Each of the methods described below has its positive and negative sides. It is important that the used method is as simple as possible in expressing the fouling layer thickness and provides real results compared to the complicated procedures. In this study, the experimental verification of results was not acceptable for the reasons mentioned in the introductory and final sections of this article. Therefore, the comparison will involve the results obtained by applying the individual methods described below.
2.1. Balance Method
The balance method is based on a comparison of the supplied and removed heat output using Equation (1). The method applicable to a crossflow cooler (
Figure 2a) is described in detail in paper [
1], while the results related to a double crossflow cooler (
Figure 2b) are presented in this article.
The equation for calculating the cooling capacity
P is as follows:
wherein
P1 is the heat output withdrawn from natural gas (W);
ηlos is the coefficient respecting the heat loss into the cooler’s structure (1);
Qm,NG or
Qm,a is the mass flow rate of gas or air flowing through the cooler (kg∙s
−1);
i1,NG,
i2,NG is the specific enthalpy of gas at the entry into and exit from the cooler (J∙kg
−1); and
i1,a,
i2,a is the specific enthalpy of air at the entry into and exit from the cooler (J∙kg
−1).
Assuming that, for example, 3% of the output
P1 transfers into the cooler’s structure, then coefficient
ηlos equals 0.97 and the following equation is applied:
Concurrently with Equation (1), the following equation is applied:
wherein
k is the overall heat transfer coefficient (W·m
−2·K
−1);
is the mean temperature gradient (K); and
SΣ is the total heat-transfer surface area of the cooler (m
2).
The total surface area of the cooler
SΣ in Equation (3) is determined by the product of the external surface area of a single tube
Se (m
2) and the number of all tubes in the cooler
np:
The surface area of a single tube is calculated using the following equation:
wherein
r is the number of fins on a single tube (1);
dr is the fin diameter (m);
d2 is the external diameter of the tube (m); and
b is the fin spacing (m).
The mean temperature gradient
(K) in Equation (3) may be identified using the equations presented in detail in paper [
1]. The analysed cooler used a double crossflow with two flow runs
n = 2. The correction coefficient
ψ that is necessary for the identification of the mean temperature gradient
is therefore calculated using the following equation:
For parameter A, the Equation (6) determines the following:
The
P and
R criteria are identified using the following equations:
wherein
KNG is the heat capacity rate of gas;
Ka is the heat capacity rate of air (W·K
-1).
The heat capacity rate expresses the output that is required to heat the mass of the flowing medium by 1 K and is calculated using the following equation:
wherein
cp is the specific heat capacity of the medium (J∙kg
−1∙K
−1).
After substituting the total heat-transfer surface area and the mean temperature gradient into Equation (3), the overall heat transfer coefficient
k may be calculated using Equation (10):
Coefficient k may also be calculated based on a detailed description of the process of heat transport from warm natural gas through the tube wall into the surrounding air. If there is a fouling layer inside the tube, the solution must also take into account the heat transfer through that fouling layer.
The authors of this article assumed that the cooler had a fouling layer inside and a clean external heat-transfer surface, and they derived the following equation for calculating the overall heat transfer coefficient:
wherein
α1 is the coefficient of heat transfer inside the tube (W∙m
−2∙K
−1);
hf is the thickness of the fouling layer in the tube (m);
λf is the thermal conductivity coefficient of the fouling layer (W∙m
−1∙K
−1);
λp is the thermal conductivity coefficient of the tube (W∙m
−1∙K
−1);
S1 is the internal surface area of the tube (m
2);
d1 is the internal diameter of the tube (m);
sp is the thickness of the tube wall;
L is the tube length (m); and
α2 is the heat transfer coefficient for the heat transfer from the finned tube into the air (W∙m
−2∙K
−1).
By comparing Equations (11) and (10), the following equation for calculating the fouling layer thickness was obtained:
Parameter
D in Equation (12) was as follows:
The key challenge associated with calculating the fouling layer thickness using Equation (12) was that some of the parameters in Equation (12) are a function of hf. As hf increases, the thermal resistance on the tube wall also increases, and this leads to a decrease in the cooling capacity P. The fouling layer reduces the internal diameter of the tube and, consequently, the natural gas flow rate increases as well as the value of coefficient α1. The heat transfer coefficient α1 is calculated using a criterial equation that contains, inter alia, the Reynolds number Re. A higher α1 value leads to a lower value of thermal resistance on the interface between the natural gas and the internal wall of the tube. As a result, the cooling capacity increases. Moreover, changes in the fouling layer thickness cause changes in the mean temperature gradient . Based on the aforementioned facts, it may be stated that the fouling layer thickness cannot be calculated directly and requires numerous iterations.
The basic geometric parameters of the analysed cooler are listed in
Table 1.
The efficiency of the gas cooling process is significantly affected by the thermal conductivity of the fouling layer. The authors of this article identified the thermal conductivity coefficient of the fouling layer in an experiment. The coefficient value was 0.746 W·m
−1·K
−1, approximately two orders lower than the value for the tube material [
1].
The key settings for the iterations were selected based on the project values of the cooler’s parameters. The cooler was designed to cool natural gas at 242.3 kg·s−1 and a pressure of 7.45 MPa from a temperature of 75 °C to 50 °C. The required quantity of the fan air with a temperature of 28 °C was 565.23 kg·s−1.
In the project, it was assumed that the heat-transfer surfaces were clean; therefore,
hj = 0 was substituted into Equation (11). A similar procedure was applied to the iterations that were used for the temperatures of the cooling air which were different from the projected temperature. The ambient temperature ranged from 28 to 0 °C. The mass flow rate, the input temperature, and the gas pressure remained constant during the process. As the ambient temperature decreased, the amount of the air decreased, as described by the following equation:
Selected results of iterations are presented in
Figure 3. For certain values of the ambient temperature, the curve of the fouling layer thickness corresponds to the relevant gas cooling degree.
The indicated calculation method is rather complicated. Moreover, it requires obtaining extensive input data before the solving process is commenced—not only geometric data, but also the values of physical properties of natural gas and air. Particularly in the case of natural gas, with a pressure ranging from approximately 6 to 7.5 MPa, complex functions that depend on a pressure and a temperature must be applied in order to describe its physical properties.
Due to the complexity of the iteration procedure, the authors attempted to identify the fouling layer thickness through dimensional analysis based on the Buckingham’s theorem.
2.2. Buckingham’s Method
In the first approximation, all the parameters that were selected for the purpose of deriving a criterial equation were identical to those used in the balance method. In addition to the parameters listed above, these also included density, the thermal conductivity coefficient and kinematic viscosity of the flowing media, as well as the thermal conductivity coefficients of the tube and fin materials. A total of 18 dimensionless criteria were created and the criterial equation was subjected to an analysis, which revealed the effects of the individual criteria on the resulting
hf value. The parameters with apparently minor effects were then withdrawn from the model, and a new, simpler model was created. In the new model, some of the geometric dimensions (e.g., the external diameter of the tube, the fin diameter and thickness, and the fin spacing) were replaced with the surface areas calculated on the basis of those parameters. The adjusted list of physical parameters (16 in total) is presented in
Table 2.
In the creation of the model law, all the dimensions of the selected physical parameters were transformed into seven SI base units (kg; m; s; K, A; mol; cd). The relevant parameters in the aforesaid model for the identification of the fouling layer thickness included only four basic dimensions—kg, m, s, and K.
A criterial equation is normally created by replacing the selected dimensional parameters φ1 through φn with similarity criteria π1 through πm, while the functional correlations between the individual criteria are identified experimentally or through numerical or analytical calculations. The resulting criterial equation then applies to the entire group of similar processes.
When a dimensional analysis is used to describe a process, the number of obtained criteria
π is always lower than the number of relevant parameters
n on which the process depends. The basic equation that expresses the corelations between
n relevant parameters
φ1,
φ2 …
φi …
φn of various dimensions is as follows [
21]:
Based on the defining equation, each of the
φ parameters may be expressed through a specific dimensional equation. It is the product of the base unit symbols with the respective exponents. For the four base units of the selected physical parameters (kg, m, s, K), the defining equation is as follows:
In Equation (16), dimensional exponents x1 through x4 are rational numbers that were identified as described below.
Equation (15) is dimensionally homogenous; therefore,
φi variables cannot be used separately, but only in the form of products:
wherein
π—is the dimensionless variable (similarity criterion) (1);
xi—is the exponent (rational number);
φi—is the physical parameter with a respective dimension.
Pursuant to Equation (15) and considering the physical parameters listed in
Table 2, the following correlation must apply:
In general, for a certain phenomenon that is described by
n relevant parameters, it is possible to create
l similarity criteria. The number of searched criteria
π is identified using the following equation:
wherein
h is the je rank of the dimension matrix.
Pursuant to Equation (17), the following applies:
The dimensional form of Equation (20) is as follows:
Since the left side of Equation (21) equals one, the sum of the dimensional exponents in every basic parameter must equal zero. Therefore, the individual dimensions of the physical parameters (kg, m, s, K) are subject to the set of Equations (22)–(25).
The rank of the matrix for the set of Equations (22)–(25) equals four. With a total of 16 physical parameters, the total number of criteria is l = 12, as calculated using Equation (19).
Parameters with identical dimensions are expressed as independent criteria, also referred to as simplexes. The number of simplexes
ls equals the difference between the total number of relevant parameters
n and the number of relevant parameters with different dimensions
nk; therefore:
Table 1 indicates that the number of parameters with different dimensions is six. This means that a task with 16 relevant parameters may be assigned 10 simplex criteria.
The simplex that was created on the basis of the heat capacity rate values, calculated for gas and air using Equation (9), is as follows:
The temperature simplex criteria are as follows:
The simplexes created from the parameters with a length dimension are as follows:
The fouling layer is affected by the flow surface area; therefore, the following simplex was created:
The simplex created from the gas and air density parameters is as follows:
The simplex for the thermal conductivity coefficients for the gas and for the fouling layer is as follows:
With regard to the created simplexes, in the set of Equations (22)–(25),
x2 =
x3 = x5 =
x8 =
x9 =
x10 =
x11 =
x12 =
x14 =
x16 = 0; therefore, the resulting equations are as follows:
The total number of searched criteria is l = 12 and the number of created simplexes is 10. The two missing complex criteria had to be identified based on two independent solutions of the set of Equations (37)–(40).
The set of Equations (37)–(40) contains six unknowns; therefore, they must be solved by determining two of those unknowns and calculating the remaining four.
In the first option, the determined unknowns were
x1 = 1 and
x6 = 0 and the calculated parameters were the following:
x4 = 0;
x7 = −1;
x13 = 0; and
x15 = −1. The identified criterion was as follows:
In the second option, the determined unknowns were
x6 = 1 and
x1 = 0 and the calculated parameters were the following:
x4 = 0;
x7 = −2;
x13 = 0; and
x15 = 0. The identified criterion was as follows:
Since the criterial equation was to be derived for a particular cooler, the criteria π4, π5, π6, π7, and π12 were constant. Therefore, they were pooled into a single new criterion π0.
As a rule, similarity criteria may be transformed into other criteria through multiplication, division, exponentiation with a constant, or multiplication by a constant [
21]. That rule was applied to obtain the following new criterion from the constant criteria:
The parameter that was being identified was the thickness of the fouling layer in the cooler tubes
hf, and since it fell within the
π8 criterion, it was expressed as a function of other criteria, with the following form:
The correlation between the dimensionless arguments in Equation (44) is exponential; therefore, the resulting equation is as follows:
In a logarithmic scale, that correlation is linear and in the following form:
The individual criteria were calculated from the parameter values that were identified through iterations as described above. For the multiple regression analysis, data from 94 iterations were available. The C constant and the unknown exponents zj were identified through multiple linear regression.
The coefficient of determination for the multiple linear regression was 0.9999. The regression sum of squares was 13.153, while the residual sum of squares was 0.005. The values of the
C constant and the individual exponents are listed in
Table 3.
For the analysed cooler, the thickness of the fouling layer in the cooler tubes was subjected to the following criterial Equation (47), obtained by breaking down Equation (45):
Criteria with a zero exponent were not specified in Equation (47). In the linear regression, their impact was automatically included in the value of the C constant.
The parameter that was being identified—the fouling layer thickness
hf—is on the left side of criterial Equation (47) and is affected by the internal diameter of the cooler tube
d1. An adjustment of this criterion leads to solving a quadratic equation. Only one of the identified roots of the equation had a physical meaning—the one with a lower value. The values of the fouling layer thickness obtained from the model and from the analytical solution exhibited very good concordance (
Figure 4).
The correlation may be described by a regression line with a slope approaching 1, more specifically 0.9987, with a reliability value (a squared correlation index) R2 = 0.9999. The standard deviation of the difference was 0.0331, i.e., 3.2%.
The results of both solutions were also subjected to a pairwise
t-test at a significance level
α = 0.05. A precondition for using a pairwise
t-test was meeting the assumption of normality of the difference scores, which was verified in a Shapiro–Wilk test of normality. The value of the test criterion
t was identified using the following equation:
wherein
m is the number of values (1) and
sΔ is the standard deviation (mm).
Parameter
is the average value of the difference Δ
hf,analyt,i − Δ
hf,mod,i, calculated using the following equation:
For the analysed data sets, m = 94 and mm; therefore, the value of the test criterion t was 0.030. The critical value tcr at a significance level of 0.05 was t0.05(94−1) = 1.986. Since t < tcr, it may be stated that both methodologies provided identical results.
2.3. Multiple Regression Analysis
In a general case, the derived Equation (47) describes the fouling layer thickness with sufficient accuracy. However, the model is not very convenient for common purposes as it includes 12 independent parameters. Therefore, the investigation was carried out with the aim of exploring how to reduce the number of relevant parameters. In any cooler, the individual criteria of Equation (47) contain certain parameters that are of a constant value. In the analysed cooler, those parameters included, for example, the thermal conductivity coefficient for the pipe material and the fouling layer, the internal and external diameters of the pipe, the pipe lengths, etc.
In this case, the fouling layer thickness was identified by applying multiple regression analysis, using the MinitabX 18 statistical software and the R package software 4.3.3 [
22].
With the use of MinitabX, out of the group of relevant parameters, the following six parameters were selected as those with the most significant impact on the fouling layer thickness:
Qm,a;
T2,NG;
T1,a;
ρNG;
ρa; and
cp,NG. Multiple linear regression was applied and the following model equation was created:
Gas density
ρNG was used in Equation (50) for the mean temperature value (
T1,NG −
T2,NG)/2, and it was identified using Equation (51):
Air density
ρa was calculated using Equation (52):
wherein
.
The specific thermal capacity of gas c
p,NG was calculated using Equation (53):
Equation (50) represents the model of a correlation between the fouling layer thickness and the selected input parameters. The regression model parameters were identified by applying the method of least squares, which is sensitive to outliers. Therefore, the input data was also assessed in terms of outliers and influential values, which were excluded from the model.
The statistical significance of the regression model, or of the regression model parameters, was verified in the tests of statistical significance at a significance level α = 0.05. As a rule, if the
p-value is lower than the significance level α, then the null hypothesis is rejected in favour of the alternative hypothesis. If the
p-value equals or is higher than the selected significance level α, then the null hypothesis is not rejected [
23]. The results of the testing showed that the regression model (50) was statistically significant (
p-value = 3 × 10
−122 < α) and that all of the analysed parameters were also statistically significant (
p-value < α). The coefficient of determination for the multiple linear regression was 0.9985; this means that as much as 99.85% of the fouling layer thickness variability may be explained by the proposed regression model with the given parameters.
Heteroscedasticity of the regression model was tested with the use of the Breusch–Pagan test, in which the null hypothesis assumes homoscedasticity. The results (p-value = 0.199 > α) indicated that the regression model did not exhibit heteroscedasticity.
The correlation between the fouling layer thickness obtained from the model created by applying the multiple regression and that obtained analytically may be described by a regression line (
Figure 5) with a slope approaching 1, in particular 0.9996, at a reliability value
R2 = 0.9985.
The values of the fouling layer thickness obtained from the model and from the analytical solution were compared in a pairwise
t-test at a significance level α = 0.05. The Shapiro–Wilk test of normality was used to verify data normality. The results of the pairwise
t-test (
p-value = 0.999 > α) indicated that the two methodologies provided comparable results. The tests were performed using the R package software [
24].