1. Introduction
In developing countries, most rural settlements are characterized by insufficient power supplies that hinders the community’s growth in terms of socioeconomic development, the lack of which has affected the standard of living and promotes poverty amongst rural inhabitants. Reliable energy access is essential for healthcare facilities in these remote communities as energy is needed to power medical equipment, for vaccine storage and to perform life-saving operations [
1]. Most times, healthcare service delivery at nights is performed using kerosene lamps, candles, rechargeable lamps or torchlights. According to [
2], maternal and child mortality rates are rapidly increasing on a daily basis, owing to the lack of good medical care amongst the rural dwellers. The poor working conditions and environment lead to a loss of medical professionals owing to a lack of job satisfaction.
Conventionally, diesel generators are mostly used to supply power to remote healthcare centers where connection to the grid is feasible and infeasible. However, there are problems associated with the use of diesel generators such as fuel costs and carbon emissions, which can have a negative effect on the health of the rural dwellers and healthcare personnel [
3]. In order to overcome these challenges, renewable energy sources serve as a better solution to provide reliable and sustainable energy for healthcare facilities in rural communities for an off-grid system and for an unreliable grid-connected network [
4]. This would improve the efficiency of healthcare service delivery, reduce operating costs and decrease the emissions effect. However, renewable energy systems are characterized by the problem of intermittency, which can lead to an imbalance in supply and demand [
5]. Hybrid energy systems have been considered to mitigate this problem owing to their high reliability and the available intensity of solar radiation and wind speed. The hybrid energy system comprises wind turbines, solar PV and battery storage with diesel generators and will present the opportunity to provide lighting and to power essential medical equipment for effective healthcare delivery for the people.
Several studies have been conducted to evaluate both the single and multiple energy source configurations for an off-grid system. A study on the power scheduling for agricultural applications using hybrid energy systems which combine heat and power, wind turbines, solar PV and a battery storage system was presented in [
5]. The system design, sizing and a techno-economic analysis of hybrid energy systems for the electrification of a rural community on a grid connected system are presented in [
6]. In [
7], a techno-economic and environmental analysis of a solar PV system for powering a water supply system for abattoirs in Nigeria was presented. The system design and an economic assessment of a hybrid microgrid system which comprises wind turbines, solar PV, generators and a battery storage system for a financial institution in a remote community is presented in [
8]. Ref. [
9] presents a feasibility study on the deployment of local renewable energy resources for an off-grid system for the electrification of a rural community in Brazil. Furthermore, a techno-economic and environmental assessment of the performance of a hybrid renewable system for the sustainable infrastructural development of an urban area in Green Vancouver is presented in [
10]. In [
11], a system design and techno-economic analysis of an isolated hybrid energy system for a radio transmitting station was presented.
Recent studies show that there is scarce literature exploring the application of hybrid energy systems for the electrification of rural healthcare facilities. A technical and economic analysis of hybrid energy systems for an off-grid healthcare center in a remote community in Nigeria is presented in [
12]. Ref. [
13] presents a techno-economic and environmental feasibility study for hybrid renewable energy resources for hospital loads in Iran. Ref. [
14] presents a system design and reliability evaluation of isolated hybrid energy systems for rural health clinics. A review that explores study feasibility, optimal sizing and a technical analysis of hybrid energy systems for the electrification of a healthcare center in the Global South is presented in [
1]. Ref. [
2] presents a techno-economic evaluation of isolated hybrid renewable energy systems for healthcare clinics in remote locations in Nigeria. In [
15], the system design and technical analysis of both grid-connected and off-grid systems for the rural electrification of healthcare clinics in the Philippines is presented. Ref. [
3] presents an analysis of a hybrid renewable energy system for an isolated microgrid powering rural healthcare clinics in South Africa.
The aforementioned literatures provide relevant information and also serve as the bedrock for this paper in terms of a techno-economic analysis of the energy design and sizing of the proposed system. However, a critical review of some of the literature as shown in
Table 1 reveals that certain studies do not consider wind energy as a source of energy supply, while diesel generators as an alternative source of power supply in off-grid systems, due to the intermittent nature of renewable energy sources, were not considered in other studies. An evaluation of the emissions contribution of diesel generators was also not considered in certain studies, which is an indication that environmental consideration has not been seriously examined in most rural electrification. Therefore, this paper comprehensively analyse the techno-economic and environmental performance of hybrid energy systems, which consist of wind turbines, solar PV, diesel generators and a battery storage system for powering a rural healthcare facility center in Nigeria. Furthermore, this research aimed at minimizing the electricity costs and emissions associated with diesel generators and to also carry out a sensitivity analysis for the optimal configuration of hybrid energy systems in rural communities for healthcare facilities. The optimization model was solved using algebraic modelling and different case studies were investigated to determine the suitable optimal configuration for the hybrid systems.
The remaining section of this article is organized as follows:
Section 2 describes the hybrid energy system configuration;
Section 3 presents the proposed simulation methodology;
Section 4 discussed the simulation results and the paper is concluded in
Section 5.
3. Simulation Methodology
To obtain optimal system configuration based on the economic and emission impact, various hybrid systems are considered and an optimum scenario was determined by using an optimization software where each system configuration is represented as a mathematical model compelled by various constraints. This paper seeks to minimize the daily operation costs of producing electrical energy for healthcare facilities in remote areas as well as the emission emanating from fossil fuel generators. The hybrid systems are designed in such a way that they meet the peak load demand of the healthcare facility and supply its load based on the availability of PV and wind resources with a backup diesel generator. Therefore, the objective function and the model constraints can be mathematically expressed as follows:
Subject to the following constraints:
where
and
are the operation costs of diesel generators and emissions contribution from diesel generators, respectively;
,
and
represent the optimal power produced by diesel generators DG, wind turbines and solar PV at time t, respectively;
represents the charging and discharging capacity of the battery storage;
represents the total power flowing in the PV and battery storage system at time t;
is the hourly electrical load of the rural clinic;
and
are the minimum and maximum power rating of the diesel generators DG, respectively; and
and
represent the maximum power rating of wind turbines and the solar PV system, respectively.
The objective function in Equation (7) aimed at minimizing the costs of operation and emissions of the diesel generators. These are two incomparable objectives, hence, a weighting factor constraint such as in Equation (8) states that the sum of all weighting factors equals unity [
29]. The power balance equation is given in Equation (9) and it indicates that the sum of the power produced from all the power sources must equal the energy demand by the load at any time t. Constraint (10) states that the total forecasted power by solar PV must be equal or greater than the total power obtainable from the charging and discharging of the battery storage system and the load power. Equations (11)–(13) are the boundary limits for the diesel generators, wind turbines and the solar PV system. Equation (14) is the state of charge constraint and it limits the available capacity of the battery.
3.1. Description of Case Study
In this study, the rural healthcare clinic considered for the assessment is a specialist hospital located in Ilumoba-Ekiti village in Ekiti State, in the southern part of Nigeria. This rural clinic is a government owned hospital that also provides healthcare delivery services to six neighboring communities that share a boundary with the host community. The study aimed at analysing the electrical appliances associated with laboratory equipment, vaccinations, maternity, medical consultations and lighting. The hospital is mostly run on a diesel generator during an emergency or when highly needed due to limited access to electricity in the community and its surroundings. Despite the significance of electricity for medical facilities, staff in this hospital do not have access to sufficient energy to perform their daily functions. This can lead to the poor storage of vaccines and the death of patients when attending unelectrified rural clinics. A hybrid energy system may be proposed for the rural healthcare facilities to improve energy supply to provide adequate service delivery in the rural clinic. The hybrid energy system comprises a wind turbine, solar PV, diesel generators and a battery storage system, which will provide energy for the proper operation of medical equipment. In order to properly design the hybrid energy for the system, an estimation of energy-consuming medical equipment is computed and the load profile for the rural healthcare clinic is presented in
Table 2.
Table 3 and
Figure 2 present the solar parameters and wind speed of the selected site location. In this study, we considered four different configurations of hybrid energy systems for providing a stable power supply for rural clinics and these configurations are as follows:
Case 1: Diesel generators only;
Case 2: Diesel generator with wind turbine;
Case 3: Diesel generator with PV system;
Case 4: Diesel generator, PV, wind turbine and battery.
3.2. Modelling and Optimization
In this study, the Advanced Interactive Multidimensional Modelling System (AIMMS) was used for modelling, simulating and optimally sizing the proposed hybrid energy system for different configurations. AIMMS is an optimization software that provides a setup for mathematical modelling and that aids in the solution of large-scale optimization problems in power systems. The solver employed in AIMMS is a CPLEX 12.6 solver.
4. Results and Discussion
This section evaluates the results obtained after the optimization of different hybrid configurations in an attempt to determine the most optimal in terms of minimized cost and emission. It assesses the outcomes to ascertain the impact of renewable energy resources on healthcare facilities in remote areas/off-grid locations and the results from the four case studies are discussed based on economic and environmental impacts.
Case 1: In this case study, the healthcare facility loads are supplied through the diesel generators with a peak capacity of 10 kW per generator, because it is designed such that no other source is available. The behavior of the three generators based on their power output is presented in
Table 4. It is observed that the first generator operates at its peak capacity daily, while the second generator only reach its peak capacity when the hospital load is at its peak demand between 09:00 to 16:00 h each day. The third generator serves as a power reserve to support the power generation when both generators cannot meet the peak load demanded by the healthcare facilities at the peak period of the day as shown in
Figure 1.
Figure 3 presents the optimal power produced from diesel generators and
Figure 4 presents the performance evaluation of the economic and emission parameters of this configuration. Since there is no other alternative source to supplement the diesel generators during operation, a large cost is incurred from the continuous operation of multiple diesel generators. Therefore, the minimized cost of running the three diesel generators is NGN 10,769/kWh. The environmental implication of running the three generators shows that this configuration produces an emission of 2536 lb/h. The high emission value obtained illustrates the environmental impacts the diesel generators have on the rural community.
Case 2: This configuration uses diesel generators and wind turbines to meet the healthcare facility load.
Table 5 presents the daily behavioral pattern of the diesel generators and the wind turbine generator. It can be observed that the integration of a wind turbine generator reduced the number of diesel generators in operation as shown in
Figure 5. This in turn will reduce the level of degradation of the diesel generators as less stress in their operation reduces wear and tear. The economic and emission performance of the system can be seen in
Figure 6. It shows that the operating conditions of the system considerably improved when compared to a system with only diesel generators in operation. The operational cost of running the system drastically reduced to NGN 9994/kWh and the emission sequentially reduced to 2385 lb/h because less generators are utilized and wind turbine generation produces no air pollution.
Case 3: In this case study, a solar PV system is added to the diesel generators to meet the required load demand of the rural clinic.
Table 6 presents the power generated by the diesel generators and PV system. The results obtained in
Figure 7 show that the power produced by the diesel generators significantly reduced owing to the presence of the PV system. However, there were inconsistencies in the availability of the PV system, which poses a setback to the configuration. The power produced from PV is only available between 08:00–18:00 h daily due to the intermittent nature of solar irradiance. In this case study, two diesel generators operated at minimal capacity. The cost of operation of this configuration is NGN 10,250/kWh and it is slightly lower when compared to a system mainly run by diesel generators. The environmental assessment shows a further reduction in emission production at 2387 lb/h as shown in
Figure 8.
Case 4: The configuration of this case study utilized a diesel generator, wind turbine, solar PV and a battery storage system to meet the load demand of the clinic and the power produced by these generating units can be seen in
Table 7. There is an indication that the power generated by the diesel generator drastically reduced when compared to other case studies as shown in
Figure 9. It is further observed that the integration of the renewable energy sources with a battery storage system into the system enhance the performance of the hybrid energy system in meeting the load demand. This configuration shows an improvement in the economic and emission performance as presented in
Figure 10. The result provides the lowest optimized cost of NGN 9312/kWh and emission performance at 2349 lb/h. This is an indication that the diesel generator is only operating at the least possible working capacity.