, K.; Akhondzada, A.; Kurnitski, J.; Olesen, B. Occupancy Schedules for Energy Simulation in New PrEN16798-1 and ISO/FDIS 17772-1 Standards. Sustain. Cities Soc. 2017, 35, 134–144. [Google Scholar] [CrossRef] [Green Version]
  18. Norouziasl, S.; Jafari, A.; Wang, C.; Turner, B.S.; Management, C.; Hall, P.F.T.; Rouge, B. An Agent-Based Simulation of Occupancy Schedule in Office Buildings. Build. Environ. 2020, 186, 107352. [Google Scholar] [CrossRef]
  19. Sun, K.; Hong, T. A Framework for Quantifying the Impact of Occupant Behavior on Energy Savings of Energy Conservation Measures. Energy Build. 2017, 146, 383–396. [Google Scholar] [CrossRef] [Green Version]
  20. Jami, S.; Forouzandeh, N.; Zomorodian, Z.S.; Tahsildoost, M.; Khoshbakht, M. The Effect of Occupant Behaviors on Energy Retrofit: A Case Study of Student Dormitories in Tehran. J. Clean. Prod. 2021, 278, 123556. [Google Scholar] [CrossRef]
  21. He, Z.; Hong, T.; Chou, S.K. A Framework for Estimating the Energy-Saving Potential of Occupant Behaviour Improvement. Appl. Energy 2021, 287, 116591. [Google Scholar] [CrossRef]
  22. Ma, Y.; Deng, W.; Xie, J.; Heath, T.; Xiang, Y.; Hong, Y. Generating Prototypical Residential Building Geometry Models Using a New Hybrid Approach. Build. Simul. 2022, 15, 17–28. [Google Scholar] [CrossRef]
  23. Yan, D.; Zhou, X.; An, J.; Kang, X.; Bu, F.; Chen, Y.; Pan, Y.; Gao, Y.; Zhang, Q.; Zhou, H.; et al. DeST 3.0: A New-Generation Building Performance Simulation Platform. Build. Simul. 2022, 1, 83–98. [Google Scholar] [CrossRef]
  24. Reinhart, C.F. Lightswitch-2002: A Model for Manual and Automated Control of Electric Lighting and Blinds. Sol. Energy. 2004, 77, 15–28. [Google Scholar] [CrossRef] [Green Version]
  25. Wang, C.; Yan, D.; Jiang, Y. A Novel Approach for Building Occupancy Simulation. Build. Simul. 2011, 4, 149–167. [Google Scholar] [CrossRef]
  26. Goldstein, R.; Tessier, A.; Khan, A. Schedule-Calibrated Occupant Behavior Simulation. In Proceedings of the Spring Simulation Multiconference, Orlando, FL, USA, 11–15 April 2010. [Google Scholar]
  27. Chen, Y.; Hong, T.; Luo, X. An Agent-Based Stochastic Occupancy Simulator. Build. Simul. 2018, 11, 37–49. [Google Scholar] [CrossRef] [Green Version]
  28. Hunt, D.R.G. Predicting Artificial Lighting Use—A Method Based upon Observed Patterns of Behaviour. Light. Res. Technol. 1980, 12, 7–14. [Google Scholar] [CrossRef]
  29. Wang, C.; Yan, D.; Sun, H.; Jiang, Y. A Generalized Probabilistic Formula Relating Occupant Behavior to Environmental Conditions. Build. Environ. 2016, 95, 53–62. [Google Scholar] [CrossRef]
  30. Nicol, J.F. Characterising Occupant Behavior in Buildings: Towards a Stochastic Model of Occupant Use of Windows, Lights, Blinds Heaters and Fans. In Proceedings of the Seventh International IBPSA Conference, Rio, Brazil, 13–15 August 2001. [Google Scholar]
  31. Haldi, F.; Robinson, D. On the Behaviour and Adaptation of Office Occupants. Build. Environ. 2008, 43, 2163–2177. [Google Scholar] [CrossRef]
  32. Yun, G.Y.; Steemers, K. Time-Dependent Occupant Behaviour Models of Window Control in Summer. Build. Environ. 2008, 43, 1471–1482. [Google Scholar] [CrossRef]
  33. Zhang, Y.; Barrett, P. Factors Influencing the Occupants’ Window Opening Behaviour in a Naturally Ventilated Office Building. Build. Environ. 2012, 50, 125–134. [Google Scholar] [CrossRef]
  34. Hong, T.; Sun, H.; Chen, Y.; Taylor-Lange, S.C.; Yan, D. An Occupant Behavior Modeling Tool for Co-Simulation. Energy Build. 2016, 117, 272–281. [Google Scholar] [CrossRef] [Green Version]
  35. ANSI/ASHRAE Standard 90.1-2016; Energy Standard for Buildings Except Low-Rise Residential Buildings. American Society of Heating, Refrigerating and Air Conditioning Engineers (Atlanta, Georgia). ASHRAE: New York, NY, USA, 2016.
  36. ANSI/ASHRAE Standard 90.1-2019; Energy Standard for Buildings except Low-Rise Residential Buildings. American Society of Heating, Refrigerating and Air Conditioning Engineers (Atlanta, Georgia). ASHRAE: New York, NY, USA, 2019.
  37. Piljae, I.; Joshua, R.; New, Y.B. Updated OpenStudio Small and Medium Office Prototype Models. In Proceedings of the 16th Conference of IBPSA, Rome, Italy, 2–4 September 2019. [Google Scholar]
  38. Thornton, B.A.; Rosenberg, M.I.; Richman, E.E.; Wang, W.; Xie, Y.; Zhang, J.; Cho, H.; Mendon, V.V.; Athalye, R.A.; Liu, B.; et al. Achieving the 30% Goal: Energy and Cost Savings Analysis of ASHRAE Standard 90.1-2010 (No. PNNL-20405); Pacific Northwest Natl. Lab.(PNNL): Richland, WA, USA, 2011. [Google Scholar]
  39. Halverson, M.; Rosenberg, W.M.; Wang, J.; Zhang, V.; Mendon, R.; Athalye, Y.; Xie, R.; Hart, S.G. ANSI/ASHRAE/IES Standard 90.1-2013. Determination of Energy Savings: Quantitative Analysis (No. PNNL-23481); Pacific Northwest Natl. Lab. (PNNL): Richland, WA, USA, 2014. [Google Scholar]
  40. ANSI/ASHRAE Standard 169-2013; Climatic Data for Building Design Standards. American Society of Heating. Refrigerating and Air Conditioning Engineers (Atlanta, Georgia). ASHRAE: New York, NY, USA, 2013.
  41. Hong, T.; D’Oca, S.; Turner, W.J.N.; Taylor-Lange, S.C. An Ontology to Represent Energy-Related Occupant Behavior in Buildings. Part I: Introduction to the DNAs Framework. Build. Environ. 2015, 92, 764–777. [Google Scholar] [CrossRef] [Green Version]
  42. Itron. Database for Energy Efficiency Resources (DEER) Update Study Final Report; Southern California Edison: Rosemead, CA, USA, 2005. [Google Scholar]
  43. Stazi, F.; Naspi, F.; Orazio, M.D. A Literature Review on Driving Factors and Contextual Events Influencing Occupants’ Behaviours in Buildings. Build. Environ. 2017, 118, 40–66. [Google Scholar] [CrossRef]
  44. Sun, K.; Hong, T. A Simulation Approach to Estimate Energy Savings Potential of Occupant Behavior Measures. Energy Build. 2017, 136, 43–62. [Google Scholar] [CrossRef] [Green Version]
  45. Wang, C. Simulation Research on Occupant Energy-Related Behaviors in Building. Ph.D. Thesis, Tsinghua University, Beijing, China, November 2014. [Google Scholar]
  46. Feng, X.; Yan, D.; Wang, C. On the Simulation Repetition and Temporal Discretization of Stochastic Occupant Behaviour Models in Building Performance Simulation. J. Build. Perform. Simul. 2017, 10, 612–624. [Google Scholar] [CrossRef]
  47. ANSI/ASHRAE Standard 14-2014; Measurement of Energy, Demand, and Water Savings. American Society of Heating, Refrigerating and Air Conditioning Engineers (Atlanta, Georgia). ASHRAE: New York, NY, USA, 2014.
  48. Athalye, R.; Halverson, M.; Rosenberg, M.; Liu, B.; Zhang, J.; Hart, R.; Mendon, V.; Goel, S.; Chen, Y.; Xie, Y.; et al. Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2016 (No. DOE/EE-1614); Pacific Northwest Natl. Lab. (PNNL): Richland, WA, USA, 2017. [Google Scholar]
  49. Alfano, D.F.R.; Dell’Isola, M.; Ficco, G.; Tassini, F. Experimental Analysis of Air Tightness in Mediterranean Buildings Using the Fan Pressurization Method. Build. Environ. 2012, 53, 16–25. [Google Scholar] [CrossRef]
  50. Lee, C.; Won, J. Analysis of Combinations of Glazing Properties to Improve Economic Efficiency of Buildings. J. Clean. Prod. 2017, 166, 181–188. [Google Scholar] [CrossRef]
  51. Chen, Z.; Chen, Y.; Yang, C. Impacts of Large Chilled Water Temperature Difference on Thermal Comfort, Equipment Sizes, and Energy Saving Potential. J. Build. Eng. 2022, 49, 104069. [Google Scholar] [CrossRef]
  52. Putra, H.C.; Andrews, C.; Hong, T. Generating Synthetic Occupants for Use in Building Performance Simulation. J. Build. Perform. Simul. 2021, 14, 712–729. [Google Scholar] [CrossRef]
  53. Putra, H.C.; Hong, T.; Andrews, C. An Ontology to Represent Synthetic Building Occupant Characteristics and Behavior. Autom. Constr. 2021, 125, 103621. [Google Scholar] [CrossRef]
  54. Xiong, J.; Tzempelikos, A.; Bilionis, I.; Karava, P. A Personalized Daylighting Control Approach to Dynamically Optimize Visual Satisfaction and Lighting Energy Use. Energy Build. 2019, 193, 111–126. [Google Scholar] [CrossRef]
  55. Ding, Y.; Ma, X.; Wei, S.; Chen, W. A Prediction Model Coupling Occupant Lighting and Shading Behaviors in Private Offices. Energy Build. 2020, 216, 109939. [Google Scholar] [CrossRef]
  56. O’Brien, W.; Kapsis, K.; Athienitis, A.K. Manually-Operated Window Shade Patterns in Office Buildings: A Critical Review. Build. Environ. 2013, 60, 319–338. [Google Scholar] [CrossRef]
  57. Sadeghi, S.A.; Awalgaonkar, N.M.; Karava, P.; Bilionis, I. A Bayesian Modeling Approach of Human Interactions with Shading and Electric Lighting Systems in Private Offices. Energy Build. 2017, 134, 185–201. [Google Scholar] [CrossRef] [Green Version]
Figure 1. An overview of the framework.
Figure 1. An overview of the framework.
Buildings 12 01108 g001
Figure 2. The basic situation of the DOE medium office building model: (a) 3D model; (b) thermal zones; (c) occupant behavior schedules.
Figure 2. The basic situation of the DOE medium office building model: (a) 3D model; (b) thermal zones; (c) occupant behavior schedules.
Buildings 12 01108 g002
Figure 3. The redefinition of the room type of each thermal zone.
Figure 3. The redefinition of the room type of each thermal zone.
Buildings 12 01108 g003
Figure 4. The probability of turning on/off the lights. (a) Probability of turning on the lights; (b) Probability of turning off the lights.
Figure 4. The probability of turning on/off the lights. (a) Probability of turning on the lights; (b) Probability of turning off the lights.
Buildings 12 01108 g004
Figure 5. The power of each type of equipment for the austerity and wasteful behavior styles: (a) Austerity behavior style; (b) Wasteful behavior style.
Figure 5. The power of each type of equipment for the austerity and wasteful behavior styles: (a) Austerity behavior style; (b) Wasteful behavior style.
Buildings 12 01108 g005
Figure 6. A guide to the use of obXML-generator.
Figure 6. A guide to the use of obXML-generator.
Buildings 12 01108 g006
Figure 7. The data flow of the co-simulation between EnergyPlus and obFMU.
Figure 7. The data flow of the co-simulation between EnergyPlus and obFMU.
Buildings 12 01108 g007
Figure 8. The verification of the occupant movement model: (a) Whole building; (b) F3C; (c) F1S.
Figure 8. The verification of the occupant movement model: (a) Whole building; (b) F3C; (c) F1S.
Buildings 12 01108 g008aBuildings 12 01108 g008b
Figure 9. The weekly source energy for the three models in Seattle in 2019: (a) Interior lighting; (b) Interior equipment; (c) HVAC; (d) Weekly source energy.
Figure 9. The weekly source energy for the three models in Seattle in 2019: (a) Interior lighting; (b) Interior equipment; (c) HVAC; (d) Weekly source energy.
Buildings 12 01108 g009aBuildings 12 01108 g009b
Figure 10. The national EUI and energy savings for the three occupant behavior styles: (a) Site EUI and energy savings; (b) Source EUI and energy savings.
Figure 10. The national EUI and energy savings for the three occupant behavior styles: (a) Site EUI and energy savings; (b) Source EUI and energy savings.
Buildings 12 01108 g010
Table 1. The characteristics of the sixteen cities and climate zones in the U.S.
Table 1. The characteristics of the sixteen cities and climate zones in the U.S.
Climate ZoneThermal Climate Zone NameRepresentative City
1AVery Hot HumidHonolulu, HI
2AHot HumidTampa, FL
2BHot DryTucson, AZ
3AWarm HumidAtlanta, GA
3BWarm DryEl Paso, TX
3CWarm MarineSan Diego, CA
4AMixed HumidNew York, NY
4BMixed DryAlbuquerque, NM
4CMixed MarineSeattle, WA
5ACool HumidBuffalo, NY
5BCool DryDenver, CO
5CCool MarinePort Angeles, WA
6ACold HumidRochester, MN
6BCold DryGreat Falls, MO
7Very ColdInternational Falls, MN
8Subarctic/ArcticFairbanks, AK
Table 2. The redefinition of the room type and movement behavior.
Table 2. The redefinition of the room type and movement behavior.
ZoneArea
(m2)
Room TypeSpace NumberOccupant Number per SpaceTotal Occupant Number per ZoneMovement Behavior ID *
F1C984.67Office16464S1
F2C984.67Other500S1
F3C984.67Office16464S2; S2_Sat
F3N207.58Office4416M
F3E131.41Office3412S2; S2_Sat
F3S207.58Other200M
F3W131.41Office3412S2; S2_Sat
F1N207.58Office4416M
F1E131.41Office3412M
F1S207.58Office4416S3; S3_Sun
F1W131.41Office3412A2
F2N207.58Office4416A2
F2E131.41Office3412A1
F2S207.58Meeting room200A1
F2W131.41Office3412A1
* Note: S, M, and A are the first letter of staff, manager, and administrator, respectively.
Table 3. The definition of the random movement event and status transition event.
Table 3. The definition of the random movement event and status transition event.
Event TypeSpace CategoryOccupancy ScheduleWeekdaysSaturdaySunday, Holiday, Other
S1, S2, S3,
M, A1
A2S2_SatS3_Sun
Random movement eventOwn officePercent time presence66%66%66%55%
Duration (min)90909090
Other officePercent time presence5%5%5%5%
Duration (min)30303030
Meeting roomPercent time presence20%20%20%20%
Duration (min)60606060
Other roomsPercent time presence5%5%5%5%
Duration (min)20202020
OutdoorPercent time presence4%4%4%15%
Duration (min)10101010
Status transition eventArrivalTime6:00–9:006:00–9:006:00–9:005:00–7:00
Short-term leavingEarly occur time12:0012:00
Typical occur time12:2512:25
Typical duration (min)4545
Minimum duration (min)2020
DepartureTime16:30–18:3022:30–23:3011:00–20:0017:00–19:00
Table 4. The definition of the meeting event.
Table 4. The definition of the meeting event.
Meeting EventDay of WeekNumber of Occupants per MeetingNumber of Meetings per DayMeeting Duration (Hour)Probability
1Monday,
Friday
2–212–50.50.12
10.72
1.50.12
≥20.04
2Tuesday,
Wednesday,
Thursday
2–213–70.50.12
Table 5. Occupant interaction models.
Table 5. Occupant interaction models.
Occupant BehaviorAusterityNormalWasteful
Control of lightsWhen people leave the room and it is empty, the lights are turned off.
When people stay in the room, lights are turned off if sensed bright and turned on if sensed dark.
The standard
schedule is followed.
When people leave the room for more than six hours and it is empty, the lights are turned off.
The lights are always turned on during working hours.
Control of appliance48% of the total plug loads are turned on during working hours, and 8% of the total plug loads are on standby after people leave work.The standardschedule is followed.100% of the total plug loads are turned on during working hours, and 61% of the total plug loads are on standby after people leave work.
Thermostat setpoint19 °C Heating/26 °C Cooling21 °C Heating/24 °C Cooling
(The standard
schedule is followed.)
22 °C Heating/23 °C Cooling
Table 6. The mean power of all equipment.
Table 6. The mean power of all equipment.
Equipment TypeAusterityWasteful
Working Hours
(on)
Leaving Less than 1 h
(Standby)
Leaving More than 1 h
(Standby)
Leaving Work
(Off)
Getting off Work
(Standby)
Working Hours
(on)
Monitors (W) 48000096
Computers (W)16416160176252
Water heater (W)38383806098
Others (W)909090459090
Total (W)34014414445326536
Percentage of total power 63%27%27%8%61%100%
Table 7. The EUI and energy savings for the normal behavior style.
Table 7. The EUI and energy savings for the normal behavior style.
Climate ZoneWeighting Factors (%)EUI (kWh/m2)Energy Savings (%)
2016 Site2016 Source2019 Site2019 SourceSiteSource
1A3.47 108.22 335.82 103.76 321.70 4.12 4.20
2A14.03 101.78 315.31 98.23 303.78 3.49 3.66
2B4.79 96.75 298.88 92.84 285.92 4.04 4.34
3A13.70 94.43 288.70 90.01 272.93 4.68 5.46
3B11.88 90.23 275.93 87.04 264.27 3.54 4.23
3C2.31 81.07 249.48 77.19 236.80 4.79 5.08
4A19.14 94.59 278.71 91.46 264.89 3.31 4.96
4B0.66 87.06 263.67 84.39 252.23 3.07 4.34
4C3.14 81.09 243.04 78.07 229.97 3.72 5.38
5A16.50 99.69 283.49 97.01 269.11 2.69 5.07
5B5.78 90.74 267.15 87.81 253.73 3.23 5.02
5C0.17 79.94 237.21 77.27 224.30 3.34 5.44
6A3.47 112.35 309.50 108.24 291.97 3.66 5.66
6B0.50 97.30 276.17 93.91 260.48 3.48 5.68
70.33 98.28 294.70 91.88 272.74 6.51 7.45
80.17 107.17 310.67 99.81 285.21 6.87 8.20
National average10096.11 287.15 92.67 273.48 3.58 4.78
Table 8. The EUI and energy savings for the austerity behavior style.
Table 8. The EUI and energy savings for the austerity behavior style.
Climate ZoneWeighting Factors (%)EUI (kWh/m2)Energy Savings (%)
2016 Site2016 Source2019 Site2019 SourceSiteSource
1A3.47 76.94 236.76 72.30 222.07 6.03 6.20
2A14.03 72.45 222.12 69.43 211.65 4.17 4.71
2B4.79 68.29 207.80 65.06 196.49 4.73 5.44
3A13.70 68.31 202.51 65.07 190.28 4.73 6.04
3B11.88 64.16 190.24 61.72 180.41 3.81 5.17
3C2.31 56.13 169.49 53.03 158.53 5.53 6.47
4A19.14 72.63 200.08 69.99 188.92 3.64 5.58
4B0.66 63.20 181.95 61.42 173.21 2.82 4.80
4C3.14 61.25 171.25 59.20 161.20 3.35 5.87
5A16.50 79.01 206.97 76.36 195.02 3.35 5.78
5B5.78 68.60 187.66 66.13 176.97 3.61 5.69
5C0.17 61.89 168.41 60.36 159.12 2.48 5.52
6A3.47 91.36 231.11 87.18 216.78 4.58 6.20
6B0.50 77.11 200.45 74.11 188.47 3.88 5.98
70.33 76.26 217.91 70.65 199.40 7.35 8.50
80.17 87.59 237.82 81.28 217.96 7.21 8.35
National average10071.66 203.81 68.76 192.43 4.05 5.59
Table 9. The EUI and energy savings for the wasteful behavior style.
Table 9. The EUI and energy savings for the wasteful behavior style.
Climate ZoneWeighting Factors (%)EUI (kWh/m2)Energy Savings (%)
2016 Site2016 Source2019 Site2019 SourceSiteSource
1A3.47 145.51 453.93 140.40 437.73 3.52 3.57
2A14.03 137.59 428.79 133.32 415.18 3.10 3.17
2B4.79 131.86 410.42 127.10 394.87 3.61 3.79
3A13.70 126.36 391.61 120.47 371.69 4.66 5.09
3B11.88 124.07 384.46 119.51 368.89 3.68 4.05
3C2.31 114.30 354.97 109.09 338.26 4.56 4.71
4A19.14 122.46 372.98 118.26 355.91 3.43 4.58
4B0.66 118.87 367.11 114.74 352.03 3.47 4.11
4C3.14 108.84 335.03 104.27 317.88 4.20 5.12
5A16.50 125.63 374.27 121.84 356.20 3.02 4.83
5B5.78 120.05 365.50 115.82 348.31 3.53 4.70
5C0.17 106.85 327.77 102.49 310.61 4.08 5.24
6A3.47 137.35 398.75 132.59 377.82 3.47 5.25
6B0.50 123.68 367.81 119.08 347.92 3.72 5.41
70.33 126.17 385.43 118.20 358.90 6.31 6.88
80.17 132.22 394.72 123.34 364.27 6.71 7.71
National average100126.83 388.33 122.27 371.28 3.60 4.42
Table 10. Some of the design parameters of the DOE medium office building models in Seattle.
Table 10. Some of the design parameters of the DOE medium office building models in Seattle.
Building Design Parameters90.1-200490.1-201090.1-201690.1-2019
Air infiltration flow per exterior surface area (m3/s)/m20.0010240.0005690.0005690.000569
VAV DX cooling coil COP3.233.403.403.40
Windows SHGC0.390.400.360.36
Windows conductance (W/m2·K)3.242.902.162.05
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

He, Y.; Chen, Y.; Chen, Z.; Deng, Z.; Yuan, Y. Impacts of Occupant Behavior on Building Energy Consumption and Energy Savings Analysis of Upgrading ASHRAE 90.1 Energy Efficiency Standards. Buildings 2022, 12, 1108. https://doi.org/10.3390/buildings12081108

AMA Style

He Y, Chen Y, Chen Z, Deng Z, Yuan Y. Impacts of Occupant Behavior on Building Energy Consumption and Energy Savings Analysis of Upgrading ASHRAE 90.1 Energy Efficiency Standards. Buildings. 2022; 12(8):1108. https://doi.org/10.3390/buildings12081108

Chicago/Turabian Style

He, Yaling, Yixing Chen, Zhihua Chen, Zhang Deng, and Yue Yuan. 2022. "Impacts of Occupant Behavior on Building Energy Consumption and Energy Savings Analysis of Upgrading ASHRAE 90.1 Energy Efficiency Standards" Buildings 12, no. 8: 1108. https://doi.org/10.3390/buildings12081108

APA Style

He, Y., Chen, Y., Chen, Z., Deng, Z., & Yuan, Y. (2022). Impacts of Occupant Behavior on Building Energy Consumption and Energy Savings Analysis of Upgrading ASHRAE 90.1 Energy Efficiency Standards. Buildings, 12(8), 1108. https://doi.org/10.3390/buildings12081108

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop